TABLE 709.

1
DRAINAGE FIXTURE UNITS FOR FIXTURE AND GROUPS
DRAINAGE FIXTURE UNIT MINIMUM OF TRAP
FIXTURE TYPE VALUE AS LOAD FACTORES (inches)
Automatic clothes washers, commercial ᵃ ᵍ 3 2
Automatic clothes washers, residential ᵍ 2 2
Bathroom group as defined in Section 202 (1.6 gpf 5 ­
water closeth) ᶠ
Bathroom group as defined in Section 202 (1.6 gpf 6 ­
water flushing greater than 1.6 gpf) ᶠ
Bathtub ᵇ (with or without overhead shower or 2 1½
whirpool attachments)
Bidet 1 1¼
Combination sink and tray 2 1½
Dental lavatory 1 1¼
Dental unit or cuspidor 1 1¼
Dishwashing machine, ᶜ domestic 2 1½
Drinkin fountain 0.5 1¼
Emergency floor drain 0 2
Floor drain 2 2
Kitchen sink domestic 2 1½
Kitchen sink, domestic with food waste grinder and/or 2 1½
dishwasher
Laundry tray (1 or 2 compartments) 2 1½
Lavatory 1 1¼
Shower 2 1½
Service sink 2 1½
Sink 2 1½
Urinal 4 Note d
Urinal, 1 gallon per flush or less 2ᶜ Note d
Urinal, nonwater supplied 0.5 Note d
Wash sink (circular or multiple) each set of faucets 2 1½
Water closet, flushometer tank, public o private 4ᵉ Note d
Water closet, private (1.6 gpf) 3ᵉ Note d
Water closet, private (flushing greater than 1.6 gpf) 4ᵉ Note d
Water closet, public (1.6 gpf) 4ᵉ Note d
Water closet, public (flushing greater than 1.6 gpf) 6ᵉ Note d
ᵃ For a traps larger than 3 inches, use Table 709.2
ᵇ A showerhead over a bathtub or whirlpool bathtub attachment does not increase the drainage fixture unit valve
ᶜ See sections 709.2 throught 709.4 for methods of computing unit value of fixtures not listed in this
table or for rating of devices with intermittent flows.
ᵈ Trap size shall be consistent with the fixture outlet size.
ᵉ For the purpose of computing loads on building drains and sewers, water closets and urinals shall
not be rated at a lower drainage fixture unit unless the lower values are confirmed by testing.
ᶠ For fixtures added to a dwelling unit bathroom group, add the dfu value of those additional fixtures
to the bathroom group fixture count.
ᵍ See the section 406.3 for sizing requeriments for fixture drain, branch, and drainage stack for an
automatic clothes washer standpipe.
TABLE 709.2
DRAINGE FIXTURE UNITS FOR FIXTURE DRAINS OR TRAPS
FIXTURE DRAIN OR TRAP SIZE
DRAIN FIXTURE UNIT VALUE
(inches)
1¼ 1
1½ 2
2 3
2½ 4
3 5
4 6
TABLE 710.1(1)
BUILDING DRAINS AND SEWERS
MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS CONNECTED TO ANY PORTION OF THE BUILDING
DIAMETER OF PIPE DRAIN OR THE BUILDING SEWER, INCLUDING BRANCHES OF THE BUILDING DRAIN ᵃ
(inches) Slope per foot
¹/₁₆ inches ⅛ inch ¼ inch ½ inch
1¼ ­ ­ 1 1
1½ ­ ­ 3 3
2 ­ ­ 21 26
2½ ­ ­ 24 31
3 ­ 36 42 50
4 ­ 180 216 250
5 ­ 390 480 575
6 ­ 700 840 1000
8 1400 1600 1920 2300
10 2500 2900 3500 4200
12 3900 4600 5600 6700
15 7000 8300 10000 12000
for SI: 1 inch = 25.4 mm, 1 inch per foot = 83.3 mm/m
ᵃ the minimun size of any building drain serving a water closet shall be 3 inches.
TABLE 710.1(2)
HORIZONTAL FIXTURE BRANCHES AND STACKS ᵃ
DIAMETER OF PIPE MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS (dfu)
(inches) Stacks ᵇ
Total for horizontal Total discharge into one Total for stack of three Total for stack greater than
branch branch interval branch intervals or less three branch intervals.
1½ 3 2 4 8
2 6 6 10 24
2½ 12 9 20 42
3 20 20 48 72
4 160 90 240 500
5 360 200 540 1100
6 620 350 960 1900
8 1400 600 2200 3600
10 2500 1000 3800 5600
12 2900 1500 6000 8400
15 7000 Note ᶜ Note ᶜ Note ᶜ
For SI: 1 inch = 25.4 mm
ᵃ Does not include branches of the building drain. Refer 710.1(1)
ᵇ Stacks shall be sized based on the total accumulated connected load at each story or branch interval.
As the total accumulated connected load decreases. Stacks are permitted to be reduced in size. the diameter
Stack diameters shall not be reduced to less than one-half of the diameter of the largest stack size required.
ᶜ Sizing load based on design criteria.
TABLE 906.1 TABLE 908.3
MAXIMUM DISTANCE OF FIXTURE TRAP FROM VENT COMMON VENT SIZES
SIZE OF TRAP SLOPE (inch PIPE SIZE
DISTANCE FROM TRAP (feet)
(inches) per foot) (inches)
1¼ ¼ 5 1½
1½ ¼ 6 2
2 ¼ 8 2½ to 3
3 ⅛ 12
4 ⅛ 16

TABLE 910.4
WASTE STACK VENT SIZE
MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS
STACK SIZE (dfu)
(inches) Total discharge into
Total discharge for stack
one branch interval
1½ 1 2
2 2 4
2½ No limit 8
3 No limit 24
4 No limit 50
5 No limit 75
6 No limit 100
TABLE 908.3 TABLE 909.3
COMMON VENT SIZES WET VENT SIZES
MAXIMUM DISCHARGE FROM WET VENT PIPE SIZE DRAINAGE FIXTURE UNIT
UPPER FIXTURE DRAIN (dfu) (inches) LOAD (dfu)
1 1½ 1
4 2 4
6 2½ to 3 6
TABLE 916.1
SIZE AND DEVELOPED LENGTH OF STACK VENTS AND VENT STACKS
DIAMETER OF SOIL TOTAL FIXTURE MAXIMUM DEVELOPED LENGTH OF VENT (feet) ᵃ
OR WASTE STACK UNITS BEING DIAMETER OF VENT (inches)
(inches) VENTED (dfu) 1¼ 1½ 2 2½ 3 4 5 6 8 10
1¼ 2 30
1½ 8 50 150 ­ ­ ­ ­ ­ ­ ­ ­
1½ 10 30 100
2 12 30 75 200
2 20 26 50 150 ­ ­ ­ ­ ­ ­
2½ 42 30 100 300
3 10 42 150 360 1,040
3 21 ­ 32 110 270 810 ­ ­ ­ ­ ­
3 53 27 94 230 680
3 102 25 86 210 620
4 43 ­ 35 85 250 980 ­ ­ ­ ­
4 140 27 65 200 750
4 320 23 55 170 640
4 540 ­ ­ 21 50 150 580 ­ ­ ­
5 190 28 82 320 990
5 490 21 63 250 760
5 940 ­ ­ ­ 18 53 210 670 ­ ­ ­
5 1400 16 49 190 590
6 500 33 130 400 1000
6 1100 ­ ­ ­ ­ 26 100 310 780 ­ ­
6 2000 22 84 260 660
6 2900 20 77 240 600
8 1800 ­ ­ ­ ­ 31 95 240 940 ­
8 3400 24 73 190 720
8 5600 20 62 160 610
8 7600 ­ ­ ­ ­ ­ 18 56 140 560
10 4000 31 78 310 960
10 7200 24 60 240 740
10 11000 ­ ­ ­ ­ ­ ­ 20 51 200 630
10 15000 18 46 180 570
12 7300 31 120 380
12 13000 ­ ­ ­ ­ ­ ­ ­ 24 94 300
12 20000 20 79 250
12 26000 18 72 230
15 15000 ­ ­ ­ ­ ­ ­ ­ 40 130
15 25000 31 96
15 38000 26 81
15 50000 ­ ­ ­ ­ ­ ­ ­ ­ 24 74
12

940
720
610
500
310
240
200
180
CONTEO DE ARTEFACTOS SANITARIOS CASA SAN BLAS (RAMAL A y B)

TOTAL PARA
DESCRIPCIÓN ARTEFACTO SANITARIO NIVEL 1 NIVEL 2 TODA LA
EDIFICACIÓN
INODOROS
Inodoro fluxómetro Ø 1" estándar
Inodoro fluxómetro Ø 1" ADA p/discapac.
Inodoro tanque estándar 2 2 4
Inodoro tanque ADA p/discapac.
LAVAMANOS
Lavamanos de colgar
Lavamanos de empotrar tipo ovalín 5 5 10
URINAL
Urinal fluxómetro 1 gpf.
FREGADEROS
Fregadero con escurridor acero inoxid. 1 1
Poceta de acero inoxidable
DUCHAS
Ducha estándar 1 2 3
Tapón resumidero 2" 1 2 3
Fecha:
PROYECTO: Por: Revisó:
Hotel ASIA Descrip:
Hoja: de

`
Calculo Total Sist. A.N Ramales A y B

UNIDADES DE
DESCRIPCION DE ARTEFACTOS CANTIDAD CARGA

TABLA 709.1 UNIDAD DE DESAGÜE PARA ARTEFACTOS


Inodoro de tanque privado 4 3.0
lavamanos privado 10 1.0
Ducha privada 3 2.0
Resumidero de piso 3 2.0
Fregadero privado 1 2.0

TOTAL
Total para la bajante para mas de 3 intervalos de ramal
Máximo dfu para B.A.N 4" (Tabla 710.1(2))
Total intervalos de ramal de la casa
Total dfu para 3 intervalos de ramal

Máximo dfu para B.A.N 4" (Tabla 710.1(2))

Diámetro de diseño para bajante de aguas negras: 4"


DIAMETRO
TOTAL MÍNIMO

12 3"
10 1¼"
6 2"
6 2"
2 1½"

36.00

500 CUMPLE
40 ˂ 90.00
120 ˂ 240.00

500 CUMPLE
Fecha:
PROYECTO: Por: Revisó:
Hotel ASIA Descrip:
Hoja: de

`
Calculo Total Sist. A.N Ramales A y B

UNIDADES DE
DESCRIPCION DE ARTEFACTOS CANTIDAD CARGA

TABLA 709.1 UNIDAD DE DESAGÜE PARA ARTEFACTOS


Inodoro fluxómetro público 4.0
Inodoro de tanque público 4.0
Inodoro de tanque privado #REF! 3.0
Urinario con válvula flux. 1 gpf 2.0
Lavamanos público 1.0
lavamanos privado #REF! 1.0
Ducha privada #REF! 2.0
Resumidero de piso #REF! 2.0
Fregadero privado 2.0
Fregadero público 2.0
Pocetas de aseo 2.0

Total para la bajante para mas de 3 intervalos de ramal


Máximo dfu para B.A.N 3" (Tabla 710.1(2))
Máximo dfu para B.A.N 4" (Tabla 710.1(2))
Total intervalos de ramal del edificio
Total dfu para 3 intervalos de ramal

Máximo dfu para B.A.N 4" (Tabla 710.1(2))

Diámetro de diseño para bajante de aguas negras: 4"


DIAMETRO
TOTAL MÍNIMO

3"
3"
#REF! 3"
2"
1¼"
#REF! 1¼"
#REF! 2"
#REF! 2"
1½"
1½"
2"

#REF!

72 NO CUMPLE
500 CUMPLE
8 ˂ 90.00
24 ˂ 240.00

500 CUMPLE
Fecha:
PROYECTO: Por: Revisó:
Hotel ASIA Descrip:
Hoja: de

`
Calculo Total Sist. A.N Ramales A y B

UNIDADES DE
DESCRIPCION DE ARTEFACTOS CANTIDAD CARGA

TABLA 709.1 UNIDAD DE DESAGÜE PARA ARTEFACTOS


Inodoro de tanque privado 2 3.0
lavamanos privado 5 1.0
Ducha privada 1 2.0
Resumidero de piso 1 2.0

Máximo dfu para 3" a S= 1% (Tabla 710.1(1))


Máximo dfu para 4" a S= 1% (Tabla 710.1(1))
DIAMETRO
TOTAL MÍNIMO

6 3"
5 1¼"
2 2"
2 2"

15.00
20 NO CUMPLE
160 CUMPLE
Fecha:
PROYECTO: Por: Revisó:
Descrip:
Hoja: de

`
Calculo Total Sist. Ventilación A.N Ramal C

UNIDADES DE
DESCRIPCION DE ARTEFACTOS CANTIDAD CARGA TOTAL
TABLA 709.1 UNIDAD DE DESAGÜE PARA ARTEFACTOS
Inodoro fluxómetro público 4.0
Inodoro de tanque público 4.0
Inodoro de tanque privado 4 3.0 12
Urinario con válvula flux. 1 gpf 2.0
Lavamanos público 1.0
lavamanos privado 10 1.0 10
Ducha privada #REF! 2.0 #REF!
Resumidero de piso #REF! 2.0 #REF!
Fregadero privado 2.0
Fregadero público 2.0
Pocetas de aseo 2.0

Total unidades de descarga (dfu) del ramal #REF!


Máximo dfu para BAN 4", Tubo Vent. Ø 3" a 200' de distancia 140
Máximo dfu para BAN 4", Tubo Vent. Ø 4" a 640' de distancia 320
Tubería principal de ventilación 4"
DIAMETRO
MÍNIMO

3"
3"
3"
2"
1¼"
1¼"
2"
2"
1½"
1½"
2"

NO CUMPLE
CUMPLE
Fecha:
PROYECTO: Por: Revisó:
Descrip:
Hoja: de

`
Calculo Total Sist. Ventilación A.N Ramales A y B

UNIDADES DE
DESCRIPCION DE ARTEFACTOS CANTIDAD CARGA TOTAL
TABLA 709.1 UNIDAD DE DESAGÜE PARA ARTEFACTOS
Inodoro de tanque privado 4 3.0 12
lavamanos privado 10 1.0 10
Ducha privada 3 2.0 6
Resumidero de piso 3 2.0 6
Fregadero privado 1 2.0 2

Total unidades de descarga (dfu) del ramal 36


Máximo dfu para BAN 6", Tubo vent. Ø 4" a 400' de distancia 500
Máximo dfu para BAN 6", Tubo Vent. Ø 6" a 780' de distancia 1100
Tubería principal de ventilación 4"
DIAMETRO
MÍNIMO

3"
1¼"
2"
2"
1½"

CUMPLE
NO CUMPLE
Fecha:
PROYECTO: Por: Revisó:
Descrip:
Hoja: de

`
Calculo Total Sist. Ventilación A.N Ramales A y B

UNIDADES DE
DESCRIPCION DE ARTEFACTOS CANTIDAD CARGA TOTAL
TABLA 709.1 UNIDAD DE DESAGÜE PARA ARTEFACTOS
Inodoro fluxómetro público 4.0
Inodoro de tanque público 4.0
Inodoro de tanque privado 2 3.0 6
Urinario con válvula flux. 1 gpf 2.0
Lavamanos público 1.0
lavamanos privado 5 1.0 5
Ducha privada 1 2.0 2
Resumidero de piso 1 2.0 2
Fregadero privado 2.0
Fregadero público 2.0
Pocetas de aseo 2.0

Total unidades de descarga (dfu) del ramal 15


Máximo dfu para 1 1/2" a 30' de distancia 42
Máximo dfu para 2" a 100' de distancia 42
Tubería horizontal de ventilación 1 1/2"
DIAMETRO
MÍNIMO

3"
3"
3"
2"
1¼"
1¼"
2"
2"
1½"
1½"
2"