Professional Documents
Culture Documents
3238.500 3244.500
3239.500 3245.500
3240.500 3245.510
3241.500 3245.600
3243.500
Yours
Rittal GmbH & Co. KG
35745 Herborn
Germany
E-mail: info@rittal.com
www.rittal.com
www.rittal.de
2 Safety instructions................................. 4
3 Product description............................... 4
3.1 Functional description........................................ 4
3.1.1 Main components............................................. 4
3.1.2 Control.............................................................. 5
3.1.3 Safety equipment.............................................. 5
3.1.4 Filter mats......................................................... 5
3.2 Intended use..................................................... 5
3.3 Scope of supply................................................ 5
6 Commissioning..................................... 8
7 Installing and changing the filter............ 8
7.1 Replacing the chopped-fibre filter...................... 8
7.2 Replacing the pleated filter................................ 9
5
Caution!
Potential threat to the product and its
environment. Fig. 1: Product description
Key
1 Function logo (to release the louvred grille)
Note: 2 Louvred grille
Useful information and special features. 3 Filter box with filter mat
4 Fan housing
5 Variable electrical connection
◾ The bullet point indicates an action to be performed.
3.1 Functional description
2 Safety instructions The EC fan-and-filter unit in conjunction with the cor-
Please observe the following safety instructions when responding outlet filter(s) is used to dissipate heat loss
assembling and operating the unit: from enclosures, ventilate the enclosure and protect
– Assembly, installation and servicing may only be temperature-sensitive components. This is achieved
performed by properly trained specialists. via the direct infeed of ambient air, the temperature
– Do not obstruct the air inlet and outlet of the EC fan- of which must be less than the admissible enclosure
and-filter unit inside and outside the enclosure (see interior temperature. The system is fitted into prepared
also section 4.2.2 "Layout of the components in the cut-outs.
enclosure", page 6).
– The louvres must always have their opening pointing 3.1.1 Main components
downwards. The EC fan-and-filter unit is comprised of the following
– Use only original spare parts and accessories. four main components: Fan motor, filter box, louvred
– Do not make any changes to the EC fan-and-filter grille with function logo and filter medium.
unit other than those described in these and other
applicable instructions.
◾ Make the cut-outs including the line width as per the Note:
drilling template To increase the protection category, a pleat-
◾ Deburr the cut-outs. ed filter or hose-proof hood must be used
for the EC fan-and-filter unit and outlet filter.
4.3.2 Fitting the EC fan-and-filter unit
– The fan may be fitted without tools, by simply snap- 4.4 Notes on electrical connection
ping into the preconfigured mounting cut-out. When performing the electrical connection, it is impor-
tant to observe all valid national and regional regula-
Note:
For technical data, refer to the rating plate.
Fig. 4: Release the bayonet connection
◾ Remove the red cover from the electrical connection. Units 3240.xxx, 3241.xxx, 3243.xxx to 3245.xxx are
released by pressing the release button of the bayonet
connection (see fig. 5), located on the opposite corner
from the connection terminal.
1.
7 Installing and changing the filter
The fan-and-filter unit and outlet filter are supplied as
standard with a standard chopped-fibre filter mat for
the pre-filtering of dry coarse dust and lint in the ambi-
ent air.
To increase the protection category and for presence of
Fig. 5: Release the bayonet connection dust with a grain size <10 μm, we recommend the use
of pleated filters (see section 13 "Accessories").
The filter should be checked at regular intervals in
5.3 Installing the control line
accordance with the level of dust exposure (recom-
To permit control of the EC fan-and-filter units via an mended: at the latest after 2,000 operating hours) and
external control unit (e.g. 3235.440 or 3235.450), the replaced as necessary.
units 3240.5xx to 3245.5xx possess a separate termi-
nal for connection of a control line. Note:
◾ To this end, release and remove the jumper between Use only original Rittal filters which bear the
the "+10 V" and "0 – 10 V/PWM" connections. Rittal logo in order to safeguard the desig-
For this purpose, use a screwdriver with a 3.5 x nated protection category, air throughout
0.5 mm blade. and operating approvals.
◾ Use the screwdriver to open the terminal and insert The chopped-fibre filter mat supplied for
the connection cable of the control line in accord- the fan-and-filter unit must be removed and
ance with the connection diagram on page 16 (line disposed of when a pleated filter is used.
cross-section 0.8 – 1.5 mm², fine wire).
◾ Remove the screwdriver.
Risk of injury!
Note: Only change the filter mat while the fan
For operation without control line, the jump- rotor is stationary.
er must be left in the connection clamp. The Never insert your fingers into the fan
unit is then operated at maximum speed rotor.
(see fig. 15).
To insert or replace the filter, proceed as follows (direc-
5.4 Changing the direction of airflow tion of airflow: drawing from outside and blowing into
The direction of airflow blows into the enclosure from the enclosure).
the outside as standard.
Should it become necessary to change the direc- 7.1 Replacing the chopped-fibre filter
tion of airflow for technical reasons (space, specific ◾ First press the catch of the louvred grille (Rittal logo)
component air routing etc.), this is easily achieved. up slightly with one finger (see fig. 6).
Simply release the fan housing and rotate it through ◾ Once it is released, the louvred grille can be dropped
180°. To release, please follow the same procedure open by approx. 70° or 90°.
as described under section 5.2 "Rotating the voltage ◾ Remove the dirty chopped-fibre filter mat and place
connection", page 7. the new chopped-fibre filter mat in the filter housing.
Please also observe the instructions outlined under ◾ When installing, ensure that the roughened side with
section 4.2.1 "General", page 5. the Rittal logo points inside.
◾ Now push the louvred grille back onto the enclosure
6 Commissioning until it snaps audibly into position.
◾ Once all the assembly and installation work is com-
plete, switch on the power supply to the EC fan-and-
filter unit.
Caution!
Risk of fire!
Never use flammable liquids for clean-
ing.
* EMC version
T2
Model No. B2 x H2 mm T2 mm
H2
3241.xxx 224 x 224 107
13 Accessories
EMC filter mat
To fit Model No. IP protection category in accordance with IEC 60529 Packs of Model No.
Hose-proof hoods
3245.xxx 350 x 480 x 160 NEMA 1, NEMA 12, NEMA 3, NEMA 3R 1 pc(s). 3245.080
Tab. 12: Hose-proof hoods
M M
1~ 1˜ EC
L N PE
PWM
0 – 10 V
+10 V
Speed
GND
L N PE
Fig. 13: Connection diagrams
3240.5xx/3241.5xx/3243.5xx/3244.5xx/3245.5xx/3245.6xx
1 2
Interface/connector Fan/motor
3 2
L AC 1 P
CON10
N 1.6 AT AC 2 N
1 – 10 V
CON11
2 1
10 V n = max. PE
1V n = min. CON12
PE 1
<1 V n=0
+10 V 1 3
3
3 4 I max. = 1.1 mA 2 4
15 V 10 V/PWM
2
47 k 47 k 1 uF
3
I max. = 10 mA GND
1
2 2
10 K
Speed 3 1
4
12 V
680 R 4 2
1 1
ZMM 47
100 % PWM n = max.
10 % PWM n = min.
<10 % PWM n =0
N Neutral conductor
PE PE conductor
0…10 V/PWM Control input 0…10 V or PWM, galvanically isolated, impedance 100 kΩ
+10 V Voltage output 10 V max. 1.1 mA, galvanically isolated, not short circuit-protected
Speed Speed output Open Collector, 1 pulse per revolution, galvanically isolated
Tab. 13: Explanations to fig. 14
11.2022/D-0000-00003198-00-EN
You can find the contact details of all
Rittal companies throughout the world here.
www.rittal.com/contact