031

PERMANENT EYEBOLTS

PRODUCT DATA SHEET REVISION NO: 002


REPORT NO: 031
PRODUCT CODE: EBRF300
031

AVIATOR PERMANENT EYEBOLTS

PRODUCT DESCRIPTION: distance connection points. If an inertia reel is used


or the eyebolts are fixed closer to the edge of the
Permanent eyebolts are designed to be fixed to window than the length of lanyard, the operator
a structural substrate such as structural steel or will be working in fall arrest. In these situations
concrete to provide suitable connection points for the operator must ensure they have read and
both fall restraint and fall arrest use. The position of understood the site rescue plan.
the eyebolts in relation to a fall hazard will determine
whether the operator is working in fall restraint Involving our specialist design teams as early as
or fall arrest. Eyebolts are supplied in stainless possible will ensure the most cost effective system
steel. They are secured to concrete and brickwork/ is used without compromising any safety or access
blockwork with resin anchors and to steelwork with requirements. Our designers will consider the welfare
stainless steel bolts, washers and vibration proof and safety of both operatives and non-operative
nuts. When fixing to metal deck or timber deck it may personal during the construction phase and future
be necessary to provide a backing plate to ensure use.
compliance.

Concrete Block / Brickwork eyebolts Restraint

Socket 2m
2m

150 100 100


mm mm mm

2m

Steel fix Timber fix

Arrest

280mm min 280mm min

50 150
mm mm

The eyebolts are designed for 1 user at any one


600mm min

time and 2 users in the event of any emergency


evacuation requirements. For fall restraint use, which
is highly recommended, the eyebolts ideally need to
be positioned at least 2.0m away from any exposed
edge. This will allow the operator to safely access the
area using a 2.m lanyard connected to a full body
harness without risk of falling. Different lengths of
fixed lanyards can be provided to accommodate
different eyebolt locations. Always consider the
shortest possible route which will minimise the fall

For any technical queries please call our advice line on 0845 241 9102 3
031

AVIATOR PERMANENT EYEBOLTS

Permanent Eyebolts are supplied in 150mm or Permanent eyebolts are designed to be left
100mm lengths for concrete and block/brick fixing. permanently in position. This must be considered
Shorter eyebolts of 50mm are used in structural when fitting them inside buildings open to the
steel. Eyebolts can be installed on the horizontal or general public such as office blocks and hotels.
vertical substrates of a building. Careful consideration Do not position the eyebolts in an area that may
must be taken when designing the eyebolt positions cause bodily damage to persons. Entrance halls
to ensure any operator lanyards will not foul with any and corridors should be avoided. The use of
roof plant or furniture or fixtures. All eyebolts must removable eyebolts should be considered during
be secured at least 280mm from any substrate edge. design for these areas. Although the eyebolt is fixed
permanently in place it must be able to be removed
during routine servicing. Sockets must be used for
resin fixed eyebolts and access to any locking nuts
must be available for timber or steel fixed eyebolts.
Greater In the event any eyebolts cannot be removed for
than service these must be treated as an eyebolt in harsh
280mm conditions and Inspection routine must be changed
accordingly –refer to Inspection/Maintenance/
Training section page.

600mm min
✔ Permanent
eyebolts

Less
than
280mm

Less than
600mm min ✘

4 For any technical queries please call our advice line on 0845 241 9102
031

AVIATOR PERMANENT EYEBOLTS

MATERIAL SPECIFICATION:
MATERIAL SPECIFICATION:

Component parts - Eyebolt


Stainless Steel - Grade 304 (UNS S30400)
Fe, <0.08% C, 17.5-20% Cr, 8-11% Ni, <2% Mn,
<1% Si, <0.045% P, <0.03% Stainless Steel

Socket
Stainless Steel - Grade 304 (UNS S30400)
Fe, <0.08% C, 17.5-20% Cr, 8-11% Ni, <2% Mn, <1% Si,
<0.045% P, <0.03% Stainless Steel

Identity disc
Polyvinyl Chloride-PVC. Tensile Strength 2.60 N/mm², Notched
Impact Strength 2.0 - 45 Kj/m², Thermal Coefficient of expansion
80 x 10-6 , Max Cont Use Temp 60 C, Density 1.38 g/cm

Neoprene washer
Elastomer – neoprene Colour - Black
Quality – Commercial Grade - c20 Hardness - 65° shore a +/-5°
S.G. - 1.4G/cm³ Tensile mpa - 5 min Elongation - 300%
Tear strength - 20 kg/cm Compression set - 35%
Operating temperature- -20° / +110° c

Stainless steel socket


Stainless steel (Concrete/Brick/Block)

Stainless steel nut


(Timber and Steel)
ID Disc PVC
Neopren washer

For any technical queries please call our advice line on 0845 241 9102 5
031

AVIATOR PERMANENT EYEBOLTS

INSPECTION/MAINTENANCE/ Maintenance to be in
accordance with SIMS
TRAINING
d3
standards. (details available
on request)
INSPECTION ROUTINE: Maintenance to be carried
All systems to be inspected at out at time of yearly Months
least every 12 months from inspection. in harsh environments

12
date of installation. Contact Sayfa Systems
In harsh environments all to arrange system
systems to be inspected at Months maintenance.
least every 3 months.
From date of installation TRAINING REQUIREMENTS:
Inspections must be carried
All personnel who use the Aviator system should have
out by approved Aviator
attended a Sayfa Systems Ltd, Aviator users course.
engineers.
Courses are available from Sayfa Systems UK Ltd.
Inspections must be

d6
approved to SIMS (Safety Courses cover the use of all Aviator and Payload
Inspection and Maintenance products, the legal and practical side of the Working
Service) standards. at Height legislation - 2005 and how to use and carry
Months
out safety checks on harnesses and all necessary PPE
All inspections to be carried in harsh environments equipment.
out to EN795:2012 and
BS 7883:2005 and WAHSA
(inspection of eyebolts) requirements for safety line
and anchor points.
All inspections to be carried out to EN364
requirements for personal protective equipment.
Contact Sayfa Systems to arrange inspections. CERTIFICATE
OF
MAINTENANCE SCHEDULE: OPERATIVE INSTRUCTIONAL TECHNIQUES AND
WORKING AT HEIGHT SAFETY
All maintenance to be
carried out by approved In recognition of successful completion of training for the installation and assembly, use,
handling and safety checks of:-
Aviator engineers.

12
Aviator Safety Line Systems n
Maintenance to be in Aviator Mobile Anchors

accordance with Sayfa Payload Access Ladder Systems


Payload Handrail Systems
Systems UK (manufacturer)
guidelines and
Months Aviator PPE n
To:

recommendations. From date of installation ........................................................................

Location of Training:
In harsh environments all ............................................................................0......................................................................

systems to be inspected at least every 3 months.


Certificate Number:

........................................................................

Name of trainee: ...................................................... Signed by trainee: .............................................

Inductor’s name: Adrian Stutterheim.................. Signed: Adrian Stutterheim................................


Date of Training: 00 January 1900 .......................

6 For any technical queries please call our advice line on 0845 241 9102
031

AVIATOR PERMANENT EYEBOLTS

OPERATING AND BS EN The company operates to the following standards


DESIGN STANDARDS: ISO
Standards
Eurocodes are designated by EN
British standards are designated by BS

• BS EN 795:2012 Class A – single anchors, anti-
pendulum anchors
• BS 7883: 2005 – Design, selection, installation, use
and maintenance for anchors conforming to EN
795
• BSMA 29: 1982 – specification for steel wire rope
• ACR (M) 002:2009
• ACR (CP) 007:2008
• ISO 9001:2008
• ISO 14001:2004
• BS OHSAS 18001:2007
• Work at height regulations 2005 (Ref.7)
• Work at height (amendment) Regulations 2007
(Ref.8) WAHR
• Provision and use of work equipment
• Provision and use of work equipment regulations • Management of health and safety at work
1999 PUWER 98 (Ref.5) regulations 1999 MHSWR (Ref.2)
• The work at height safety association WAHSA-
guidance on inspecting eyebolts for personal fall
protection purposes

Typical connection loads (Maximum cantilever from face 200mm dependent on substrate)

Ultimate factored load on bracket base Bracket moment

12.0kN 7.89kN/m

Note: For guidelines only to be checked by Chief Engineer.

For any technical queries please call our advice line on 0845 241 9102 7
031

AVIATOR PERMANENT EYEBOLTS

COMPONENT PART DETAILS:


Resin fix permanent eyebolts Steelwork permanent eyebolts
EBRF370 EBSF365
BIM No: SpecEquip_RfSftySymPermEyeBltCon_SayfaSystems_ BIM No: SpecEquip_RfSftySymPermEyeBltStl_SayfaSystems_
EBRF370_M3_G2 EBRF365_M3_G2

Timber permanent eyebolt Resin anchor socket RAS100


EBRF390 BIM No: SpecEquip_RfSftySymPermEyeBltCon_SayfaSystems_
BIM No: SpecEquip_RfSftySymPermEyeBltTimb_SayfaSystems_ RAS100_M3_G2
EBRF390_M3_G2

8 For any technical queries please call our advice line on 0845 241 9102
031
THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

AVIATOR PERMANENT EYEBOLTS


Jubilee House
Unit 3, Gelders Hall Road
Shepshed
Leicestershire
LE12 9NH
T:01509 502 155
F:0845 130 4520
www.sayfasystems.com
System Details

· Line to be located as indicated on the


roof plan.
· Line primarily used to gain access to

Aviator™ Permanent Eyebolt System Fixed To Concrete Slab


exposed roof edges.
· Incorporates Aviator™ units and all
Sayfa Systems components required.
· Fixing details for Aviator™ units as
indicated within layout.
· System to be used in conjunction with
2m restraining lanyard unless stated
otherwise.
· Structural Engineer to confirm
substructure can wistand LSD

NOTES:
12-15kN. SLD 4-6kN of post/davit.
· Enables two users simultaneously at
any one time.
Drawing Symbols

· CONCRETE TO BE MINIMUM 175mm THICK


· 300mm MINIMUM SPACING BETWEEN ANCHORS REV BY
DRAWING REVISIONS

DATE COMMENTS

· NO TRIAL TEST NEEDED IN CONCRETE UNLESS SUSPECT B C.S 20/06/2018 Part No.s added

· 6kN PROOF TEST REQUIRED


· EACH PROJECT TO BE ASSESSED BY SAYFA SYSTEMS
DESIGN & OPERATIONS DEPARTMENTS FOR FEASIBILITY

THIS DRAWING WAS CREATED IN


CONJUNCTION WITH N/A
DRAWING NO. N/A

150

SYSTEM LABEL

M12 STAINLESS STEEL


EYE BOLT

EBRF390/ST/ST
Client:
STAINLESS STEEL SAYFA SYSTEMS UK

EYEBOLT M12 x 95mm LIMITED


NW12
RESIN ANCHORED IN
NEOPRENE WASHER
TO CONCRETE
Contract:
FIXING DETAILS

Project Title:
AVIATOR™ PERMANENT
EYEBOLT SYSTEM FIXED TO
CONCRETE SLAB

Released By:

Job No: N/A Status: FOR DESIGN

DWG No: N/A Scale: 1:4 @ A3

Revision: B Date: 20/06/2018

Drawn By:C.S Checked By:M.S

UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

For any technical queries please call our advice line on 0845 241 9102 9
031

AVIATOR PERMANENT EYEBOLTS


THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

Jubilee House
Unit 3, Gelders Hall Road
Shepshed
Leicestershire
LE12 9NH

Aviator™ Permanent Yebolt System Fixed To Solid Brickwork/


T:01509 502 155
F:0845 130 4520
www.sayfasystems.com

Stonework
System Details

· Line to be located as indicated on the


roof plan.
· Line primarily used to gain access to
exposed roof edges.
· Incorporates Aviator™ units and all
Sayfa Systems components required.
· Fixing details for Aviator™ units as
indicated within layout.
· System to be used in conjunction with
2m restraining lanyard unless stated
otherwise.
· Structural Engineer to confirm
substructure can wistand LSD
12-15kN. SLD 4-6kN of post/davit.
· Enables two users simultaneously at

· SOLID BRICKWORK/STONEWORK TO BE MINIMUM 215mm THICK


any one time.
Drawing Symbols

· 350mm MINIMUM SPACING BETWEEN ANCHORS (UNRENDERED)


· 500mm MINIMUM SPACING BETWEEN ANCHORS (RENDERED) DRAWING REVISIONS

· 12kN TRIAL TEST NEEDED REV BY DATE COMMENTS

· 6kN PROOF TEST REQUIRED


B C.S 20/06/2018 Part No.s added

· FIXING TO NON LOAD BEARING STRUCTURES SUBJECT TO


STRUCTURAL CALCULATIONS

THIS DRAWING WAS CREATED IN


CONJUNCTION WITH N/A
DRAWING NO. N/A

280 MIN
SYSTEM LABEL

M12 STAINLESS STEEL


EYE BOLT

NW12
NEOPRENE WASHER

EBRF390ST/ST Client:

STAINLESS STEEL SAYFA SYSTEMS UK


LIMITED
M12 x 95mm EYEBOLT
RESIN ANCHORED TO
BRICKWORK
Contract:
FIXING DETAILS

Project Title:
AVIATOR™ PERMANENT
EYEBOLT SYSTEM FIXED TO
SOLID BRICKWORK/
STONEWORK

Released By:

Job No: N/A Status: FOR DESIGN

DWG No: N/A Scale: 1:4 @ A3

Revision: B Date: 20/06/2018

Drawn By:C.S Checked By:M.S

UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

10 For any technical queries please call our advice line on 0845 241 9102
THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©
031

AVIATOR PERMANENT EYEBOLTS Jubilee House


Unit 3, Gelders Hall Road
Shepshed
Leicestershire
LE12 9NH
T: 01509 502 155
F:0845 130 4520
www.sayfasystems.com

System Details
· Line to be located as indicated on th
roof plan.
· Line primarily used to gain access t

Aviator™ Permanent Eyebolt System Fixed To Brickwork With Cavity


exposed roof edges.
· Incorporates Aviator™ units and all
Sayfa Systems
components required.
· Fixing details for Aviator™ units as
indicated within layout.
· System to be used in conjunction w
2m restraining lanyard unless state
otherwise.
· Enables two users simultaneously a
any one time.

Drawing Symbols

NOTES:
DRAWING REVISION
REV DATE COMMENT
· INSTALLATION ALLOWS FOR ANY THICKNESS OF WALL
· 350mm MINIMUM SPACING BETWEEN ANCHORS (UNRENDERED) A 18/04/2018 Issued for intern
review

· 500mm MINIMUM SPACING BETWEEN ANCHORS (RENDERED)


· MUST NOT BE LOAD TESTED AT ANY STAGE

BRICKWORK

THIS DRAWING WAS CREATED IN

280 MIN
CONJUNCTION WITH N/A
DRAWING NO. N/A
ANTI-COMPRESSION TUBE
(ONLY REQUIRED IN CAVITY
CONSTRUCTIONS)

SYSTEM LABEL

M12 STAINLESS STEEL


EYE BOLT

M12 STAINLESS
STEEL NUT

STAINLESS STEEL
NEOPRENE WASHER BACK PLATE

STAINLESS STEEL
M12 EYEBOLT
THROUGH FIXED TO
BLOCKWORK
BRICK/BLOCK WALL

Client:

SAYFA SYSTEMS U
LIMITED

Contract:

FIXING DETAIL

Project Title:

AVIATOR™
PERMANENT EYEBO
SYSTEM FIXED TO
BRICKWORK WITH
CAVITY

Job No: N/A Status: For Desig

DWG No: N/A Scale: As Dimensi

For any technical queries please call our advice line on 0845 241 9102 11
Revision: A Date: 18/04/2018

Drawn By: C.S Checked By: M.S

UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.
031

AVIATOR PERMANENT EYEBOLTS

THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

Aviator™ Permanent Eyebolt System Fixed To Hollowcore Concrete Jubilee House


Unit 3, Gelders Hall Road

Slab Shepshed
Leicestershire
LE12 9NH
T: 01509 502 155
F:0845 130 4520
www.sayfasystems.com

System Details
· Line to be located as indicated on the
roof plan.
· Line primarily used to gain access to
exposed roof edges.
· Incorporates Aviator™ units and all
Sayfa Systems

NOTES:
components required.
· Fixing details for Aviator™ units as
indicated within layout.
· System to be used in conjunction with
2m restraining lanyard unless stated
otherwise.

· CONCRETE TO BE MINIMUM 176mm THICK


· Enables two users simultaneously at
any one time.

· 300mm MINIMUM SPACING BETWEEN ANCHORS Drawing Symbols


· NO TRIAL TEST NEEDED IN CONCRETE
· 6kN PROOF TEST REQUIRED OR TIGHTEN TO REQUIRED TORQUE
DRAWING REVISIONS
REV DATE COMMENT
A 18/04/2018 Issued for internal
review

THIS DRAWING WAS CREATED IN

150 MIN
CONJUNCTION WITH N/A
DRAWING NO. N/A

SYSTEM LABEL M12 STAINLESS


STEEL NUT
M12 EN795
STAINLESS STEEL
EYE BOLT

NEO PRENE WASHER


STAINLESS STEEL
BACK PLATE
STAINLESS STEEL
Client:
EYEBOLT M12 EXTENDED
SAYFA SYSTEMS
WITH THREADED COUPLER
THROUGH FIXED TO
CONCRETE
Contract:

FIXING DETAIL

Project Title:

AVIATOR™
PERMANENT EYEBOLT
SYSTEM FIXED TO
HOLLOWCORE
CONCRETE SLAB

Job No: N/A Status: For Design

DWG No: N/A Scale: As Dimensioned

Revision: A Date: 18/04/2018

12 For any technical queries please call our advice line on 0845 241 9102 Drawn By: C.S Checked By: M.S

UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.
031

AVIATOR PERMANENT EYEBOLTS


THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

Jubilee House
Unit 3, Gelders Hall Road
Shepshed
Leicestershire
LE12 9NH
T: 01509 502 155
F:0845 130 4520
www.sayfasystems.com

Aviator™ Permanent
NOTES: Eyebolt System Fixed To Thin Hollowcore System Details

Concrete ·SlabCONCRETE TO BE 150-175mm THICK


· Line to be located as indicated on the
THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©
roof plan.
· Line primarily used to gain access to
exposed roof edges.
· Incorporates Aviator™ units and all
Sayfa Systems

· 300mm MINIMUM SPACING BETWEEN ANCHORS ·


components required.
Fixing details for Aviator™ units as
indicated within layout.

· NO TRIAL TEST NEEDED IN CONCRETE Jubilee


· Houseto be used in conjunction with
System
Unit 3, Gelders
Shepshed
Halllanyard
2m restraining
otherwise.
Roadunless stated

· 6kN PROOF TEST REQUIRED Leicestershire


·
LE12 9NH
Enables two users simultaneously at
any one time.
T: 01509 502 155
F:0845 130 4520
Drawing Symbols
www.sayfasystems.com

NOTES: System Details


· Line to be located as indicated on the
roof plan.
· Line primarily used to gain access to

· CONCRETE TO BE 150-175mm THICK ·


DRAWING REVISIONS
exposed roof edges.
Incorporates Aviator™ units and all
Sayfa Systems

· 300mm MINIMUM SPACING BETWEEN ANCHORS ·


REV DATE
components required. COMMENT
Fixing details for Aviator™ units as
A 18/04/2018
indicated within layout.
Issued for internal

· NO TRIAL TEST NEEDED IN CONCRETE


review
· System to be used in conjunction with
2m restraining lanyard unless stated
otherwise.

· 6kN PROOF TEST REQUIRED · Enables two users simultaneously at


any one time.

Drawing Symbols

DRAWING REVISIONS
REV DATE COMMENT
A THIS DRAWING
18/04/2018 WAS
Issued forCREATED
internal IN
CONJUNCTION WITH N/A
review
DRAWING NO. N/A

150 MIN
THIS DRAWING WAS CREATED IN

SYSTEM LABEL CONJUNCTION WITH N/A


DRAWING NO. N/A

M12 EN795
200
STAINLESS STEEL
EYE BOLT
150 MIN
SYSTEM LABEL
M12 STAINLESS
M12 EN795 STAINLESS STEEL
200 STEEL NUT
STAINLESS STEEL EYEBOLT M12 x 200mm
Client:

STAINLESS STEEL SAYFA SYSTEMS


EYE BOLT THROUGH FIXED
NEO PRENE WASHER BACK PLATE
TO CONCRETE
Contract:
M12 STAINLESS
FIXING DETAIL
STEEL NUT
STAINLESS STEEL
EYEBOLT M12 x 200mm
Client:

STAINLESS STEEL Project Title:


SAYFA SYSTEMS
THROUGH FIXED
NEO PRENE WASHER BACK PLATE AVIATOR™
TO CONCRETE PERMANENT EYEBOLT
SYSTEM FIXED TO
THIN HOLLOWCORE
Contract:
CONCRETE SLAB

FIXING DETAIL
Job No: N/A Status: For Design

DWG No: N/A Scale: As Dimensioned

Revision: A Date: 18/04/2018

Drawn By: C.S Checked By: M.S

UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.
Project Title:

AVIATOR™
PERMANENT EYEBOLT
SYSTEM FIXED TO

For any technical queries please call our advice line on 0845 241 9102 THIN HOLLOWCORE
13
CONCRETE SLAB

Job No: N/A Status: For Design

DWG No: N/A Scale: As Dimensioned

Revision: A Date: 18/04/2018


031

AVIATOR PERMANENT EYEBOLTS


THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

Jubilee House
Unit 3, Gelders Hall Road
Shepshed
Jubilee House
Unit 3,Leicestershire

Aviator™ Permanent Eyebolt System Fixed To Thin Concrete Slab


Gelders Hall Road
LE12 9NH
Shepshed
T:01509 502 155
Leicestershire
LE12 F:0845
9NH 130 4520
www.sayfasystems.com
T:01509 502 155
F:0845 130 4520
System Details
www.sayfasystems.com
· Line to be located
System Details as indicated on the
roof plan.
· · to Line
Line primarily
be located as used to gain
indicated access to
on the
exposed
roof plan. roof edges.
· · primarily
Line Incorporates
used toAviator™ unitstoand all
gain access
exposed Sayfa Systems components required.
roof edges.

NOTES: · · FixingAviator™
Incorporates details forunits
indicatedcomponents
Sayfa Systems
· details
System
Aviator™
and allunits as
within layout.required.
fortoAviator™
be used in conjunction with
NOTES: ·

·
Fixing
2mwithin
indicated restraining
Systemotherwise.
units as
layout.lanyard unless stated
to be used in conjunction with

· CONCRETE TO BE 150-175mm THICK 2m· restraining


Structural Engineer
lanyard to confirm
unless stated
substructure can wistand LSD
otherwise.
12-15kN. SLDto 4-6kN of post/davit.

· · CONCRETE TO BE 150-175mm THICK


· Structural Engineer confirm

300mm MINIMUM SPACING BETWEEN ANCHORS · Enables


substructure
12-15kN.anySLD
cantwo
one4-6kN
usersLSD
wistand simultaneously at
time. of post/davit.

· · 300mm MINIMUM
NO TRIAL TESTSPACING
NEEDED BETWEEN ANCHORS
IN CONCRETE UNLESS SUSPECT
· Enables two users
any one time.
simultaneously
Drawing Symbols at

· · NO6kN
TRIAL TESTTEST
NEEDED IN CONCRETE UNLESS SUSPECT
Drawing Symbols
PROOF REQUIRED
· · 6kN PROOF
EACH TEST REQUIRED
PROJECT TO BE ASSESSED BY SAYFA SYSTEMS DRAWING REVISIONS

· EACH PROJECT
DESIGN TO BE ASSESSED
& OPERATIONS BY SAYFA
DEPARTMENTS SYSTEMS
FOR SUITABILITY DRAWING
REV BY REVISIONS
DATE COMMENTS

DESIGN & OPERATIONS DEPARTMENTS FOR SUITABILITY REV A


BY C.S
DATE22/06/2018 Issued for
COMMENTS
internal review
A C.S 22/06/2018 Issued for
internal review

THIS DRAWING WAS CREATED IN


CONJUNCTION WITH N/A
THIS DRAWINGDRAWING NO. N/AIN
WAS CREATED
CONJUNCTION WITH N/A
DRAWING NO. N/A

150 MIN
150 MIN

SYSTEM LABEL
SYSTEM LABEL
200
M12 EN795
M12 EN795
STAINLESS STEEL
200
STAINLESS
EYE BOLTSTEEL
EYE BOLT

NSS12
NSS12
M12 STAINLESS
STAINLESS STEEL M12 STAINLESS
STEEL NUT
STAINLESS
EYEBOLTSTEEL
M12 x 200mm STEEL NUT
EYEBOLT M12FIXED
THROUGH x 200mm
NEO PRENE WASHER STAINLESS STEEL
THROUGH FIXED
TO CONCRETE
NEO PRENE WASHER STAINLESS STEEL
Client:

TO CONCRETE BACK PLATE SAYFA SYSTEMS UK


Client:
LIMITED
BACK PLATE SAYFA SYSTEMS UK
LIMITED

Contract:
FIXING DETAILS
Contract:
FIXING DETAILS

Project Title:
AVIATOR™
Project Title: PERMANENT
EYEBOLT SYSTEM FIXED TO
AVIATOR™ PERMANENT
THIN CONCRETE SLAB
EYEBOLT SYSTEM FIXED TO
THIN CONCRETE SLAB

Released By:

JobBy:
Released No: N/A Status: FOR DESIGN

Job No:DWG
N/A No: N/A Scale:DESIGN
Status: FOR 1:3 @ A3

Revision:
DWG No: N/A A Date:
Scale: 1:3 @ 22/06/2018
A3
Drawn
Revision: A By:C.S Date: 22/06/2018
Checked By:M.S

UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY. Drawn By:C.S Checked By:M.S

14 For any technical queries please call our advice line on 0845 241 9102
UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.
031

AVIATOR PERMANENT EYEBOLTS

THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

Aviator™ Permanent Eyebolt System Fixed To Steelwork Jubilee House


Unit 3, Gelders Hall Road
Shepshed
Leicestershire
LE12 9NH
T:01509 502 155
F:0845 130 4520
www.sayfasystems.com
NOTES: System Details

· Line to be located as indicated on the


roof plan.
· SOLID SWIVEL EYEBOLT REQUIRES MINIMUM 10mm THICKNESS · Line primarily used to gain access to
exposed roof edges.
· MINIMUM 27mm EDGE DISTANCE · Incorporates Aviator™ units and all
Sayfa Systems components required.
· MINIMUM 50mm SPACING BETWEEN ANCHORS · Fixing details for Aviator™ units as
indicated within layout.
· NO TRIAL TEST REQUIRED · System to be used in conjunction with
2m restraining lanyard unless stated
· 6kN PROOF LOAD TEST REQUIRED otherwise.
· Structural Engineer to confirm
· 14mm COUNTERSUNK HOLE substructure can wistand LSD
12-15kN. SLD 4-6kN of post/davit.
· Enables two users simultaneously at
PVCW16 any one time.

M16 CLEAR PLASTIC WASHER Drawing Symbols

SYSTEM LABEL M12 STAINLESS STEEL


EBSF365ST/ST SOLID SWIVEL STEELWORK DRAWING REVISIONS

M12 EN795 STAINLESS STEEL EYEBOLT BOLTED THROUGH REV BY DATE COMMENTS

EYE BOLT 52mm LONG STEEL BEAM B C.S 20/06/2018 Part No.s added

STAINLESS STEEL STAINLESS STEEL


WASHER WASHER

NEOPRENE WASHER

THIS DRAWING WAS CREATED IN


CONJUNCTION WITH N/A
DRAWING NO. N/A

NOTES:

· SOLID SWIVEL EYEBOLT REQUIRES MINIMUM 12mm THICKNESS


· MINIMUM 25mm EDGE DISTANCE
· MINIMUM 50mm SPACING BETWEEN ANCHORS
· NO TRIAL TEST REQUIRED
· 6kN PROOF LOAD TEST REQUIRED
· 10.2mm COUNTERSUNK & TAP M12

STAINLESS STEEL
SPACER
SYSTEM LABEL
Client:
M12 EN795 STAINLESS STEEL M12 KEE SAFETY
SAYFA SYSTEMS UK
EYE BOLT STEELWORK EYEBOLT LIMITED
BLIND FIXED TO STEEL

Contract:
FIXING DETAILS
STAINLESS STEEL
WASHER

PVCW16
M16 CLEAR PLASTIC WASHER
Project Title:
AVIATOR™ PERMANENT
EYEBOLT SYSTEM FIXED TO
STEELWORK

Released By:

Job No: N/A Status: FOR DESIGN

DWG No: N/A Scale: 1:4 @ A3

Revision: B Date: 20/06/2018

For any technical queries please call our advice line on 0845 241 9102 15
Drawn By:C.S Checked By:M.S

UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.
031

AVIATOR PERMANENT EYEBOLTS

THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

Aviator™ Permanent Cantilever Eyebolt Fixed In To Concrete Slab


Jubilee House
Unit 3, Gelders Hall Road
Shepshed
Leicestershire
LE12 9NH
T:01509 502 155
F:0845 130 4520
www.sayfasystems.com
System Details

· Line to be located as indicated on the


roof plan.
· Line primarily used to gain access to

NOTES:
exposed roof edges.
· Incorporates Aviator™ units and all
Sayfa Systems components required.
· Fixing details for Aviator™ units as
indicated within layout.
· System to be used in conjunction with
2m restraining lanyard unless stated

· CONCRETE TO BE MINIMUM 200mm THICK ·


otherwise.
Structural Engineer to confirm
substructure can wistand LSD

· 300mm MINIMUM SPACING BETWEEN ANCHORS


12-15kN. SLD 4-6kN of post/davit.
· Enables two users simultaneously at
any one time.

· NO TRIAL TEST NEEDED IN CONCRETE UNLESS SUSPECT


Drawing Symbols

· 6kN PROOF TEST REQUIRED


· EACH PROJECT TO BE ASSESSED BY SAYFA SYSTEMS DRAWING REVISIONS

DESIGN & OPERATIONS DEPARTMENTS FOR FEASIBILITY


REV BY DATE COMMENTS

A C.S 22/06/2018 Issued for


internal review

INSULATION/VOID

THIS DRAWING WAS CREATED IN


CONJUNCTION WITH N/A
DRAWING NO. N/A

Varies Varies Varies


KEE SAFETY
M12 EN795 EYEBOLT

SYSTEM LABEL
KA-CANT
KEE SAFETY CANTILEVER
EYEBOLT SOCKET (AVAILABLE
FOR CANTILEVER BETWEEN Client:
65-175mm) RESIN ANCHORED SAYFA SYSTEMS UK
LIMITED
IN TO CONCRETE

Contract:
FIXING DETAILS

Project Title:
AVIATOR™ PERMANENT
CANTILEVER EYEBOLT
FIXED IN TO CONCRETE
SLAB

Released By:

Job No: N/A Status: FOR DESIGN

DWG No: N/A Scale: 1:3 @ A3

Revision: A Date: 22/06/2018

Drawn By:C.S Checked By:M.S

16 For any technical queries please call our advice line on 0845 241 9102
UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.
031

AVIATOR PERMANENT EYEBOLTS

Aviator™ Permanent Eyebolt System Fixed To Concrete Slab

1 2 3 4 5 6 7 8 9
A F
P
TOLERANC

EBSF365ST/ST - M12 EN795 STAINLESS STEEL EYEBOLT 52mm LONG UNLESS O


NO DECIM
ONE DECIM
TWO DECI
ANGLES +
COMPARE
ALL INSTR
MAKE NO

B WITHOUT

12
8
R1
55

EBRF370ST/ST-100 - ABSEIL EYEBOLT 100mm LONG


D
12

8
E R1 95

F EBRF370ST/ST-150 - ABSEIL EYEBOLT 150mm LONG


12

G
8
R1 A Issue
150 REV D

THIS DRAW
THE INFOR
THE DRAW
H INFORMAT
OR DISCLO
PERMISSIO

SAYFA
RAS120 - EYEBOLT SOCKET 120mm

I
16

JUBILEE H
UNIT3, GE
SHEPSHED
LEICESTER

120 WEIGHT TITLE


LE12 9NH

DRAWING NO. DRAW


0.19 kg Aviator™ Eyebolt Components N/A C.Sc
MATERIAL/FINISH CLIENT SHEET
J
/ Sayfa Systems UK Limited 1/1
1 2 3 4 5 6 7 8 9

For any technical queries please call our advice line on 0845 241 9102 17
Sayfa Systems UK Ltd
Jubilee House
No. 3 Gelders Hall Road
Shepshed, Loughborough
Leicestershire LE12 9NH

T: 0845 241 9102


F: 0845 130 4520
email: info@sayfasystems.com
www.sayfasystems.co.uk
Ref: 125/031-11/18