You are on page 1of 228

EDADT1505A

AHU

Standard Series AHUR06-120DBV(H)/CBV(H)


Outdoor Air Series AHUR08-60DBL(H)/CBL(H)

Cooling only 50/60Hz


EDADT1505A

Table of Contents
Part 1 General Information ............................................................ 3
1. External appearance ...............................................................................3
1.1 Air Handing Unit .......................................................................................3
2. Model name, power supply and nomenclature .......................................4
2.1 Model name and power supply ................................................................4
2.2 Nomenclature ...........................................................................................5

Part 2 Air Handling Unit (Standard series) .................................... 7


1. Specifications ..........................................................................................7
1.1 AHUR_DBV(H).........................................................................................7
1.2 AHUR_CBV(H).......................................................................................14
2. Dimensions and service space .............................................................21
2.1 Indoor unit ..............................................................................................21
2.2 Standard series PCB..............................................................................45
2.3 Expansion valve .....................................................................................46
2.4 Wired remote controller (Optional) .........................................................47
3. Piping diagrams ....................................................................................48
3.1 Indoor unit ..............................................................................................48
4. Wiring diagrams ....................................................................................54
4.1 Standard series PCB..............................................................................54
4.2 Installation manual for KRP4AA51 .........................................................55
4.3 External connection diagram..................................................................60
5. Field preparation ...................................................................................66
5.1 External wiring connection diagram .......................................................66
6. Electrical characteristics........................................................................73
6.1 Indoor unit ..............................................................................................73
7. Capacity tables......................................................................................74
8. Fan Performances.................................................................................75
9. Operation limits .....................................................................................76
10.Sound Pressure Level (SPL).................................................................76
11.Fan Sound Power Level (PWL).............................................................78

Part 3 Air Handling Unit (Outdoor air series) .............................. 79


1. Specifications ........................................................................................79
1.1 AHUR_DBL(H) .......................................................................................79
1.2 AHUR_CBL(H) .......................................................................................84
2. Dimensions and service space .............................................................89
2.1 Indoor unit ..............................................................................................89
2.2 Outdoor air series PCB ........................................................................105
2.3 Expansion valve ...................................................................................106
3. Piping diagrams ..................................................................................107
3.1 Indoor unit ............................................................................................107
4. Wiring diagrams ..................................................................................110
4.1 Outdoor air series PCB ........................................................................110

AHUR-DB/CB 1
EDADT1505A

5. Field preparation .................................................................................111


5.1 External wiring connection diagram .....................................................111
5.2 Wiring connection summary for MicroTech III ......................................114
5.3 MicroTech III wiring diagram for EKEQFCBAV3 ..................................115
6. Electrical characteristics......................................................................118
6.1 Indoor unit ............................................................................................118
7. Capacity tables....................................................................................119
8. Fan Performances...............................................................................119
9. Operation limits ...................................................................................119
10.Sound Pressure Level (SPL)...............................................................120
11.Fan Sound Power Level (PWL)...........................................................121

Part 4 Options............................................................................. 123

Part 5 Installation and maintenance manual ............................ 129


1. Installation manual of air handling unit................................................129
2. Installation of control box (EKEQMCBAV3) ........................................136
3. Installation of control box (EKEQFCBAV3) .........................................148
4. MicroTech III commissioning manual..................................................164
5. MicroTech III operation manual...........................................................183

2 AHUR-DB/CB
EDADT1505A External appearance

Part 1 General Information


1. External appearance
1.1 Air Handing Unit
AHUR06-120DBV(H)
AHUR06-120CBV(H)
AHUR08-60DBL(H)
AHUR08-60CBL(H)

CBV
CBL Series DBL Series

1.1.1 Outdoor Air Series PCB / Standard Series PCB


EKEQFCBAV3
EKEQMCBAV3

Remark: This unit is included with air handling unit.

1.1.2 Expansion Valve


EKEXV140
EKEXV200
EKEXV250
EKEXV400
EKEXV500

Remark: This unit is included with air handling unit.

AHUR-DB/CB 3
Model name, power supply and nomenclature EDADT1505A

2. Model name, power supply and nomenclature


2.1 Model name and power supply

Indoor Model name Skin panel Power supply


AHUR06DBV Double (50mm)
AHUR08DBV Double (50mm)
AHUR10DBV Double (50mm)
AHUR16DBV Double (50mm)
AHUR20DBV Double (50mm)
AHUR32DBV Double (50mm)
AHUR40DBV Double (50mm)
AHUR48DBV Double (50mm)
AHUR60DBV Double (50mm)
AHUR80DBV Double (50mm)
AHUR100DBV Double (50mm)
AHUR120DBV Double (50mm)
3 phase, 380-415V, 50Hz
AHUR06CBV Double (25mm)
AHUR08CBV Double (25mm)
AHUR10CBV Double (25mm)
AHUR16CBV Double (25mm)
AHUR20CBV Double (25mm)
AHUR32CBV Double (25mm)
AHUR40CBV Double (25mm)
AHUR48CBV Double (25mm)
AHUR60CBV Double (25mm)
AHUR80CBV Double (25mm)
AHUR100CBV Double (25mm)
AHUR120CBV Double (25mm)
Air handling unit (Standard series)
AHUR06DBVH Double (50mm)
AHUR08DBVH Double (50mm)
AHUR10DBVH Double (50mm)
AHUR16DBVH Double (50mm)
AHUR20DBVH Double (50mm)
AHUR32DBVH Double (50mm)
AHUR40DBVH Double (50mm)
AHUR48DBVH Double (50mm)
AHUR60DBVH Double (50mm)
AHUR80DBVH Double (50mm)
AHUR100DBVH Double (50mm)
AHUR120DBVH Double (50mm)
3 phase, 380-415V, 60Hz
AHUR06CBVH Double (25mm)
AHUR08CBVH Double (25mm)
AHUR10CBVH Double (25mm)
AHUR16CBVH Double (25mm)
AHUR20CBVH Double (25mm)
AHUR32CBVH Double (25mm)
AHUR40CBVH Double (25mm)
AHUR48CBVH Double (25mm)
AHUR60CBVH Double (25mm)
AHUR80CBVH Double (25mm)
AHUR100CBVH Double (25mm)
AHUR120CBVH Double (25mm)

4 AHUR-DB/CB
EDADT1505A Model name, power supply and nomenclature

Indoor Model name Skin panel Power supply


AHUR08DBL Double (50mm)
AHUR10DBL Double (50mm)
AHUR16DBL Double (50mm)
AHUR20DBL Double (50mm)
AHUR32DBL Double (50mm)
AHUR40DBL Double (50mm)
AHUR48DBL Double (50mm)
AHUR60DBL Double (50mm)
3 phase, 380-415V, 50Hz
AHUR08CBL Double (25mm)
AHUR10CBL Double (25mm)
AHUR16CBL Double (25mm)
AHUR20CBL Double (25mm)
AHUR32CBL Double (25mm)
AHUR40CBL Double (25mm)
AHUR48CBL Double (25mm)
AHUR60CBL Double (25mm)
Air handling unit (Outdoor air series)
AHUR08DBLH Double (50mm)
AHUR10DBLH Double (50mm)
AHUR16DBLH Double (50mm)
AHUR20DBLH Double (50mm)
AHUR32DBLH Double (50mm)
AHUR40DBLH Double (50mm)
AHUR48DBLH Double (50mm)
AHUR60DBLH Double (50mm)
3 phase, 380-415V, 60Hz
AHUR08CBLH Double (25mm)
AHUR10CBLH Double (25mm)
AHUR16CBLH Double (25mm)
AHUR20CBLH Double (25mm)
AHUR32CBLH Double (25mm)
AHUR40CBLH Double (25mm)
AHUR48CBLH Double (25mm)
AHUR60CBLH Double (25mm)
Outdoor air series PCB / Standard EKEQFCBAV3
1 phase, 230V ±10%, 50Hz
series PCB EKEQMCBAV3
EKEXV140
EKEXV200
Expansion valve EKEXV250
EKEXV400
EKEXV500

2.2 Nomenclature

Indoor unit

AHUR 06 DB V H

Blank: 50 Hz, H: 60 Hz

V: Standard, L: Outdoor Air

DB: Double skin 50 mm thickness, CB: Double skin 25 mm thickness

Cooling Capacity: 06 = 6 HP

AHUR = DX Air Handling Unit Horizontal Mount

AHUR-DB/CB 5
Model name, power supply and nomenclature EDADT1505A

6 AHUR-DB/CB
EDADT1505A Specifications

Part 2 Air Handling Unit (Standard series)


1. Specifications
1.1 AHUR_DBV(H)
MODEL NAME: AHUR_DBV(H)
1 CASING 50 mm Thickness Double Skinned Panel (Thermal Break)
0.5 mm Thickness White Colourbond Steel Sheet
Insulation 50 mm Thickness Polyurethane Foam 40 kg/m3 Density
2 CASING-FRAME Steel with Black Epoxy Paint
3 COIL DX Coil
Tube Copper Tube
Fin Aluminum Slit
Header Copper Tube
Frame Galvanized Steel
Working Pressure 10 kg/cm2G
4 FAN (Brand = Kruger)
Type Double Width Double Inlet Forward Curved Centrifugal Belt Drive Fan
Wheel Galvanized Steel
Housing Galvanized Steel
Frame Steel with Polyester Powder Coating
5 MOTOR (Brand = Teco)
Type Three-Phase Induction Motor Totally Enclosed Fan-Cooled Type
Protection = IP55, Insulation Class = F, IE1
6 VIBRATION ISOLATOR (FAN) Spring Isolator
7 DRAIN PAN 1.2 mm (SUS304)
Beneath the Drain Pan is Covered with PU Insulation 40 kg/m3 Density
8 AIR FILTER (Brand = AAF)
Pre Filter Type = R29, CLASS = G3 (AFI = 80-85%) Synthetic washable
SIZE = FULL (24”x24”x2”/595x595x50mm), HALF (12”x24”x2”/290x595x50mm)
9 STANDARD SERIES PCB EKEQMCBAV3
10 EXPANSION VALVE EKEXV140, EKEXV200, EKEXV250, EKEXV400, EKEXV500

AHUR-DB/CB 7
Specifications EDADT1505A

Air Handling Unit


Model AHUR06DBV(H) AHUR08DBV(H)
Total Cooling Capacity kW 16.4 16.3 16.2 16.0 15.9 22.9 22.8 22.7 22.4 22.3
Net +1
Total Sensible Cooling Capacity kW 11.9 11.8 11.7 11.5 11.4 16.8 16.7 16.6 16.3 16.2
Total Cooling Capacity kW 17.6 24.0
Gross +2
Sensible Cooling Capacity kW 13.1 17.9
Air Flow cmh / m³/min 3,240/54 4,080/68
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 14.7/13.3 13.6/12.7
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 0.491 0.443
Coil Face Vel. m/s 1.83 2.56
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 1 1
Air Filter Size 24”x24”x2” +3 pcs. 1 1
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA200CM FDA250TM
kW 1.5 2.2 1.5 2.2
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 3.64 5.28 3.64 5.28
Machine Weight kg 545 550 550 560
Sound Pressure Level (SPL) dB(A) 60 61 62 63 64 54 56 57 59 60
Standard Series PCB Model/pcs. EKEQMCBAV3/1pc. EKEQMCBAV3/1pc.
Expansion Valve Model/pcs. EKEXV140/1pc. EKEXV200/1pc.
Dimension: (WxDxH) m 1.3x1.2x1.2 1.3x1.4x1.2
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ9.5 (Brazing connection) φ9.5 (Brazing connection)
Piping Connections Gas pipes +5 mm φ15.9 (Brazing connection) φ19.1 (Brazing connection)
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 140 200

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

8 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR10DBV(H) AHUR16DBV(H)
Total Cooling Capacity kW 28.4 28.3 28.2 28.0 27.8 45.7 45.5 45.3 45.0 44.6
Net +1
Total Sensible Cooling Capacity kW 20.9 20.8 20.7 20.5 20.3 33.5 33.3 33.1 32.6 32.4
Total Cooling Capacity kW 29.8 48.3
Gross +2
Sensible Cooling Capacity kW 22.3 36.2
Air Flow cmh / m³/min 4,680/78 8,160/136
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 12.5/12.4 13.5/12.7
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 0.54 0.78
Coil Face Vel. m/s 2.41 2.91
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - 1
Air Filter Size 24”x24”x2” +3 pcs. 2 2
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA250TM FDA315TM
kW 2.2 3.0 3.0 4.0
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 5.28 6.58 6.58 8.92
Machine Weight kg 600 610 765 775
Sound Pressure Level (SPL) dB(A) 54 56 57 59 60 62 63 64 66 67
Standard Series PCB Model/pcs. EKEQMCBAV3/1pc. EKEQMCBAV3/1pc.
Expansion Valve Model/pcs. EKEXV250/1pc. EKEXV400/1pc.
Dimension: (WxDxH) m 1.5x1.4x1.2 1.8x1.5x1.2
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ9.5 (Brazing connection) φ12.7 (Brazing connection)
Piping Connections Gas pipes +5 mm φ22.2 (Brazing connection) φ28.6 (Brazing connection)
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 250 400

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

AHUR-DB/CB 9
Specifications EDADT1505A

Air Handling Unit


Model AHUR20DBV(H) AHUR32DBV(H)
Total Cooling Capacity kW 56.8 56.6 56.3 56.0 55.7 91.4 91.0 90.6 90.0 89.2
Net +1
Total Sensible Cooling Capacity kW 41.8 41.6 41.3 40.9 40.7 67.0 66.6 66.2 65.3 64.8
Total Cooling Capacity kW 59.4 96.6
Gross +2
Sensible Cooling Capacity kW 44.3 72.4
Air Flow cmh / m³/min 9,960/166 16,320/272
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 13.4/12.6 13.5/12.7
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 0.99 1.56
Coil Face Vel. m/s 2.79 2.91
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - 2
Air Filter Size 24”x24”x2” +3 pcs. 3 4
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA355TM FDA450TM
kW 3.0 4.0 5.5 5.5 7.5
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 6.58 8.92 12.0 12.0 15.4
Machine Weight kg 890 900 920 1,090 1,110
Sound Pressure Level (SPL) dB(A) 61 61 62 64 65 62 63 64 65 66
Standard Series PCB Model/pcs. EKEQMCBAV3/1pc. EKEQMCBAV3/2pcs.
Expansion Valve Model/pcs. EKEXV500/1pc. EKEXV400/2pcs.
Dimension: (WxDxH) m 2.1x1.6x1.2 1.8x1.8x1.6
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ15.9 (Brazing connection) φ12.7 (Brazing connection) x2
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) φ28.6 (Brazing connection) x2
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 500 800

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

10 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR40DBV(H) AHUR48DBV(H)
Total Cooling Capacity kW 113.6 113.2 112.7 112.0 111.3 137.1 136.6 136.0 135.0 133.7
Net +1
Total Sensible Cooling Capacity kW 83.6 83.2 82.7 81.8 81.3 100.5 100.0 99.4 97.9 97.1
Total Cooling Capacity kW 118.8 144.9
Gross +2
Sensible Cooling Capacity kW 88.6 108.6
Air Flow cmh / m³/min 19,920/332 24,480/408
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 13.4/12.6 13.5/12.7
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 1.98 2.34
Coil Face Vel. m/s 2.79 2.91
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - 3
Air Filter Size 24”x24”x2” +3 pcs. 6 6
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA500TM FDA560TM
kW 7.5 11.0 7.5 11.0
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 15.4 22.1 15.4 22.1
Machine Weight kg 1,260 1,300 1,400 1,440
Sound Pressure Level (SPL) dB(A) 61 62 63 65 65 64 65 65 66 67
Standard Series PCB Model/pcs. EKEQMCBAV3/2pcs. EKEQMCBAV3/3pcs.
Expansion Valve Model/pcs. EKEXV500/2pcs. EKEXV400/3pcs.
Dimension: (WxDxH) m 2.1x1.8x1.6 1.8x1.95x2.3
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ15.9 (Brazing connection) x2 φ12.7 (Brazing connection) x3
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x2 φ28.6 (Brazing connection) x3
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 1,000 1,200

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

AHUR-DB/CB 11
Specifications EDADT1505A

Air Handling Unit


Model AHUR60DBV(H) AHUR80DBV(H)
Total Cooling Capacity kW 170.4 169.7 169.0 168.0 167.0 227.2 226.3 225.4 224.0 222.6
Net +1
Total Sensible Cooling Capacity kW 125.4 124.7 124.0 122.7 122.0 167.2 166.3 165.4 163.6 162.6
Total Cooling Capacity kW 178.2 237.6
Gross +2
Sensible Cooling Capacity kW 132.9 177.2
Air Flow cmh / m³/min 29,880/498 39,840/664
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 13.4/12.6 13.4/12.6
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 2.97 3.96
Coil Face Vel. m/s 2.79 2.79
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - -
Air Filter Size 24”x24”x2” +3 pcs. 9 12
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA630TM FDA500T2M
kW 11.0 15.0 18.5
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 22.1 29.9 36.6
Machine Weight kg 1,640 2,160 2,195
Sound Pressure Level (SPL) dB(A) 62 63 64 65 66 67 67 68 70 71
Standard Series PCB Model/pcs. EKEQMCBAV3/3pcs. EKEQMCBAV3/4pcs.
Expansion Valve Model/pcs. EKEXV500/3pcs. EKEXV500/4pcs.
Dimension: (WxDxH) m 2.1x1.95x2.3 4.0x1.8x1.6
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ15.9 (Brazing connection) x3 φ15.9 (Brazing connection) x4
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x3 φ28.6 (Brazing connection) x4
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 1,500 2,000

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

12 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR100DBV(H) AHUR120DBV(H)
Total Cooling Capacity kW 284.0 282.9 281.7 280.0 278.3 340.8 339.5 338.0 336.0 334.0
Net +1
Total Sensible Cooling Capacity kW 209.0 207.9 206.7 204.5 203.3 250.8 249.5 248.0 245.4 244.0
Total Cooling Capacity kW 297.0 356.4
Gross +2
Sensible Cooling Capacity kW 221.5 265.8
Air Flow cmh / m³/min 49,800/830 59,760/996
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 13.4/12.6 13.4/12.6
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 4.95 5.94
Coil Face Vel. m/s 2.79 2.79
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - -
Air Filter Size 24”x24”x2” +3 pcs. 18 18
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA560T2M FDA630T2M
kW 15.0 18.5 22.0 18.5 22.0 30.0
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 29.9 36.6 44.3 36.6 44.3 58.1
Machine Weight kg 2,580 2,615 2,630 2,830 2,845 2,925
Sound Pressure Level (SPL) dB(A) 68 69 70 71 72 69 69 70 71 73
Standard Series PCB Model/pcs. EKEQMCBAV3/5pcs. EKEQMCBAV3/6pcs.
Expansion Valve Model/pcs. EKEXV500/5pcs. EKEXV500/6pcs.
Dimension: (WxDxH) m 4.0x1.95x2.3 4.0x1.95x2.35
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ15.9 (Brazing connection) x5 φ15.9 (Brazing connection) x6
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x5 φ28.6 (Brazing connection) x6
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 2,500 3,000

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

AHUR-DB/CB 13
Specifications EDADT1505A

1.2 AHUR_CBV(H)
MODEL NAME: AHUR_CBV(H)
1 CASING 25 mm Thickness Double Skinned Panel
Outside 0.5 mm Thickness White Colourbond Steel Sheet
Inside 0.5 mm Thickness Galvanized Steel Sheet
Insulation 25 mm Thickness Polyurethane Foam 40 kg/m3 Density
2 CASING-FRAME Extruded Aluminium Pentapost Profile
3 COIL DX Coil
Tube Copper Tube
Fin Aluminum Slit
Header Copper Tube
Frame Galvanized Steel
Working Pressure 10 kg/cm2G
4 FAN (Brand = Kruger)
Type Double Width Double Inlet Forward Curved Centrifugal Belt Drive Fan
Wheel Galvanized Steel
Housing Galvanized Steel
Frame Steel with Polyester Powder Coating
5 MOTOR (Brand = Teco)
Type Three-Phase Induction Motor Totally Enclosed Fan-Cooled Type
Protection = IP55, Insulation Class = F, IE1
6 VIBRATION ISOLATOR (FAN) Spring Isolator
7 DRAIN PAN 1.6 mm (Steel Sheet with Epoxy Coated)
Beneath the Drain Pan is Covered with PU Insulation Foam 40 kg/m3 Density
8 AIR FILTER (Brand = AAF)
Pre Filter Type = R29, CLASS = G3 (AFI = 80-85%) Synthetic washable
SIZE = FULL (24”x24”x2”/595x595x50mm), HALF (12”x24”x2”/290x595x50mm)
9 STANDARD SERIES PCB EKEQMCBAV3
10 EXPANSION VALVE EKEXV140, EKEXV200, EKEXV250, EKEXV400, EKEXV500

14 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR06CBV(H) AHUR08CBV(H)
Total Cooling Capacity kW 16.4 16.3 16.2 16.0 15.9 22.9 22.8 22.7 22.4 22.3
Net +1
Total Sensible Cooling Capacity kW 11.9 11.8 11.7 11.5 11.4 16.8 16.7 16.6 16.3 16.2
Total Cooling Capacity kW 17.6 24.0
Gross +2
Sensible Cooling Capacity kW 13.1 17.9
Air Flow cmh / m³/min 3,240/54 4,080/68
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 14.7/13.3 13.6/12.7
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 0.491 0.443
Coil Face Vel. m/s 1.83 2.56
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 1 1
Air Filter Size 24”x24”x2” +3 pcs. 1 1
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA200CM FDA250TM
kW 1.5 2.2 1.5 2.2
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 3.64 5.28 3.64 5.28
Machine Weight kg 480 485 480 485
Sound Pressure Level (SPL) dB(A) 60 61 62 63 64 54 56 57 59 60
Standard Series PCB Model/pcs. EKEQMCBAV3/1pc. EKEQMCBAV3/1pc.
Expansion Valve Model/pcs. EKEXV140/1pc. EKEXV200/1pc.
Dimension: (WxDxH) m 1.2x1.1x0.85 1.3x1.2x1.1
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ9.5 (Brazing connection) φ9.5 (Brazing connection)
Piping Connections Gas pipes +5 mm φ15.9 (Brazing connection) φ19.1 (Brazing connection)
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 140 200

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

AHUR-DB/CB 15
Specifications EDADT1505A

Air Handling Unit


Model AHUR10CBV(H) AHUR16CBV(H)
Total Cooling Capacity kW 28.4 28.3 28.2 28.0 27.8 45.7 45.5 45.3 45.0 44.6
Net +1
Total Sensible Cooling Capacity kW 20.9 20.8 20.7 20.5 20.3 33.5 33.3 33.1 32.6 32.4
Total Cooling Capacity kW 29.8 48.3
Gross +2
Sensible Cooling Capacity kW 22.3 36.2
Air Flow cmh / m³/min 4,680/78 8,160/136
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 12.5/12.4 13.5/12.7
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 0.54 0.78
Coil Face Vel. m/s 2.41 2.91
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - 1
Air Filter Size 24”x24”x2” +3 pcs. 2 2
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA250TM FDA315TM
kW 2.2 3.0 3.0 4.0
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 5.28 6.58 6.58 8.92
Machine Weight kg 530 540 740 750
Sound Pressure Level (SPL) dB(A) 54 56 57 59 60 62 63 64 66 67
Standard Series PCB Model/pcs. EKEQMCBAV3/1pc. EKEQMCBAV3/1pc.
Expansion Valve Model/pcs. EKEXV250/1pc. EKEXV400/1pc.
Dimension: (WxDxH) m 1.5x1.2x1.1 1.7x1.4x1.1
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ9.5 (Brazing connection) φ12.7 (Brazing connection)
Piping Connections Gas pipes +5 mm φ22.2 (Brazing connection) φ28.6 (Brazing connection)
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 250 400

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

16 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR20CBV(H) AHUR32CBV(H)
Total Cooling Capacity kW 56.8 56.6 56.3 56.0 55.7 91.4 91.0 90.6 90.0 89.2
Net +1
Total Sensible Cooling Capacity kW 41.8 41.6 41.3 40.9 40.7 67.0 66.6 66.2 65.3 64.8
Total Cooling Capacity kW 59.4 96.6
Gross +2
Sensible Cooling Capacity kW 44.3 72.4
Air Flow cmh / m³/min 9,960/166 16,320/272
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 13.4/12.6 13.5/12.7
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 0.99 1.56
Coil Face Vel. m/s 2.79 2.91
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - 2
Air Filter Size 24”x24”x2” +3 pcs. 3 4
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA355TM FDA450TM
kW 3.0 4.0 5.5 5.5 7.5
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 6.58 8.92 12.0 12.0 15.4
Machine Weight kg 850 860 880 990 1,010
Sound Pressure Level (SPL) dB(A) 61 61 62 64 65 62 63 64 65 66
Standard Series PCB Model/pcs. EKEQMCBAV3/1pc. EKEQMCBAV3/2pcs.
Expansion Valve Model/pcs. EKEXV500/1pc. EKEXV400/2pcs.
Dimension: (WxDxH) m 2.0x1.5x1.1 1.7x1.7x1.5
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ15.9 (Brazing connection) φ12.7 (Brazing connection) x2
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) φ28.6 (Brazing connection) x2
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 500 800

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

AHUR-DB/CB 17
Specifications EDADT1505A

Air Handling Unit


Model AHUR40CBV(H) AHUR48CBV(H)
Total Cooling Capacity kW 113.6 113.2 112.7 112.0 111.3 137.1 136.6 136.0 135.0 133.7
Net +1
Total Sensible Cooling Capacity kW 83.6 83.2 82.7 81.8 81.3 100.5 100.0 99.4 97.9 97.1
Total Cooling Capacity kW 118.8 144.9
Gross +2
Sensible Cooling Capacity kW 88.6 108.6
Air Flow cmh / m³/min 19,920/332 24,480/408
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 13.4/12.6 13.5/12.7
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 1.98 2.34
Coil Face Vel. m/s 2.79 2.91
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - 3
Air Filter Size 24”x24”x2” +3 pcs. 6 6
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA500TM FDA560TM
kW 7.5 11.0 7.5 11.0
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 15.4 22.1 15.4 22.1
Machine Weight kg 1,120 1,160 1,250 1,290
Sound Pressure Level (SPL) dB(A) 61 62 63 65 65 64 65 65 66 67
Standard Series PCB Model/pcs. EKEQMCBAV3/2pcs. EKEQMCBAV3/3pcs.
Expansion Valve Model/pcs. EKEXV500/2pcs. EKEXV400/3pcs.
Dimension: (WxDxH) m 2.0x1.7x1.5 1.7x1.85x2.1
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ15.9 (Brazing connection) x2 φ12.7 (Brazing connection) x3
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x2 φ28.6 (Brazing connection) x3
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 1,000 1,200

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

18 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR60CBV(H) AHUR80CBV(H)
Total Cooling Capacity kW 170.4 169.7 169.0 168.0 167.0 227.2 226.3 225.4 224.0 222.6
Net +1
Total Sensible Cooling Capacity kW 125.4 124.7 124.0 122.7 122.0 167.2 166.3 165.4 163.6 162.6
Total Cooling Capacity kW 178.2 237.6
Gross +2
Sensible Cooling Capacity kW 132.9 177.2
Air Flow cmh / m³/min 29,880/498 39,840/664
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 13.4/12.6 13.4/12.6
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 2.97 3.96
Coil Face Vel. m/s 2.79 2.79
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - -
Air Filter Size 24”x24”x2” +3 pcs. 9 12
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA630TM FDA500T2M
kW 11.0 15.0 18.5
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 22.1 29.9 36.6
Machine Weight kg 1,480 1,885 1,920
Sound Pressure Level (SPL) dB(A) 62 63 64 65 66 67 67 68 70 71
Standard Series PCB Model/pcs. EKEQMCBAV3/3pcs. EKEQMCBAV3/4pcs.
Expansion Valve Model/pcs. EKEXV500/3pcs. EKEXV500/4pcs.
Dimension: (WxDxH) m 2.0x1.95x2.2 3.9x1.7x1.5
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ15.9 (Brazing connection) x3 φ15.9 (Brazing connection) x4
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x3 φ28.6 (Brazing connection) x4
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 1,500 2,000

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

AHUR-DB/CB 19
Specifications EDADT1505A

Air Handling Unit


Model AHUR100CBV(H) AHUR120CBV(H)
Total Cooling Capacity kW 284.0 282.9 281.7 280.0 278.3 340.8 339.5 338.0 336.0 334.0
Net +1
Total Sensible Cooling Capacity kW 209.0 207.9 206.7 204.5 203.3 250.8 249.5 248.0 245.4 244.0
Total Cooling Capacity kW 297.0 356.4
Gross +2
Sensible Cooling Capacity kW 221.5 265.8
Air Flow cmh / m³/min 49,800/830 59,760/996
On Coil °CDB/°CWB 27/19 27/19
Off Coil °CDB/°CWB 13.4/12.6 13.4/12.6
Coil Type DX.Coil (R410A) φ8mm. Wave slit surface & Straight edge
Coil Face Area m² 4.95 5.94
Coil Face Vel. m/s 2.79 2.79
Air PD.In Coil Pa 100 100
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. - -
Air Filter Size 24”x24”x2” +3 pcs. 18 18
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 460 510 560 660 710 460 510 560 660 710
Fan Type Forward curve
Model FDA560T2M FDA630T2M
kW 15.0 18.5 22.0 18.5 22.0 30.0
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380-415/3/50(60) 380-415/3/50(60)
FLA amp. 29.9 36.6 44.3 36.6 44.3 58.1
Machine Weight kg 2,280 2,315 2,330 2,470 2,485 2,565
Sound Pressure Level (SPL) dB(A) 68 69 70 71 72 69 69 70 71 73
Standard Series PCB Model/pcs. EKEQMCBAV3/5pcs. EKEQMCBAV3/6pcs.
Expansion Valve Model/pcs. EKEXV500/5pcs. EKEXV500/6pcs.
Dimension: (WxDxH) m 3.9x1.85x2.2 3.9x1.95x2.2
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ15.9 (Brazing connection) x5 φ15.9 (Brazing connection) x6
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x5 φ28.6 (Brazing connection) x6
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 2,500 3,000

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
cfm=m³/min×35.3
+4. Motor is induction motor class F, IP 55.
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
VRV DX indoor unit(s) + AHU 50 - 110% 0 - 110% 0 - 60%
Only AHU 50 - 110% – 50 - 110%
(Pair AHU & Multi AHU)

20 AHUR-DB/CB
EDADT1505A Dimensions and service space

2. Dimensions and service space


2.1 Indoor unit
2.1.1 AHUR_DBV(H) (Air handling unit)

AHUR06DBV(H)
Unit (mm)

C: SDR4902701A

AHUR-DB/CB 21
Dimensions and service space EDADT1505A

AHUR08DBV(H)
Unit (mm)

C: SDR4902702A

22 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR10DBV(H)
Unit (mm)

C: SDR4902703A

AHUR-DB/CB 23
Dimensions and service space EDADT1505A

AHUR16DBV(H)
Unit (mm)

C: SDR4902705A

24 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR20DBV(H)
Unit (mm)

C: SDR4902706A

AHUR-DB/CB 25
Dimensions and service space EDADT1505A

AHUR32DBV(H)
Unit (mm)

C: SDR4902707A

26 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR40DBV(H)
Unit (mm)

C: SDR4902708A

AHUR-DB/CB 27
Dimensions and service space EDADT1505A

AHUR48DBV(H)
Unit (mm)

C: SDR4902709A

28 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR60DBV(H)
Unit (mm)

C: SDR4902710A

AHUR-DB/CB 29
Dimensions and service space EDADT1505A

AHUR80DBV(H)
Unit (mm)

C: SDR4902711A

30 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR100DBV(H)
Unit (mm)

C: SDR4902712A

AHUR-DB/CB 31
Dimensions and service space EDADT1505A

AHUR120DBV(H)
Unit (mm)

C: SDR4902713A

32 AHUR-DB/CB
EDADT1505A Dimensions and service space

2.1.2 AHUR_CBV(H) (Air handling unit)

AHUR06CBV(H)
Unit (mm)

C: SDR4902714A

AHUR-DB/CB 33
Dimensions and service space EDADT1505A

AHUR08CBV(H)
Unit (mm)

C: SDR4902715A

34 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR10CBV(H)
Unit (mm)

C: SDR4902716A

AHUR-DB/CB 35
Dimensions and service space EDADT1505A

AHUR16CBV(H)
Unit (mm)

C: SDR4902718A

36 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR20CBV(H)
Unit (mm)

C: SDR4902719A

AHUR-DB/CB 37
Dimensions and service space EDADT1505A

AHUR32CBV(H)
Unit (mm)

C: SDR4902720A

38 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR40CBV(H)
Unit (mm)

C: SDR4902721A

AHUR-DB/CB 39
Dimensions and service space EDADT1505A

AHUR48CBV(H)
Unit (mm)

C: SDR4902722A

40 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR60CBV(H)
Unit (mm)

C: SDR4902723A

AHUR-DB/CB 41
Dimensions and service space EDADT1505A

AHUR80CBV(H)
Unit (mm)

C: SDR4902724A

42 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR100CBV(H)
Unit (mm)

C: SDR4902725A

AHUR-DB/CB 43
Dimensions and service space EDADT1505A

AHUR120CBV(H)
Unit (mm)

C: SDR4902726A

44 AHUR-DB/CB
EDADT1505A Dimensions and service space

2.2 Standard series PCB

EKEQMCBA

AHUR-DB/CB 45
Dimensions and service space EDADT1505A

2.3 Expansion valve

EKEXV

46 AHUR-DB/CB
EDADT1505A Dimensions and service space

2.4 Wired remote controller (Optional)

BRC1E62

AHUR-DB/CB 47
Piping diagrams EDADT1505A

3. Piping diagrams
3.1 Indoor unit

AHUR06DBV(H) / AHUR06CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE 9.5 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
Field piping (9.5 CuT) 9.5 CuT 9.5 CuT Fan
Field piping (15.9 CuT) 19.1 CuT

Reducer

AHUR08DBV(H) / AHUR08CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE 12.7 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
Field piping (9.5 CuT) 9.5 CuT 9.5 CuT Fan
Field piping (19.1 CuT) 22.2 CuT

Reducer

AHUR10DBV(H) / AHUR10CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE 12.7 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
Field piping (9.5 CuT) 9.5 CuT 9.5 CuT Fan
Field piping (22.2 CuT) 28.6 CuT

Reducer

AHUR16DBV(H) / AHUR16CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
Field piping (12.7 CuT) 12.7 CuT 12.7 CuT Fan
Field piping (28.6 CuT) 34.9 CuT

Reducer

48 AHUR-DB/CB
EDADT1505A Piping diagrams

AHUR20DBV(H) / AHUR20CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
Field piping (15.9 CuT) 15.9 CuT 15.9 CuT Fan
Field piping (28.6 CuT) 34.9 CuT

Reducer

AHUR32DBV(H) / AHUR32CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T
+KHRP26M73TP 12.7 CuT 12.7 CuT
Field piping (19.1 CuT)

Field piping (*34.9 CuT) 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT


M
Filter Filter Fan

Electronic Heat
expansion valve exchanger

12.7 CuT 12.7 CuT

28.6 CuT 34.9 CuT

Reducer

AHUR40DBV(H) / AHUR40CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T
+KHRP26M73TP
Field piping (19.1 CuT) 15.9 CuT 15.9 CuT

Field piping (*41.3 CuT) 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT


M
Filter Filter Fan

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

Reducer

Note: REFNET is for example, it use header type, please refer to VRV IV Engineering data.
*Do not let the connection piping exceed main refrigerant piping size.

AHUR-DB/CB 49
Piping diagrams EDADT1505A

AHUR48DBV(H) / AHUR48CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T KHRP26A73T
+KHRP26M73TP +KHRP26M73TP
Field piping (19.1 CuT) 19.1 CuT 12.7 CuT 12.7 CuT

Field piping (*41.3 CuT) *34.9 CuT 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
12.7 CuT 12.7 CuT Fan
28.6 CuT 34.9 CuT

EXPANSION VALVE-3 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

12.7 CuT 12.7 CuT

28.6 CuT 34.9 CuT

Reducer

AHUR60DBV(H) / AHUR60CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T KHRP26A73T
+KHRP26M73TP +KHRP26M73TP
Field piping (19.1 CuT) 19.1 CuT 15.9 CuT 15.9 CuT

Field piping (*41.3 CuT) *41.3 CuT 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
15.9 CuT 15.9 CuT Fan
28.6 CuT 34.9 CuT

EXPANSION VALVE-3 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

Reducer

Note: REFNET is for example, it use header type, please refer to VRV IV Engineering data.
*Do not let the connection piping exceed main refrigerant piping size.

50 AHUR-DB/CB
EDADT1505A Piping diagrams

AHUR80DBV(H) / AHUR80CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T
+KHRP26M73TP
Field piping (19.1 CuT) 15.9 CuT 15.9 CuT

Field piping (*41.3 CuT) 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT

Filter Filter

Heat
Electronic
exchanger
expansion valve

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

EXPANSION VALVE-3 Reducer 15.9 CuT


M
Filter Filter
Fan

Heat
Electronic
exchanger
expansion valve
KHRP26A73T
+KHRP26M73TP 15.9 CuT 15.9 CuT
Field piping (19.1 CuT)
Field piping (*41.3 CuT) 28.6 CuT 34.9 CuT
EXPANSION VALVE-4 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

Reducer

Note: REFNET is for example, it use header type, please refer to VRV IV Engineering data.
*Do not let the connection piping exceed main refrigerant piping size.

AHUR-DB/CB 51
Piping diagrams EDADT1505A

AHUR100DBV(H) / AHUR100CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T
+KHRP26M73TP
Field piping (19.1 CuT) 15.9 CuT 15.9 CuT

Field piping (*41.3 CuT) 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

EXPANSION VALVE-3 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T KHRP26A73T M
+KHRP26M73TP +KHRP26M73TP 15.9 CuT 15.9 CuT
19.1 CuT Fan
Field piping (19.1 CuT)
28.6 CuT 34.9 CuT
Field piping (*41.3 CuT) *41.3 CuT
EXPANSION VALVE-4 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

EXPANSION VALVE-5 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

Reducer

Note: REFNET is for example, it use header type, please refer to VRV IV Engineering data.
*Do not let the connection piping exceed main refrigerant piping size.

52 AHUR-DB/CB
EDADT1505A Piping diagrams

AHUR120DBV(H) / AHUR120CBV(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T KHRP26A73T
+KHRP26M73TP +KHRP26M73TP
Field piping (19.1 CuT) 19.1 CuT 15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT


Field piping (*41.3 CuT) *41.3 CuT
EXPANSION VALVE-2 Reducer 15.9 CuT

Filter Filter

Heat
Electronic
exchanger
expansion valve

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

EXPANSION VALVE-3 Reducer 15.9 CuT

Filter Filter

Heat
Electronic
exchanger
expansion valve

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

EXPANSION VALVE-4 Reducer 15.9 CuT


M
Filter Filter Fan

Electronic Heat
expansion valve exchanger
KHRP26A73T KHRP26A73T
+KHRP26M73TP +KHRP26M73TP 15.9 CuT 15.9 CuT
Field piping (19.1 CuT) 19.1 CuT
28.6 CuT 34.9 CuT
Field piping (*41.3 CuT) *41.3 CuT
EXPANSION VALVE-5 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

EXPANSION VALVE-6 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

Reducer

Note: REFNET is for example, it use header type, please refer to VRV IV Engineering data.
*Do not let the connection piping exceed main refrigerant piping size.

AHUR-DB/CB 53
Wiring diagrams EDADT1505A

4. Wiring diagrams
4.1 Standard series PCB

EKEQMCBA

54 AHUR-DB/CB
EDADT1505A Wiring diagrams

4.2 Installation manual for KRP4AA51

AHUR-DB/CB 55
Wiring diagrams EDADT1505A

56 AHUR-DB/CB
EDADT1505A Wiring diagrams

AHUR-DB/CB 57
Wiring diagrams EDADT1505A

58 AHUR-DB/CB
EDADT1505A Wiring diagrams

AHUR-DB/CB 59
Wiring diagrams EDADT1505A

4.3 External connection diagram

AHUR06DBV(H) / AHUR06CBV(H) / AHUR08DBV(H) / AHUR08CBV(H) / AHUR10DBV(H) / AHUR10CBV(H) /


AHUR16DBV(H) / AHUR16CBV(H) / AHUR20DBV(H) / AHUR20CBV(H)

Power supply
1 2 3 N

Main switch

Air handling unit

1 2 3 N
Switch
M
Fuse

Thermistor lines (3x)


L (Standard 2.5m)
(Max. 20m)
Transmission
Fan switch
L N Digital output
Gas pipe
Control & Starter Panel
Switch Liquid pipe

Fuse
Expansion valve Connector
L (Max. 20m)
Power supply

L
N F2 F1
P1 Remote
EKEQMCBA P2
controller
EKEXV
Expansion valve Standard series PCB

Electronic Notes:
expansion valve
1 All wiring, components and materials to be produced on the site must comply
with the applicable local and national codes.
2 Use copper conductors only.
Filter Filter 3 For more details, see wiring diagram.
4 Install a circuit breaker for safety.
5 All field wiring and components must be provided by a licensed electrician.
6 The unit shall be grounded in compliance with the applicable local and
national codes.
7 Wiring shown are general points-of-connection guides only and are not
intended for or to include all details for a specific installation.
8 Be sure to install the switch and the fuse to the power line of each equipment.
9 Install the main switch that can interrupt all power sources in an integrated
manner because this system consists of the equipment utilizing the multiple
power sources.
10 For detailed standard series PCB side connection, see standard series PCB
manual and wiring diagram.
Wiring 11 For detailed pipe connections and limitations, see manuals.
Refrigerant piping 12 Connection appliance can be standard indoor unit or free choice of air
handling unit.

60 AHUR-DB/CB
EDADT1505A Wiring diagrams

AHUR32DBV(H) / AHUR32CBV(H) / AHUR40DBV(H) / AHUR40CBV(H)

Power supply
1 2 3 N

Main switch

Air handling unit

1 2 3 N
Switch
M
Fuse

Thermistor lines (3x)


L (Standard 2.5m)
(Max. 20m)

Transmission Fan switch


L N Digital output
Gas pipe
Control & Starter Panel
Switch Liquid pipe

Fuse
Expansion valve Connector
L (Max. 20m)
Power supply

L
N F2 F1
P1 Remote
EKEXV EKEQMCBA P2
controller
Expansion valve-1 Standard
series PCB-1
Electronic
expansion valve

Filter Filter
L
N F2 F1
P1
EKEQMCBA P2

Standard
EKEXV series PCB-2
Expansion valve-2

Electronic Notes:
expansion valve
1 All wiring, components and materials to be produced on the site must comply
with the applicable local and national codes.
2 Use copper conductors only.
Filter Filter 3 For more details, see wiring diagram.
4 Install a circuit breaker for safety.
5 All field wiring and components must be provided by a licensed electrician.
6 The unit shall be grounded in compliance with the applicable local and
national codes.
7 Wiring shown are general points-of-connection guides only and are not
intended for or to include all details for a specific installation.
8 Be sure to install the switch and the fuse to the power line of each equipment.
9 Install the main switch that can interrupt all power sources in an integrated
manner because this system consists of the equipment utilizing the multiple
power sources.
10 For detailed standard series PCB side connection, see standard series PCB
Wiring manual and wiring diagram.
Refrigerant piping 11 For detailed pipe connections and limitations, see manuals.
12 Connection appliance can be standard indoor unit or free choice of air
handling unit.

AHUR-DB/CB 61
Wiring diagrams EDADT1505A

AHUR48DBV(H) / AHUR48CBV(H) / AHUR60DBV(H) / AHUR60CBV(H)

Power supply
1 2 3 N

Main switch

Air handling unit

1 2 3 N
Switch
M
Fuse

Thermistor lines (3x)


L (Standard 2.5m)
(Max. 20m)

Transmission Fan switch


L N Digital output
Gas pipe
Control & Starter Panel
Switch Liquid pipe

Fuse
Expansion valve Connector
L (Max. 20m)
Power supply

L
N F2 F1
P1 Remote
EKEQMCBA P2
EKEXV controller
Expansion valve-1 Standard
series PCB-1
Electronic
expansion valve

Filter Filter
L
N F2 F1
P1
EKEQMCBA P2

EKEXV Standard
Expansion valve-2 series PCB-2

Electronic
expansion valve

L
F2F1
Filter Filter N P1
EKEQMCBA P2

Standard
series PCB-3
EKEXV
Expansion valve-3

Electronic Notes:
expansion valve 1 All wiring, components and materials to be produced on the site must comply
with the applicable local and national codes.
2 Use copper conductors only.
Filter Filter 3 For more details, see wiring diagram.
4 Install a circuit breaker for safety.
5 All field wiring and components must be provided by a licensed electrician.
6 The unit shall be grounded in compliance with the applicable local and
national codes.
7 Wiring shown are general points-of-connection guides only and are not
intended for or to include all details for a specific installation.
8 Be sure to install the switch and the fuse to the power line of each equipment.
Wiring 9 Install the main switch that can interrupt all power sources in an integrated
Refrigerant piping manner because this system consists of the equipment utilizing the multiple
power sources.
10 For detailed standard series PCB side connection, see standard series PCB
manual and wiring diagram.
11 For detailed pipe connections and limitations, see manuals.
12 Connection appliance can be standard indoor unit or free choice of air
handling unit.

62 AHUR-DB/CB
EDADT1505A Wiring diagrams

AHUR80DBV(H) / AHUR80CBV(H)
Power supply
1 2 3 N

Main switch

Air handling unit

1 2 3 N
Switch
Gas pipe M
Fuse
Liquid pipe
Thermistor lines (3x)
L (Standard 2.5m)
(Max. 20m)

Transmission Fan switch


L N Digital output
Gas pipe
Control & Starter Panel
Switch Liquid pipe

Fuse
Expansion valve Connector
L (Max. 20m)
Power supply

L
N F2 F1
P1 Remote
EKEQMCBA P2
controller
EKEXV
Expansion valve-1 Standard
series PCB-1
Electronic
expansion valve

Filter Filter
L
N F2 F1
P1
EKEQMCBA P2

Standard
EKEXV
series PCB-2
Expansion valve-2

Electronic
expansion valve
Power supply
1 2 3 N

Main switch Filter Filter

1 2 3 N
Switch

Fuse

L
N F2 F1
P1
EKEQMCBA P2

Standard
series PCB-3
EKEXV
Expansion valve-3

Electronic
expansion valve L
N F2 F1
P1
EKEQMCBA P2

Filter Filter Standard


series PCB-4

Notes:
1 All wiring, components and materials to be produced on the site must comply
EKEXV with the applicable local and national codes.
Expansion valve-4 2 Use copper conductors only.
3 For more details, see wiring diagram.
Electronic 4 Install a circuit breaker for safety.
expansion valve 5 All field wiring and components must be provided by a licensed electrician.
6 The unit shall be grounded in compliance with the applicable local and
national codes.
7 Wiring shown are general points-of-connection guides only and are not
Filter Filter intended for or to include all details for a specific installation.
8 Be sure to install the switch and the fuse to the power line of each equipment.
9 Install the main switch that can interrupt all power sources in an integrated
manner because this system consists of the equipment utilizing the multiple
power sources.
10 For detailed standard series PCB side connection, see standard series PCB
manual and wiring diagram.
Wiring 11 For detailed pipe connections and limitations, see manuals.
Refrigerant piping 12 Connection appliance can be standard indoor unit or free choice of air
handling unit.

AHUR-DB/CB 63
Wiring diagrams EDADT1505A

AHUR100DBV(H) / AHUR100CBV(H)

Expansion valve-1 Standard


series PCB-1

Standard
Expansion valve-2 series PCB-2

Expansion valve-3

Standard
series PCB-3

Expansion valve-4
Standard
series PCB-4

Expansion valve-5 Standard


series PCB-5
Notes:
1 All wiring, components and materials to be produced on the site must comply with the
applicable local and national codes.
2 Use copper conductors only.
3 For more details, see wiring diagram.
4 Install a circuit breaker for safety.
5 All field wiring and components must be provided by a licensed electrician.
6 The unit shall be grounded in compliance with the applicable local and national codes.
7 Wiring shown are general points-of-connection guides only and are not intended for or
to include all details for a specific installation.
8 Be sure to install the switch and the fuse to the power line of each equipment.
9 Install the main switch that can interrupt all power sources in an integrated manner
because this system consists of the equipment utilizing the multiple power sources.
10 For detailed standard series PCB side connection, see standard series PCB manual
and wiring diagram.
11 For detailed pipe connections and limitations, see manuals.
12 Connection appliance can be standard indoor unit or free choice of air handling unit.

64 AHUR-DB/CB
EDADT1505A Wiring diagrams

AHUR120DBV(H) / AHUR120CBV(H)

Expansion valve-1 Standard


series PCB-1

Standard
Expansion valve-2 series PCB-2

Standard
series PCB-3

Expansion valve-3

Expansion valve-4
Standard
series PCB-4

Standard
Expansion valve-5
series PCB-5

Standard
series PCB-6
Expansion valve-6

Notes:
1 All wiring, components and materials to be produced on the site must comply with the
applicable local and national codes.
2 Use copper conductors only.
3 For more details, see wiring diagram.
4 Install a circuit breaker for safety.
5 All field wiring and components must be provided by a licensed electrician.
6 The unit shall be grounded in compliance with the applicable local and national codes.
7 Wiring shown are general points-of-connection guides only and are not intended for or
to include all details for a specific installation.
8 Be sure to install the switch and the fuse to the power line of each equipment.
9 Install the main switch that can interrupt all power sources in an integrated manner
because this system consists of the equipment utilizing the multiple power sources.
10 For detailed standard series PCB side connection, see standard series PCB manual
and wiring diagram.
11 For detailed pipe connections and limitations, see manuals.
12 Connection appliance can be standard indoor unit or free choice of air handling unit.

AHUR-DB/CB 65
Field preparation EDADT1505A

5. Field preparation
5.1 External wiring connection diagram

AHUR06DBV(H) / AHUR06CBV(H) / AHUR08DBV(H) / AHUR08CBV(H) / AHUR10DBV(H) / AHUR10CBV(H) /


AHUR16DBV(H) / AHUR16CBV(H) / AHUR20DBV(H) / AHUR20CBV(H)

66 AHUR-DB/CB
EDADT1505A Field preparation

AHUR32DBV(H) / AHUR32CBV(H) / AHUR40DBV(H) / AHUR40CBV(H)

AHUR-DB/CB 67
Field preparation EDADT1505A

AHUR48DBV(H) / AHUR48CBV(H) / AHUR60DBV(H) / AHUR60CBV(H)

68 AHUR-DB/CB
EDADT1505A Field preparation

AHUR80DBV(H) / AHUR80CBV(H)

AHUR-DB/CB 69
Field preparation EDADT1505A

AHUR100DBV(H) / AHUR100CBV(H)

70 AHUR-DB/CB
EDADT1505A Field preparation

AHUR120DBV(H) / AHUR120CBV(H)

AHUR-DB/CB 71
72
Field preparation

Table connection and application

Cross section Maximum length


Description Connect to Type of cable (mm²)(*) (m) Specifications
L, N,
Power supply Power supply H05VV-F3G2.5 2.5 — Power supply 230 V 1-50 Hz
earth
Expansion valve
Y1~Y6 Expansion valve LIYCY3 x 2 x 0.75 20 Digital output 12 V DC
connection
Thermistor R2T
R1,R2
(liquid pipe)
Standard: 2.5
Thermistor R3T Analog input 16 V DC
R3,R4 — Max.: 20
(gas pipe) 0.75
R5,R6 Thermistor R1T (air) H05VV-F2 x 0.75
P1,P2 Remote control
Communication to 100 Communication line 16 V DC
F1,F2 Outdoor unit
outdoor unit
T1,T2 ON/OFF — Digital input 16 V DC
— Capacity step
Controller field supply Optional connection: when the function of the switch box needs to be
— Error signal LIYCY4 x 2 x 0.75
extended: see KRP4A51 for details of settings and instructions.
— Operation signal
Air handling unit fan Digital output: voltage free.
C1,C2 Fan signal H05VV-F3G2.5 2.5 —
field supply Maximum 230 V, maximum 2 A
(*) Recommended size (all wiring must comply with local codes).

AHUR-DB/CB
EDADT1505A
EDADT1505A Electrical characteristics

6. Electrical characteristics
6.1 Indoor unit
Power supply IFM
Model
Hz Volts Voltage range MFA KW FLA

AHUR06DBV / AHUR06CBV Max. 50Hz 456V 15 2.2 5.28


Min. 50Hz 342V

AHUR08DBV / AHUR08CBV Max. 50Hz 456V 15 2.2 5.28


Min. 50Hz 342V

AHUR10DBV / AHUR10CBV Max. 50Hz 456V 15 2.2 5.28


Min. 50Hz 342V

AHUR16DBV / AHUR16CBV Max. 50Hz 456V 20 4.0 8.92


Min. 50Hz 342V
Max. 50Hz 456V
AHUR20DBV / AHUR20CBV Min. 50Hz 342V 20 4.0 8.92

Max. 50Hz 456V


AHUR32DBV / AHUR32CBV Min. 50Hz 342V 30 7.5 15.40
50 380-415
AHUR40DBV / AHUR40CBV Max. 50Hz 456V 40 11.0 22.10
Min. 50Hz 342V

AHUR48DBV / AHUR48CBV Max. 50Hz 456V 50 11.0 22.10


Min. 50Hz 342V

AHUR60DBV / AHUR60CBV Max. 50Hz 456V 50 11.0 22.10


Min. 50Hz 342V

AHUR80DBV / AHUR80CBV Max. 50Hz 456V 80 18.5 36.60


Min. 50Hz 342V

AHUR100DBV / AHUR100CBV Max. 50Hz 456V 100 22.0 44.30


Min. 50Hz 342V
Max. 50Hz 456V
AHUR120DBV / AHUR120CBV Min. 50Hz 342V 130 30.0 58.10

Max. 60Hz 456V


AHUR06DBVH / AHUR06CBVH Min. 60Hz 342V 15 2.2 5.29

AHUR08DBVH / AHUR08CBVH Max. 60Hz 456V 15 2.2 5.29


Min. 60Hz 342V

AHUR10DBVH / AHUR10CBVH Max. 60Hz 456V 15 2.2 5.29


Min. 60Hz 342V

AHUR16DBVH / AHUR16CBVH Max. 60Hz 456V 20 4.0 9.11


Min. 60Hz 342V

AHUR20DBVH / AHUR20CBVH Max. 60Hz 456V 20 4.0 9.11


Min. 60Hz 342V
Max. 60Hz 456V
AHUR32DBVH / AHUR32CBVH Min. 60Hz 342V 30 7.5 15.24
60 380-415
Max. 60Hz 456V
AHUR40DBVH / AHUR40CBVH Min. 60Hz 342V 40 11.0 22.47

AHUR48DBVH / AHUR48CAVH Max. 60Hz 456V 50 11.0 22.47


Min. 60Hz 342V

AHUR60DBVH / AHUR60CBVH Max. 60Hz 456V 50 11.0 22.47


Min. 60Hz 342V

AHUR80DBVH / AHUR80CBVH Max. 60Hz 456V 80 18.5 36.62


Min. 60Hz 342V

AHUR100DBVH / AHUR100CBVH Max. 60Hz 456V 100 22.0 44.48


Min. 60Hz 342V
Max. 60Hz 456V
AHUR120DBVH / AHUR120CBVH Min. 60Hz 342V 130 30.0 57.83

Symbols: Notes:
MFA : Max. fuse amps (A) 1. Voltage range
Units are suitable for use on electrical systems
IFM : Indoor fan motor where voltage supplied to unit terminals
KW : Fan motor rated output (kW) is not below or above listed range limits.
2. Maximum allowable voltage unbalance between phases is 2%.
FLA : Full load amps (A) 3. Either a fuse or a circuit breaker acceptable.

AHUR-DB/CB 73
Capacity tables EDADT1505A

7. Capacity tables
EKEQMCBA Cooling capacity

14WB 16WB 18WB 19WB 20WB 22WB 24WB


Capacity 20DB 22DB 25DB 27DB 28DB 30DB 32DB
index
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
140 10.8 8.3 12.9 9.3 15.0 10.7 16.0 11.5 16.5 11.7 17.3 11.6 17.6 11.7
200 15.1 11.9 18.0 13.1 21.0 15.3 22.4 16.3 23.1 16.7 24.2 16.6 24.6 16.8
250 18.9 14.9 22.5 16.6 26.2 19.2 28.0 20.5 28.8 20.9 30.2 20.7 30.8 21.0
400 30.4 23.6 36.2 26.3 42.1 30.4 45.0 32.6 46.4 32.8 48.5 32.8 49.5 33.4
500 37.8 29.8 45.0 33.1 52.4 38.3 56.0 40.9 57.7 40.9 60.4 41.3 61.6 42.0

Note:
1. Capacity table include fan heat for selection.
2. Expansion valve (EV) EKEXV140, 200, 250, 400 and 500 are used for each of air handling unit (AHU) 6HP, 8HP, 10HP, 16HP and 20HP,
respectively. For AHU that over 20HP, it will use multiple EV. Please calculate data from capacity tables multiply by quantity of EV.

74 AHUR-DB/CB
EDADT1505A Fan Performances

8. Fan Performances

Airflow Fan speed


Model Standard point
Range (CMH) (CMM) Pa 250 300 350 450 500
(rpm) 1,923 2,004 2,081 2,230 2,300
Min 2,940 49
(kW) 1.04 1.12 1.20 1.36 1.44
(rpm) 1,962 2,043 2,121 2,266 2,334 Airflow = 54 m³/m,
AHUR06 Std 3,240 54 ESP = 450 Pa,
(kW) 1.20 1.30 1.39 1.57 1.66
Fan speed = 1,376 rpm
(rpm) 2,068 2,140 2,209 2,344 2,412
Max 3,840 64
(kW) 1.65 1.74 1.84 2.03 2.14
(rpm) 1,387 1,464 1,543 1,705 1,784
Min 3,660 61 Airflow = 68 m³/m,
(kW) 0.99 1.09 1.20 1.46 1.59
AHUR08 ESP = 450 Pa,
(rpm) 1,393 1,462 1,530 1,669 1,740
Std 4,080 68 Fan speed = 1,669 rpm
(kW) 1.15 1.24 1.34 1.58 1.71
(rpm) 1,396 1,465 1,531 1,664 1,732
Min 4,200 70 Airflow = 78 m³/m,
(kW) 1.20 1.30 1.40 1.62 1.75
AHUR10 ESP = 450 Pa,
(rpm) 1,406 1,475 1,541 1,664 1,724
Std 4,680 78 Fan speed = 1,664 rpm
(kW) 1.40 1.51 1.63 1.85 1.97
(rpm) 1,096 1,150 1,206 1,369 1,371
Min 7,380 123 Airflow = 136 m³/m,
(kW) 2.13 2.31 2.49 3.09 3.07
AHUR16 ESP = 450 Pa,
(rpm) 1,109 1,160 1,209 1,309 1,359
Std 8,160 136 Fan speed = 1,309 rpm
(kW) 2.49 2.67 2.87 3.27 3.47
(rpm) 933 980 1,029 1,131 1,182
Min 9,000 150 Airflow = 166 m³/m,
(kW) 2.21 2.39 2.60 3.07 3.32
AHUR20 ESP = 450 Pa,
(rpm) 946 988 1,029 1,116 1,161
Std 9,960 166 Fan speed = 1,116 rpm
(kW) 2.61 2.80 2.98 3.40 3.64
(rpm) 751 786 821 889 922
Min 14,760 246 Airflow = 272 m³/m,
(kW) 3.60 3.89 4.18 4.79 5.11
AHUR32 ESP = 450 Pa,
(rpm) 762 796 828 892 924
Std 16,320 272 Fan speed = 892 rpm
(kW) 4.25 4.54 4.86 5.49 5.82
(rpm) 713 747 779 841 871
Min 18,000 300 Airflow = 332 m³/m,
(kW) 4.41 4.77 5.13 5.88 6.26
AHUR40 ESP = 450 Pa,
(rpm) 723 756 787 847 876
Std 19,920 332 Fan speed = 847 rpm
(kW) 5.18 5.56 5.94 6.75 7.15
(rpm) 623 652 680 736 763
Min 22,140 369 Airflow = 408 m³/m,
(kW) 5.09 5.50 5.92 6.80 7.28
AHUR48 ESP = 450 Pa,
(rpm) 632 661 688 740 765
Std 24,480 408 Fan speed = 740 rpm
(kW) 5.96 6.41 6.86 7.77 8.24
(rpm) 562 589 614 663 687
Min 27,000 450 Airflow = 498 m³/m,
(kW) 6.41 6.96 7.53 8.69 9.27
AHUR60 ESP = 450 Pa,
(rpm) 569 596 621 668 690
Std 29,880 498 Fan speed = 664 rpm
(kW) 7.47 8.05 8.65 9.88 10.51
(rpm) 742 777 811 875 906
Min 36,000 600 Airflow = 664 m³/m,
(kW) 9.47 10.25 11.04 12.65 13.47
AHUR80 ESP = 450 Pa,
(rpm) 752 786 819 881 911
Std 39,840 664 Fan speed = 881 rpm
(kW) 11.13 11.95 12.78 14.50 15.38
(rpm) 650 680 709 765 794
Min 45,000 750 Airflow = 830 m³/m,
(kW) 11.23 12.12 13.02 14.91 15.93
AHUR100 ESP = 450 Pa,
(rpm) 660 689 717 771 797
Std 49,800 830 Fan speed = 771 rpm
(kW) 13.18 14.16 15.15 17.12 18.13
(rpm) 585 612 639 689 714
Min 54,000 900 Airflow = 996 m³/m,
(kW) 13.78 14.96 16.19 18.68 19.93
AHUR120 ESP = 450 Pa,
(rpm) 592 619 646 695 718
Std 59,760 996 Fan speed = 695 rpm
(kW) 16.07 17.32 18.59 21.23 22.61

AHUR-DB/CB 75
Operation limits EDADT1505A

9. Operation limits
Temperature range
Cooling
Entering air temperature Minimum 14°CWB
on heat exchanger AHU Maximum 35°CDB / 25°CWB
Minimum -5°CDB
Outdoor unit VRV IV
Maximum 49°CDB
Minimum -5°CDB
Expansion valve
Maximum 46°CDB
Minimum -10°CDB
Standard series PCB
Maximum 40°CDB

10. Sound Pressure Level (SPL)


Overall

Location of microphone (for sound pressure level) Notes:


1. The operating conditions are assumed to be standard
(JIS conditions).
m
1.0 2. These operating values were obtained in anechoic
chamber (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipment installed.
1.5 m

dB(A)
Sound pressure level
Model
380-415V, 50/60Hz
AHUR06DBV(H)/CBV(H) 63
AHUR08DBV(H)/CBV(H) 59
AHUR10DBV(H)/CBV(H) 59
AHUR16DBV(H)/CBV(H) 66
AHUR20DBV(H)/CBV(H) 64
AHUR32DBV(H)/CBV(H) 65
AHUR40DBV(H)/CBV(H) 65
AHUR48DBV(H)/CBV(H) 66
AHUR60DBV(H)/CBV(H) 65
AHUR80DBV(H)/CBV(H) 70
AHUR100DBV(H)/CBV(H) 71
AHUR120DBV(H)/CBV(H) 71

76 AHUR-DB/CB
EDADT1505A Sound Pressure Level (SPL)

Octave Band Level


380-415V, 50/60Hz
AHUR06DBV(H)/CBV(H) AHUR08DBV(H)/CBV(H) AHUR10DBV(H)/CBV(H)
53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800

80 80 80

NC-70 NC-70 NC-70


OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL


OCTAVE BAND SOUND PRESSURE LEVEL
70 70 70

NC-60 NC-60
NC-60
dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)
60 60

dB (0dB=0.0002µ bar)
60

NC-50 NC-50 NC-50


50 50 50

NC-40 NC-40 NC-40


40 40 40

NC-30 NC-30 NC-30


30 30 30

NC-20 NC-20 NC-20


20 20 20
APPROXIMATE APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

AHUR16DBV(H)/CBV(H) AHUR20DBV(H)/CBV(H) AHUR32DBV(H)/CBV(H)


53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800

80 80 80

NC-70 NC-70 NC-70


OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL


70 70 70

NC-60 NC-60 NC-60


dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)
60 60 60

NC-50 NC-50 NC-50


50 50 50

NC-40 NC-40 NC-40


40 40 40

NC-30 NC-30 NC-30


30 30 30

NC-20 NC-20 NC-20


20 20 20
APPROXIMATE APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

AHUR40DBV(H)/CBV(H) AHUR48DBV(H)/CBV(H) AHUR60DBV(H)/CBV(H)


53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800

80 80 80

NC-70
NC-70 NC-70
OCTAVE BAND SOUND PRESSURE LEVEL
OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

70 70 70

NC-60 NC-60 NC-60


dB (0dB=0.0002µ bar)

60
dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)

60 60

NC-50 NC-50 NC-50


50 50 50

NC-40 NC-40 NC-40


40 40 40

NC-30 NC-30 NC-30


30 30 30

NC-20 NC-20 NC-20


20 20 20
APPROXIMATE APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

AHUR80DBV(H)/CBV(H) AHUR100DBV(H)/CBV(H) AHUR120DBV(H)/CBV(H)


53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800

80 80 80

NC-70 NC-70 NC-70


OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

70 70 70

NC-60 NC-60 NC-60


dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)

60 60 60

NC-50 NC-50 NC-50


50 50 50

NC-40 NC-40 NC-40


40 40 40

NC-30 NC-30 NC-30


30 30 30

NC-20 NC-20 NC-20


20 20 20
APPROXIMATE APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

AHUR-DB/CB 77
Fan Sound Power Level (PWL) EDADT1505A

11. Fan Sound Power Level (PWL)


Octave band center frequency
Model
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
AHUR06DBV(H)/CBV(H) 82 85 85 84 82 77 75 73
AHUR08DBV(H)/CBV(H) 80 84 82 78 75 72 69 62
AHUR10DBV(H)/CBV(H) 81 84 82 79 75 72 69 62
AHUR16DBV(H)/CBV(H) 82 86 86 85 87 84 82 79
AHUR20DBV(H)/CBV(H) 86 89 85 83 82 77 73 67
AHUR32DBV(H)/CBV(H) 81 85 86 85 85 81 80 76
AHUR40DBV(H)/CBV(H) 86 88 86 86 84 80 78 73
AHUR48DBV(H)/CBV(H) 86 88 87 87 85 80 78 72
AHUR60DBV(H)/CBV(H) 86 89 86 87 81 77 73 67
AHUR80DBV(H)/CBV(H) 90 93 91 90 90 86 84 79
AHUR100DBV(H)/CBV(H) 90 92 92 91 90 86 83 78
AHUR120DBV(H)/CBV(H) 92 95 93 93 88 84 80 74

78 AHUR-DB/CB
EDADT1505A Specifications

Part 3 Air Handling Unit (Outdoor air series)


1. Specifications
1.1 AHUR_DBL(H)
MODEL NAME: AHUR_DBL(H)
1 CASING 50 mm Thickness Double Skinned Panel (Thermal Break)
0.5 mm Thickness White Colourbond Steel Sheet
Insulation 50 mm Thickness Polyurethane Foam 40 kg/m3 Density
2 CASING-FRAME Steel with Black Epoxy Paint
3 COIL DX Coil
Tube Copper Tube
Fin Aluminum Slit
Header Copper Tube
Frame Galvanized Steel
Working Pressure 10 kg/cm2G
4 FAN (Brand = Kruger)
Type Double Width Double Inlet Forward Curved Centrifugal Belt Drive Fan
Wheel Galvanized Steel
Housing Galvanized Steel
Frame Steel with Polyester Powder Coating
5 MOTOR (Brand = Teco)
Type Three-Phase Induction Motor Totally Enclosed Fan-Cooled Type
Protection = IP55, Insulation Class = F, IE1
6 VIBRATION ISOLATOR (FAN) Spring Isolator
7 DRAIN PAN 1.2 mm (SUS304)
Beneath the Drain Pan is Covered with PU Insulation 40 kg/m3 Density
8 AIR FILTER (Brand = AAF)
Pre Filter Type = R29, CLASS = G3 (AFI = 80-85%) Synthetic washable
SIZE = FULL (24”x24”x2”/595x595x50mm), HALF (12”x24”x2”/290x595x50mm)
9 WEATHER PROOF ROOF SUS304
10 OUTDOOR AIR SERIES PCB EKEQFCBAV3
11 EXPANSION VALVE EKEXV200, EKEXV250, EKEXV400, EKEXV500

AHUR-DB/CB 79
Specifications EDADT1505A

Air Handling Unit


Model AHUR08DBL(H) AHUR10DBL(H)
Total Cooling Capacity kW 22.8 22.8 22.7 22.6 22.5 28.3 28.3 28.2 28.1 28.0
Net +1
Total Sensible Cooling Capacity kW 10.9 10.9 10.8 10.7 10.6 13.2 13.2 13.1 13.0 12.9
Total Cooling Capacity kW 23.3 28.9
Gross +2
Sensible Cooling Capacity kW 11.4 13.8
Air Flow cmh / m³/min 2,040/34 2,340/39
On Coil °CDB/°CWB 33/28 33/28
Off Coil °CDB/°CWB 19.4/18.9 18.4/18
Coil Type DX.Coil (R410A) φ8 mm. Wave slit surface & Straight edge
Coil Face Area m² 0.443 0.54
Coil Face Vel. m/s 1.28 1.20
Air PD.In Coil Pa 50 50
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 1 -
Air Filter Size 24”x24”x2” +3 pcs. 1 2
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 410 460 510 610 660 410 460 510 610 660
Fan Type Forward curve
Model FSA280CM FSA280CM
kW 0.75 1.1 0.75 1.1
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380/3/50(60) 380/3/50(60)
FLA amp. 2.05 2.82 2.05 2.82
Machine Weight kg 545 550 605 610
Sound Pressure Level (SPL) dB(A) 56 58 60 62 63 56 57 58 60 62
Outdoor Air Series PCB Model/pcs. EKEQFCBAV3/1pc. EKEQFCBAV3/1pc.
Expansion Valve Model/pcs. EKEXV200/1pc. EKEXV250/1pc.
Dimension: (WxDxH) m 1.3x1.4x1.2 1.5x1.4x1.2
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ9.5 (Brazing connection) φ9.5 (Brazing connection)
Piping Connections Gas pipes +5 mm φ19.1 (Brazing connection) φ22.2 (Brazing connection)
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 200 250

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
+4. Motor is induction motor class F, IP 55. cfm=m³/min×35.3
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
Only AHU 50 - 110% – 50 - 110%
(Pair AHU)
7. Air temperature control via an external DDC controller (field supplied).

80 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR16DBL(H) AHUR20DBL(H)
Total Cooling Capacity kW 45.3 45.2 45.1 44.9 44.7 56.7 56.6 56.5 56.2 56.1
Net +1
Total Sensible Cooling Capacity kW 17.0 16.9 16.8 16.6 16.4 21.3 21.2 21.1 20.8 20.7
Total Cooling Capacity kW 46.3 58.4
Gross +2
Sensible Cooling Capacity kW 22.7 29.3
Air Flow cmh / m³/min 4,080/68 5,460/91
On Coil °CDB/°CWB 33/28 33/28
Off Coil °CDB/°CWB 19.3/19.0 19.9/19.6
Coil Type DX.Coil (R410A) φ8 mm. Wave slit surface & Straight edge
Coil Face Area m² 0.784 0.99
Coil Face Vel. m/s 1.45 1.53
Air PD.In Coil Pa 50 50
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 1 -
Air Filter Size 24”x24”x2” +3 pcs. 2 3
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 410 460 510 610 660 410 460 510 610 660
Fan Type Forward curve
Model FDA250TM FDA250TM
kW 1.5 2.2 2.2 3.0
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380/3/50(60) 380/3/50(60)
FLA amp. 3.64 5.28 5.28 6.58
Machine Weight kg 700 710 815 825
Sound Pressure Level (SPL) dB(A) 55 56 57 58 59 55 56 57 58 59
Outdoor Air Series PCB Model/pcs. EKEQFCBAV3/1pc. EKEQFCBAV3/1pc.
Expansion Valve Model/pcs. EKEXV400/1pc. EKEXV500/1pc.
Dimension: (WxDxH) m 1.8x1.5x1.2 2.1x1.6x1.2
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ12.7 (Brazing connection) φ15.9 (Brazing connection)
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) φ28.6 (Brazing connection)
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 400 500

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
+4. Motor is induction motor class F, IP 55. cfm=m³/min×35.3
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
Only AHU 50 - 110% – 50 - 110%
(Pair AHU)
7. Air temperature control via an external DDC controller (field supplied).

AHUR-DB/CB 81
Specifications EDADT1505A

Air Handling Unit


Model AHUR32DBL(H) AHUR40DBL(H)
Total Cooling Capacity kW 90.3 90.1 89.9 89.5 89.3 114.4 114.2 114.0 113.5 113.2
Net +1
Total Sensible Cooling Capacity kW 33.7 33.5 33.3 32.9 32.7 43.6 43.4 43.2 42.7 42.4
Total Cooling Capacity kW 92.6 116.8
Gross +2
Sensible Cooling Capacity kW 45.4 58.6
Air Flow cmh / m³/min 8,160/136 10,920/182
On Coil °CDB/°CWB 33/28 33/28
Off Coil °CDB/°CWB 19.3/19.0 19.9/19.6
Coil Type DX.Coil (R410A) φ8 mm. Wave slit surface & Straight edge
Coil Face Area m² 1.568 1.98
Coil Face Vel. m/s 1.45 1.53
Air PD.In Coil Pa 50 50
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 2 -
Air Filter Size 24”x24”x2” +3 pcs. 4 6
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 410 460 510 610 660 410 460 510 610 660
Fan Type Forward curve
Model FDA315TM FDA400TM
kW 3.0 4.0 3.0 4.0 5.5
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380/3/50(60) 380/3/50(60)
FLA amp. 6.58 8.92 6.58 8.92 12.0
Machine Weight kg 985 1,005 1,175 1,180 1,185
Sound Pressure Level (SPL) dB(A) 63 64 65 66 67 60 61 62 63 64
Outdoor Air Series PCB Model/pcs. EKEQFCBAV3/2pcs. EKEQFCBAV3/2pcs.
Expansion Valve Model/pcs. EKEXV400/2pcs. EKEXV500/2pcs.
Dimension: (WxDxH) m 1.8x1.8x1.6 2.1x1.8x1.6
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ12.7 (Brazing connection) x2 φ15.9 (Brazing connection) x2
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x2 φ28.6 (Brazing connection) x2
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 800 1,000

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
+4. Motor is induction motor class F, IP 55. cfm=m³/min×35.3
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
Only AHU 50 - 110% – 50 - 110%
(Pair AHU)
7. Air temperature control via an external DDC controller (field supplied).

82 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR48DBL(H) AHUR60DBL(H)
Total Cooling Capacity kW 136.0 135.8 135.6 135.1 134.8 171.7 171.4 171.0 170.3 170.0
Net +1
Total Sensible Cooling Capacity kW 51.1 50.9 50.7 50.2 49.9 65.5 65.2 64.8 64.1 63.8
Total Cooling Capacity kW 138.9 175.2
Gross +2
Sensible Cooling Capacity kW 68.1 87.9
Air Flow cmh / m³/min 12,240/204 16,380/273
On Coil °CDB/°CWB 33/28 33/28
Off Coil °CDB/°CWB 19.3/19.0 19.9/19.6
Coil Type DX.Coil (R410A) φ8 mm. Wave slit surface & Straight edge
Coil Face Area m² 2.35 2.97
Coil Face Vel. m/s 1.45 1.53
Air PD.In Coil Pa 50 50
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 3 -
Air Filter Size 24”x24”x2” +3 pcs. 6 9
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 410 460 510 610 660 410 460 510 610 660
Fan Type Forward curve
Model FDA400TM FDA500TM
kW 4.0 5.5 4.0 5.5 7.5
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380/3/50(60) 380/3/50(60)
FLA amp. 8.92 12.0 8.92 12.0 15.4
Machine Weight kg 1,280 1,285 1,615 1,625 1,645
Sound Pressure Level (SPL) dB(A) 60 61 62 63 64 61 62 63 64 65
Outdoor Air Series PCB Model/pcs. EKEQFCBAV3/3pcs. EKEQFCBAV3/3pcs.
Expansion Valve Model/pcs. EKEXV400/3pcs. EKEXV500/3pcs.
Dimension: (WxDxH) m 1.8x1.95x2.2 2.1x1.95x2.2
Panel Type Sandwich panel thickness 50 mm Sandwich panel thickness 50 mm
Liquid pipes mm φ12.7 (Brazing connection) x3 φ15.9 (Brazing connection) x3
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x3 φ28.6 (Brazing connection) x3
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 1,200 1,500

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
+4. Motor is induction motor class F, IP 55. cfm=m³/min×35.3
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
Only AHU 50 - 110% – 50 - 110%
(Pair AHU)
7. Air temperature control via an external DDC controller (field supplied).

AHUR-DB/CB 83
Specifications EDADT1505A

1.2 AHUR_CBL(H)
MODEL NAME: AHUR_CBL(H)
1 CASING 25 mm Thickness Double Skinned Panel
Outside 0.5 mm Thickness White Colourbond Steel Sheet
Inside 0.5 mm Thickness Galvanized Steel Sheet
Insulation 25 mm Thickness Polyurethane Foam 40 kg/m3 Density
2 CASING-FRAME Extruded Aluminium Profile
3 COIL DX Coil
Tube Copper Tube
Fin Aluminum Slit
Header Copper Tube
Frame Galvanized Steel
Working Pressure 10 kg/cm2G
4 FAN (Brand = Kruger)
Type Double Width Double Inlet Forward Curved Centrifugal Belt Drive Fan
Wheel Galvanized Steel
Housing Galvanized Steel
Frame Steel with Polyester Powder Coating
5 MOTOR (Brand = Teco)
Type Three-Phase Induction Motor Totally Enclosed Fan-Cooled Type
Protection = IP55, Insulation Class = F, IE1
6 VIBRATION ISOLATOR (FAN) Spring Isolator
7 DRAIN PAN 1.6 mm (Steel Sheet with Epoxy Coated)
Beneath the Drain Pan is Covered with PU Insulation Foam 40 kg/m3 Density
8 AIR FILTER (Brand = AAF)
Pre Filter Type = R29, CLASS = G3 (AFI = 80-85%) Synthetic washable
SIZE = FULL (24”x24”x2”/595x595x50mm), HALF (12”x24”x2”/290x595x50mm)
9 OUTDOOR AIR SERIES PCB EKEQFCBAV3
10 EXPANSION VALVE EKEXV200, EKEXV250, EKEXV400, EKEXV500

84 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR08CBL(H) AHUR10CBL(H)
Total Cooling Capacity kW 22.8 22.8 22.7 22.6 22.5 28.3 28.3 28.2 28.1 28.0
Net +1
Total Sensible Cooling Capacity kW 10.9 10.9 10.8 10.7 10.6 13.2 13.2 13.1 13.0 12.9
Total Cooling Capacity kW 23.3 28.9
Gross +2
Sensible Cooling Capacity kW 11.4 13.8
Air Flow cmh / m³/min 2,040/34 2,340/39
On Coil °CDB/°CWB 33/28 33/28
Off Coil °CDB/°CWB 19.4/18.9 18.4/18
Coil Type DX.Coil (R410A) φ8 mm. Wave slit surface & Straight edge
Coil Face Area m² 0.443 0.54
Coil Face Vel. m/s 1.28 1.20
Air PD.In Coil Pa 50 50
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 1 -
Air Filter Size 24”x24”x2” +3 pcs. 1 2
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 410 460 510 610 660 410 460 510 610 660
Fan Type Forward curve
Model FSA280CM FSA280CM
kW 0.75 1.1 0.75 1.1
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380/3/50(60) 380/3/50(60)
FLA amp. 2.05 2.82 2.05 2.82
Machine Weight kg 475 480 520 525
Sound Pressure Level (SPL) dB(A) 56 58 60 62 63 56 57 58 60 62
Outdoor Air Series PCB Model/pcs. EKEQFCBAV3/1pc. EKEQFCBAV3/1pc.
Expansion Valve Model/pcs. EKEXV200/1pc. EKEXV250/1pc.
Dimension: (WxDxH) m 1.3x1.2x1.1 1.5x1.2x1.1
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ9.5 (Brazing connection) φ9.5 (Brazing connection)
Piping Connections Gas pipes +5 mm φ19.1 (Brazing connection) φ22.2 (Brazing connection)
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 200 250

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
+4. Motor is induction motor class F, IP 55. cfm=m³/min×35.3
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
Only AHU 50 - 110% – 50 - 110%
(Pair AHU)
7. Air temperature control via an external DDC controller (field supplied).

AHUR-DB/CB 85
Specifications EDADT1505A

Air Handling Unit


Model AHUR16CBL(H) AHUR20CBL(H)
Total Cooling Capacity kW 45.3 45.2 45.1 44.9 44.7 56.7 56.6 56.5 56.2 56.1
Net +1
Total Sensible Cooling Capacity kW 17.0 16.9 16.8 16.6 16.4 21.3 21.2 21.1 20.8 20.7
Total Cooling Capacity kW 46.3 58.4
Gross +2
Sensible Cooling Capacity kW 22.7 29.3
Air Flow cmh / m³/min 4,080/68 5,460/91
On Coil °CDB/°CWB 33/28 33/28
Off Coil °CDB/°CWB 19.3/19.0 19.9/19.6
Coil Type DX.Coil (R410A) φ8 mm. Wave slit surface & Straight edge
Coil Face Area m² 0.784 0.99
Coil Face Vel. m/s 1.45 1.53
Air PD.In Coil Pa 50 50
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 1 -
Air Filter Size 24”x24”x2” +3 pcs. 2 3
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 410 460 510 610 660 410 460 510 610 660
Fan Type Forward curve
Model FDA250TM FDA250TM
kW 1.5 2.2 2.2 3.0
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380/3/50(60) 380/3/50(60)
FLA amp. 3.64 5.28 5.28 6.58
Machine Weight kg 670 680 775 785
Sound Pressure Level (SPL) dB(A) 55 56 57 58 59 55 56 57 58 59
Outdoor Air Series PCB Model/pcs. EKEQFCBAV3/1pc. EKEQFCBAV3/1pc.
Expansion Valve Model/pcs. EKEXV400/1pc. EKEXV500/1pc.
Dimension: (WxDxH) m 1.7x1.4x1.1 2.0x1.5x1.1
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ12.7 (Brazing connection) φ15.9 (Brazing connection)
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) φ28.6 (Brazing connection)
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 400 500

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
+4. Motor is induction motor class F, IP 55. cfm=m³/min×35.3
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
Only AHU 50 - 110% – 50 - 110%
(Pair AHU)
7. Air temperature control via an external DDC controller (field supplied).

86 AHUR-DB/CB
EDADT1505A Specifications

Air Handling Unit


Model AHUR32CBL(H) AHUR40CBL(H)
Total Cooling Capacity kW 90.3 90.1 89.9 89.5 89.3 114.4 114.2 114.0 113.5 113.2
Net +1
Total Sensible Cooling Capacity kW 33.7 33.5 33.3 32.9 32.7 43.6 43.4 43.2 42.7 42.4
Total Cooling Capacity kW 92.6 116.8
Gross +2
Sensible Cooling Capacity kW 48.4 58.6
Air Flow cmh / m³/min 8,160/136 10,920/182
On Coil °CDB/°CWB 33/28 33/28
Off Coil °CDB/°CWB 19.3/19.0 19.9/19.6
Coil Type DX.Coil (R410A) φ8 mm. Wave slit surface & Straight edge
Coil Face Area m² 1.568 1.98
Coil Face Vel. m/s 1.45 1.53
Air PD.In Coil Pa 50 50
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 2 -
Air Filter Size 24”x24”x2” +3 pcs. 4 6
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 410 460 510 610 660 410 460 510 610 660
Fan Type Forward curve
Model FDA315TM FDA400TM
kW 3.0 4.0 3.0 4.0 5.5
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380/3/50(60) 380/3/50(60)
FLA amp. 6.58 8.92 6.58 8.92 12.0
Machine Weight kg 870 890 975 980
Sound Pressure Level (SPL) dB(A) 63 64 65 66 67 60 61 62 63 64
Outdoor Air Series PCB Model/pcs. EKEQFCBAV3/2pcs. EKEQFCBAV3/2pcs.
Expansion Valve Model/pcs. EKEXV400/2pcs. EKEXV500/2pcs.
Dimension: (WxDxH) m 1.7x1.7x1.5 2.0x1.7x1.5
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ12.7 (Brazing connection) x2 φ15.9 (Brazing connection) x2
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x2 φ28.6 (Brazing connection) x2
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 800 1,000

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
+4. Motor is induction motor class F, IP 55. cfm=m³/min×35.3
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
Only AHU 50 - 110% – 50 - 110%
(Pair AHU)
7. Air temperature control via an external DDC controller (field supplied).

AHUR-DB/CB 87
Specifications EDADT1505A

Air Handling Unit


Model AHUR48CBL(H) AHUR60CBL(H)
Total Cooling Capacity kW 136.0 135.8 135.6 135.1 134.8 171.7 171.4 171.0 170.3 170.0
Net +1
Total Sensible Cooling Capacity kW 51.1 50.9 50.7 50.2 49.9 65.5 65.2 64.8 64.1 63.8
Total Cooling Capacity kW 138.9 175.2
Gross +2
Sensible Cooling Capacity kW 68.1 87.9
Air Flow cmh / m³/min 12,240/204 16,380/273
On Coil °CDB/°CWB 33/28 33/28
Off Coil °CDB/°CWB 19.3/19.0 19.9/19.6
Coil Type DX.Coil (R410A) φ8 mm. Wave slit surface & Straight edge
Coil Face Area m² 2.35 2.97
Coil Face Vel. m/s 1.45 1.53
Air PD.In Coil Pa 50 50
Air PD.In Pre Filter +3 Pa 80 80
Air Filter Size 12”x24”x2” +3 pcs. 3 -
Air Filter Size 24”x24”x2” +3 pcs. 6 9
Air PD.In Casing Pa 30 30
ESP.Initial Pa 250 300 350 450 500 250 300 350 450 500
Total Statics Pressure Pa 410 460 510 610 660 410 460 510 610 660
Fan Type Forward curve
Model FDA400TM FDA500TM
kW 4.0 5.5 4.0 5.5 7.5
Fan Motor +4
pole 4 4
Power Supply Volt/Ph./Hz 380/3/50(60) 380/3/50(60)
FLA amp. 8.92 12.0 8.92 12.0 15.4
Machine Weight kg 1,075 1,080 1,265 1,275 1,295
Sound Pressure Level (SPL) dB(A) 60 61 62 63 64 61 62 63 64 65
Outdoor Air Series PCB Model/pcs. EKEQFCBAV3/3pcs. EKEQFCBAV3/3pcs.
Expansion Valve Model/pcs. EKEXV400/3pcs. EKEXV500/3pcs.
Dimension: (WxDxH) m 1.7x1.85x2.1 2.0x1.95x2.2
Panel Type Sandwich panel thickness 25 mm Sandwich panel thickness 25 mm
Liquid pipes mm φ12.7 (Brazing connection) x3 φ15.9 (Brazing connection) x3
Piping Connections Gas pipes +5 mm φ28.6 (Brazing connection) x3 φ28.6 (Brazing connection) x3
Drain pipes mm φ32 φ32
Refrigerant Control Electronic expansion valve Electronic expansion valve
Capacity Index 1,200 1,500

Notes:
+1. Net capacity includes indoor fan heat. Conversion formula
+2. Gross capacity does not include indoor fan heat. kcal/h=kW×860
+3. With pre filter, AAF synthetic R29 & class G3 (Washable) eff 80-85%. Btu/h=kW×3412
+4. Motor is induction motor class F, IP 55. cfm=m³/min×35.3
+5. It is necessary to reduce piping size by reducer when connection (19.1→15.9, 22.2→19.1, 28.6→22.2, 34.9→28.6).
6. Connection Ratio:
System Pattern Total CR VRV indoor AHU
Only AHU 50 - 110% – 50 - 110%
(Pair AHU)
7. Air temperature control via an external DDC controller (field supplied).

88 AHUR-DB/CB
EDADT1505A Dimensions and service space

2. Dimensions and service space


2.1 Indoor unit
2.1.1 AHUR_DBL(H) (Air handling unit)

AHUR08DBL(H)
Unit (mm)

C: SDR4902685A

AHUR-DB/CB 89
Dimensions and service space EDADT1505A

AHUR10DBL(H)
Unit (mm)

C: SDR4902686A

90 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR16DBL(H)
Unit (mm)

C: SDR4902687A

AHUR-DB/CB 91
Dimensions and service space EDADT1505A

AHUR20DBL(H)
Unit (mm)

C: SDR4902688A

92 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR32DBL(H)
Unit (mm)

C: SDR4902689A

AHUR-DB/CB 93
Dimensions and service space EDADT1505A

AHUR40DBL(H)
Unit (mm)

C: SDR4902690A

94 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR48DBL(H)
Unit (mm)

C: SDR4902691A

AHUR-DB/CB 95
Dimensions and service space EDADT1505A

AHUR60DBL(H)
Unit (mm)

C: SDR4902692A

96 AHUR-DB/CB
EDADT1505A Dimensions and service space

2.1.2 AHUR_CBL(H) (Air handling unit)

AHUR08CBL(H)
Unit (mm)

C: SDR4902693A

AHUR-DB/CB 97
Dimensions and service space EDADT1505A

AHUR10CBL(H)
Unit (mm)

C: SDR4902694A

98 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR16CBL(H)
Unit (mm)

C: SDR4902695A

AHUR-DB/CB 99
Dimensions and service space EDADT1505A

AHUR20CBL(H)
Unit (mm)

C: SDR4902696A

100 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR32CBL(H)
Unit (mm)

C: SDR4902697A

AHUR-DB/CB 101
Dimensions and service space EDADT1505A

AHUR40CBL(H)
Unit (mm)

C: SDR4902698A

102 AHUR-DB/CB
EDADT1505A Dimensions and service space

AHUR48CBL(H)
Unit (mm)

C: SDR4902699A

AHUR-DB/CB 103
Dimensions and service space EDADT1505A

AHUR60CBL(H)
Unit (mm)

C: SDR4902700A

104 AHUR-DB/CB
EDADT1505A Dimensions and service space

2.2 Outdoor air series PCB

EKEQFCBA

AHUR-DB/CB 105
Dimensions and service space EDADT1505A

2.3 Expansion valve

EKEXV

106 AHUR-DB/CB
EDADT1505A Piping diagrams

3. Piping diagrams
3.1 Indoor unit

AHUR08DBL(H) / AHUR08CBL(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE 12.7 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
Field piping (9.5 CuT) 9.5 CuT 9.5 CuT Fan
Field piping (19.1 CuT) 22.2 CuT

Reducer

AHUR10DBL(H) / AHUR10CBL(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE 12.7 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
Field piping (9.5 CuT) 9.5 CuT 9.5 CuT Fan
Field piping (22.2 CuT) 28.6 CuT

Reducer

AHUR16DBL(H) / AHUR16CBL(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
Field piping (12.7 CuT) 12.7 CuT 12.7 CuT Fan
Field piping (28.6 CuT) 34.9 CuT

Reducer

AHUR20DBL(H) / AHUR20CBL(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
Field piping (15.9 CuT) 15.9 CuT 15.9 CuT Fan
Field piping (28.6 CuT) 34.9 CuT

Reducer

AHUR-DB/CB 107
Piping diagrams EDADT1505A

AHUR32DBL(H) / AHUR32CBL(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T
+KHRP26M73TP 12.7 CuT 12.7 CuT
Field piping (19.1 CuT)

Field piping (*34.9 CuT) 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT


M
Filter Filter Fan

Electronic Heat
expansion valve exchanger

12.7 CuT 12.7 CuT

28.6 CuT 34.9 CuT

Reducer

AHUR40DBL(H) / AHUR40CBL(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T
+KHRP26M73TP
Field piping (19.1 CuT) 15.9 CuT 15.9 CuT

Field piping (*41.3 CuT) 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT


M
Filter Filter Fan

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

Reducer

Note: REFNET is for example, it use header type, please refer to VRV IV Engineering data.
*Do not let the connection piping exceed main refrigerant piping size.

108 AHUR-DB/CB
EDADT1505A Piping diagrams

AHUR48DBL(H) / AHUR48CBL(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T KHRP26A73T
+KHRP26M73TP +KHRP26M73TP
Field piping (19.1 CuT) 19.1 CuT 12.7 CuT 12.7 CuT

Field piping (*41.3 CuT) *34.9 CuT 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
12.7 CuT 12.7 CuT Fan
28.6 CuT 34.9 CuT

EXPANSION VALVE-3 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

12.7 CuT 12.7 CuT

28.6 CuT 34.9 CuT

Reducer

AHUR60DBL(H) / AHUR60CBL(H)
Unit (mm)
INDOOR UNIT

EXPANSION VALVE-1 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
KHRP26A73T KHRP26A73T
+KHRP26M73TP +KHRP26M73TP
Field piping (19.1 CuT) 19.1 CuT 15.9 CuT 15.9 CuT

Field piping (*41.3 CuT) *41.3 CuT 28.6 CuT 34.9 CuT

EXPANSION VALVE-2 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger
M
15.9 CuT 15.9 CuT Fan
28.6 CuT 34.9 CuT

EXPANSION VALVE-3 Reducer 15.9 CuT

Filter Filter

Electronic Heat
expansion valve exchanger

15.9 CuT 15.9 CuT

28.6 CuT 34.9 CuT

Reducer

Note: REFNET is for example, it use header type, please refer to VRV IV Engineering data.
*Do not let the connection piping exceed main refrigerant piping size.

AHUR-DB/CB 109
Wiring diagrams EDADT1505A

4. Wiring diagrams
4.1 Outdoor air series PCB

EKEQFCBA

110 AHUR-DB/CB
EDADT1505A Field preparation

5. Field preparation
5.1 External wiring connection diagram

AHUR08DBL(H) / AHUR08CBL(H) / AHUR10DBL(H) / AHUR10CBL(H) / AHUR16DBL(H) / AHUR16CBL(H) /


AHUR20DBL(H) / AHUR20CBL(H)

AHUR-DB/CB 111
Field preparation EDADT1505A

AHUR32DBL(H) / AHUR32CBL(H) / AHUR40DBL(H) / AHUR40CBL(H)

112 AHUR-DB/CB
EDADT1505A Field preparation

AHUR48DBL(H) / AHUR48CBL(H) / AHUR60DBL(H) / AHUR60CBL(H)

AHUR-DB/CB 113
Field preparation EDADT1505A

5.2 Wiring connection summary for MicroTech III

114 AHUR-DB/CB
EDADT1505A Field preparation

5.3 MicroTech III wiring diagram for EKEQFCBAV3

AHUR08DBL(H) / AHUR08CBL(H) / AHUR10DBL(H) / AHUR10CBL(H) / AHUR16DBL(H) / AHUR16CBL(H) /


AHUR20DBL(H) / AHUR20CBL(H)

AHUR-DB/CB 115
Field preparation EDADT1505A

AHUR32DBL(H) / AHUR32CBL(H) / AHUR40DBL(H) / AHUR40CBL(H)

116 AHUR-DB/CB
EDADT1505A Field preparation

AHUR48DBL(H) / AHUR48CBL(H) / AHUR60DBL(H) / AHUR60CBL(H)

AHUR-DB/CB 117
Electrical characteristics EDADT1505A

6. Electrical characteristics
6.1 Indoor unit
Power supply IFM
Model
Hz Volts Voltage range MFA KW FLA

AHUR08DBL / AHUR08CBL Max. 50Hz 456V 15 1.1 2.82


Min. 50Hz 342V

AHUR10DBL / AHUR10CBL Max. 50Hz 456V 15 1.1 2.82


Min. 50Hz 342V

AHUR16DBL / AHUR16CBL Max. 50Hz 456V 15 2.2 5.28


Min. 50Hz 342V

AHUR20DBL / AHUR20CBL Max. 50Hz 456V 15 3.0 6.58


Min. 50Hz 342V
50 380-415
Max. 50Hz 456V
AHUR32DBL / AHUR32CBL Min. 50Hz 342V 20 4.0 8.92

Max. 50Hz 456V


AHUR40DBL / AHUR40CBL Min. 50Hz 342V 20 4.0 8.92

AHUR48DBL / AHUR48CBL Max. 50Hz 456V 25 5.5 12.00


Min. 50Hz 342V

AHUR60DBL / AHUR60CBL Max. 50Hz 456V 25 5.5 12.00


Min. 50Hz 342V

AHUR08DBLH / AHUR08CBLH Max. 60Hz 456V 15 1.1 2.81


Min. 60Hz 342V

AHUR10DBLH / AHUR10CBLH Max. 60Hz 456V 15 1.1 2.81


Min. 60Hz 342V

AHUR16DBLH / AHUR16CBLH Max. 60Hz 456V 15 2.2 5.29


Min. 60Hz 342V
Max. 60Hz 456V
AHUR20DBLH / AHUR20CBLH Min. 60Hz 342V 15 3.0 6.45
60 380-415
Max. 60Hz 456V
AHUR32DBLH / AHUR32CBLH Min. 60Hz 342V 20 4.0 9.11

AHUR40DBLH / AHUR40CBLH Max. 60Hz 456V 20 4.0 9.11


Min. 60Hz 342V

AHUR48DBLH / AHUR48CBLH Max. 60Hz 456V 25 5.5 12.14


Min. 60Hz 342V

AHUR60DBLH / AHUR60CBLH Max. 60Hz 456V 25 5.5 12.14


Min. 60Hz 342V

Symbols: Notes:
MFA : Max. fuse amps (A) 1. Voltage range
Units are suitable for use on electrical systems
IFM : Indoor fan motor where voltage supplied to unit terminals
KW : Fan motor rated output (kW) is not below or above listed range limits.
2. Maximum allowable voltage unbalance between phases is 2%.
FLA : Full load amps (A) 3. Either a fuse or a circuit breaker acceptable.

118 AHUR-DB/CB
EDADT1505A Capacity tables

7. Capacity tables
EKEQFCBA Cooling capacity
Entering air 18.0 23.0 28.0 30.0 32.0
°CWB
Capacity index Entering air 33.0 33.0 33.0 33.0 33.0
°CDB
Capacity TC SHC TC SHC TC SHC TC SHC TC SHC
200
AFR34CMM BF(0.15) 18.0 11.4 20.7 11.5 23.3 11.4 24.4 11.6 25.4 11.3
250
AFR39CMM BF(0.15) 22.4 14.0 25.6 14.0 28.9 13.8 30.2 14.1 31.5 13.6
400
AFR68CMM BF(0.14) 35.8 22.8 41.1 23.0 46.3 22.7 48.4 23.3 50.5 22.7
500
AFR91CMM BF(0.14) 45.2 29.1 51.8 29.5 58.4 29.3 61.1 30.1 63.7 29.3

Note:
1. Gross capacity does not include indoor fan heat.
2. Expansion valve (EV) EKEXV200, 250, 400 and 500 are used
for each of air handling unit (AHU) 8HP, 10HP, 16HP and
20HP, respectively. For AHU that over 20HP, it will use
multiple EV. Please calculate data from capacity tables
multiply by quantity of EV.

8. Fan Performances
Airflow Fan speed
Model Standard point
Range (CMH) (CMM) Pa 250 300 350 450 500
(rpm) 1,189 1,265 1,340 1,485 1,552 Airflow= 34 m³/m, ESP = 450 Pa,
AHUR08 Std 2,040 34
(kW) 0.49 0.55 0.61 0.75 0.82 Fan speed = 1,485 rpm
(rpm) 1,201 1,264 1,327 1,457 1,523 Airflow= 39 m³/m, ESP = 450 Pa,
AHUR10 Std 2,340 39
(kW) 0.59 0.64 0.70 0.84 0.91 Fan speed = 1,457 rpm
(rpm) 1,320 1,393 1,462 1,599 1,669 Airflow= 68 m³/m, ESP = 450 Pa,
AHUR16 Std 4,080 68
(kW) 1.05 1.15 1.24 1.45 1.58 Fan speed = 1,559 rpm
(rpm) 1,367 1,432 1,496 1,621 1,681 Airflow= 91 m³/m, ESP = 450 Pa,
AHUR20 Std 5,460 91
(kW) 1.68 1.80 1.93 2.18 2.31 Fan speed = 1,621 rpm
(rpm) 1,055 1,109 1,160 1,258 1,309 Airflow= 136 m³/m, ESP = 450 Pa,
AHUR32 Std 8,160 136
(kW) 2.32 2.49 2.67 3.07 3.27 Fan speed = 1,258 rpm
(rpm) 804 845 886 972 1,018 Airflow= 182 m³/m, ESP = 450 Pa,
AHUR40 Std 10,920 182
(kW) 2.40 2.61 2.83 3.33 3.62 Fan speed = 972 rpm
(rpm) 819 858 897 971 1,008 Airflow= 204 m³/m, ESP = 450 Pa,
AHUR48 Std 12,240 204
(kW) 2.90 3.12 3.35 3.83 4.08 Fan speed = 971 rpm
(rpm) 671 707 741 807 839 Airflow= 273 m³/m, ESP = 450 Pa,
AHUR60 Std 16,380 273
(kW) 3.51 3.84 4.18 4.88 5.24 Fan speed = 807 rpm

9. Operation limits
Temperature range
Cooling
Entering air temperature Minimum 14°CWB
on heat exchanger AHU Maximum 32°CWB
Minimum -5°CDB
Outdoor unit VRV IV
Maximum 49°CDB
Minimum -5°CDB
Expansion valve
Maximum 46°CDB
Minimum -10°CDB
Outdoor air series PCB
Maximum 40°CDB

AHUR-DB/CB 119
Sound Pressure Level (SPL) EDADT1505A

10. Sound Pressure Level (SPL)


Overall

Location of microphone (for sound pressure level) Notes:


1. The operating conditions are assumed to be standard
(JIS conditions).
m
1.0 2. These operating values were obtained in anechoic
chamber (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipment installed.
1.5 m

dB(A)
Sound pressure level
Model
380-415V, 50/60Hz
AHUR08DBL(H)/CBL(H) 62
AHUR10DBL(H)/CBL(H) 60
AHUR16DBL(H)/CBL(H) 58
AHUR20DBL(H)/CBL(H) 58
AHUR32DBL(H)/CBL(H) 66
AHUR40DBL(H)/CBL(H) 63
AHUR48DBL(H)/CBL(H) 63
AHUR60DBL(H)/CBL(H) 64

Octave Band Level


380-415V, 50/60Hz
AHUR08DBL(H)/CBL(H) AHUR10DBL(H)/CBL(H) AHUR16DBL(H)/CBL(H)
53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800

80 80 80

NC-70
NC-70 NC-70
OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

70 70 70

NC-60 NC-60 NC-60


dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)

60 60 60

NC-50 NC-50 NC-50


50 50 50

NC-40 NC-40 NC-40


40 40 40

NC-30 NC-30 NC-30


30 30 30

NC-20 NC-20 NC-20


20 20 20
APPROXIMATE APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

120 AHUR-DB/CB
EDADT1505A Fan Sound Power Level (PWL)

AHUR20DBL(H)/CBL(H) AHUR32DBL(H)/CBL(H) AHUR40DBL(H)/CBL(H)


53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800

80 80 80

NC-70 NC-70 NC-70


OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL


70 70 70

NC-60
NC-60 NC-60
dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)
60 60 60

NC-50 NC-50 NC-50


50 50 50

NC-40 NC-40 NC-40


40 40 40

NC-30 NC-30 NC-30


30 30 30

NC-20 NC-20 NC-20


20 20 20
APPROXIMATE APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

AHUR48DBL(H)/CBL(H) AHUR60DBL(H)/CBL(H)
53 106 212 425 850 1700 3400 6800 53 106 212 425 850 1700 3400 6800

80 80

NC-70 NC-70
OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

70 70

NC-60 NC-60
dB (0dB=0.0002µ bar)

dB (0dB=0.0002µ bar)

60 60

NC-50 NC-50
50 50

NC-40 NC-40
40 40

NC-30 NC-30
30 30

NC-20 NC-20
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

11. Fan Sound Power Level (PWL)


Octave band center frequency
Model
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
AHUR08DBL(H)/CBL(H) 82 83 85 78 79 78 77 74
AHUR10DBL(H)/CBL(H) 80 81 83 76 77 76 73 70
AHUR16DBL(H)/CBL(H) 80 83 81 78 74 71 67 61
AHUR20DBL(H)/CBL(H) 80 83 81 77 74 71 68 63
AHUR32DBL(H)/CBL(H) 82 85 85 85 86 83 81 77
AHUR40DBL(H)/CBL(H) 78 84 82 85 82 79 77 72
AHUR48DBL(H)/CBL(H) 78 84 82 85 82 79 77 72
AHUR60DBL(H)/CBL(H) 85 87 85 84 82 79 77 71

AHUR-DB/CB 121
Fan Sound Power Level (PWL) EDADT1505A

122 AHUR-DB/CB
EDADT1505A Options

Part 4 Options
Wide range of options are available to meet your design requirements.
Please contact Daikin’s sales office on options below:
• Fan type • AHU coil material type
9 Backward curve aerofoil 9 Copper fin
9 Plug fan 9 Blue fin
9 Brushless DC fan 9 Epoxy coated fin and coil
• Fan motor control • Special option
9 VSD 9 Electric heater
9 Fixed speed 9 Mixing box
• AHU drain pan type 9 Outdoor roof
9 Acrylic enamel with steel coating 9 Heat pipes
9 Galvanized steel 9 Motor starter box
• AHU air filter type • Customisation
9 Medium filter 9 Airflow
9 Extra filter 9 Capacity
9 Synthetic 9 ESP
9 Bag 9 Discharge direction
9 HEPA 9 Heat recovery wheel
9 Aluminum 9 Piping outlet
9 Cartridge • Controller
9 ULPA 9 MicroTech lll (DDC)

MicroTech III Box


Unit (mm)

VRV AHU CONTROLLER UNIT

MT3041 POL638.70

POL955.0 POL955.0

AHUR-DB/CB 123
Options EDADT1505A

Motor starter box (Indoor type)


Unit (mm)

C: SDR3220002

124 AHUR-DB/CB
EDADT1505A Options

Motor starter box (Indoor type)

C: SDR3220002
Unit (mm)

AHUR-DB/CB 125
Options EDADT1505A

Motor starter box (Outdoor type)


Unit (mm)

C: SDR3220005

126 AHUR-DB/CB
EDADT1505A Options

Motor starter box (Outdoor type)


Unit (mm)

C: SDR3220005

AHUR-DB/CB 127
Options EDADT1505A

128 AHUR-DB/CB
EDADT1505A Installation manual of air handling unit

Part 5 Installation and maintenance manual


1. Installation manual of air handling unit
Features

1. Casing
All casings are double-skinned sandwich panel with high-density filled-in foamed Polyurethane that do not allow contact
with internal conditioned air, resulting in much cleaner air to be supplied to the conditioning space.

2. Water coil
All coils are constructed with rippled-corrugated fins in diameter copper tubes. Copper tubes are mechanically expanded
to fin holes to assure optimum tube-to-fin contact and blazed with return bends. Each of the manufactured coil has leak
testing with 24kgs/cm² (350psig) compressed air filled into the coil circuit and being submerged in water pool warranted
operating water pressure water pressure of 17kgs/cm² (250psig) or the lower.

3. Fan
All fans are double width double inlet (DWDI) centrifugal fan with forward/backward curved impellers of approved
manufacturer for optimum application to provide required air volume and static pressure. All fan assemblies are test run
and adjusted balance at factory before shipment of units. When test run is made, be sure that the rotation is correct. In
case wires are connected opposite to the instruction, the fan rotation is incorrect.

Fan rotating direction

4. Motor
All motors used for AHU are induction motors totally enclosed fan cooled type, with IP55 degree of protection good for
3-phase, alternating current (AC). No need for lubrication.

The motor terminal should have waterproof protection


and seal that can prevent water coming into lead wire Current box
connection. Insulated wires can tolerate humidity and
seal that can prevent water seeping into lead wire Steel pipe
connection.

Used wire connected motor terminal to bended conduit


P or U shape that can prevent water seeping into lead
wire.

AHUR-DB/CB 129
Installation manual of air handling unit EDADT1505A

5. V-Belts
V-belts tend to elongate during operation in a long run. Be sure to adjust the tension of the belts so that the belts have
adequate tension. However, after twenty-four hours of operation, it should be checked and adjusted. If the tension is
more than normal acceptable degree, motor and blower bearings receive undue strain and, as the consequence, the unit
will create vibration and noise problem. Should be readjusted to recommend tension following table of tensioning force
V-drive belt.
Belt tension indicator
applied to mid-centre
Centre distance.
Distan
ce
16mm
1 me deflectio
tre of n
span per

Table of tensioning forces

Force required to deflect belt


Belt tension 16 mm per meter of span
Small Pulley Diameter (mm) Newton (N) Kilogram Force (kgf)
A 80 - 140 10 - 15 1.5 - 1.5
B 125 - 200 20 - 30 2.0 - 3.1

Uneven length of V-belts get damage after long run, totally replace all belts. Do not use old and new belts together.
When replacing belts, be sure that all belts selected have an even length before fitting them on to the unit.
When adjusting the tension and/or replacing the belts, motor level may be adjusted slightly by bolts on the motor base.

6. Blower bearing
Bearings used are either deep ball bearing type with an eccentric locking collar or an adapter sleeve, or spherical roller
bearing type sealed at both sides for different duty application.

The bearings are lubricated for long life and maintenance-free. If re-lubrication is necessary, it is recommended to use a
lithium base grease suitable for all temperatures within the operational limits.

Bearing Lubrication, Fan equipped with pillow block bearing inserted in rubber damper are pre-lubricated and should not
require additional grease for start up.

However, for plumber block bearing, with lubrication point can be further lubricated when the life of grease is expectancy.
This will depend on the type of grease, speed and operating temperature of the bearing. The best way to determine the
republication frequency is to inspect the condition of the old grease that purges from the seals when adding new grease.
Lf the purges grease looks just like the new grease, you can go a longer time between republications. If the purges
grease is much darker than the new grease, this indicator that the grease is oxidized and you must reduplicate more
frequently.

7. Ducted installation
Improper installation with inlet or discharge configurations may result in reduced performance. Free discharge or
turbulent flow in the discharge ductwork will result in system effect losses.
Ducted outlet installation

• Discharge duct turns

Rotation Length of
straight duct
(at least 3 equivalent duct φ)

Rotation

Good Poor

130 AHUR-DB/CB
EDADT1505A Installation manual of air handling unit

8. Drain - pan
The air borne dirt will stuck onto fins drips on the drain pan with condensate water, which tends to interrupt smooth drain.
Remove such dirt concentrated at the drain outlet through the access door installed right above it. For AHU containing
water spray type humidifier, the access may be reached via manhole.

When AHU. has an extra high negative pressure in the unit due to high resistance in return air side, air may be sucked
adversely into the unit through drain outlet. In this case, draining stream for drain pan will become insufficient. To avoid
possible trouble trouble, the drain pipe end shall be adequately trapped.

9. Filters
Washable type filters
recommended on dirt accumulation through the side of filter boxes. When washing filter material, take out filter cores
from filter box, remove filter material from holding frames, and wash it by water. Use of detergent helps to remove the dirt
easily. In case, dirt accumulation is in slight degree, a quick spray water on the entire filter surface, without removing the
filter material from frames, may do, for that easy cleaning purpose. Remember filter plays not only its primary role of air
cleaning but also another important role of preventing stuck-up of dirt and fur on finned coil to maintain the specified
cooling / heating capacity of AHU.

10. Drain trap


Cooling coil (PC) Filter(PF) Duct(PD) Total
ROW mmH2O mmH2O mmH2O mmH2O
3 7.5
4 10 70 BY CUSTOMER PC+PF+PD
6 15

Recommended u-trap height (mm)


Upper is at least 2 x Pressure (Pa)/ 9.810
drain pan Pressure
(P) at the REMARK
drain pan
T-joint PC : Pressure drop in cooling coil
2P PF : Pressure drop in filter
Drain trap PD : Pressure drop in duct
2P

Base
Lower drain pan
Insulate securely

AHUR-DB/CB 131
Installation manual of air handling unit EDADT1505A

Features

Hoisting
• All units are provided with hoisting brackets located at the base of units.
• When hoisting is required hoisting strips should have a suitable length so that no unnecessary force is being applied to the
casing while hoisting.
• Only non-metal slings are to be used for hoisting to avoid damage to the side panels. Wooden pieces are to be inserted
between the slings as an additional protection for the casing.
• When using a fork-lift truck to lift the unit ,care must be taken to ensure that the insulation under the drain pan is not
damaged.
• It is generally recommended that the AHU should not be dragged, as this will damage the insulation under the units.
• If for whatever reasons, the contractor is unable to make use of the hoisting brackets, then care should be taken to prevent
the casing from damage while moving and handling the units.

Non metal sling


Wooden piece

Wiring connection
Wiring connection of star / delta (>3kW) Wiring connection of star (<3kW)

INDOOR UNIT INDOOR UNIT


G G
U1 W2 U1
W2
V1 M3 U 2 V1 M3 U2
W1 V2 W1
V2
Fa n m o t o r Fa n m o t o r

U1 V1 W1 V2 U2 W2 G U1 V1 W1 G

132 AHUR-DB/CB
EDADT1505A Installation manual of air handling unit

Features

INSTALLATION
The system design and installation should follow accepted industrial practice, such as described in the ASHRAE Handbook.

These units are not designed to be waterproof and therefore should not be installed outdoor.
Adequate space should be catered around the unit for piping coils and drains, filters replacement, and maintenance such as
lubrication and belt adjustment. Sufficient space should be provided on the side of the unit for shaft removal and coil removal
if necessary. Space required for coil removal should at least equal to the length of the coil.

Flexible connectors should be used on the outlet and inlet duct connections for all units. A minimal amount of air leakage is
normal on the cabinet and it will not affect unit performance.

Isolator
Due to the unit design has no internal isolator, the external isolator must be fixed to absorb the vibration. For hanging
mounting type, use 'rubber hanger' and floor mounting type use “rubber pad” at 4 corners.

Required space for installation

Air filter Rubber pad


Air flow at 4 corners
outlet
Air filter
Air flow
inlet
Floor mounting type

Air filter

MIN 1500

MIN 100
(Back side)

MIN 1000
(Front side)
MIN 1000

Remark: For 80HP, 100HP and 120HP series, service space of back side is MIN 600.

AHUR-DB/CB 133
Installation manual of air handling unit EDADT1505A

Daikin commercial air handling unit

1. Motor 12. Filter frame


2. Blower 13. Filter media
3. Insulator 14. Aluminum frame
4. Common base 15. Corner post
5. Drive system 16. Center post
6. 25 mm Double skin panel 17. Bottom frame
7. Access door 18. Hanging position
8. Coil assy 19. Outlet flange
9. Drain pan assy 20. Inlet flange
10. Drain plug
11. Coil cover

Spare parts list and approx. lead-time

Fan - Locally available ( 3 Weeks )


Shaft - Locally available ( 2 Weeks )
Pulley - Locally available ( 2 Weeks )
Bearing - Locally available ( 2 Weeks )
Motor - Locally available ( 1 Week )
V-Belt - Locally available ( 2 Days )
Coil - Locally available ( 3 Weeks )
Drain Pan - Locally available ( 1 Week )
Casing - Locally available ( 3 Weeks )

134 AHUR-DB/CB
EDADT1505A Installation manual of air handling unit

Maintenance guide for Daikin AHU

AHUR-DB/CB 135
Installation of control box (EKEQMCBAV3) EDADT1505A

2. Installation of control box (EKEQMCBAV3)


Control box will be assemblied by Daikin factory. For field setting, please refer to field preparing. Some
contents and model names are for Europe models, please confirm to Daikin’s sales office

136 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQMCBAV3)

AHUR-DB/CB 137
Installation of control box (EKEQMCBAV3) EDADT1505A

138 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQMCBAV3)

AHUR-DB/CB 139
Installation of control box (EKEQMCBAV3) EDADT1505A

140 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQMCBAV3)

AHUR-DB/CB 141
Installation of control box (EKEQMCBAV3) EDADT1505A

142 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQMCBAV3)

AHUR-DB/CB 143
Installation of control box (EKEQMCBAV3) EDADT1505A

144 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQMCBAV3)

AHUR-DB/CB 145
Installation of control box (EKEQMCBAV3) EDADT1505A

146 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQMCBAV3)

AHUR-DB/CB 147
Installation of control box (EKEQFCBAV3) EDADT1505A

3. Installation of control box (EKEQFCBAV3)


Control box will be assemblied by Daikin factory. For field setting, please refer to field preparing. Some
contents and model names are for Europe models, please confirm to Daikin’s sales office.

148 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQFCBAV3)

AHUR-DB/CB 149
Installation of control box (EKEQFCBAV3) EDADT1505A

150 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQFCBAV3)

AHUR-DB/CB 151
Installation of control box (EKEQFCBAV3) EDADT1505A

152 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQFCBAV3)

AHUR-DB/CB 153
Installation of control box (EKEQFCBAV3) EDADT1505A

154 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQFCBAV3)

AHUR-DB/CB 155
Installation of control box (EKEQFCBAV3) EDADT1505A

156 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQFCBAV3)

AHUR-DB/CB 157
Installation of control box (EKEQFCBAV3) EDADT1505A

158 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQFCBAV3)

AHUR-DB/CB 159
Installation of control box (EKEQFCBAV3) EDADT1505A

160 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQFCBAV3)

AHUR-DB/CB 161
Installation of control box (EKEQFCBAV3) EDADT1505A

162 AHUR-DB/CB
EDADT1505A Installation of control box (EKEQFCBAV3)

AHUR-DB/CB 163
MicroTech III commissioning manual EDADT1505A

4. MicroTech III commissioning manual


MicroTech III is an option. For field setting, please refer to field preparing. Some contents and model
names are for Europe models, please confirm to Daikin’s sales office.

164 AHUR-DB/CB
EDADT1505A MicroTech III commissioning manual

AHU ʹ COMMISSIONING MANUAL 2

Index
1. Air Handling Unit Safety Information ........................................................................................................ 3
2. Introduction ............................................................................................................................................... 4
3. AHU Configuration screen ......................................................................................................................... 5
4. Unit Type Configuration............................................................................................................................. 6
5. Components Configuration........................................................................................................................ 8
6. Functions Configuration .......................................................................................................................... 12
7. Fans Configuration ................................................................................................................................... 17

AHUR-DB/CB 165
MicroTech III commissioning manual EDADT1505A

AHU ʹ COMMISSIONING MANUAL 3

1. Air Handling Unit Safety Information


Observe all safety directions and comply with the corresponding general safety regulations in order to
prevent personal injury and damage to property.

ͻ Safety devices may not be removed, bypassed or taken out of operation.


ͻ Apparatus and system components may only be used in a technically fault-free state. Faults that
can affect safety must be rectified immediately.
ͻ Observe the required safety instructions against excessively high contact voltages.
ͻ The plant may not be in operation if the standard safety devices are out of operation or if their
effects are influenced in some other way.
ͻ All handling that affects the prescribed disconnection of the protective extra-low voltage (AC 24 V)
must be avoided.
ͻ Disconnect the supply voltage before opening the apparatus cabinet. Never work when the
power is on!
ͻ Avoid electromagnetic and other interference voltages in signal and connection cables.
ͻ Assembly and installation of system and plant components may only be performed in accordance
with corresponding installation instructions and instructions for use.
ͻ Every electric part of the system must be protected against static charging: electronic components,
open printed circuit boards, freely accessible connectors and apparatus components that are
connected with the internal connection.
ͻ All equipment that is connected to the system must be CE marked and comply with the Machine
Safety Directive.

166 AHUR-DB/CB
EDADT1505A MicroTech III commissioning manual

AHU ʹ COMMISSIONING MANUAL 4

2. Introduction
This commissioning manual provides the information needed to configure the Daikin Air Handling Unit
(AHU), both Compact and Professional models. Please refer to D-AHU operating manual for detailed
information about control functions and how to operate on AHU controller.

AHUR-DB/CB 167
MicroTech III commissioning manual EDADT1505A

AHU ʹ COMMISSIONING MANUAL 5

3. AHU Configuration screen


Through the AHU Configuration screen the user can access to all sub-menus necessary to properly
configure the AHU.
NOTE! In order to access the ͞AHU Configuration͟ screen, the user must enter the service level
password, otherwise the ͞Commissioning͟ item is not shown on the ͞Main Menu͟ screen.

HMI Path: Main Menu Î Commissioning Î AHU Configuration

The following table shows all the items needed for AHU configuration and the sections where they are
described.
Menu item Section
Config unit type Display and configure AHU type and coils
(Section number 0)
Config components Display and configure installed components
(Section number 5)
Config functions Display and configure available functions
(Section number 0)
Config fan Display and configure AHU fans type and sensors.
(Section number 7)

IMPORTANT! dŚĞ ,h ĐŽŶĨŝŐƵƌĂƚŝŽŶ ƉƌŽĐĞĚƵƌĞ ŵƵƐƚ ďĞ ĞdžĞĐƵƚĞĚ ĨŽůůŽǁŝŶŐ ƚŚĞ ͞,h
ŽŶĨŝŐƵƌĂƚŝŽŶ͟ŵĞŶƵitem order (i.e. Config Unit Type -> Config Components -> Config functions ->
Config fan), because some menu items are strictly dependent on how the AHU has been
configured in previous sections.

168 AHUR-DB/CB
EDADT1505A MicroTech III commissioning manual

AHU ʹ COMMISSIONING MANUAL 6

4. Unit Type Configuration


This page allows to configure the AHU type and to choose which kind of coil is used for both heating and
cooling mode. Please refer to the I/O map for the detailed description of all input and output available with
different AHU type.

NOTE! When the configuration in this page is finished, the menu item ͞Configuration͟ must be set
ƚŽ͞Done͟and ͞Apply Changes!͟ must be executed so that the changes can take effect.

HMI Path: Main Menu Î Commissioning Î AHU Configuration Î Config Unit Type

Menu item Value Description


AHU Model 1. Professional Display the actual AHU model. This parameter is automatically
(read only) 2. Compact configured according to the controller used:
1. Professional: AHU Professional model.
In this case POL638 controller is being used.
2. Compact: AHU Compact model.
In this case POL687 controller is being used.

Unit Type 1. AH-W-U Modify the type of AHU based on the external devices used to
2. AH-WDX-U produce cooling or heating. This setting specifies the I/O map that
3. AH-DX-U will be used:
4. AH-ERQ-U
1. AH-W-U: the AHU is connected to a water coil;
2. AH-WDX-U: the AHU is connected to a water coil and a
generic direct expansion coil. The water coil is used to produce
heating, while the DX coil produces cooling;
3. AH-DX-U: the AHU is connected to a generic direct expansion
coil;
4. AH-ERQ-U: the AHU is connected with the Daikin ERQ
condensing unit*.

*Select this unit type if it is also present a water heating coil.

AHUR-DB/CB 169
MicroTech III commissioning manual EDADT1505A

AHU ʹ COMMISSIONING MANUAL 7

Menu item Value Description


Cooling 1. No Specify the type of AHU coil used to produce cooling:
2. Water
1. No: no cooling coil is present;
3. ERQ
2. Water: the device used to produce cooling is a water coil*;
4. Dx
3. ERQ: the device used to produce cooling is the ERQ;
4. Dx: the device used to produce cooling is a generic direct
expansion coil.

Ύ/Ĩ͞Unit Type = AH-WDX-U͟ĐŚŽŽƐĞ͞Dx͟ĐŽŽůŝŶŐĐŽŝů(if present).

Heating 1. No Specify the type of AHU coil used to produce heating:


2. Water
1. No: no heating coil is present;
3. ERQ
2. Water: the device used to produce heating is a water coil;
4. ERQ+Water
3. ERQ: the device used to produce heating is the ERQ;
5. Dx
4. ERQ+Water: the devices used to produce heating are both
ERQ and water coil*.
5. Dx: the device used to produce heating is a generic direct
expansion coil**.

*In this case ͞Unit Type͟ŵƵƐƚďĞƐĞƚƚŽ͞AH-ERQ-U͟.


ΎΎ/Ĩ͞Unit Type = AH-WDX-U͟ĐŚŽŽƐĞ͞Water͟ŚĞĂƚŝŶŐĐŽŝů(if
present).

Below a diagram that summarizes all available AHU type configurations.

Heat = Water

AH-W-U
Cool = Water

Heat = Water
AH-WDX-U
Cool = Dx
Unit Type

Heat = Dx
AH-DX-U
Cool = Dx

Heat = ERQ / Water / ERQ+Water


AH-ERQ-U

Cool = ERQ

170 AHUR-DB/CB
EDADT1505A MicroTech III commissioning manual

AHU ʹ COMMISSIONING MANUAL 8

5. Components Configuration
This page allows to configure the type and number of components installed on the AHU. This step must be
executed only after the configuration of the AHU type.

NOTE! When the configuration in this page is finished, the menu item ͞Configuration͟ must be set
ƚŽ͞Done͟ and ͞Apply Changes!͟ must be executed so that the changes can take effect.

HMI Path: Main Menu Î Commissioning Î AHU Configuration Î Config components

Menu item Value Description


Heating pump - No Specify the presence of an enabling pump contact for the heating
(only available if - Yes water coil.
͞Water͟ŝƐƐĞůĞĐƚĞĚ
as Heating coil)

Cooling pump - No Specify the presence of an enabling pump contact for the cooling
(only available if - Yes water coil.
͞Water͟ŝƐƐĞůĞĐƚĞĚ
as Cooling coil)

Water Coil Type - Separated Specify if the heating and cooling water coils are separated or
(only available if - Combined combined.
͞Water͟ŝƐƐĞůĞĐƚĞĚ Based on the value selected, consider different I/O on the controller:
as both Heating
Value selected Cooling coil Heating Coil
and Cooling coil) Pump = Q53 (POL638) Pump = Q33 (POL955-B)
Separated Signal = X6 (POL638) Signal = X7 (POL955-A)
Alarm = X4 (POL955-A) Alarm = X5 (POL955-B)
Pump = Q53 (POL638) Pump = Q53 (POL638)
Combined Signal = X6 (POL638) Signal = X6 (POL638)
Alarm = X4 (POL955-A) Alarm = X4 (POL955-A)

AHUR-DB/CB 171
MicroTech III commissioning manual EDADT1505A

AHU ʹ COMMISSIONING MANUAL 9

Menu item Value Description


Pre Htg Wtr - No Specify whether there is a water type pre-heating coil.
- Yes

Num of Dx step 0..3 Specify the number of steps of the direct expansion coil.
(only available if
͞Dx͟ŝƐƐĞůĞĐƚĞĚas
Heating or Cooling
coil)

Num of ERQ 0..2 [Compact] Specify the number of Daikin ERQ condensing units.
(only available if 0..4 [Pro]
͞ERQ͟ is selected
as Heating or
Cooling coil)

Return Fan - No Specify the presence of the return fan.


- Yes

Fans for chn 1, 2 Specify the number of fans per channel.


(only available for
AHU ͞ŽŵƉĂĐƚ͟
model)

Mix Damper - No Specify if the mixing damper is being controlled by a modulating


- Yes actuator.
NOTE! This value ŵƵƐƚďĞƐĞƚƚŽ͞No͟ if the mixing damper
is controlled by an On/Off actuator or not controlled at all.

Outs Dampers - No Specify if the outside dampers (fresh/exhaust/return) are being


- Yes controlled by On/Off actuators.

Rec Device 1. No Specify the type of the recovery device:


2. Wheel
1. No: no recovery device is present in the AHU;
3. Cube
2. Wheel: the recovery device is a Heat-Wheel;
4. Water
3. Cube: the recovery device is a Heat-Cube;
4. Water: the recovery device is a RAR type.

Supply temp - No Specify the presence of the supply air temperature sensor.
- Yes

Outside temp - No Specify the presence of the external air temperature sensor.
- Yes

Return temp - No Specify the presence of the return air temperature sensor.
- Yes

Room temp - No Specify the presence of the room unit device (POL822).
- 1 Unit

172 AHUR-DB/CB
EDADT1505A MicroTech III commissioning manual

AHU ʹ COMMISSIONING MANUAL 10

Menu item Value Description


Pre-Heat temp - No Specify the presence of the pre-heating air temperature sensor.
- Yes
NOTE! Only one type of pre-heating can be enabled at a
time.

Frost Switch - No Specify the presence of the frost protection switch for the heating
(only available if - Yes coil.
͞ERQ+Water͟Žƌ
͞Water͟ is selected
as Heating coil)

Other Sns 1. No Specify the type of other sensors installed on the AHU:
(only available for 2. CO2
1. No: no other sensor is present in the AHU;
,h͞ŽŵƉĂĐƚ͟ 3. Humidity
2. CO2: the air quality (CO2) sensor is present;
model)
3. Humidity: the room humidity sensor is present;

Room hum - No Specify the presence of the room humidity sensor.


(only available for - Yes
,h͞WƌŽĨĞƐƐŝŽŶĂů͟
model)

Air qual (CO2) - No Specify the presence of the air quality (CO2) sensor.
(only available for - Yes
,h͞WƌŽĨĞƐƐŝŽŶĂů͟
model)

Electric htg - No Specify if the AHU is provided with a post-heating electric coil and its
- 1 Step number of activation stages:
- 2 Steps
1. No: no post-heating electric coil is present in the AHU;
2. 1 Step: the post-heating electric coil features only one
activation stage;
3. 2 Steps: the post-heating electric coil features two
activation stages.

NOTE! dŚŝƐǀĂůƵĞƐƚƌŝĐƚůLJĚĞƉĞŶĚƐŽŶ͞WƌĞ,ƚŐůĞĐƚ͟
stages number: the sum of the steps from both pre/post
heating electric coil cannot exceed two stages.

Pre Htg Elect - No Specify if the AHU is provided with a pre-heating electric coil and its
- 1 Step number of activation stages:
- 2 Steps
1. No: no pre-heating electric coil is present in the AHU;
2. 1 Step: the pre-heating electric coil features only one
activation stage;
3. 2 Steps: the pre-heating electric coil features two
activation stages.

NOTE! dŚŝƐǀĂůƵĞƐƚƌŝĐƚůLJĚĞƉĞŶĚƐŽŶ͞ůĞĐƚƌŝĐŚƚŐ͟ƐƚĂŐĞƐ
number: the sum of the steps from both pre/post heating
electric coil cannot exceed two stages.

AHUR-DB/CB 173
MicroTech III commissioning manual EDADT1505A

AHU ʹ COMMISSIONING MANUAL 11

Menu item Value Description


Humidifier 1. No Configure the humidification device:
2. On/Off
1. No: no humidifier is present in the AHU;
3. Modulate(*)
2. On/Off: the humidifier is an On/Off device;
3. Modulate(*): the humidifier is a modulating device.

(*) only available ĨŽƌ,h͞WƌŽĨĞƐƐŝŽŶĂů͟ŵŽĚĞů.

174 AHUR-DB/CB
EDADT1505A MicroTech III commissioning manual

AHU ʹ COMMISSIONING MANUAL 12

6. Functions Configuration
This page allows to configure the control functions that can be performed by the AHU. This step must be
executed only after the configuration of AHU components.

NOTE! When the configuration in this page is ĨŝŶŝƐŚĞĚ͕ƚŚĞŵĞŶƵŝƚĞŵ͞Configuration͟ŵƵƐƚďĞƐĞƚ


ƚŽ͞Done͟ĂŶĚ͞Apply Changes!͟ must be executed so that the changes can take effect.

HMI Path: Main Menu Î Commissioning Î AHU Configuration Î Config functions

Menu item Value Description


Fan ctrl mode 1. Direct Specify the control mode for supply/return fans:
2. Fix Speed
1. Direct: supply/return fans On/Off controlled.
3. Pressure
By selecting this mode, no fans setpoints are used;
4. Air Flow
2. Fix Speed: supply/return fans open loop controlled with a
fixed speed value. By selecting this mode, fans setpoints are a
percentage of max fan speed [%];
3. Pressure: supply/return fans closed loop controlled in
pressure. By selecting this mode, fans setpoints measurement
unit is in Pascal [Pa];
4. Air Flow: supply/return fans closed loop controlled in air-
flow. By selecting this mode, fans setpoints measurement unit
is in cube meters per hour [m3/h].

Fan Fdbk 1. No Specify the feedback type for supply/return fans:


2. Pressure
1. No: no feedback is received by the controller;
3. Air Flow
2. Pressure: the feedback for fan control logic is a pressure
value [Pa];

AHUR-DB/CB 175
MicroTech III commissioning manual EDADT1505A

AHU ʹ COMMISSIONING MANUAL 13

Menu item Value Description


3. Air Flow: the feedback for fan control logic is an air flow
value [m3/h];

Fan Compensation 1. None Specify the compensation type for supply/return fans:
2. Temperature
1. None: no compensation function selected;
3. CO2(*)
2. Temperature: fan temperature compensation function
selected.
By enabling this function, fans setpoints are dynamically
reduced in order to increase the heating/cooling effect of the
selected coil type;
3. CO2(*): CO2 compensation function selected.
By enabling this function, fans setpoints are dynamically
increased in order to reduce CO2 concentration in the air.

(*) only available when ͞ŝƌYƵĂů;CO2Ϳ͟sensor is selected.


Fan Defrst Limit - No Enable of the fan defrost limitation logic. (TBD)
(read only - - Yes
function not yet
available)

MxDmp St - Open Specify mixing damper ƐƚĂƚĞĚƵƌŝŶŐ,h͞sĞŶƚŝůĂƚŝŽŶ͟ŵŽĚĞ.


Ventilation - Close
(only available if a
͞Mix Damper͟ŝƐ
selected )

Tmp ctrl mode 1. Supply Specify the temperature controlled by the regulation logic:
2. Room
1. Supply: the regulation logic controls the supply air
3. Return
temperature;
2. Room: the regulation logic controls the room temperature
provided by the room unit (POL822);
3. Return: the regulation logic controls the return air
temperature.

Tmp stpt sel 1. Htg+Dz Specify the type of temperature setpoints used in heating/cooling
2. Htg/Clg modes:
3. +/- 1/2Dz
1. Htg+Dz: direct control over heating setpoint with a
4. Clg-Dz
deadzone for cooling setpoint;
2. Htg/Clg: direct control over both heating and cooling
setpoints;
3. +/- 1/2Dz: temperature control over a central temperature
and a deadzone setpoints for both heating and cooling;
4. Clg-Dz: direct control over cooling setpoint with a deadzone
for cooling setpoint.
Recovery Type 1. On/Off Specify the control logic for the recovery device:
(only available if a 2. Modulate
1. On/Off: the heat recovery can either have a fixed speed
͞ZĞĐĞǀŝĐĞ͟ŝƐ
device (wheel), a damper (cube) or a water pump enabling
selected)
contact (RAR) and it is controlled by an On/Off contact;

176 AHUR-DB/CB
EDADT1505A MicroTech III commissioning manual

AHU ʹ COMMISSIONING MANUAL 14

Menu item Value Description


2. Modulate: the heat recovery is a variable speed device
controlled by a modulating signal.

ERQ Wtr Priority 1. Auto Specify the activation sequence of the ERQ and water coils for
(only available if 2. ERQfirst heating mode:
͞ERQ+Water͟ŝƐ 3. Waterfirst
1. Auto: the activation sequence is automatically determined
selected as Heating
from the comparison between a threshold temperature
coil)
(changeable) and the outside air temperature:
Tout > Ttreshold -> ERQ first
Tout < Ttreshold -> Water first
2. ERQfirst: the ERQ is activated first;
3. Waterfirst: the water coil is activated first.

MxDmp cmp CO2 - No Specify the activation of the CO2 compensation logic for the mixing
(only available if - Yes damper.
͞Mix Damper͟ĂŶĚ By enabling this function, the maximum aperture of the mixing
͞Air qual (CO2)͟ damper is being dynamically limited in order to facilitate room air
sensor are exchange.
selected)

Adiabatic Recovery - No Specify the activation of the adiabatic recovery function.


(only available if - Yes
͞On/Off͟ŝƐ
selected as
Humidifier type)

Humidity ctrl 1. No Specify the type of the humidification control functions:


(only available if a 2. Hum
1. No: no humidification/dehumidification control selected;
͞Room hum͟ 3. DeHum
2. Hum: only humidification control selected;
and/or a 4. Hum+DeHum
3. DeHum: only dehumidification control selected;
͞,ƵŵŝĚŝĨŝĞƌ͟ĂƌĞ
4. Hum+DeHum: both humidification/dehumidification
selected)
controls selected.

Post Htg DeHum 1. No Specify the type of the post-heating coil used for dehumidification
(only available if 2. Water control logic:
͞DeHum͟Žƌ 3. Electric
1. No: no post-heating coil for dehumidification is present;
͞,ƵŵнĞ,Ƶŵ͟ŝƐ
2. Water: the post-heating coil for dehumidification control is a
selected as
water type coil;
humidity control
3. Electric: the post-heating coil for dehumidification is an
type)
electric type coil.

Fan Alarm 1. No Select the fan for which the respective alarm is being enabled:
2. Supply
1. No: no fan alarms;
3. Return
2. Supply: alarm active only for supply fan;
4. Sply+Ret
3. Return: alarm active only for return fan;
4. Sply+Ret: alarm active for both supply and return fans.

AHUR-DB/CB 177
MicroTech III commissioning manual EDADT1505A

AHU ʹ COMMISSIONING MANUAL 15

Menu item Value Description


Fan Alm Type 1. Inverter Specify the type of the supply/return fan alarm:
2. DPS
1. Inverter: alarm is generated by an external fan inverter (not
3. Both
for EBM-Papst fan);
2. DPS: alarm is generated by a Differential Pressure Switch
(DPS) or by the EMB-Papst fan;
3. Both: both alarms type available.

Fan Alm Dly Ϭ͙ϭϴϬƐĞĐ Specify the delay time for the activation of the supply/return fan
alarm.

Fan Dev Alm 1. No Select the fan for which the respective setpoint deviation alarm is
2. Supply being enabled:
3. Return
1. No: no fan setpoint deviation alarms;
4. Sply+Ret
2. Supply: setpoint deviation alarm active only for supply fan;
3. Return: setpoint deviation alarm active only for return fan;
4. Sply+Ret: setpoint deviation alarm active for both supply
and return fans.

Filter alarm 1. No Select the filters for which the respective alarm is being enabled:
2. Supply
1. No: no filter alarms;
3. Return
2. Supply: filter alarm active only for supply fan;
4. Sply+Ret
3. Return: filter alarm active only for return fan;
4. Sply+Ret: filter alarm active for both supply and return fans.

Recovery Alm - No Specify the presence of the heat recovery digital input alarm.
(only available for - Yes
͞ŽŵƉĂĐƚ͟,h
model)

Htg Pump Alm - No Specify the presence of the heating coil pump digital input alarm.
(only available if a - Yes
͞,ƚŐWƵŵƉ͟ŝƐ
selected)

Clg Pump Alm - No Specify the presence of the cooling coil pump digital input alarm.
(only available if a - Yes
͞ůŐWƵŵƉ͟is
selected)

Clg Dx Alarm - No Specify the presence of the direct expansion cooling coil digital
(only available if - Yes input alarm.
͞dž͟ is selected as
cooling coil)

El htg alarm - No Specify the presence of the electrical heating digital input alarm.
(only available if an - Yes
electrical heating
coil is selected)

178 AHUR-DB/CB
EDADT1505A MicroTech III commissioning manual

AHU ʹ COMMISSIONING MANUAL 16

Menu item Value Description


Fire alarm 1. No Specify the presence and the type of the fire alarm:
2. Alm
1. No: no fire alarm active;
3. Tmp
2. Alm: fire alarm active as a physical digital input value;
4. Alarm+Tmp
3. Tmp: fire alarm active as a monitoring function on the
controlled temperature (supply or return);
4. Alarm+Tmp: both fire alarm types active.

Fire dmp ctrl 1. No Specify the presence and the behavior of the fire damper when a
(only available for 2. Yes fire alarm occurs:
͞WƌŽĨĞƐƐŝŽŶĂů͟,h 3. FollowUnit
1. No: no fire damper is present;
model)
2. Yes: the fire damper is present and it will close when a fire
alarm occurs;
3. FollowUnit: the fire damper is present and it will close when
a fire alarm occurs, but follows the behavior of the AHU when
not in alarm.

AHUR-DB/CB 179
MicroTech III commissioning manual EDADT1505A

AHU ʹ COMMISSIONING MANUAL 17

7. Fans Configuration
This page allows to configure AHU supply and return (if present) fans, together with fans sensors scales.
This is the last AHU configuration step and must be executed only after the configuration of AHU functions.

HMI Path: Main Menu Î Commissioning Î AHU Configuration Î Config fan

Menu item Value Description


Supply Fan
Type 1. EC-Aluminium Specify model and material type of the supply fan.
2. EC-Plastic
According to this value, the Pressure/AirFlow conversion factor
3. Other
͞K͟ƚŚĂƚis considered will be the one of the selected fan type (i.e.
ŝĨ͞Type = EC-Aluminium͟-х͞K-Actual͟ŵŽĚŝĨŝĞĚďLJ͞Aluminium͟
value):
1. EC-Aluminium: EBM-Papst supply fan of aluminium type;
͞K-Actual͟ŵŽĚŝĨŝĞĚďLJ͞Aluminium͟ŵĞŶƵŝƚĞŵǀĂůƵĞ͘
2. EC-Plastic: EBM-Papst supply fan of plastic type;
͞K-Actual͟ŵŽĚŝĨŝĞĚďLJ͞Plastic͟ŵĞŶƵŝƚĞŵǀĂůƵĞ͘
3. Other: custom supply fan (not EBM-Papst);
͞K-Actual͟ĞƋƵĂůƚŽ͞K-Custom͟ŵĞŶƵŝƚĞŵǀĂůƵĞ͘

Aluminium 250, 280, 310, Specify the size of the EBM-Papst aluminium type supply fan.
355, 400, 450, ĞƉĞŶĚŝŶŐŽŶƚŚĞĨĂŶƐŝnjĞƚŚĞĐŽŶǀĞƌƐŝŽŶĨĂĐƚŽƌ͞<͟ǁŝůůďĞ
500, 560, 630, automatically determined.
710
NOTE! ŽŶƐŝĚĞƌƚŚŝƐŵĞŶƵŝƚĞŵŽŶůLJŝĨĨĂŶ͞dLJƉĞ͟ŝƐƐĞƚƚŽ
͞-ůƵŵŝŶŝƵŵ͘͟

180 AHUR-DB/CB
EDADT1505A MicroTech III commissioning manual

AHU ʹ COMMISSIONING MANUAL 18

Menu item Value Description


Plastic 250, 280, 310, Specify the size of the EBM-Papst plastic type supply fan.
355, 400, 450, ĞƉĞŶĚŝŶŐŽŶƚŚĞĨĂŶƐŝnjĞƚŚĞĐŽŶǀĞƌƐŝŽŶĨĂĐƚŽƌ͞<͟ǁŝůůďĞ
500, 560, 630, automatically determined.
710
NOTE! ŽŶƐŝĚĞƌƚŚŝƐŵĞŶƵŝƚĞŵŽŶůLJŝĨĨĂŶ͞dLJƉĞ͟ŝƐƐĞƚƚŽ
͞-ůƵŵŝŶŝƵŵ͘͟

K-Custom Ϭ͙10000 Specify the value of the conversion factor ͞K͟ for custom supply
fan type.

NOTE! Consider this menu itĞŵŽŶůLJŝĨĨĂŶ͞dLJƉĞ͟ŝƐƐĞƚƚŽ


͞KƚŚĞƌ͘͟

K-Actual Ϭ͙ϭϬϬϬϬ Display the actual value of the conversion factor ͞K͟ƚŚĂƚǁŝůůďĞ
(read only) used in supply fan control logic.

Sply Prs Scale Ϭ͙ϭϬϬϬϬ Specify the value of the supply fan pressure sensor scale.
(only available if
͞&ĂŶĨĚďŬ͟ŝƐƐĞƚƚŽ
͞WƌĞƐƐƵƌĞ͟)

Sply Flow Scale Ϭ͙ϭϬϬϬϬϬ Specify the value of the supply fan airflow sensor scale.
(only available if
͞&ĂŶĨĚďŬ͟ŝƐƐĞƚƚŽ
͞ŝƌ&ůŽǁ͟)

Return Fan ;ŽŶůLJĂǀĂŝůĂďůĞŝĨ͞ZĞƚƵƌŶ&ĂŶ͟ĐŽŵƉŽŶĞŶƚŝƐƐĞůĞĐƚĞĚͿ


Type 1. EC-Aluminium Specify model and material type of the return fan.
2. EC-Plastic
According to this value, the Pressure/AirFlow conversion factor
3. Other
͞K͟ƚŚĂƚŝƐĐŽŶƐŝĚĞƌĞĚwill be the one of the selected fan type (i.e.
ŝĨ͞Type = EC-Aluminium͟-х͞K-Actual͟ŵŽĚŝĨŝĞĚďLJ͞Aluminium͟
value):
1. EC-Aluminium: EBM-Papst return fan of aluminium type;
͞K-Actual͟ŵŽĚŝĨŝĞĚďLJ͞Aluminium͟ŵĞŶƵŝƚĞŵǀĂůƵĞ͘
2. EC-Plastic: EBM-Papst return fan of plastic type;
͞K-Actual͟ŵŽĚŝĨŝĞĚďLJ͞Plastic͟ŵĞŶƵŝƚĞŵǀĂůƵĞ͘
3. Other: custom return fan (not EBM-Papst);
͞K-Actual͟ĞƋƵĂůƚŽ͞K-Custom͟ŵĞŶƵŝƚĞŵǀĂůƵĞ͘

Aluminium 250, 280, 310, Specify the size of the EBM-Papst aluminium type return fan.
355, 400, 450, ĞƉĞŶĚŝŶŐŽŶƚŚĞĨĂŶƐŝnjĞƚŚĞĐŽŶǀĞƌƐŝŽŶĨĂĐƚŽƌ͞<͟ǁŝůůďĞ
500, 560, 630, automatically determined.
710
NOTE! ŽŶƐŝĚĞƌƚŚŝƐŵĞŶƵŝƚĞŵŽŶůLJŝĨĨĂŶ͞dLJƉĞ͟ŝƐƐĞƚƚŽ
͞-ůƵŵŝŶŝƵŵ͘͟

AHUR-DB/CB 181
MicroTech III commissioning manual EDADT1505A

AHU ʹ COMMISSIONING MANUAL 19

Menu item Value Description


Plastic 250, 280, 310, Specify the size of the EBM-Papst plastic type return fan.
355, 400, 450, ĞƉĞŶĚŝŶŐŽŶƚŚĞĨĂŶƐŝnjĞƚŚĞĐŽŶǀĞƌƐŝŽŶĨĂĐƚŽƌ͞<͟ǁŝůůďĞ
500, 560, 630, automatically determined.
710
NOTE! ŽŶƐŝĚĞƌƚŚŝƐŵĞŶƵŝƚĞŵŽŶůLJŝĨĨĂŶ͞dLJƉĞ͟ŝƐƐĞƚƚŽ
͞-ůƵŵŝŶŝƵŵ͘͟

K-Custom Ϭ͙ϭϬϬϬϬ Specify the ǀĂůƵĞŽĨƚŚĞĐŽŶǀĞƌƐŝŽŶĨĂĐƚŽƌ͞K͟ĨŽƌĐƵƐƚŽŵƌĞƚƵƌŶ


fan type.

NOTE! ŽŶƐŝĚĞƌƚŚŝƐŵĞŶƵŝƚĞŵŽŶůLJŝĨĨĂŶ͞dLJƉĞ͟ŝƐƐĞƚƚŽ
͞KƚŚĞƌ͘͟

K-Actual Ϭ͙ϭϬϬϬϬ Display the actual value of the conversion factor ͞K͟ƚŚĂƚǁŝůůďĞ
(read only) used in return fan control logic.

Rtrn Prs Scale Ϭ͙ϭϬϬϬϬ Specify the value of the return fan pressure sensor scale.
(only available if
͞&ĂŶĨĚďŬ͟ŝƐƐĞƚƚŽ
͞WƌĞƐƐƵƌĞ͟)
Rtrn Flow Scale Ϭ͙ϭϬϬϬϬϬ Specify the value of the return fan airflow sensor scale.
(only available if
͞&ĂŶĨĚďŬ͟ is set to
͞ŝƌ&ůŽǁ͟)

182 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

5. MicroTech III operation manual


MicroTech III is an option. For field setting, please refer to field preparing. Some contents and model
names are for Europe models, please confirm to Daikin’s sales office.

AHUR-DB/CB 183
MicroTech III operation manual EDADT1505A

184 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 185
MicroTech III operation manual EDADT1505A

186 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 187
MicroTech III operation manual EDADT1505A

188 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 189
MicroTech III operation manual EDADT1505A

190 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 191
MicroTech III operation manual EDADT1505A

192 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 193
MicroTech III operation manual EDADT1505A

194 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 195
MicroTech III operation manual EDADT1505A

196 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 197
MicroTech III operation manual EDADT1505A

198 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 199
MicroTech III operation manual EDADT1505A

200 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 201
MicroTech III operation manual EDADT1505A

202 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 203
MicroTech III operation manual EDADT1505A

204 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 205
MicroTech III operation manual EDADT1505A

206 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 207
MicroTech III operation manual EDADT1505A

208 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 209
MicroTech III operation manual EDADT1505A

210 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 211
MicroTech III operation manual EDADT1505A

212 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 213
MicroTech III operation manual EDADT1505A

214 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 215
MicroTech III operation manual EDADT1505A

216 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 217
MicroTech III operation manual EDADT1505A

218 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 219
MicroTech III operation manual EDADT1505A

220 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 221
MicroTech III operation manual EDADT1505A

222 AHUR-DB/CB
EDADT1505A MicroTech III operation manual

AHUR-DB/CB 223
MicroTech III operation manual EDADT1505A

224 AHUR-DB/CB
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Specifications, designs and other content appearing in this brochure are current as of September 2016 but subject to change without notice.

c All rights reserved 09/16 FS