Professional Documents
Culture Documents
History:
Application of Standards
Standards Documents contain requirements that are to be complied with on a global basis. However, it is
recognized that market, operational and technical requirements will change over time, so input from regional
engineering teams and other stakeholders is encouraged. Also, as regional teams work with outside engineering
firms, it should be emphasized that those firms are responsible to provide designs and detailed construction
documents that are fully compliant with all applicable codes, and that conflicts between Equinix standards and
applicable codes are to be brought to our attention.
Purpose
The purpose of this standard is to define the requirements, assumptions and acceptance criteria for
Computational Fluid Dynamic (CFD) modeling of IBX whitespace and exterior air flow conditions.
Applicability
This standard shall apply to all new IBX Facilities and significant expansions to existing facilities.
1.0 RESPONSIBILITIES:
Global Design and Construction Director shall maintain this standard current with the assistance of the global
design engineering teams.
It is the responsibility of the design manager, construction manager, and their designates to ensure that the
Engineer of Record and the Mechanical and Electrical contractor adheres to the content of this standard during
the design and construction of the HVAC and electrical systems for a particular project.
2.0 SCOPE
This standard covers the modeling assumptions and acceptance criteria for CFD modeling of both the interior
whitespace airflows as well as modeling of total building airflows and prevailing wind conditions to validate the
performance and heat rejection capacities of exterior equipment in relation to all building intake and exhaust air
paths.
The CFD model shall be a computerized 3-dimensional, finite numerical analysis of simulating air flow of all
spaces including in the air flow of the space together with flow patterns for ceiling and/or floor plenums, air
handlers or CRAC units, and all electronic equipment. The finite numerical analysis model must include the
temperature, pressure and velocity results.
The preferred CFD modeling software is Future Facilities 6SigmaDC. The version of 6Sigma being used shall be
coordinated with Equinix. Original format data files for the CFD model shall be turned over to Equinix for our use
after project completion. The version of 6Sigma being used shall be coordinated with Equinix. Any other
modeling software must be preapproved and capable of performing the same analysis requirements.
During schematic design and design development milestones, the models may be simplified to reduce the
processing time and facilitate decision making. During these stages the models may contain the major equipment
and geometries of the room and details of the room infrastructure appropriate to the level of completeness for the
design documents. During these early stages the failure transient analysis may be omitted and the control
functionality may be simplified.
B. As subsets of the above conditions, the space should be modeled to demonstrate the effect of high density
cabinets in the following cases for the failure condition, only:
1. Evenly distributed high density loading in 25% of the cabinets at 10kW/cab, with the rest of the design load
spread evenly throughout the remaining cabinets.
2. Localized extreme high density in 1% the cabinets of 45 kw/cab located in close proximity, with the
remaining load distributed evenly across the remaining cabinets.
3. A variation request should be submitted if it is desired to omit these scenarios as being outside of the site
specific design criteria.
2. Actual expected whitespace installed equipment, and infrastructure including obstructions, physical
geometries, heat loads material, air flow, and thermal characteristics for the following:
a. HVAC equipment
3. Where there are raised access floors or suspended ceilings being used as air plenums the model shall
include leakage rates appropriate to the system used [starting point of 0.02” (0.51 mm) gap between tiles]
+10% for imperfect penetrations.
4. System bypass rate (airflow bypass through/around IT room equipment) shall be calculated, values less
than 25% of the total system air flow shall be validated.
5. All Computer Room Air Conditioning units, in row air conditioners, along with any external air handling units
that supply and return conditioned air to the space via ductwork. Inputs into the model shall include, but is
not limited to:
a. Computer Room Air Conditioner (CRAC) or Air Handler (CRAH) Length, Width, & Height - this
shall be manufacturer specific with model number.
b. Duct connections to the raised floor plenum or mechanical gallery walls.
c. Location and type of supply airflow fans - in the units or under the raised floor, EC plug fans or FC
centrifugal fans.
d. Damper installations used to limit recirculation of conditioned air through failed/off units.
e. External air handling units supply and return registers.
D. Acceptance Criteria: The model, including all failure conditions shall demonstrate the following conditions for
acceptance of the proposed design.
1. The standard Service Level Agreement (SLA) conditions shall be maintained at the designated SLA sensor
locations for temperature measurements at between three (3) and five (5) feet (0.9m to 1.5m) from the floor
and no closer than twelve (12) inches (0.3m) from the cool air intake side of all cabinet.
a. Temperature: 64.4°F (18.0°C) to 80.6°F (27°C)
2. The temperature at the top intake of every rack shall not exceed ASHRAE Class A1 allowable:
a. Temperature: 59°F (15°C) to 89.6°F (32°C)
3. Upon request, it may be acceptable for the design to accommodate a short term excursion beyond the
above SLA at peak IT loads during a transition between utility and generator within the SLA limit of ~4
minutes/month. An evaluation of the utility supply reliability as well as the transient model required above
should be done to validate this requirement can be met. This condition must be identified in the CFD report
with the expected duration and magnitude of the excursion prior to acceptance by Equinix.
2. Actual structures, equipment and infrastructure including obstructions, physical geometries, heat loads
material, air flow, humidity (if required,) and thermal characteristics for the following::
a. Building geometries, including structure, louvered walls, fences, equipment access platform
grating, sound attenuating walls, parapets, etc.
b. Buildings exhaust openings and airflows.
c. Building outside air intake airflows.
d. Heat rejection equipment airflows including radiators, condensing units, cooling towers, dry-
coolers, etc.
e. Generator exhaust stacks
f. Generator air intake and exhaust air flows.
g. Exterior mounted equipment.
3. The airflow path information for the above components shall include directional vectors, volume,
temperature and humidity.
4. If requested by Equinix, Generator and evaporative heat rejection equipment modeling results shall include
particulate dispersion mapping and humidity dispersion mapping to determine the likelihood of cross
contamination or impact to adjacent equipment.
C. Acceptance Criteria: The model, including all failure conditions shall demonstrate the following conditions for
acceptance of the proposed design.
1. The modeled outside air intake temperature and humidity conditions at the equipment intakes match the
selection criteria for all equipment and that adjacent unit operation and airflow influences do not result in a
required derating of equipment capacities.
2. If requested by Equinix, the generator exhaust particulate dispersion map shall indicate that while
generators are in operation and all other equipment intakes are at full flow rate, the exhaust concentration
at outside air intakes are less than 296 μg/m³.
3.3 REPORTING
A. To be done by External Consultants as part of design milestones deliverables.
B. Upon completion of the CFD model a detailed report shall be provided which details the modeling process, the
assumptions within the model, and an analysis of the results of both steady state and worst case failure
conditions.
C. The report shall be submitted with the following content:
1. Introduction – Description of the project,
End of Document