METHOD STATEMENT

Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 1 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

METHOD STATEMENT

A) Main Power System

B) Lighting and Small Power System

C) Earthing & lightning Protection system.

METHOD STATEMENT:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 2 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

The procedures and methodologies that shall be employed herein shall be done in accordance with the
Project's Technical Specification, the Rules and Regulations of the Local Authority, and the latest
standards as set forth by the Qatar Construction Specifications. Importantly, all testing and commissioning
works shall be done in a safe manner so as to avoid danger to people and to the equipment.

Testing and commissioning must be carried out in sequence as set out below:

Stage 1: Tests before connection of Electrical Supply - To carry out all visual inspection and
electrical tests to ensure that all electrical equipment like panels , board sand devices,
cables and wires, etc., are completed prior to the supply or connection of power.

Stage 2: Pre-commissioning Test - To carry out all pre-commissioning test to demonstrate that all
electrical equipment or devices are properly operating in accordance with its required
function.

Stage 3: Commissioning Test - To carry out the full commissioning test to the following electrical
systems:
A) Main Power System
B) Lighting and Small Power System
C) Earthing & lightning Protection system.
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 3 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

STAGE 1

TEST BEFORE CONNECTION OF


ELECTRICAL SUPPLY
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 4 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

1.1 Test/Checks on Main Switch Board MV PANELS


LOCATION:- BASEMENT-1
MSB Manufacturer: SCHNEIDER Electric- M/s. Bin Galib Engineering
Ampere/Voltage Rating: 2500 Ampere
Bus bar Rating: 2500 Ampere
Fault Rating: 44 KA for 3 Seconds
Form/Separation: form-4B Type2
IP Rating: IP -54
Earthing:
Drawing Ref. No.:
Checks Checked
01 Check equipment nameplate data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify appropriate anchorage, required clearance, and alignment. 
04 Inspect all doors, panels, and sections for corrosion, dents, scratches, etc. 
05 Verify that fuse and/or circuit breaker size and types correspond to drawings. 
06 Check all outgoing MCCB ratings with drawings and specifications. 
07 Test all outgoing feeder circuits to verify insulation resistance and continuity 
08 All cables including gland connections were checked for tightness. 
09 Verify that all CTs, fuses, metering and indicating instruments, and selector switches 
correspond to drawings.
10 Inspect insulators for evidence of physical damage or contaminations. 
11 Verify if proper labels were provided or mounted on panels. 
12 Check if a laminated single line diagram is posted adjacent to the MSB. 
13 Verify all the interfaces with BMS demo s per the approved drawings. 
14 Check all the Battery charged connected & working properly. 
15 Insulation Resistance test shall be done twice the system supply voltage. 
16 Check cable trench chequered plates are provided properly 
17 Verify REF relay connection is completed. 
18 Check the entire Pipe sleeves/wall Penetration are sealed by fire sealant. 
Note:
1) See attached Factory Test and Insulation Test Reports at APPENDIX.
2) MV panel will be energizing in the presence of manufacturer and contractor engineer.
3) REF relay settings will be checked by Kahrama Engineer.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 5 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

1.2 Test/Checks on all Sub main Boards (SMBs)


LOCATION:- BASEMENT-1
SMB Manufacturer: SCHNEIDER Electric- Bin Galib Engineering
SMB Ref.:
Voltage Rating: 415 Volt.
Bus bar Rating:
Fault Rating: 25 KA for 3s
IP Rating:
Drawing Ref. No.:
Checks Checked
01 Check sub main board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check MCCB ratings with drawings and specifications 
06 Test all outgoing sub feeder circuits to verify insulation resistance and continually. 
07 Inspect dead front covers, panel doors for dents, scratches, etc. 
08 All cables including gland connections were checked for tightness. 
09 Check main and outgoing MCCB ratings against drawings. 
10 Inspect terminations/connections to CBs and terminals for tightness. 
11 Verify proper labeling and designating of circuits. 
12 Check SMB diagram is posted at inside of door. 
13 Ensure the operation at full load and no load properly. 
14 Earth continuity shall be checked for while the metal bodies. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.3 Test/Checks on all Sub main Boards (SMBs)


METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 6 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

LOCATION:- GROUND FLOOR


SMB Manufacturer: SCHNEIDER Electric- Bin Galib Engineering
SMB Ref.:
Voltage Rating: 415 Volt.
Bus bar Rating:
Fault Rating: 25 KA for 3s
IP Rating:
Drawing Ref. No.:
Checks Checked
01 Check sub main board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check MCCB ratings with drawings and specifications 
06 Test all outgoing sub feeder circuits to verify insulation resistance and continually. 
07 Inspect dead front covers, panel doors for dents, scratches, etc. 
08 All cables including gland connections were checked for tightness. 
09 Check main and outgoing MCCB ratings against drawings. 
10 Inspect terminations/connections to CBs and terminals for tightness. 
11 Verify proper labeling and designating of circuits. 
12 Check SMB diagram is posted at inside of door. 
13 Ensure the operation at full load and no load properly. 
14 Earth continuity shall be checked for while the metal bodies. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.4 Test/Checks on all Sub main Boards (SMBs)


LOCATION:- FIRST FLOOR
SMB Manufacturer: SCHNEIDER Electric- Bin Galib Engineering
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 7 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

SMB Ref.:
Voltage Rating: 415 Volt.
Bus bar Rating:
Fault Rating: 25 KA for 3s
IP Rating:
Drawing Ref. No.:
Checks Checked
01 Check sub main board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check MCCB ratings with drawings and specifications 
06 Test all outgoing sub feeder circuits to verify insulation resistance and continually. 
07 Inspect dead front covers, panel doors for dents, scratches, etc. 
08 All cables including gland connections were checked for tightness. 
09 Check main and outgoing MCCB ratings against drawings. 
10 Inspect terminations/connections to CBs and terminals for tightness. 
11 Verify proper labeling and designating of circuits. 
12 Check SMB diagram is posted at inside of door. 
13 Ensure the operation at full load and no load properly. 
14 Earth continuity shall be checked for while the metal bodies. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.5 Test/Checks on all Sub main Boards (SMBs)


LOCATION:- SECOND FLOOR
SMB Manufacturer: SCHNEIDER Electric- Bin Galib Engineering
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 8 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

SMB Ref.:
Voltage Rating: 415 Volt.
Bus bar Rating:
Fault Rating: 25 KA for 3s
IP Rating:
Drawing Ref. No.:
Checks Checked
01 Check sub main board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check MCCB ratings with drawings and specifications 
06 Test all outgoing sub feeder circuits to verify insulation resistance and continually. 
07 Inspect dead front covers, panel doors for dents, scratches, etc. 
08 All cables including gland connections were checked for tightness. 
09 Check main and outgoing MCCB ratings against drawings. 
10 Inspect terminations/connections to CBs and terminals for tightness. 
11 Verify proper labeling and designating of circuits. 
12 Check SMB diagram is posted at inside of door. 
13 Ensure the operation at full load and no load properly. 
14 Earth continuity shall be checked for while the metal bodies. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.6 Test/Checks on all Sub main Boards (SMBs)


LOCATION:- THIRD FLOOR
SMB Manufacturer: SCHNEIDER Electric-Bin Galib Engineering
SMB Ref.:
Voltage Rating: 415 Volt.
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 9 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

Bus bar Rating:


Fault Rating: 25 KA for 3s
IP Rating:
Drawing Ref. No.:
Checks Checked
01 Check sub main board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check MCCB ratings with drawings and specifications 
06 Test all outgoing sub feeder circuits to verify insulation resistance and continually. 
07 Inspect dead front covers, panel doors for dents, scratches, etc. 
08 All cables including gland connections were checked for tightness. 
09 Check main and outgoing MCCB ratings against drawings. 
10 Inspect terminations/connections to CBs and terminals for tightness. 
11 Verify proper labeling and designating of circuits. 
12 Check SMB diagram is posted at inside of door. 
13 Ensure the operation at full load and no load properly. 
14 Earth continuity shall be checked for while the metal bodies. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.7 Test/Checks on all Sub main Boards (SMBs)


LOCATION:- ROOF FLOOR

SMB Manufacturer: SCHNEIDER Electric- Bin Galib Engineering


SMB Ref.:
Voltage Rating: 415 Volt.
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 10 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

Bus bar Rating:


Fault Rating: 25 KA for 3s
IP Rating:
Drawing Ref. No.:
Checks Checked
01 Check sub main board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check MCCB ratings with drawings and specifications 
06 Test all outgoing sub feeder circuits to verify insulation resistance and continually. 
07 Inspect dead front covers, panel doors for dents, scratches, etc. 
08 All cables including gland connections were checked for tightness. 
09 Check main and outgoing MCCB ratings against drawings. 
10 Inspect terminations/connections to CBs and terminals for tightness. 
11 Verify proper labeling and designating of circuits. 
12 Check SMB diagram is posted at inside of door. 
13 Ensure the operation at full load and no load properly. 
14 Earth continuity shall be checked for while the metal bodies. 

Note: See attached Insulation Test Report at APPENDIX.

WITNESSED / APPROVED BY CONSULTANT


CARRIED OUT BY
Name: Name:

Signature: Signature:

Date: Date:

1.8 Test/Checks on all Control Panels;


MCC Manufacturer: Bin Galib Engineering
MCC Ref.: AHU’s CONTROL PANELS
Voltage Rating:
Bus bar Rating:
Fault Rating:
IP Rating: IP65
Drawing Ref. No.:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 11 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

Checks Checked
01 Check Control panel’s data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check isolator and MCBs ratings with drawings and specifications. 
06 Test all outgoing sub feeder circuits to verify insulation resistance and continuity 
07 Inspect dead front covers, panel doors for dents, scratches, etc. 
08 Circuit homeruns were checked for its designated phase colures. 
09 All cables including gland connections were checked for tightness. 
10 Inspect terminations/connections to CBs and terminals for tightness. 
11 Verify proper labeling and designating of branch circuits. 
12 Check if a laminated control panel drawing is posted at inside of door. 
13 Verify all the metal parts are connected by Earth continuity conductor. 
14 Ensure the polarities and phase rotation of all the rotating machines. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.9 Test/Checks on all Distribution Boards (DBs)


LOCATION:- BASEMENT-1
MCC Manufacturer: SCHNEIDER. BIN GALIB
DB Ref.:
Voltage Rating:
Bus bar Rating:
Fault Rating:
IP Rating:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 12 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

Drawing Ref. No.:


Checks Checked
01 Check distribution board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check main isolator, and all outgoing branch MCBs with drawings and specifications. 
06 Inspect terminations/connections to MCBs and terminals for tightness. 
07 Test all outgoing branch circuits to verify insulation resistance and continuity. 
08 Inspect dead front covers, panel doors for dents, scratches, etc. 
09 Check cable gland connection if terminated properly. 
10 Verify proper labeling and designating of circuits. 
11 Check DB Schedule is posted at inside of door. 
12 Verify all the metal parts are connected by Earth continuity conductor. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.10 Test/Checks on all Distribution Boards (DBs)


LOCATION:- GROUND FLOOR
MCC Manufacturer: SCHNEIDER. BIN GALIB
DB Ref.:
Voltage Rating:
Bus bar Rating:
Fault Rating:
IP Rating:
Drawing Ref. No.:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 13 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

Checks Checked
01 Check distribution board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check main isolator, and all outgoing branch MCBs with drawings and specifications. 
06 Inspect terminations/connections to MCBs and terminals for tightness. 
07 Test all outgoing branch circuits to verify insulation resistance and continuity. 
08 Inspect dead front covers, panel doors for dents, scratches, etc. 
09 Check cable gland connection if terminated properly. 
10 Verify proper labeling and designating of circuits. 
11 Check DB Schedule is posted at inside of door. 
12 Verify all the metal parts are connected by Earth continuity conductor. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.11 Test/Checks on all Distribution Boards (DBs)


LOCATION:- FIRST FLOOR
MCC Manufacturer: SCHNEIDER. BIN GALIB
DB Ref.:
Voltage Rating:
Bus bar Rating:
Fault Rating:
IP Rating:
Drawing Ref. No.:
Checks Checked
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 14 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

01 Check distribution board's data with drawings and specification. 


02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check main isolator, and all outgoing branch MCBs with drawings and specifications. 
06 Inspect terminations/connections to MCBs and terminals for tightness. 
07 Test all outgoing branch circuits to verify insulation resistance and continuity. 
08 Inspect dead front covers, panel doors for dents, scratches, etc. 
09 Check cable gland connection if terminated properly. 
10 Verify proper labeling and designating of circuits. 
11 Check DB Schedule is posted at inside of door. 
12 Verify all the metal parts are connected by Earth continuity conductor. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.12 Test/Checks on all Distribution Boards (DBs)


LOCATION:- SECOND FLOOR
MCC Manufacturer: SCHNEIDER. BIN GALIB
DB Ref.:
Voltage Rating:
Bus bar Rating:
Fault Rating:
IP Rating:
Drawing Ref. No.:
Checks Checked
01 Check distribution board's data with drawings and specification. 
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 15 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

02 Inspect physical and mechanical condition. 


03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check main isolator, and all outgoing branch MCBs with drawings and specifications. 
06 Inspect terminations/connections to MCBs and terminals for tightness. 
07 Test all outgoing branch circuits to verify insulation resistance and continuity. 
08 Inspect dead front covers, panel doors for dents, scratches, etc. 
09 Check cable gland connection if terminated properly. 
10 Verify proper labeling and designating of circuits. 
11 Check DB Schedule is posted at inside of door. 
12 Verify all the metal parts are connected by Earth continuity conductor. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.13 Test/Checks on all Distribution Boards (DBs)


LOCATION:- THIRD FLOOR
MCC Manufacturer: SCHNEIDER. BIN GALIB
DB Ref.:
Voltage Rating:
Bus bar Rating:
Fault Rating:
IP Rating:
Drawing Ref. No.:
Checks Checked
01 Check distribution board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 16 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

04 Inspect bus bar, neutral & earth terminals, and internal components. 
05 Check main isolator, and all outgoing branch MCBs with drawings and specifications. 
06 Inspect terminations/connections to MCBs and terminals for tightness. 
07 Test all outgoing branch circuits to verify insulation resistance and continuity. 
08 Inspect dead front covers, panel doors for dents, scratches, etc. 
09 Check cable gland connection if terminated properly. 
10 Verify proper labeling and designating of circuits. 
11 Check DB Schedule is posted at inside of door. 
12 Verify all the metal parts are connected by Earth continuity conductor. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.14 Test/Checks on all Distribution Boards (DBs)


LOCATION:- ROOF FLOOR
MCC Manufacturer: SCHNEIDER. BIN GALIB
DB Ref.:
Voltage Rating:
Bus bar Rating:
Fault Rating:
IP Rating:
Drawing Ref. No.:
Checks Checked
01 Check distribution board's data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify mounting at wall, anchorage, clearances, and alignment. 
04 Inspect bus bar, neutral & earth terminals, and internal components. 
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 17 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

05 Check main isolator, and all outgoing branch MCBs with drawings and specifications. 
06 Inspect terminations/connections to MCBs and terminals for tightness. 
07 Test all outgoing branch circuits to verify insulation resistance and continuity. 
08 Inspect dead front covers, panel doors for dents, scratches, etc. 
09 Check cable gland connection if terminated properly. 
10 Verify proper labeling and designating of circuits. 
11 Check DB Schedule is posted at inside of door. 
12 Verify all the metal parts are connected by Earth continuity conductor. 

Note: See attached Insulation Test Report at APPENDIX.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.15 Tests/Checks on Power Factor Correction Units; PFCUs


Manufactures: SCHNEIDER. BIN GALIB
Drawing Ref. No.:

Checks Checked
01 Check equipment nameplate data with drawings and specification. 
02 Inspect physical and mechanical condition. 
03 Verify appropriate anchorage, required clearance, and alignment. 
04 Inspect all doors, panels, and sections for corrosion, dents, scratches, etc. 
05 Verify that fuse and/or circuit breaker size and types correspond to drawings. 
06 Check all outgoing MCCB ratings with drawings and specifications. 
07 Test all outgoing feeder circuits to verify insulation resistance and continuity 
08 All cables including gland connections were checked for tightness. 
09 Verify that all CTs, fuses, metering and indicating instruments, and selector switches 
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 18 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

correspond to drawings.
10 Inspect insulators for evidence of physical damage or contaminations. 
11 Verify if proper labels were provided or mounted on panels. 
12 Check if a laminated single line diagram is posted adjacent to the MSB. 
13 Check all the metal bodies are connected by ECC. 
14 Verify all the interface connections with BMS done by properly 

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

1.16 Tests/Checks on all Electrical & Auxiliary Wiring Devices;


Device Manufacturer:
Designations: Switches, Socket Outlets, Flex Outlets, DP Switches, Switched &
Un-switched Spur Units
Drawing Ref. No.:

Checks Checked
01 Compare nameplate with drawings and specification. 
02 Inspect for any missing components or loose parts, defects, etc. 
03 Inspect for proper terminations, and wire management. 
04 Check for plate cover mounting as to alignment and tightness. 
05 Inspect plate covers for dirt, scratches, dents, etc. 
06 Check all the earth wires are connected properly. 
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 19 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

07 Check the effectiveness of completed earthing installation earth fault loop impedance test 
08 Test continuity of ring main circuits of all final power. 

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

STAGE 2
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 20 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

PRE-COMMISSIONING TEST

Operational/Functional Test of the following:

Checks Checked
01 Test on Main Switch Board
02 Test on SMDB's
03 Test on all Control Panels
04 Test on Earthing and lightning protection system.
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 21 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

Notes/Comments:

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

2.1 Tests on Main Switch Board;


Ensure all incoming / outgoing Breaker ACBs will be kept off before.

Checks Checked
01 Check the power supply is available on the incomer ACB and indication lights are working 
normal.
02 Check the system voltage on each phases & neutral. 
03 Ensure all the incoming breakers of all SMDB's are kept open position. 
04 Kept off all O/G Breakers while Charge the power supply of MV panel incomer ACB 
05 Check the voltages and phases on the front panel. 
06 Close the MCCB's of outgoing feeders step by step and check the voltages & phase 
indication are properly working on the SMDB's.
07 RFE relay functions to be checked by Kahramaa Engineer while energizing the MV panel 
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 22 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

08 Check the battery Charger voltage showing properly. 

Note:
MV panel supply will be energized with the presence of manufacturer,Kahramaa and contractor.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

2.2 Test on SMDB's;

Checks Checked
01 Check the system voltage and phase indication are showing properly on the SMDB's front 
panel.
02 Ensure all the outgoing breakers are kept off before switch on the main incomer. 
03 Switch on the main incomer. 
04 Switch on the outgoing breakers one by one after switch the main breaker. 
05 Ensure the DB incomer isolators will be kept off while switch on the outgoing breakers. 
06 Ensure all the outgoing Feeders are found normal. 
07 Check the panels connected with full load. 
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 23 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

Note:

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

2.3 Test on all Control Panels;

Checks Checked
01 Check the system voltage and phase indication are working normal. 
02 Kept off all the outgoing breakers before switch on the main isolator. 
03 Check the power supply available at isolator end after switch on the sub feeders. 
04 Then switch on the isolator and check the rotation is working normal. 
05 Check all the BMS & fire alarm interface controls are working properly. 
06 Verify all the metal bodies are connected by ECC. 
07 Verify the polarity and phase rotation of all rotating equipments. 

Note:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 24 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

2.4 Test on Earthing and lightning protection system

Checks Checked
01 Check the Earth resistance is showing according to the Kahramaa regulations. 
02 Ensure the electrical Earth resistance reading found normal. 
03 Check the Qtel Earth resistance not grated than 1 Ohm. 
04 Check the cut ape/installations are done properly. 
05 Verify all the mechanical equipments are connected through network. 
06 Check earth fault loop impedance test of all the effectiveness earthing system installation 

Note:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 25 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

STAGE 3
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 26 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

COMMISSIONING TEST

Commissioning Test of the following:

Checks Checked
Test on Main Switch Board
Test on all Sub main Boards (SMBs)
Test on all Control Panels.
Test on all Distribution Boards (DBs)
Tests on Power Factor Correction Units
Tests on all Electrical & Auxiliary Wiring Devices
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 27 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

Notes:
1) Found the MV panels, PFCU, SMDB's, DB's & control panels working in normal conditions.
2) Ensure all the electrical wiring devices are working properly.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:

APPENDIX

In APPENDIX, attach all Test Results as required, Calibration Certificate of the Test Instrument
used, and all other attachments as necessary to complete this Document.

1- MV panel factory test reports.


Sub main board factory test reports.
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 28 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

Power factor correction unit’s factory test reports.

2- Calibration certificates of insulation Tester and multi meter. And earth resistance tester.
3- Insulation and continuity report of MV panels, SMDB's out going Feeder cables.
4- Insulation and continuity test report of distribution board final circuits for lighting and
power system.
5- Chick lists.
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 29 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

PROCEDURES

1- ELECTRICAL LIGHTING AND POWER SYSTEM


2- EARTHING AND LIGHTNING PROTECTION SYSTEM
3- TOOLS & SAFETY PROCEDURES
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 30 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

PROCEDURES

1.0 ELECTRICAL LIGHTING AND POWER


SYSTEM

Procedures:
1) All electrical Installations to be completed and approved by the consultant prior to start
the Testing and commissioning.
2) MV panels, SMDB's& PFCU's are tested at factory witnessed by the Consultant.
3) Insulation and Continuity test sheets provided along with inspection of each SMDB's and
DB's incoming and outgoing cables and final circuits.
4) Continuity/ insulation test will be take each phase to phase, phase to neutral and neutral
to earth conductors.
5) Test will be conducted within all the breakers in open position to confirm no short circuits
in the feeders.
6) Earth Leakage circuits will be tested for tripping the breakers properly.
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 31 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

7) Ensure main isolator of MVP, SMDB's& DB's will be kept off while energizing the power
supply.
8) Check the system Voltage reading by the selector switch on the front panel. (Phase to
phase and phase to neutral) and 3 phase supply available indication are showing
properly.
9) Outgoing feeders of MVP, SMDB's& final circuits of DB's close one by one.
10) Ensure all the feeders, sub feeders and final circuits are working in normal condition.
11) Verify the Polarity and phase rotation of all Fuses, control switches Isolators and
Motor/Pumps etc….
12) A test shall be made to verify the Continuity of all conductors (including ECC) of every
ring circuits and all reading shall be tabulated
Notes:
1- Earth continuity shall be checked for all the metal connecting points.
2- Checked all the wiring devices are connected and working properly.
3- Insulation resistance test shall be conducted twice the system supply voltage.

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 32 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

PROCEDURES

2.0 EARTHING AND LIGHTING


PROTECTION SYSTEM

Procedures:
1) ALL Earthing and lighting protection system installation to be completed and approved
prior to start Testing and Commissioning.
2) All Earth Pits shall be tested individually by the earth resistance tester and record the
values on the attached table while installation.
3) Check the electrical earth resistance up to the MVP, Generator and reading to be record.
4) QTEL and low current earth pit shall be tested separately.
5) Earthing for lightning protection system shall be tested from the down conductors to
earth pit.
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 33 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

6) Over all earth resistance readings to be taken for the lightning protection system earthing
and shall not be greater than 10 Ohms.
7) Verify all mechanical equipments are connected to the network.
8) Earth fault loop impedance test conducted for the complete earthing system installation.

Notes:

CARRIED OUT BY WITNESSED / APPROVED BY CONSULTANT

Name: Name:

Signature: Signature:

Date: Date:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 34 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

3.0 TOOLS & SAFETY PROCEDURES

3.1 Testing and commissioning tools:

1) Multi meter for continuity testing and voltage check.


2) Clamp meter
3) Electrical tool kit
4) Insulation resistance tester (Megger)
5) Earth Resistance Tester

3.2 SAFTY PROCEDURES

Project safety plan shall be adhered during the complete Testing &Commissioning of Room
Management System. Necessary safety precautions shall be taken care of:
METHOD STATEMENT
Issue Date 14/10/2013 ELECTRICAL TESTING & PAGE 35 of 35

Rev # 00 00 COMMISSIONING DOCUMENT NO.

• All employees shall wear PPE which shall be fit for purpose.

• Safe access to the place of work shall be provided for all employees.

• Only qualified and competent technicians shall perform the work in accordance with
relevant codes and practice.
• Good House Keeping shall be performed prior to leaving the work area.