Professional Documents
Culture Documents
jl
N,|cos(0, +8,-&) (241)
Reactive power
, sin (0, +&, -8) (2.42)
We have two equations for cach load bus, given by Eqs. (2.41) and (2.42),
and onc cquation for cach voltage controlled bus, given by Eq. (2.41). Expanding
Eqs. (2.41) and (2.42) in Taylor's series about the initial estimate and neglecting
all higher order tems result in the following set of linear equations.
LoadFlow Analysis 101
Ap S, (2.43)
S,
the slack bus. The Jacobian
In the above cquation, bus 1 is assumed to be angle
matrix gives the linearised relationship between small changes in voltage
A8 and voltage magnitude A| with the small changes in real and
powers A" and AQrespectively. The elements of the Jacobian
reactive
(2.42), calculated at A84)
and
matrix are the partial derivatives of Eqs. (2,41)
and Ar:
The above cquation canbe written as
(2.44)
Computation procedure
1. Set flat start
slack bus or 1Z0°.
" For load buses, set the voltages equal to the the slack bus or 0°.
" For generator buses, set the angles equal to
Load Flow
Analysis 103
2. Calculate power mismatch
. For load buses, calculate pl) (Eq. (2.41)) and o4l
injections using the known and estimated system voltages. (Eq (242)
For generator buses, calculate pk1 (Eq. (2.41)
(Eq. (2.53)). and ap
3. Form the Jacobian matrix
" Use the various equations for the partial derivatives
with
to the voltage angle and magnitudes (form the Jacobian respect
" The elements of Jacobian matrix (J, J, J, and J) matrix),
from Eqs. (2.45) to (2.52). calculated
4. Find the matrix solution
. Inyerse the Jacobian matrix and multiply by the mismatch Douer
Compute AÕand A|V.
s. Difference in scheduled to calculated power
**6. Find thë new estimätes for the voltage magnitude and angle
7. Repeat the process until the mismatch (residuals) is less than the
specified accuracy
A|se
ase
8. After solving for bus voltages and angles, power flows and losses an
the network branches are calculated
Transimission lines and transformers are network branches.
" The direction of positive current flow is defined for a branch
element (demonstrated on amedium length line).
" Power flow is defined for each end of the branch.
Example: The power leaving bus i and flowing to busj as shou
below.
Bus i Busj
104 Electrical Power Systems: Analysis, Security and Deregulation
Current and power flows
i’j
j’i
Power loss
Sossi Syt S
This completes the load flow study. Finally, in Figure 2.13 all the computational
steps are summarized in the detailed flow chart.
200 MW
Example 2.6.
diagram of a simple three-bus system
Load Flow Analysis 105
Start
Form Ybus
Bust count i= I
i=i+1
Calculate,
p o
No
Is refer PV bus
Yes
sch
Calculate, AP= P-P
Calculate, AP = P. -P.
inax
0<min
Check limit
ischimax
O.imin
Yes
Ls i<n
No
Form Jacobian matrix
OP P
S...LAPI
i+a
Yes Calculate power
Check JAP, 4¢se flow and losses
No End
Set k = k+l
Newton-Raphson method.
chart for
Figure 2.13 Flow
106 Electrical Power Systems: Analysis, Security and Deregulation
Solution:
(a) Form the Yus
0.02 + j0.04
=10- j20
Z12
1
=10- j30
13 0.01+ j0.03
=16- j32
Z23 0.0125 + j0.025
Y, =yi2 t yj3 = (10-j20) + (10-j30) = 20 -j50
Y2 =Y =-} =-(10 -j20) = -10 +j20
Y =Ys =-y =-(10-j30) =-10 +j30
Y221 t'3 = (10 -j20) + (16 -j32) = 26 - j52
Yg =Ys =- =-(16 -j32) =-16 +j32
Y33 31t32 = (10 -j30) + (16 - j32) = 26 - j62
20- j50 -10+j20 -10+j30|
=-10 + j20 26- j52 -16+ j32
Yus -10 +j30-16+ j32 26 j62
[53.85165Z-1.9029 22.3606822.03443.62278Z1.8925
Ypus 22.36068/2.0344 58.137772-1.1071 35.77709{2.0344
31.622781.8925 35.7770922.0344 67.23095Z-1.1737
[53.85165Z-68.2 22.36068Z116.6- 31.62278Z108.4
[AP
A60) -0.04521
-0.0077
-0.0266
Load Flow Analysis 109
New bus voltages and angles in the first iteration are
V= o+ Av=1+-0.0266) =0.9734
(b) Verify the result using Power World Simulator (PWS): The one line
diagram of asimple bus system is drawn in PWS, which is shown in Figure 2.15.
194 MW 2
400 MW
Slack
250 MVAR
200 MW
144 MVAR
The first step is the formation of [Y,using the inspection method. The
calculated [Ypu values are given in Figure 2.16. Since the given problem is
a three-bus system, the size of [Yis 3 x 3 matrix.
X YBus (eus Admttance Mabic)
Newton-Raphson method
This method is cxecuted by pressing the icon Newton-Raphson power flow
iterations
available in tools ribbon, Before executing this method, the number of
and power
is to be fixed as 1in simulator options ribbon. The Jacobian values
the lst iteration.
flow results are given in Figure 2.17 and Figure 2.18 for
Electrical Power Systems: Analysis, Security and Deregulation
Fher adavd RE
- Frd... Peove
Number Name Jacobian Equation Angle Angle Volt Mag Volt Mad
Bus 2. Bus 3Bus 2 Bus 3
Frd. Raeo
Number Name Jacobian Equation Angde Ange Volt Mag volt Meg
Bus 2 Bus 3BUs 2Bus 3
to
r
frpee
Ord
MVA 1.0500
139,0 KA MYar
140.853 259.9
218.42
179.36, 118.73 215.1
22. 12 44.9
1 39.06
33 ¿4 215.42 140.85 o.9717 -2.70 11
138.0 M var MVA
2 2 400.00 250.00 471.7
1 -170. 97 -101.35 199.1
1 1 1 -229.03 -142.05 272.7
TO 3 3
1.0400 -0.59 1 1
133.0 Myar
33 206.09 145.18R 247.7
GENERATOR 1 -38.87 -21.57 44.5
1
1 1 167.75 291.9
238.89
22 200.00 146.13
4MI smach
PSS/E
software and it is iv
The same problem is taken and drawn in PSS/E
Figure 2.22.
1
Slack bus 2
Load bus
179.4 -171:0|0.972
-101.9400.0
218,4|118.7
140.9R 39.1 -229.1 230.0
22.1 -148.1
1.050 -38,9
-21.6
238.9
T167.7
146.2R
200.0 1.040
Generation bus
1 1
1
X---AREA--X
TRANSFORMERS X--AREA-.-X X---AREA----X
1 1 1 1
1 1
X---LOSSES---XX---LOSSES---X method.
%MVA
FOR MVAR
16.780.55 MVAR16.78 X---LOSSES---X
19.69 MVAR0.55 19.69
Newton-Raphson
%1 MW8.390.18
Report
MW 8.399.85 MW
0.189.85
RAT0NG
11:50 SET
A 0.00 0.9717PU-2.70 -0.50
MVA
%
1.050PU kV." MVA
1.0400PU.
% -kV. using
2011 kV
results
27
JUN 260
259.9 % 247.7
248 Converged
Mon, 44.9 MVA 471.7
215.1 199.0
272.7 44.5291.9
MVAR'
140.8R MW,
MVAR250.0 -148.0"MVAR
-229.0 146.2R 2.23
39.1
22.1
118.7 -171.0
-101.9 167.7
-21.6
SYSTEM
SIMULATOR--PSS®E Figure
POWER
179.3
MW218.4 400.0 -38.9
MW200.0238.9
INTERACTIVE
PTI
CKT CKT CKT
1 1 1
GENERATION
FROM FROM
GENERATION
SLACK
1BUS TO LOAD
2BUS 1
SLACK
BUS SLACK
BUSLOAD
2BUS
2LOAD
BUSGEN
3BUS BUS 3
3GEN GEN
BUS
TO
LOAD-PQ
1
Equations (2.68) and (2.69) show that the matrix equations are separated
into two decoupledequations requiring considerably less time to solve compared
to the time required for the solution of Eq. (2.57).
Furthernore, considerable simplifications can be made to eliminate the
need for recalculating J, and J, during iteration.
The elements of Jacobian matrix J, are as follows.
The diagonal elements are
=-|VV)sin(0, - 6, + 8)
=-( sin(0,)
.
t(2.72),
Similárlý, the diagonal êlementsof J, may be written as
-Vl,|sin@,-,lG|
j=l
sin (e, - 6,+8,)
Multiplying the above equation by V, we get
=-VAY)sin 0,
(2.74)
116 Electrical Power Systems: Analysis,
Applying these
Security and Deregulation
assumptions to Eqs. (2.68) and
(2.69), we get
J8.-)B,
--VB A8)B,
AP =-B,A;
AP
=-B'A,
Similarly, (2.75)
--7B Or
=-|V| B
=-B,A|]
=-B'A|VA (2.76)
where, B and B" are the imaginary part of the bus admittance
such that B' contains all buses admittance except those related to thematrix Yue
slack bus,
and B'" is Bdeprived from all ivoltage controlled buses related admittances.
Finally, all these approximations and. simplifications, lead to the folowing.
successive voltage magnitude and voltage angle updating equations.
A6=-[BT AP
(2.77)
AV=-[BT (2.78)
FDLF technique is very useful in contingency analysis where numerous
outages are to be simulated or a load flow solution is required for online control.
The algorithm written according to the equations derived in the previous
section is as follows:
Step 1: Create the bus admittance matrix [YpusJ
setting all bus volt
Step 2: Detect all kinds and numbers of buses -and- and the
voltage angles to 0,
ages to an initial value of 1 p.u., all
iteration counter iter to.0.
matrics B and B" according to Eqs. (2:75) and (2.76).
Step,3: Create the
Step 4: If max (AP, A0) S accuracy
AP = sch -P
A0, =0h-O.
then go to Step 6
Load Flow Analysis 117
else
(i) Calculate J, and J, elements of Eqs. (2.71), (2.72), (2.73)
and (2.74).
(iü) Calculate the real and reactive powers at each bus, and chcck
if MVAR of generator buses are within the limits, otherwise
update the voltage magnitude at these buses by ±2 %.
If imin <,<my, calculate pl
If Qimase Drsch max
If < ,min Dsch 2min
The PV bus will act as PO bus.
(iüi) Calculate the power residuals, AP and A0.
(iv) Calculate the bus voitage and voltage angle updates AVand A&
[A8, 8T'
(v) Update the voltage magnitude Vand the voltage angle &at
each bus.
s{k*l = +sol
then go to Step 4
. else print out Solution did not converge and go to Step 6.
display of
Step 6: Print out of the power tlow solution, computation and
the line ilow and losses.
Figure 2.24 all the
This conpletes the load flow study. Finally, in chart.
computational steps are summarized in the detailed tlow
Electrical Power Systems: Analysis, Security and Deregulation
Start
Buscount i 1
Calculatc, P
No
Is refer PV bus
Yes
Calculate, AP" Pschpl4
sch
Calculate, AP=P,-P" =Osch-"
Check Q limit
Oisch imin
QschOmax se"-.uch-e =Qisch'
AO"=O.-o
Yes Is iSn
No
Calculate
Yes.Calculate power
flow and iosses
Check|Ae", JAe"se
End
No
k+ 1
Set k=
for FDLF method.
Flow chart
Figure 2.24
Load Flow Analysis 119
EXAMPLE 2.7 Figure 2.25 shows the one line diagram of a simple three
bus system with generation at bus 1. The magnitude of voltage at bus I is
adjusted to 1.05 p.u. The scheduled loads at buses 2 and 3 are given in the
diagram. Line impedances are marked as n p.u. on a 100 MVA base and the
line charging susceptances are neglected.
(a) Using the fast decoupled load flow method, determine the phasor
values of the voltages at the load buses 2 and 3(PO bus) accurate to
decimal places.
(b) Verify the result with Power World Simulator and PSS/E.
1
0.02 + j0.04 2
400 MW
200 MW
Figure 2,25., One line diagram of a simple
three-bus system.
Solution: (a) Form the YpS
Y12=
Z12 0.02 + j0.04 =10- j20
1 1
=B'T'
-2.8586
-0.028182 -0.014545 1.0
-0.014545 -o.023636 1.43846
1.04
-0.028182 -0.014545|-2.8586|
*00145450.023636| T:3831
-0.060483
-0.008909
Since bus 3 is a regulated bus, the corresponding row and column of B' are
eliminated and we get
B"= (-52]
-1
[B"T=-0.01923
52
(AV,j0= B"T'
[AV,0--0.01923)--00042308.
1.0
The new bus voltages and the angles in the frst iteration are
S = 8+ A6 =0+(-0.060483) =-0.060483
=8 t A =0+(-0.008909) = -0.008909