You are on page 1of 1

25/23

LEGENDS:
ACCENT LIGHT - LED
PINLIGHT - LED
EMERGENCY LIGHT
WALL LIGHT - LED
2-LED FLOURESCENT WITH
REFLECTIVE CASE
S LIGHT SWITCH
S3 3-WAY SWITCH
EXHAUST FAN
CONVENIENCE OUTLET
ACU AIR CONDITIONING UNIT
CCTV CAMERA
F FIRE ALARM BELL
SL STROBE LIGHT
S PA/BGM SPEAKER

NON-RADIOACTIVE SINGLE
WITH 100 METERS PROTECTIVE RADIUS
NOTES:
AIRCRAFT OBSTRUCTION LIGHTING FIXTURE WITH 100
1. 3-600A BUSBAR GUTTER, GA #16 WITH COVER
WATTS BULB, 230V, 60HZ, BODY SHALL BE ALUMINUM
ALLOY WITH RED GLASS GLOBES SIMLAR
COMPLETE WITH BUSBAR WITH GROUND BUS,
SUPPORT, LATCH FOR SEAL AND OTHER RELATED
LIGHTNING ARRESTER
TO LOCATED @
HIGHEST POINT
CONNECT TO NEAREST EMERGENCY
LIGHTING CIRCUIT (2-3.5mm² THHN &
ACCESSORIES BUSBAR LENGTH SHALL 75% OF
1-2.00mm² THHN IN 15mmØ CONDUIT)
OF THE BUILDING
GUTTER LENGTH.
MAST ASSEMBLY WITH GUY WIRE

ROOF 1-32mmØ WITH LIGHTNING ARRESTER CABLE


RISER DOWN TO GROUND ROD @ SECOND FLOOR 2. BREAKER GUTTER, GA#16 WITH COVER COMPLETE
1-100mm² BCW IN 32mmØ PVC CONDUIT
C-RL
3
3-8.0mm² THHN +
1-5.5mm² THHN IN WITH BREAKER, SUPPORT AND OTHER RELATED
25mmØ IMC

3 sets of 3-150mm² THHN + MCB C-RL


4
ACCESSORIES, SAME LENGTH TO BUSBAR GUTTER.
21
1-22mm² THHN IN 75mmØ
TO GROUND @
PVC
LOWER GROUND
C-RL 50AT,3P,230V
ECB-ELEV 1600AT, 230V, 3P
5
ECB IN NEMA 3R 2-5.5mm² THHN +
1-3.5mm² THHN IN CUSA-RL
25mmØ PVC

ROOF LEVEL M 220HP 5HP 5HP 5HP

ELEVATOR MOTOR BOOSTER PUMP


2-8.0mm² THHN +
1-5.5mm² THHN IN
20mmØ IMC

TO SERVICE ENTRANCE
50AT 50AT 50AT
230V, 3Ø, 3WIRES +
50AT 50AT 50AT
GROUND, 60HZ
UNIT UNIT UNIT UNIT CUSA-TF
CS-TF
12 11 10 9 4 SETS OF (3-250mm²
THHN + 1-30mm² THHN IN
THIRD FLOOR 100mmØ IMC)
1800AT, 2000AF, 230V, 3P,
2-8.0mm² THHN +
ECB IN NEMA 3R
1-5.5mm² THHN IN
20mmØ IMC

50AT 50AT 50AT


WIRE GUTTER
50AT 50AT 50AT
UNIT UNIT UNIT UNIT CUSA-SF
CS-SF ECB-EL CS-TF UNIT 11 UNIT 9 CS-SF UNIT 7 UNIT 5 CS-UG UNIT 3 UNIT 1 CUSA-LG
8 7 6 5

SECOND FLOOR
M M M M M M M M M M M
2-8.0mm² THHN +
M M M M M M M M M M NOTE: USE PURE
1-5.5mm² THHN IN CUSA-RL UNIT 12 UNIT 10 CUSA-TF UNIT 8 UNIT 6 CUSA-SF UNIT 4 UNIT 2 CUSA-UG COPPER 15mmx300mm
20mmØ IMC GROUNDING ROD
(TYPICAL)
1600AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 50AT 250AT
50AT 50AT 50AT 50AT 50AT 50AT
GCB
BREAKER GUTTER
UNIT UNIT UNIT UNIT CUSA-UG
TO ATS
CS-UG
4 3 2 1
UPPER G 100kW STAND BY GENSET,

GROUND 3PHASE, 230V, 3-WIRES +


GROUND, 60HZ 1800RPM,
ATS
GROUND WIRE C-LG
TO GCB GROUND WIRE
15
200AT, 225AF,
230V, 3P ECB IN ATS
NEMA 3R C-LG
13 3-50mm² THHN
+1-14mm² THHN IN
3-5.5mm² THHN+
3-5.5mm² FRC + 50mmØ IMC
1-3.5mm² THN IN C-LG
1-3.50mm² FRC 20mmØ IMC 14
IN
50AT, 50AF, 50AT, 50AF,
32mmØ iMC
230V, 3P 230V, 3P
ECB IN NEMA ECB IN NEMA 250AT
LOWER 3R 3R
CUSA-LG
GROUND 5HP 5HP 5HP 5HP

1 SCHEDULE OF LOADS FIRE


PUMP
JOCKEY
PUMP
TRANSFER
PUMP
SCALE:
E7 NTS.

2 POWER RISER DIAGRAM


SCALE: NTS.
E 7
THIS DRAWING AS AN INSTRUMENT OF SERVICE PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE: OWNER: SHEET CONTENT: DRAWN BY: SHEET NO:
IS THE PROPERTY OF THE ARCHITECT. IT IS
UNLAWFUL FOR ANY PERSON TO COPY WITHOUT AS SHOWN JIBM

E:\01_Office Files\03_Logos\Amvisions Logo_02.png


SPECIFIC PERMISSION AT THE OFFICE. (RA 9266)

PRESIDENTIAL DECREE NO. 49


RONALDO B. RAMOS THREE STOREY COMMERCIAL
BUILDING WITH BASEMENT
DATE 01/26/2023 7 E7
PROTECTION OF INTELLECTUAL PROPERTY
NOV. 14, 1972, WORKS OF ART, ARCHITECTURE, PRC NO.: 4842 DATE VALIDITY: 05/12/2024 MR. WILSON SY
MODELS AND DESIGNS ARE CREATIVE WORKS
AND CONSIDERED AS PART OF INTELLECTUAL
PROPERTY OF THE AUTHOR DULY PROTECTED
UNDER PD 49
PTR NO.: 1305144 DATE ISSUED: 01/12/23

PLACE ISSUED: CALOOCAN CITY


LOT 236-D-1-A-B,C GENERAL LUIS STREET KAYBIGA,
LOCATION: CALOOCAN CITY DATE
8 ELECTRICAL