You are on page 1of 10

ELECTRICAL DESIGNS AND DRAWINGS

client

MINISTRY OF INTERNAL SECURITY (PUNTLAND STATE


POLICE), PUNTLAND - SOMALIA

project

PROPOSED POLICE STATION IN ABAAREY - SOMALIA


-
ELECTRICAL DRAWINGS (PV SOLAR POWER)

MAY 2023

PROJECT NUMBER: TSU - 2022 - 004A REV


PROJECT STATUS: TENDER DRAWINGS 00
East Africa Hub (EAH), Nairobi
UNOPS Building, UN lane,
Off UN Avenue P.O. Box 783,
Village Market, 00621
Nairobi, Kenya.
UNOPS is ISO 9001 certified
NOTES
1. All dimensions are in mm, unless
otherwise stated.
2. All dimensions to be checked and
confirmed on site before commencement
ELECTRICAL DRAWINGS LIST of any work.
3. Written dimensions overrides scaled
dimensions,thus all dimensions are to
ITEM DWG NO. DESCRIPTION be read and not at any time scaled
from the drawing.
4. Any discrepancy to be reported to
the UNOPS Site Engineer/ Project
Manager promptly before proceeding.

1 EE-00 COVER SHEET


NO. REVISION DATE APPR.

2 EE-01 DRAWING LIST

3 EE-02 ELECTRICAL NOTES

4 EE-03 ELECTRICAL - SCHEDULE OF SYMBOLS

5 EE-04 SOLAR PANEL LAYOUT / ARRANGEMENT CLIENT

MINISTRY OF INTERNAL
6 EE-05 BATTERY ROOM LAYOUT SECURITY (PUNTLAND STATE
POLICE), PUNTLAND - SOMALIA

7 EE-06 SITE PLAN- DUCT LAYOUT


PROJECT

8 EE-07
SINGLE LINE DRAWING PROPOSED POLICE STATION IN
ABAAREY

9 EE-08 PANEL MOUNTING DETAILS


DRAWING TITLE

10 EE-10 DETAIL - 1: EARTHING DETAILS electrical drawing list

TECHNICAL SERVICES UNIT


SIGN DATE
DRAWN BY
OKOTH M
CHECKED BY Anthony A.
APPROVED BY PHILIP G
P.M.
ISSUE DATE:
May 2023 Signature

DRAWING NUMBER: REV.


EE-01
TENDER DRAWINGS

COPYRIGHT RESERVED
THIS DESIGN AND DETAILS ARE, AND AT ALL TIMES
THE EXCLUSIVE PROPERTY OF THE
UNOPS-KEMC-TSU,NAIROBI.
AND CANNOT BE USED OR REPRODUCED WITHOUT
WRITTEN CONSENT.
Kenya Multi Country Office
(KEMC), Nairobi
UNOPS Building, UN lane,
Off UN Avenue P.O. Box 783,
GENERAL
Village Market, 00621
1.0 2.0 CABLES 6.0 SOLAR PANELS
Nairobi, Kenya.
1.1 THE DESIGN DRAWINGS SHALL BE READ IN CONJUNCTION 2.1 ALL WIRES AND CABLES SHALL BE STRANDED COPPER CONDUCTORS, 3.12 ALL BENDS IN DUCTS, CONDUITS AND OTHER RACEWAYS 6.1 SOLAR MODULE SHALL BE MADE BY MONO-CRYSTALLINE
WITH THE RELEVANT SPECIFICATIONS AND ARCHITECTURAL, PVC INSULATED COMPLYING WITH BS 6004 OR XLPE INSULATED AS PER SHALL BE SUITABLE TO ALLOW MINIMUM CABLE BENDING COMPLYING WITH IEC 61215 AND IEC 61701
STRUCTURAL, CIVIL & MECHANICAL DRAWINGS AND RADIUS IN ACCORDANCE WITH MANUFACTURER'S
SPECIFICATIONS.
IEC 502 AS SHOWN ON DRAWINGS OR SCHEDULES, EXCEPT FOR
INFLAMABLE/EXPLOSIVE AND OTHER EXCEPTIONAL SITUATIONS. RECOMMENDATIONS. NOTES
1.2 THESE NOTES ARE GENERALLY APPLICABLE TO THE 6.2 SOLAR PANELS SHALL BE INSTALLED AT AN ANGLE
2.2 COLOUR CODE OF ELECTRICAL WIRES AND CABLES SHALL 3.13 ALL ENDS OF BURIED DUCTS AND CONDUITS SHALL HAVE OF ‘(LATITUDE OF THE PLACE + 10) DEGREES
OVERALL SYSTEMS INSTALLATION. ANY ADDITIONAL NOTES FROM HORIZONTAL
BE RED, YELLOW, BLUE, BLACK AND GREEN/YELLOW FOR L1, BELL MOUTH PIPE ENDS AND SHALL BE SEALED BY A 1. All dimensions are in mm, unless
ON INDIVIDUAL DRAWINGS WHICH ARE SUPPLEMENTARY TO
L2, L3, NEUTRAL AND EARTH RESPECTIVELY IN A THREE PROPRIETARY PIPE SEALING PRODUCT. otherwise stated.
THESE NOTES SHALL BE READ WITH THE INSTRUCTIONS SOLAR PANELS SHALL BE INSTALLED SOUTH FACING IN
PHASE CONFIGURATION. 6.3 2. All dimensions to be checked and
STATED HEREIN. 3.14 CABLE LADDERS AND CABLE TRAYS SHALL BE INSTALLED THE NORTHERN HEMISPHERE AND NORTH FACING IN THE
2.3 THE CONDUCTOR SIZES FOR ALL CABLES SHALL BE IN confirmed on site before commencement
1.3 THE FINAL POSITION OF ALL EQUIPMENT, PANELS, WHERE NECESSARY AND ARE NOT LIMITED TO WHAT IS SOUTHERN HEMISPHERE
ACCORDANCE WITH THE PANEL BOARD/CABLE SCHEDULES of any work.
LUMINAIRES, DETECTORS, SWITCHES, OUTLETS AND OTHER SHOWN ON THE DRAWINGS. WIDTH, LENGTH, NUMBERS AND
AND SINGLE LINE DIAGRAMS. 3. Written dimensions overrides scaled
ACCESSORIES SHALL BE COORDINATED WITH THE ROUTES OF CABLE TRAYS, LADDERS, PIPES AND OTHER
ARCHITECTURAL, MECHANICAL AND INTERIOR DESIGN 2.4 THE MINIMUM SIZE OF ALL CIRCUIT CONDUCTORS SHALL BE dimensions,thus all dimensions are to
CABLE RACEWAYS SHALL BE SHOWN ON SHOP DRAWINGS AS MOUNTING STRUCTURE
DETAILS AND WILL BE APPROVED AT SITE BY THE COORDINATED WITH THE STARTING AND OPERATING PER STANDARDS FOR APPROVAL.
be read and not at any time scaled
ENGINEER. CHARACTERISTICS OF THE EQUIPMENT THEY SERVE. 6.4 MOUNTING STRUCTURE SHALL BE HOT DIP GALVANIZED MS from the drawing.
1.4 UNLESS OTHERWISE SPECIFIED ALL EQUIPMENT AND 2.5 UNLESS OTHERWISE INDICATED, MINIMUM WIRE SIZE SHALL 3.15 WHERE OPENINGS ARE PROVIDED IN STRUCTURE TO CROSS MOUNTING STRUCTURES SHALL BE USED FOR MOUNTING 4. Any discrepancy to be reported to
MATERIALS TO BE USED SHALL BE SUITABLE AND RATED BE 1.5MM² FOR LIGHTING AND 2.5MM² FOR POWER. CABLE TRAYS, PIPES, ETC. THE OPENING SHALL BE SEALED THE MODULES/PANELS/ARRAYS AND SHALL BE CORROSION the UNOPS Site Engineer/ Project
FOR THE SITE AMBIENT CONDITIONS. BY FIRE STOP MATERIAL SUITABLY RATED, AFTER RESISTANT Manager promptly before proceeding.
1.5 ALL ELECTRICAL WORKS SHALL COMPLY WITH THE 2.6 LIGHTING AND SMALL POWER INSTALLATIONS SHALL BE INSTALLATION OF CABLES.
RELEVANT MINISTRY OF PUBLIC WORKS REGULATIONS, CARRIED OUT USING SINGLE CORE PVC INSULATED WIRES INVERTER / CHARGER
LATEST EDITION OF IEE WIRING REGULATIONS, IN RIGID PVC CONDUITS EMBEDDED IN CONCRETE. 4.0 SWITCHGEAR / DISTRIBUTION BOARDS
6.5 INVERTER SHALL BE PURE SINE WAVE, HIGH EFFICIENCY
INTERNATIONAL ELECTRO-TECHNICAL COMMISSION (IEC) 2.7 ALL MULTICORE CABLES INSIDE THE BUILDING SHALL BE 4.1 ALL LIGHTING AND POWER DISTRIBUTION BOARDS (DB) TYPE NO. REVISION DATE APPR.
STANDARDS AND ISO RECOMMENDATIONS. INSTALLED ON CABLE TRAYS OR CABLE LADDERS. RAISED SHALL BE FLUSH MOUNTED TYPE IN ALL PUBLIC AND
SUN SHADES (COVERS) SHALL BE PROVIDED FOR ALL ROOF CIRCULATION AREAS AND SURFACE MOUNTED IN 6.6 INVERTER SHALL COMPLY WITH IEC 61683, 62109, UL 1741
1.6 THE INSTALLATION SHALL COMPLY IN ALL RESPECTS TO
MOUNTED CABLE TRAYS/LADDERS. ELECTRICAL/MECHANICAL AND PLANT ROOMS, UNLESS AMONG OTHER STANDARDS
THE REQUIREMENTS OF THE MANUFACTURERS AND THE
OTHERWISE INDICATED. THESE SHALL BE PROVIDED WITH
CODES REFERRED IN THE SPECIFICATIONS. 2.8 THE WIRES/CABLES FOR LV CIRCUITS INSIDE BUILDINGS LOCKABLE DOORS.
1.7 ANY EQUIPMENT DIMENSIONS AND ELECTRICAL LOAD SHALL BE INSTALLED AT A MINIMUM DISTANCE OF 300MM 4.2 THE TOTAL LOAD ON THE THREE PHASES SHALL BE BATTERIES
STATED ON THE DRAWINGS SHALL BE FROM HOT WATER LINES AND 150MM FROM OTHER SERVICE BALANCED AS EVENLY AS PROVIDED ON ALL SWITCHGEAR 6.7 BATTERIES SHALL BE MAINTENANCE FREE, DEEP CYCLE
COORDINATED/CONFIRMED WITH THE ACTUAL DIMENSIONS PIPES. AND DISTRIBUTION BOARDS. TYPE
AND ACTUAL ELECTRICAL LOAD OF EQUIPMENT FROM
2.9 WHERE EXTERNAL CABLES ARE DIRECT BURIED IN THE
RESPECTIVE MANUFACTURER(S). 6.8 BATTERIES SHALL BE LONG LIFE TYPE WITH DESIGN LIFE
GROUND, THESE SHALL RUN THROUGH UNDERGROUND 4.3 MINIATURE CIRCUIT BREAKERS (MCB) WITH APPROPRIATE
1.8 ALL MATERIALS AND EQUIPMENT MUST BE OF THE BEST OF MIN 20-YEARS
CONCRETE ENCASED UPVC DUCTS WHEN PASSING UNDER SHORT CIRCUIT CURRENT RATING SHALL BE PROVIDED FOR
QUALITY AND ACCORDING TO THE LATEST INTERNATIONAL ROADS AND BUILDINGS. LIGHTING, SWITCHED SOCKET OUTLETS, ELECTRIC WATER
STANDARDS. THE CONTRACTOR SHALL SUBMIT SAMPLES 6.9 BATTERIES SHALL COMPLY WITH IEC 61427, 61147
HEATERS/COOLERS, REFRIGERATORS, COOKERS, DOMESTIC CLIENT
AND CATALOGUES OF ALL MATERIALS AND OBTAIN 3.0 CONDUITS, CABLE TRAYS AND TRUNKING WATER PUMPS AND SIMILAR EQUIPMENT.
ENGINEER'S APPROVAL BEFORE THE COMMENCEMENT OF MINISTRY OF INTERNAL
ANY WORK. 3.1 THE MINIMUM SIZE OF CONDUIT USED FOR ANY SYSTEM 4.4 THE OVERALL POWER FACTOR OF EVERY ELECTRICAL
WIRING SHALL BE 20MM INTERNAL DIAMETER. SUBSTATION SHALL BE MAINTAINED WITHIN THE RANGE OF SECURITY (PUNTLAND STATE
1.9 IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY TO 0.9 LAGGING AND UNITY. PROVIDE AUTOMATIC P.F. POLICE), PUNTLAND - SOMALIA
LIASE WITH THE LOCAL ELECTRICITY SUPPLY AUTHORITY 3.2 PVC CONDUITS SHALL BE HEAVY GAUGE, POLISHED AND
SMOOTH INSIDE AND OUTSIDE, FLAME-RETARDANT AND IMPROVEMENT PLANT.
FOR THE ELECTRICITY SUPPLY CONNECTION TO THE
FACILITY AND MAKE PROVISIONS IN INSTALLATION TO SUITABLE FOR USE AT AMBIENT TEMPERATURE OF 50°C. 4.5 THE CONTRACTOR HAS TO CHECK THE PHYSICAL DIMENSION PROJECT
SATISFY THEIR REQUIREMENTS. THE SERVICES PROVIDED 3.4 RIGID STEEL CONDUITS (RSC) SHALL BE HEAVY GAUGE, HOT OF THE PANELS WITH THE SPACE AVAILABILITY PRIOR TO
SHALL CONFORM IN ALL RESPECTS WITH THE LOCAL CODES DIP GALVANIZED TO CLASS 4 PROTECTION BOTH INSIDE PLACING THE ORDER. DRAWINGS FOR PANELS SHALL BE
SUBMITTED TO THE ENGINEER FOR APPROVAL. PROPOSED POLICE STATION IN
AND REGULATIONS. AND OUTSIDE.
ABAAREY
1.10 IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY TO 3.5 ALL PVC BOXES SHALL BE RIGID, FLAME-RETARDANT,
LIASE WITH LOCAL TELEPHONE AUTHORITY FOR THE SMOOTH AND ACCORDING TO LATEST 5.0 EARTHING/GROUNDING
REQUIRED TELEPHONE LINES TO THE FACILITY AND MAKE STANDARDS/SPECIFICATIONS.
PROVISIONS IN INSTALLATION TO SATISFY THEIR 3.6 ALL STEEL BOXES SHALL BE HEAVY GAUGE, HOT DIP 5.1 PROVIDE COMPLETELY INDEPENDENT AND CLEAN EARTHING DRAWING TITLE
REQUIREMENTS. THE SERVICES PROVIDED SHALL CONFORM GALVANIZED ACCORDING TO LATEST SYSTEM FOR LOW CURRENT/COMMUNICATION SYSTEMS,
IN ALL RESPECTS WITH THEIR STANDARDS/REGULATIONS. STANDARDS/SPECIFICATIONS. WHEN REQUIRED AS PER MANUFACTURER'S electrical notes
3.7 BRASS BUSHINGS AND RINGS SHALL BE USED TO SECURE
RECOMMENDATIONS OR LOCAL AUTHORITY REGULATIONS. sheet 1 of 2
1.11 THE LIGHTING, POWER AND LOW CURRENT SYSTEMS SHALL 5.2 A SEPARATE GROUNDING CONDUCTOR SHALL BE RUN WITH
STEEL CONDUITS WITH STEEL BOXES.
BE INSTALLED SEPARATELY FROM EACH OTHER. i.e. EACH CIRCUIT. ALL LIGHTING FIXTURES, RECEPTACLES,
CONDUITS, RACEWAYS, WIRES, BOXES, ETC. 3.8 ALL STEEL COUPLERS SHALL BE PAINTED SUITABLY, SWITCHES, METALLIC JUNCTION BOXES AND FITTINGS
IMMEDIATELY AFTER INSTALLATION. SHALL BE EFFECTIVELY AND PROPERLY EARTHED.
TECHNICAL SERVICES UNIT
1.12 CABLE SIZES, MCB's,MCCBs AND ISOLATORS SHOWN ON THE 3.9 NO CONDUIT RUN SHALL BE LONGER THAN 15M (STRAIGHT) SIGN DATE
DRAWINGS ARE BASED ON DESIGNED LOADS. THE 5.3 EARTH CONTINUITY CONDUCTORS AND BONDING
DRAWN BY
OKOTH M
OR WITH MORE THAN TWO 90° BENDS, OTHERWISE IT MUST
CONTRACTOR SHALL PROVIDE THE SIZE OF CABLE, MCB, BE PASSED THROUGH PULL OR DRAW BOX SUFFICIENT TO CONDUCTORS SHALL BE SINGLE CORE, PVC INSULATED.
MCCB AND ISOLATOR BASED ON ACTUAL LOADS OF THE CHECKED BY Anthony A.
PERMIT EASY PULLING OF WIRES. 5.4 EARTHING CONDUCTOR OF THE RESPECTIVE CIRCUIT SHALL
EQUIPMENT APPROVED BY THE ENGINEER
RUN IN THE SAME TRENCH/PIPE/TRUNKING OR ON SAME APPROVED BY PHILIP G
3.10 THE TOTAL FILL OF THE WIRES DRAWN IN CONDUIT SHALL CABLE TRAY/LADDER AS THE ASSOCIATED CABLE.
BE AS PER IEE REGULATIONS AND NORMALLY NOT TO P.M.
1.13 FOR SPECIAL SYSTEMS, THE CONTRACTOR IS TO SUBMIT 5.5 EXTRANEOUS METALWORK AS METALLIC PIPES, DUCTING, ISSUE DATE:
May 2023
EXCEED 40% OF THE INTERNAL CROSS-SECTIONAL AREA OF Signature
SHOP DRAWINGS PREPARED BY SPECIALISTS EXPERIENCED CABLE TRAYS, METALWORK IN TOILETS, ETC. SHALL BE
THE CONDUIT.
IN THE DESIGN OF THE RELEVANT SYSTEMS AND AS PER BONDED TO EARTHING SYSTEM BY PVC INSULATED CABLE IN DRAWING NUMBER: REV.
3.11 ALL CONDUITS AND RECEWAYS PASSING THROUGH THE
THE MANUFACTURERS REQUIREMENTS. ACCORDANCE WITH APPLICABLE STANDARDS.
BUILDING EXPANSION JOINTS SHALL BE PROVIDED WITH EE-002
EXPANSION JOINT COUPLING AND EXECUTED AS PER
STANDARD DETAILS, APPROVED BY THE ENGINEER ON SITE. TENDER DRAWINGS

COPYRIGHT RESERVED
THIS DESIGN AND DETAILS ARE, AND AT ALL TIMES
THE EXCLUSIVE PROPERTY OF THE
UNOPS-KEMC-TSU,NAIROBI.
AND CANNOT BE USED OR REPRODUCED WITHOUT
WRITTEN CONSENT.
Kenya Multi Country Office
POWER LEGEND EMS EMERGENCY STOP (KEMC), Nairobi
SYMBOL DESCRIPTION UNOPS Building, UN lane,
SWA STEEL WIRE ARMOURED
Off UN Avenue P.O. Box 783,
AFTER FINISHED FLOOR LEVEL / ABOVE FLOOR Village Market, 00621
AFFL
FINISHED LEVEL Nairobi, Kenya.
DB DISTRIBUTION BOARD
MCB MINIATURE CIRCUIT BREAKER
MB METER BOARD
MCCB MOULDED CASE CIRCUIT BREAKER
NOTES
CP CONTROL PANEL 1. All dimensions are in mm, unless
CU CONSUMER UNIT otherwise stated.
BCC 2. All dimensions to be checked and
BATTERY CHARGER CONTROLLER
confirmed on site before commencement
600 X 450 X 600 DEEP POWER MANHOLE COMPLETE of any work.
P
HEAVY DUTY WATER PROOF CONCRETE COVER CT CURRENT TRANSFORMER 3. Written dimensions overrides scaled
dimensions,thus all dimensions are to
VT VOLTAGE TRANSFOMER be read and not at any time scaled
from the drawing.
C/W COMPLETE WITH 4. Any discrepancy to be reported to
the UNOPS Site Engineer/ Project
Manager promptly before proceeding.
AMF AUTOMATIC MAINS FAILURE

ATS AUTOMATIC TRANSFER SWITCH


NO. REVISION DATE APPR.
ECC EARTH CONDUCTIVE CONDUCTOR

A AMPERE

KVA KILOVOLT AMPERE


ABBREVIATIONS
V VOLT
ABBREV DESCRIPTION
CL CURRENT LIMITED UPS UNINTERRUPTED POWER SUPPLY
HG HEAVY GAUGE HD HEAT DETECTOR CLIENT
PVC POLYVINYL CHLORIDE
SD SMOKE DETECTOR MINISTRY OF INTERNAL
BT BOTTOM ENTRY SECURITY (PUNTLAND STATE
POLICE), PUNTLAND - SOMALIA
TT TOP ENTRY PABX PRIVATE AUTOMATIC BRANCH EXCHANGE
TT / BT TOP AND BOTTOM ENTRY, TOP AND BOTTOM EXIT SP SPEAKER PROJECT

CIR CIRCUIT
TS TIME SWITCH PROPOSED POLICE STATION IN
TP / N OR TPN TRIPLE POLE AND NEUTRAL ABAAREY
PEC PHOTOELECTRIC CELL
SP / N OR SPN SINGLE POLE AND NEUTRAL
AB ADAPTABLE BOX DRAWING TITLE
CU CONSUMER UNIT
ELECTRICAL
JB JUNCTION BOX
DB DISTRIBUTION BOARD SCHEDULE OF SYMBOLS
LV PIR PASSIVE INFRARED
LOW VOLTAGE
HM HEAT MOTION DETECTOR
TECHNICAL SERVICES UNIT
SWG STANDARD WIRE GAUGE
SIGN DATE
BG BREAK GLASS
DRAWN BY
OKOTH M
MM MILLIMETRE
CHECKED BY Anthony A.
H/L HIGH LEVEL
SQ MM SQUARE MILLIMETRE
APPROVED BY PHILIP G
ELV EPS EMERGENCY POWER SUPPLY
EXTRA LOW VOLTAGE P.M.
ISSUE DATE: May 2023 Signature

HG HEAVY GAUGE UPVC UNPLASTICISED POLYVINYL CHLORIDE DRAWING NUMBER: REV.


EE-03
GI GALVANISED IRON CCU COOKER CONTROL UNIT
TENDER DRAWINGS
AWTL ABOVE WORKTOP LEVEL NTS NOT TO SCALE
COPYRIGHT RESERVED
THIS DESIGN AND DETAILS ARE, AND AT ALL TIMES
THE EXCLUSIVE PROPERTY OF THE
UNOPS-KEMC-TSU,NAIROBI.
AND CANNOT BE USED OR REPRODUCED WITHOUT
WRITTEN CONSENT.
Kenya Multi Country Office
(KEMC), Nairobi
UNOPS Building, UN lane,
Off UN Avenue P.O. Box 783,
1 2 3 4 Village Market, 00621
Nairobi, Kenya.

NOTES
1. All dimensions are in mm, unless
otherwise stated.
2. All dimensions to be checked and
confirmed on site before commencement
of any work.
3. Written dimensions overrides scaled
slope slope dimensions,thus all dimensions are to
be read and not at any time scaled
from the drawing.
4. Any discrepancy to be reported to
the UNOPS Site Engineer/ Project
Manager promptly before proceeding.

p e
slope

slope
sl slo
op
e NO. REVISION DATE APPR.

CLIENT

MINISTRY OF INTERNAL
SECURITY (PUNTLAND STATE
POLICE), PUNTLAND - SOMALIA

PROJECT

PANEL DETAILS: PROPOSED POLICE STATION IN


ABAAREY
Approx Length= 1135mm
Width = 1722mm DRAWING TITLE

weight= 21kg ROOF- PV PANEL


ARRANGEMENT LAYOUT

TECHNICAL SERVICES UNIT


16Nr. 420W PV SOLAR DRAWN BY
OKOTH M
SIGN DATE

PANELS- ROOF MOUNTED CHECKED BY Anthony A.


APPROVED BY PHILIP G
P.M.
ISSUE DATE:
May 2023 Signature

DRAWING NUMBER: REV.


EE-04
TENDER DRAWINGS

COPYRIGHT RESERVED
THIS DESIGN AND DETAILS ARE, AND AT ALL TIMES
THE EXCLUSIVE PROPERTY OF THE
UNOPS-KEMC-TSU,NAIROBI.
AND CANNOT BE USED OR REPRODUCED WITHOUT
WRITTEN CONSENT.
Kenya Multi Country Office
(KEMC), Nairobi
UNOPS Building, UN lane,
Off UN Avenue P.O. Box 783,
Village Market, 00621
Nairobi, Kenya.

NOTES
1. All dimensions are in mm, unless
otherwise stated.
2. All dimensions to be checked and
confirmed on site before commencement
of any work.
3. Written dimensions overrides scaled
dimensions,thus all dimensions are to
A B be read and not at any time scaled
from the drawing.
4. Any discrepancy to be reported to
the UNOPS Site Engineer/ Project
Manager promptly before proceeding.

1
5kW inverter NO. REVISION DATE APPR.

BATTERY DETAILS:

Approx Length= 521mm


Width = 268mm
Height= 225mm
weight= 73kg Battery Room CLIENT

MINISTRY OF INTERNAL
20Nr, BATTERY SECURITY (PUNTLAND STATE
POLICE), PUNTLAND - SOMALIA
OPzV12-200 (12V 200Ah)
2
PROJECT

step PROPOSED POLICE STATION IN


ABAAREY

DRAWING TITLE

BATTERY
ROOM-BATTERY
BATTERY ROOM LAYOUT ARRANGEMENT LAYOUT

TECHNICAL SERVICES UNIT


SIGN DATE
DRAWN BY
OKOTH M
CHECKED BY Anthony A.
APPROVED BY PHILIP G
P.M.
ISSUE DATE:
May 2023 Signature

DRAWING NUMBER: REV.


EE-05
TENDER DRAWINGS

COPYRIGHT RESERVED
THIS DESIGN AND DETAILS ARE, AND AT ALL TIMES
THE EXCLUSIVE PROPERTY OF THE
UNOPS-KEMC-TSU,NAIROBI.
AND CANNOT BE USED OR REPRODUCED WITHOUT
WRITTEN CONSENT.
Kenya Multi Country Office
(KEMC), Nairobi
UNOPS Building, UN lane,
Off UN Avenue P.O. Box 783,
new Village Market, 00621
bou Nairobi, Kenya.
nda
ry w NOTES
all
1. All dimensions are in mm, unless
otherwise stated.
2. All dimensions to be checked and
confirmed on site before commencement
of any work.
3. Written dimensions overrides scaled
EARTH INSPECTION dimensions,thus all dimensions are to
PIT-300x300x be read and not at any time scaled
200MM,C/W COVER,AS from the drawing.
DETAILED ON DRAWING
BATTERY 4. Any discrepancy to be reported to

all
ROOM the UNOPS Site Engineer/ Project
ry w WALL-MOUNTED Manager promptly before proceeding.
METER BOARD
nda

2x50MMØ PVC 75MMØ


CONDUITS IN FLOOR UNDERGROUND NO. REVISION DATE APPR.
SLAB P PVC DUCT
bou

600x450x600MM
MANHOLE COMPLETE
MAIN POLICE WITH COVER
POST BUILDING
new

32MMØ
UNDERGROUND PVC
CONDUIT TO
TOILET

INCOMING
ELECTRICITY
parking area with well SUPPLY
compacted murram CLIENT

MINISTRY OF INTERNAL
SECURITY (PUNTLAND STATE

all
ABLUTION POLICE), PUNTLAND - SOMALIA

ry w
BLOCK
PROJECT

nda
PROPOSED POLICE STATION IN
ABAAREY

bou
DRAWING TITLE

new
SITE PLAN
ELECTRICAL DUCTS/MANHOLE
LAYOUT
new
bou TECHNICAL SERVICES UNIT
n dary mai SIGN DATE
wal entr n
DRAWN BY
OKOTH M
l gate y
CHECKED BY Anthony A.
APPROVED BY PHILIP G
P.M.
ISSUE DATE:
May 2023 Signature

DRAWING NUMBER: REV.

new EE-06
bou TENDER DRAWINGS
nda
ry w
General Site Layout all
COPYRIGHT RESERVED
THIS DESIGN AND DETAILS ARE, AND AT ALL TIMES
THE EXCLUSIVE PROPERTY OF THE
UNOPS-KEMC-TSU,NAIROBI.
AND CANNOT BE USED OR REPRODUCED WITHOUT
WRITTEN CONSENT.
Kenya Multi Country Office
(KEMC), Nairobi
UNOPS Building, UN lane,
Off UN Avenue P.O. Box 783,
Village Market, 00621
Nairobi, Kenya.

NOTES
1. All dimensions are in mm, unless
otherwise stated.
2. All dimensions to be checked and
confirmed on site before commencement
of any work.
FOR FUTURE 3. Written dimensions overrides scaled
dimensions,thus all dimensions are to
be read and not at any time scaled
16mm 2/C PVC CU. from the drawing.
CABLES IN 4. Any discrepancy to be reported to
50MMØ PVC HG
SINGLE-PHASE CONDUIT the UNOPS Site Engineer/ Project
METER (BY LOCAL
POWER SUPPLIER)
Manager promptly before proceeding.
INCOMING
UNDERGROUND 10A SP
M
SERVICE LINE (BY SINGLE-PHASE 63A DP 3*1.5 SQ. MM SC CABLES IN Ø20MM PVC CONDUIT TO LIGHTING
LOCAL POWER CUT-OUT MCB
10A SP CCT CU 01/1
SUPPLIER) FUSE
3*1.5 SQ. MM SC CABLES IN Ø20MM PVC CONDUIT TO LIGHTING
NO. REVISION DATE APPR.
WEATHER PROOF WALL 16MM SQ. CCT CU 01/2
MOUNTED METER
10A SP
PVC/SWA/PVC
BOARD (AT THE 3*1.5 SQ. MM SC CABLES IN Ø20MM PVC CONDUIT TO LIGHTING
2/C CU.CABLE
BATTERY ROOM) CCT CU 01/3
3*2.5 SQ MM SC CABLES IN Ø25MM PVC CONDUIT TO 13 AMPS
30A SP RINGMAIN SOCKET OUTLETS CCT CU 01/4
3*2.5 SQ MM SC CABLES IN Ø25MM PVC CONDUIT TO 13 AMPS
ON 30A SP RINGMAIN SOCKET OUTLETS CCT CU 01/5

100mA
RCD
63A AUTO OFF 4.0MM SQ XLPE SWA PVC SHEATHED AND INSULATED CABLES
CHANGE OVER 100A SP/N 20A SP IN TRENCH AT 400MM UNDER GROUND CCT CU 01/06
ON ISOLATOR
SWITCH WITH 20A 240V, 50HZ 2-POLE CONTACTOR AC1 IN ENCLOSURE
MANUAL BYPASS
420Wp PV SOLAR PANELS
MOUNTED ON THE 4-CHANNEL COMBINER BOX 10A PHOTOCELL & OVERRIDE-SWITCH
MATERNITY BUILDING 200V, 100A WITH SURGE 4.0 SQ MM 4/C PVC/SWA/PVC CU. CABLES IN TRENCHES /
PROTECTION AND ISOLATOR SURGE
ROOF.(total=16 panels) 1 PROTECTION 30A SP DUCTS TO 32A SP ISOLATOR TO WATER PUMP CCT CU 01/7
DEVICE 100A DC CLIENT
2 ENERGY
ISOLATOR 2.5 SQ MM 2/C PVC/SWA/PVC CU. CABLES IN Ø32MM PVC
METER
1 4 20A SP CONDUIT TO 2WAY CONSUMER UNIT FOR TOILETS CCT 01/8 MINISTRY OF INTERNAL
M
SPARES SECURITY (PUNTLAND STATE
100A DC KWH
1 4
ISOLATOR
POLICE), PUNTLAND - SOMALIA
SPARES
1 4
2
10 WAY, 63A SPN CONSUMER PROJECT
UNIT CU-01 WITH 30mA RCD
1 4 EARTHING/ MAIN BUILDING)
GROUNDING PROPOSED POLICE STATION IN
ABAAREY
5.0kW,
24V/36V/48VDC-240VAC
CABLES: PURE SINE WAVE
INVERTER/ WITH CHARGE DRAWING TITLE
1. 4SQ.MM SC XLPE/SWA/XLPE COPPER CABLE CONTROLLER
2. 16SQ.MM SC XLPE/SWA/XLPE COPPER CABLE 20No, 200 AH
3. 6SQ.MM 2C XLPE/SWA/XLPE COPPER CABLE 12V SEALED- LONG LIFE
MAINTENANCE FREE
SINGLE LINE DIAGRAM
SPACE REQUIREMENTS: BATTERIES
1. EACH 300Wp SOLAR PANEL - 2200MM
(L)x1100MM (W) --APPROXIMATELY.

WEIGHT REQUIREMENTS:
TECHNICAL SERVICES UNIT
SIGN DATE
1. EACH SOLAR PANEL - 21KG (APPROX.) DRAWN BY
OKOTH M
CHECKED BY Anthony A.
APPROVED BY PHILIP G
P.M.
ISSUE DATE:
may 2023 Signature

DRAWING NUMBER: REV.


EE-07
TENDER DRAWINGS

COPYRIGHT RESERVED
THIS DESIGN AND DETAILS ARE, AND AT ALL TIMES
THE EXCLUSIVE PROPERTY OF THE
UNOPS-KEMC-TSU,NAIROBI.
AND CANNOT BE USED OR REPRODUCED WITHOUT
WRITTEN CONSENT.
Kenya Multi Country Office
(KEMC), Nairobi
UNOPS Building, UN lane,
Off UN Avenue P.O. Box 783,
Village Market, 00621
Nairobi, Kenya.

NOTES
1. All dimensions are in mm, unless
otherwise stated.
2. All dimensions to be checked and
confirmed on site before commencement
of any work.
3. Written dimensions overrides scaled
A B C D E F dimensions,thus all dimensions are to
be read and not at any time scaled
from the drawing.
4. Any discrepancy to be reported to
SEPARATION BETWEEN the UNOPS Site Engineer/ Project
Manager promptly before proceeding.
ROOF MOUNTED SOLAR THE TWO ROWS OF THE
PANELS WITH SOLAR PANELS
INCLINATION ANGLE OF
15-DEGREES NO. REVISION DATE APPR.

600
15

STEEL MOUNTING
STRUCTURE FIRMLY
ANCH0RED ON THE
ROOF SLAB CLIENT

MINISTRY OF INTERNAL
SECURITY (PUNTLAND STATE
Complaints POLICE), PUNTLAND - SOMALIA
Entrance Female Cell
Desk
PROJECT

PROPOSED POLICE STATION IN


ABAAREY

DRAWING TITLE

EARTHING AND
EQUIPOTENTIAL
BONDING STANDARDS.

TECHNICAL SERVICES UNIT


SIGN DATE
DRAWN BY
OKOTH M
CHECKED BY Anthony A.
APPROVED BY PHILIP G
P.M.
ISSUE DATE:
May 2023 Signature

DRAWING NUMBER: REV.


EE-08
TENDER DRAWINGS

COPYRIGHT RESERVED
THIS DESIGN AND DETAILS ARE, AND AT ALL TIMES
THE EXCLUSIVE PROPERTY OF THE
UNOPS-KEMC-TSU,NAIROBI.
AND CANNOT BE USED OR REPRODUCED WITHOUT
WRITTEN CONSENT.
Kenya Multi Country Office
(KEMC), Nairobi
UNOPS Building, UN lane,
Off UN Avenue P.O. Box 783,
Village Market, 00621
Nairobi, Kenya.

PIT COVER HANDLE NOTES


HEAVY DUTY RECESSED
COVER & FRAME. FINISH TO
MATCH WITH SURROUNDING. CONCRETE INSPECTION PIT 1. All dimensions are in mm, unless
FINISHED GRADE OR PAVEMENT
2 otherwise stated.
FINISHED LEVEL OF 2. All dimensions to be checked and
ROAD OR PAVED AREA confirmed on site before commencement
NATURAL SOIL FILLING of any work.
1 TO THE NORMAL LEVEL 3. Written dimensions overrides scaled
INSPECTION PIT dimensions,thus all dimensions are to
9 6 CABLE LUG be read and not at any time scaled
WARNING TAPE from the drawing.
EARTH BAR 4. Any discrepancy to be reported to
IF APPLICABLE CABLE COVERING TILES the UNOPS Site Engineer/ Project
Manager promptly before proceeding.
7
Y/G EARTH CABLE

8 8
PRE-DRILLED HOLE TO DEPTH OF 6m NO. REVISION DATE APPR.
SOIL

3
COUPLING
15mm HC HD COPPER
EARTH ELECTRODE
4 INSERTED IN TO
MINIMUM DEPTH OF 1500MM PRE-DRILLED HOLE TO
DEPTH MINIMUM OF 6m.
CLIENT

5 BACK-FILL HOLE WITH MINISTRY OF INTERNAL


MARCONITE IMPREGNATED SECURITY (PUNTLAND STATE
CONCRETE POLICE), PUNTLAND - SOMALIA

EARTH ELECTRODE INSPECTION PIT PROJECT

TYPICAL INSTALLATION DETAIL PROPOSED POLICE STATION IN


1 INSPECTION PIT, CONCRETE OR OF APPROVED EQUAL MATERIAL
TYPICAL DETAIL OF EARTH PIT ABAAREY

REMOVABLE PIT COVER, CAST IRON OR OF APPROVED EQUAL


2
MATERIAL DRAWING TITLE

3 EARTH ROD, Ø20MM COPPER CLAD STEEL, 3000MM LONG


ELECTRICAL
EARTHING DETAILS
4 EARTH ROD CONNECTOR

5 DRIVING TIP TECHNICAL SERVICES UNIT


DRIVING HEAD SIGN DATE
6 DRAWN BY
OKOTH M

7 ELECTRODE STRIP TO ROD CLAMP CHECKED BY Anthony A.


APPROVED BY PHILIP G
8 EARTH ELECTRODE, 70SQ MM BARE COPPER CONDUCTOR
P.M.
EARTHING CONDUCTOR OF THE FACILITY, 300MM COPPER-XLPEINSULATED
ISSUE DATE:
May 2023 Signature
9
WITH TWO OR THREE COIL TURNS OF APPROX. 250MM DIAMETER DRAWING NUMBER: REV.
EE-09
EARTHING STANDARD DETAILS TENDER DRAWINGS

COPYRIGHT RESERVED
THIS DESIGN AND DETAILS ARE, AND AT ALL TIMES
THE EXCLUSIVE PROPERTY OF THE
UNOPS-KEMC-TSU,NAIROBI.
AND CANNOT BE USED OR REPRODUCED WITHOUT
WRITTEN CONSENT.