You are on page 1of 13

Project : Zanitty Date

Location : Zanitty Designed b

Assumed Data * You are allowed to cha


Calculated data * You are NOT ALLOWE
No. of Rooms = 328
No. of persons per room = 2
Building Lowest level (m) = 0
Building Highest level (m) = 20
Total No. of persons = 656
: Zanitty
: Zanitty

* You are allowed to change


* You are NOT ALLOWED to change
Project : Zanitty Date
Location : Zanitty Designed b

Assumed Data
Calculated data

Table of total fixtures

Fixture type : private

FIXTURES / POINT NO. B3 B2 B1 G.F. F.F

Water closet (flush valve) 1 1 1 1 1


Water closet (flush tank) 1 1 1 1 1
Water Bidet 1 1 1 1 1
Hose for W.C 1 1 1 1 1
Lavatory (& H.B.) 1 1 1 1 1
Janitor Sink 1 1 1 1 1
Service sink 1 1 1 1 1
Shower 1 1 1 1 1
Bath tub 1 1 1 1 1
Kitchen sink 1 1 1 1 1
Dishwashing machine 1 1 1 1 1
Laundry 1 1 1 1 1
Ablution (Public) 1 1 1 1 1
Urinal (1" flush valve) 1 1 1 1 1
Urinal (3/4" flush valve) 1 1 1 1 1
Urinal (flush tank) 1 1 1 1 1

TOTAL DOMESTIC WATER DEMAND CALCULATION Fixtures type : private


Weight in Fixture units
FIXTURES Quantity
Cold Hot Total
Water closet (flush valve) 6 0 6 15
Water closet (flush tank) 3 0 3 15
Water Bidet 0.75 0.75 1 15
Hose for W.C 0.75 0.75 1 15
Lavatory (& H.B.) 0.75 0.75 1 15
Janitor Sink 0.75 0.75 1 15
Service sink 1.5 1.5 2 15
Shower 1.5 1.5 2 15
Bath tub 1.5 1.5 2 15
Kitchen sink 1.5 1.5 2 15
Dishwashing machine 0 1 1 15
Laundry 1.5 1.5 2 15
Ablution (Public) 1 1 1.5 15
Urinal (1" flush valve) 10 0 10 15
Urinal (3/4" flush valve) 5 0 5 15
Urinal (flush tank) 3 0 3 15
Total Fixture Units
WATER DEMAND ( GPM )
WATER DEMAND ( m3/ h )

flush tank valve


577.5 139.0 153.2
187.5 62.5 88.6875
652.5 152.5 163.96
0 0 0
6 5 27
8 6.5 27
10 8 27
12 9.2 28.6
14 10.4 30.2
16 11.6 31.8
18 12.8 33.4
20 14 35
25 17 38
30 20 41
35 22.5 43.8
40 24.8 46.5
45 27 49
50 29 51.5
60 32 55
70 35 58.5
80 38 62
90 41 64.8
100 43.5 67.5
120 48 72.5
140 52.5 77.5
160 57 82.5
180 61 87
200 65 91.5
225 70 97
250 75 101
275 80 105.5
300 85 110
400 105 126
500 125 142
750 170 178
1000 208 208
1250 240 240
1500 267 267
1750 294 294
2000 321 321
2250 348 348
2500 375 375
2750 402 402
3000 432 432
4000 525 525
5000 593 593
6000 643 643
7000 685 685
8000 718 718
9000 745 745
10000 769 769

Public Private
Cold Hot Total Cold Hot
Water closet (flush valve) 10 0 10 6
Water closet (flush tank) 5 5 3
Water Bidet 1.5 1.5 2 0.75 0.75
Hose for W.C 1.5 1.5 2 0.75 0.75
Lavatory (& H.B.) 1.5 1.5 2 0.75 0.75
Janitor Sink 1.5 1.5 2 0.75 0.75
Service sink 2.25 2.25 3 1.5 1.5
Shower 3 3 4 1.5 1.5
Bath tub 3 3 4 1.5 1.5
Kitchen sink 3 3 4 1.5 1.5
Dishwashing machine 1 1 1
Laundry 3 3 4 1.5 1.5
Ablution (Public) 1 1 1.5 1 1
Urinal (1" flush valve) 10 10 10
Urinal (3/4" flush valve) 5 5 5
Urinal (flush tank) 3 3 3
: Zanitty
: Zanitty

* You are allowed to change


* You are NOT ALLOWED to change

2nd.F 3rd F 4th F. 5th F 6th F 7th F 8th F 9th F

1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1

Total weight in fixture units


Cold Hot Total
90 0 90
45 0 45
11.25 11.25 15
11.25 11.25 15
11.25 11.25 15
11.25 11.25 15
22.5 22.5 30
22.5 22.5 30
22.5 22.5 30
22.5 22.5 30
0 15 15
22.5 22.5 30
15 15 22.5
150 0 150
75 0 75
45 0 45
577.5 187.5 652.5
153.2 GPM 88.7 GPM 164.0 GPM
34.77 m3/h 20.13 m3/h 37.22 m3/h
Private
Total
6
3
1
1
1
1
2
2
2
2
1
2
1.5
10
5
3
10th F 11th F 12th F 13th F 14th F Total fixtures

1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
1 1 1 1 1 15
Project : Zanitty
Location : Zanitty

Assumed Data
Calculated data
Given Data:
Number of persons = 656
Design Basis of Water Supply System
Water Supply Demand:

Water Consumption(L/person/day) = 400


Water demand per day(m3/ day) = 262

Main Water Feeder :

Flow rate required ; Q(m3/ sec) = 0.003

Under Ground Water Tank :

Duration Assumption (day) = 2


Storage Fire Fighting Demand (m3) = 150

Storage water supply Demand (m3) = 656


Total Storage Demand (m3) = 806

Tank depth (m) = 3 * Could be changed according to Arch. Requirement


Tank Length (m) = 10 * Could be changed according to Arch. Requirement
Tank Width (m) = 27
Actual Area of Tank (m2) = 269
Tank depth (m) = 3
Tank Length (m) = 10
Tank Width (m) = 27

Upper Roof Water Tank :

Duration Assumption (day) = 0.5


Tank Storage Required (m3) = 131
Date : Zanitty
Designed b : Zanitty

* You are allowed to change


* You are NOT ALLOWED to change

ding to Arch. Requirement


ding to Arch. Requirement
Project : Zanitty Date : Zanitty
Location : Zanitty Designed b : Zanitty

Assumed Data * You are allowed to change


Calculated data * You are NOT ALLOWED to change
Q (m3/day) = 262.4
Pump working hours = 12
Then

Lifting Pump Calculations


Pump Discharge
Q (GPM) = 96

Pump Head
Static Head Hs (m) = 22
Assume Losses (m) = 0.3 of static Head
Losses = 6.6

Pump Head (m) = 31

Time Required to Fill Upper Roof Tank

T (Hr) = 0.379747

Power

Pump Efficiency = 0.8


Power (Hp) = 3

Booster Pump Calculations

Pump Discharge

Q (GPM) = 164
Pump Head (m) = 22

Power

Pump Efficiency = 0.8


Power (Hp) = 4