SIPROTEC 5

New features of V7.5

Unrestricted © Siemens AG 2017 siemens.com/siprotec5


New Features for SIPROTEC 5 Release 7.50

Feeder Protection Machine Protection

• Ground Fault Detection (Pulse Generator Protection (7UM8)


Detection, Harmonic Detection) • Balancing commands (U,f) for
• Automatic Load Shedding synchronisation
• Vector jump protection • Power Plant Disconnection
Protection
• Overload Protection for rotor and
Line Protection Transformer Protection stator with cold gas consideration
• Vector jump protection
• LineDiff Enhancements (7SD8) • Voltage regulator for parallel
• Voltage comparison for supervision
• Improved Fast Stage transformers
of voltage transformer circuits
• Improved stability for delay time • New unrestrained tripping stage for
drifts transformer differential protection Motor Protection (7SK82)
• Distance Protection (7SA8, 7SL8)
• Integrated Temp. Measurement
• Adaptive Protection Settings
(IO111 with 12 RTD sensors)
• Circular Characteristic

Unrestricted © Siemens AG 2017


Page 2 October 2017 Automation Products
New system features and DIGSI 5 features with
releases 7.50 and 7.30

DIGSI 5 Fault Recording

• Compatibility with Windows 10 • Sequence of analog and binary


• Logging of security-relevant events traces within a fault record freely
• IEC 61850 flexible engineering adaptable
enhancements • User changeable trace names

CFC New Hardware Communications


• Read access for protection settings
News of V7.3 • Line sensor for arc protection • PROFINET IO support
• Copy and paste of function groups • 1/6 on-site operation panel with 8 (complete data types)
(FG), functions (FN) and function push buttons and LEDs • Simplified IEC 61850 GOOSE
blocks (FB) routing and flexible engineering
• Online monitoring of CFC charts
• chart-in-chart (sub-chart)
• write & access protection of charts
• Cross reference list

Unrestricted © Siemens AG 2017


Page 3 October 2017 Automation Products
Read Access for settings in CFC

Use setting as input


for CFC plan

• Make settings visible in CFC signal


list
• Settings SPG (bool), ING (integer),
ASG (float) and ENG
(enumeration) are included in
signal list
• Settings used in CFC are marked
in DIGSI
• View in CFC Online Test

Unrestricted © Siemens AG 2017


Page 4 October 2017 Automation Products
SIPROTEC 5 –
Integrated Cyber Security
Secure development
Mutually authenticated and encrypted communication line Patch management
between DIGSI 5 and the SIPROTEC 5 device
Antivirus compatibility
Connection password handling according to
BDEW White Paper, NERC-CIP, IEEE 1686, IEC 62443
Recording of security-relevant events and alarms
over Syslog and in non-volatile security log in device

Confirmation codes for safety-critical operations (safety)


Product hardening

SIPROTEC 5 Independent testing


Separation of process and management communication
Crypto-chip for secure information
storage and transmission
Bay level
Device uses key stored in crypto-chip to allow
only firmware signed by Siemens to load

Unrestricted © Siemens AG 2017


Page 5 October 2017 Automation Products
SIPROTEC 5 –
Integrated Cyber Security

Highlight 1 Highlight 2

• Central logging of • Device-firmware is protected against


security-relevant events manipulation
• Only firmware digitally signed by EM
DG PRO can be loaded and
processed
• This is ensured via an integrated
crypto-chip with secured key
storage and signature technology

Unrestricted © Siemens AG 2017


Page 6 October 2017 Automation Products
SIPROTEC 5 – Earth fault detection
80% of faults are earth faults
Reliable detection – essential in transmission and distribution
Distribution grids 10/20/30/110kV

• Star point treatment often


compensated
• Different methods with dedicated
devices

SIPROTEC 5 Watt
Watt metric
metric Transient
Transient Harmonics
Harmonics

• Full parallel operation of different


methods
• Increase of reliability
• Saving costs
• Saving engineering efforts

All in One with SIPROTEC 5


Unrestricted © Siemens AG 2017
Page 7 October 2017 Automation Products
SIPROTEC 5
Earth fault detection – All Advantages in one Device

Combining advantages of several


Transient function (digital) methods in one device
• Higher sensitivity
cos/sinϕ, 3I0>, U0>, admittance, 20 x compared to former algorithms
Phi(U,I)
• Detection of
• High impedance / ohmic faults
Harmonics 3rd, 5th, 7th • Very short ground faults
• Static faults
• Integrated solutions in SIPROTEC 5 reduces
Pulse pattern costs
SIPROTEC 5
• Elimination of operational 3I0
• For closed rings and meshed networks
• Easy settings of the function
Directional intermittend
• Almost 4 years of positive field experiences

Signalization of earth fault direction to control center


using a priority scheme (user defined CFC)
Unrestricted © Siemens AG 2017
Page 8 October 2017 Automation Products
SIPROTEC 5 – Adaptive Protection Settings
Remote control of protection settings through IEC 61850

grid transmission capacity Control Center


Situation
• Calculation of protection settings & thermal
Today‘s reserve
limits for worst case conditions due to fixed limits
• Restrictive limits are to high during >90%
of the year Grid capacity
used today
Solution:
• Automatic adaption of protection settings
• Increased limits during >90% of the year
• Enhanced capacity of the transmission
system without building new lines

How is this done:
• Calculation of settings to be adapted on
control center level
• Download of new settings to SIPROTEC
protection relays using IEC 61850

Unrestricted © Siemens AG 2017


Page 9 October 2017 Automation Products
Voltage Regulator – From Single to Parallel Control Operation

• Voltage regulator for transformer parallel IEC61850 Goose


operation
Requirement

• Protection and voltage regulation with one


device OLTC OLTC OLTC OLTC OLTC
T11 T12 T13 T14 Txx
• Methods: Circulating current minimization or
Master-Follower operation
7500A/1A 7500A/1A 7500A/1A 7500A/1A 7500A/1A

QA11 QA21 QA31 QA41 QAx1

• SIPROTEC 5 voltage regulator function QB11 QB12


B1
QB21 QB22 QB31 QB32 QB41 QB42 QBx1 QBx2

• Master-Follower, circulating current and B2


independent mode
• Interconnection between the devices via
Solution

IEC 61850 Goose late binding (preconfigured • Reduced investment (one device for
data structures) protection and regulation)

Benefits
• Supports up to 8 transformer in parallel • Easy parameterization with DIGSI and
operation IEC 61850 system configurator
• Reduced wiring
• Faster commissioning
Unrestricted © Siemens AG 2017
Page 10