You are on page 1of 51

Edited by Foxit Reader

Copyright(C) by Foxit Corporation,2005-2009


For Evaluation Only.

Q 4700
INSTALLATION
AND

OPERATIONS MANUAL

- Q4700 gamma leve I indicator UNIRAD

T HIGH L&VEL

@ ADJUST

50•••• 0•••

LOWLEVEL

(0)1 AD.lUST

200.400,.

DOfoADJUST
CDAASE
'00.,. AII.JUBT C........;...__ N_O_A_M_A_L
_FU_N_CT_'D_N J
~:6

FINE
FAST
SLDW
METER RESP. J
I

UNIRAD Instrument AB
Svärdlångsvägen 32
If needed contact
SE-120 Nuklidtech Sweden AB on +46 8 180845 or email info@nuklidtech.se
60 ÄRSTA
to get
SWEDEN more information or support. You can+46
Phone: even visit
818 www.nuklidtech.se.
08 45 Fax: +46 818 0846
Q 4700
GAMMA LEVEL
INDICATOR
INSTALLATION AND OPERATIONS MANUAL
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.

Contents
Page

1. Introduction 1
2. Safety regulations 3
3. Technical data, electronic unit 5
4. Technical data, detectors 7
5. Installation 8
6. Connection s 12
7. Initial adjustments 14
8. Circuitry description 15
9. Fault tracing 20
10. ABCs of radioactivity 24
11. Dimension drawings 27
12. Components list 35
13. Circuit diagrams 39

UNIRAD Instrument AB

Svärdlångsvägen 32

S-120 60 ÅRSTA • SWEDEN

Te1.08-180845
Phone: Fax08-180846
+46 818 08 45 Fax: +46 818 08 46

Printed in Sweden by
WOXNADALSTRYCK AB, P. O. Box 94, S-828 22 EDSBYN
Phone domestic 0271-225 10
1. INTRODUCTION

1:1 General

The Q 4700 level indicator is based on the use of radioac-


tive radiation, and it is used mainly for level measure-
ments in closed vessels, vessels containing corrosive mate-
rials and applications that impose stringent reliability re-
quirements. The radiation source unit is positioned on
one side of the vessel, and the intensity of radiation is mea-
sured on the opposite side of the vessel.

The level indicator consists of one or more detectors pro-


vided with cables (Fig. 1), an electronic unit (Fig. 2) and
one or more source units (Fig. 3). Each source unit con-
tains a radioactive substance and a radiation shield.

Since the equipment is mounted on the outside of the ves-


sel, it is ideal for level monitoring at high pressures, at high
temperatures and under severe corrosive condition . T)1,:
vessels can thus be hermetically sealed, and they can con-
tain liquids, slurries, paper pulp, wood chips, crushed ma-
terials, etc.

Fig. 3. Radiation source unit, type Q 45828.

Fig. 1. Detector Q 4700/5 with casing removed

c:::------
....
-
~-------------------------------------
Fig. 2. Electronic unit mounted in sheet metal ca ing. Fig 4. Radiation ource units and detectors mounted on
the outside of the vessel.

1
1:2 Radiation source unit

The radiation source unit consists of a radioactive sub- The capsules for Co-60 and Cs-137 are tested and classi-
stance enclosed in a lead shield. The lead wall thickne is fied in accordance with the international ISO 2919
based on the strength of the radioactive substance. Radia- -1980 E standard.
tion is allowed to emerge through a port in the lead wall.
Different radiation spread angles can be obtained by pro- The source units - source and shield - are supplied ready
viding ports of different design. A lockable handle can be for use, and must be installed in accordance with the di-
turned to one of two positions: radiation on or radiation rections set forth in chapter 5 entitled "Installation".
off (shielded).
Gamma radiation from the radioactive sources is harm-
les to all materials except living tissue, which is darnaged
by internaI ionization. For this reason, the safety regul-
Radioactive S· .'1
ations set forth in chapter 2 must be rigorously observed.
r8sing
substance Lead There is no risk of any radiation damage to the vessel or its
container contents.

I'=:---::-=-----~-;--
Fig. 5. Cross-seetian of radiarion source unit

Radiation also "leaks" through the lead container, thus


making it necessary to limit the time throughout which
anyone is aLlowed to remain in the immediate vicinity of
the source unit. However, at a distance of one metre from
the lead container, the dose rate is always less than 0.75
pSv /h, except for the beam itself when the port is open.
There is thus a radiation zone within one metre of the lead
container, but outside this zone personnel can work full-
time without encountering any radiation hazard.

The radiation sources used in the unit are prepared in ac-


cordance with international regulations. Those usually
employed are Co-60 (Cobalt) and Cs-137 (Cesium).

The Co-60 source consists of a solid cylindrical piece of


cobolt about 4 mm in diameter enclo ed in a stainless steel
capsule.

The Cs-137 source consists of cerarnic-bonded cesium in


a dual-wall stainless steel capsule.

2
2. SAFETV REGULATIONS

RADIATION SAFETY REGULATIONS


The following safety regulations comply with applicable regulations in Sweden. For installation in other countries, due re-
gard must, of course, be given to the regulations that are in force in the country in question.

2:1 Maximum dose rate 2:4 Surveillance after installation

Under current regulations, personnel who are exposed to The responsible overseer must check that all source units
radioactive radiation in the course of their work must not are in place, that they are in good condition and that they
receive agreater weekly dose than 300 pSv. This is equiv- have been installed in accordance with the regulations. At
alent to a dose rate of 0.75 pSv /h throughout a 40-hour the same time, a check must be made to see that the dose
work-week. rate at the detectordoes not exceed 7.5pSv/h and that the
warning signs are posted correctly.
For personnel engaged in radiological work who are pro-
vided with a personal dosimeter and who are examined 2:5 Changing a source unit
medically at least every third year, the perrnissible radia-
tion dose is three times higher than the figure stated When the radioactivity of the source unit has decayed to
above. a certain leve\, replacement becomes necessary. This ap-
plies primarily to cobolt-60 which has a half-lite of 5.3
Since the dose rate does not exceed 0.75 ,uSv/h at a dis- years, and for which replacement can become necessary
tance of one metre from the shield, personnel can remain after about 10 years. Cesium-137 has a half-life of 30 ye-
constantly beyond this distance without receiving morc ars and does not normally have to be replaced during the
than the permissible weekly dose. service life of the equipment. For replacement, an ap-
proved supplier must be notified. He will install a new
Even personnel who never work with the radiological source unit having the same activity level as the old one
equipment are exposed to radiation. Radioactive sub- had when it was delivered. If it seems advisable, the sup-
stances are present in nature, and these natural sources to- plier can use the old radiation shield and sirnply recharge
gether with cosmic rays subject us to a dose of about 10 the unit with a fresh radioactive substance. If the activity is
pSv per day. A radiation dose of up to 20 ,uSv/h (gamma altered, a new application must be submitted to the radia-
rays) has been recorded directly from wristwatches. Radi- tion-protection authorities.
ological examinations subject the body to quite heavy
doses; a pulmonary X-ray, for example, provides about
10 000 pSv. 2:6 Transportation of source units

Contact your supplier for further information.


2:2 Responsibility

Anyone planning to install a facility employing radioac-


tive sources must first abtain permission to possess and
use the source unit. He must appoint a "responsible over-
seer" who will assume full responsibility for seeing to it
that instructions are followed. Not until this is done will
the radiation-protection authorities grant permission for
the possession and use of the equipment.

2:3 Moving a source unit

If, for any reason, the source unit must be moved, the re-
sponsible overseer must be so informed. Prior to dis-
mounting, the source unit must be turned off and locked.
During the period throughout which the source unit is re-
moved, it must be kept in a locked and fireproof area.

3
ELECTRICAL SAFETV REGULATIONS

2:7 General

The Q 4700 level indicator has been designed, contructed


and tested in accordance with the following safety regu-
lations for electrical measuring instruments of dass I: IEC
348, IEC 414 and VDE 0160.

Warning

Personnel doing fault tracing with the mains voltage


turned on and using pointed objects such as probes can
come inte contact with dangerous volta ges.
- Personnel engaged in fault tracing during operation
must use insulated toois.
- The mains voltage must not be turned on while person-
nel are replacing or repairing circuit boards.
- Always check to see that no dangerous external volt-
ages are connected via relay contacts.

(Illustration taken from "Elioreskriiter", published in


Stockholm 1980 by "Elfackets Centrala Yrkesnämnd"
and "Liber Läromedel".)

Signal ground 2:9 Setting the mains voltage

The device s signal ground - TP1 on the panel board and Check to see that the mains voltage selector (SK20 1) on
OVon the base board - must not be connected to chassis the base board is set to the local mains voltage. Remember
ground if the 4-20 mA or -15 V outputs are connected that this must be done before the mains voltage is connect-
galvanically to ground. ed up. Use the 115 V setting for 110-127 V AC, and use
the 230 V setting for 220-240 V AC.
2:8 Grounding
2:10 Fuse
As setground
The forth inline
IEC, UL be
must andconnected
CSA, the ground lead must be
to the threaded
connected
ground only toonterminal
terminal E on! terminal board BU20l.
the casing The Q 4700 level indicator is provided with a fuse desig-
The ground lead must be at least 1 cm longer than the nated VL20 1. This fuse must be replaced if the setting of
phase and neutral leads so that it will break last, in the the mains volta ge selector is changed. Use a 5 x 20 mm,
event that the leads are tom loose. 160 rnA slow-blow, glass-tube fuse for 230 V AC. For
115 V AC, use a 315 rnA fuse of the same type.

4
3. TECHNICAL DATA, ELECTRONICS UNIT

3:1 Power requirements Low-Ievel alarm:


Relay signal can be adjusted to issue an alarm between
Mains voltage
20-40 % of full-seale deflection.
50-60 Hz
115 V ± 15%
230 V ± 15% Relay signal used to monitor operation:
During normal operation, relay RE203 is pulled in.
SK 201
115 V The following are monitored:
230 V 1. That the supply voltages are normal.
2. That the flow of pulses to the e\ectronic unit is not
Fuse (VL 201) interrupted.
315 mA 3. That no error signal has been received from any of
160 mA the detectors.

3:2 Electrical safety provisions The l-pole transfer contacts in relays RE201, RE202
and RE203 can be loaded to a maximum of 1 A, 220
As set forth for IEC 348, dass I, all input and output V (resistive load). For an inductive load, a spark sup-
signals are galvanically isolated from ground. The max- pressor must be used as shown in Fig. 6.
imum permissible voltages vis-a-vis ground are 250
V AC and 350 V DC. 3:5 Time eonstant

3:3 Environment The rate of decay of the radioactive source varies widely.
To provide sufficient output-signal stab iIity and thus stab-
Ambient temperature ilize the pointer deflection, the output signal is sent
while in operation: 0-+ 50'C through a low-pass filter. The meter response switch
Relative humidity: 0-90% (SK101) can be u ed to se\ect a time eonstant that pro-
Vibration test: As per IEC 68 vides a fast or slow response.
Shock test Example:(7.5IlSv/h at the detector)
Moisture and temperature test: Alarm-level measurement carried out using one detector
of type Q 4700/5 with the meter response switch at the
3:4 Output signals fast-response position provides an alarm response time of
about 3.5 s. If additional detectors are used, the alarm re-
pon e time will be shorter.
mA-output:
Galvanically isolated from ground.Provides 4-20 mA
output depending upon level (0-100 %). Max load is
470 ohms.

High-Ievel alarm:
Relay signal can be adju ted to issue an alarm bctween
70-100 % of full-seale deflection.

ro 4700/2 - - - -l ,,;--------,
104700/2 I
1 RE 201,202,203 1 RE 201,202,2031
1
I I I I
I 1 oto I I oto
I
L__ _
1
J D::2
o . o
I
L___
I
J ~
o . o
C
NO C NG
!
NO NG
I

"fl
220Jl.
1 W lOOALL~
lw
11-
0,22 uF
I
(1000 Vl "" (500 v) ""

Mains supply 220 V AC Mains supply 110 V AC

Fig. 6. Relays used for high-levet and low-levcl alarms. and performance mottitoring.

5
3:6 Sensitivity 3:10 Connections

The maximum sensitivity for a Q 4700/5 detector is about The mains voltage and relay signals are connected via
0.2pSv/h for alarm-level measurement. If additional de- terminal board BU202 (12 terminals). Max cable area is
teetors are connected, the sensitivity is even higher. The 2.5 mrn-.
natural (background) radiation is about 0.1 pSv/h and
this limits the possibilities of working at higher sensitivit- The other inputs and outputs are connected via terminal
res. board BU201 (20 terminals). Max cable area is 4 mm".

3:7 Maximum cable length A maximum of four detectors can be connected to each
detector-input section on BU201, since these sections are
connected in paralleI.
To make certain that PFM transmission is not disturbed,
the total cable capacitance must not exceed 68 000 pF.
When the standard Philips cable (240 pF/m) is used, the
total cable length can thus be 280 m. If a low-capacity
coaxial cable (68 pF/m) is used for the signal sent out
from the detector, the cable can be as long as 1 000 m.

3:8 Temperature drift

Measured at the 4-20 mA output with steady-state input


pulse frequency.
Max ±0.05% re, typical ±0.02 %/C·.

3:9 Casing

Q 4700/3-Sheet metal casing with grey enamel finish,


tightness as per IP65.
~ 4766/ 4 ~Reet fHctal ful I ack: mouoLing. Clttörnauzed
sheet s~.

Fig. 7. Ca ing, type 4700/3

6
4. TECHNICAL DATA, DETECTORS
Types Q 4700/5 and Q 4700/9

4:1 Supply voltage 4:7 Temperature drift

+15 V DC, +10-20%, galvanically isolated from Pulse frequency drift at steady-state dose rate:
ground, max 15 mA. Max ± 0.02%I·C
Typical value <0.01%I·C
4:2 Electrical safety provisions
4:8 Detector cable, type Q 4700/"7
As set forth for IEC 348, dass I.
This 4-conductor, 0.22 mm? cable is provided with
4:3 Environment a 0.75 mm? shield and black plastic sheathing having an
outside diameter of 7 mm. The standard lengths are 5 and
Ambient temperature 10 m. Maximum capacity between conductors is 240 pF 1
wbile in operation: -40·C-+70·C m. The circular ö-socker connector complies with MILC-
Relative humidity: 0-95% 26482-1. Gold-plated sockets are of the bayonet type.
Vibration test: As per IEC68
Shocktest: " " " u

Moisture and temperature test:

4:4 Output signals

PFM-output:
Galvanicallyisolated from ground. Pulse duration of 12±
2 ps, amplitude of 10 mA.

Error signal:
Performance monitoring, normally at +14 V. EITor indi-
cation provides +6.5 V output signal.

4:5 Connectors

Circular, ö-pin chassis connector as per MILC- 26482-l.


Gold-plated pins of bayonet type.

4:6 Casing

Stainless steel casing with anodized, chromatized alumi-


nium insert which withstands long-term exposure to se-
vere environments.
Tightness as per IP67.

7
5. INST ALLATION
READ THROUGH THE SAFETV REGULATIONS BEFORE INSTALLING
THE EOUIPMENT

5:1 General

It is very important to have the source unit installed by


personnel who have acquired the neces ary knowledge
about radioactive material. These personnel must be
equipped with instruments that can measure the radiation

D
dose rate. However, no restrictions are imposed for com-
ponents other than the source unit.

Before the equipment is put into operation, the installa-


tion must be checked by the responsible overseer.

If any doubt should arise in connection with the relative


• •
positions of the radiation sources and the detectors, ask Fig. 10 Retainer p/a te.
your supplier for information. The relative positions can
vary, depending upon the diameter of the vessel and the If the vessel is insulated, it may be necessary to provide
typ e of radiation shield being used. spacers between the retainer plate and the vessel wall. See
Fig. 11.
5:2 Radiation source unit
Vessel wall
Make certain that the radiation beam is turned off and
locked before commencing installation.
Retainer plate
You must see to it that the source unit is not mounted in
such away that it can be obstructed by a concealed struc-
tural beam or anything else that can significantly block the
radiation.

Spacer

Insulation

I-beam

<! ~ -O- Signal

(!- O ~ O- No signal
Fig. 11.lnsu/ated vesse/ with spacers between theretainer
p/ate and the vesse/ wall.
~- ---- -O- Signal
~~t:1 If it is possible to insert your hand (for example) between
the front of the radiation source unit and the wall of the
vessel, a safety guard that will prevent this must be mount-
ed. It can be made of sheet steel, sheet aluminium or the
Fig. 9. Check to see that radiation is not b/ock ed by beam like. See Fig. 12.
or other parts of the vessel.

All types of source units are provided with holes for


mounting bolts. All types have four holes in the front pan-
el, while the large types also have a baseplate provided
with retainer holes. See the dimension drawings. A retain-
er plate with mating holes and an opening for the radia-
tion beam (see Fig. 10) must be welded or secured in some
other way to the vessel wall.

Fig. 12. Safety guard between the radiation source and the
vessel wall.

8
Sometimes it is necessary to be able to adjust the equip-
ment vertically in situations where production varies and
5:3 Detectors of type a 4700/5, alarm level
where there is som e uncertainty as to which working level The short detector is intended for alarm-level measure-
is best. Here, the radiation source unit shall be mounted ment. This detector is mounted horizontally on the oppo-
on slider bars. See Fig. 13. The detectors must also be ver- site side of the vessel and at the same height as the source
tically adjustable, and thus must be mounted on similar unit. If bot h a high level and low level alarm are to be issu-
bars. ed, one horizontal detector must be mounted at each
alarm leve!.

~ ------1

Fig. 13. Radiation source unit mounted on slider bars. Fig. 15. Higb-level and low-level alarm.

If, after installation, the radiation dose rate at the detector Stainless steel holder Q 4700/8 for this detector is pro-
i higher than 7.5 pSv Ih, a steel or lead plate can be mount- vided with two M8x25 mm bolts that are welded in place.
ed in front of the source unit. It is recommended that this See the dimension drawings. Two steel angles with holes
absorber plate be designed in the same way as the retainer for the aforesaid M8 bolts must be attached to the wall of
plate, but without any opening for the radiation beam. It the vessel. See Fig. 16. The holder can then be secured to
can then be inserted between the retainer plate and the the angles by means of nuts. The drainage hole in the hol-
source unit. See Fig. 14. der must be at the bottom.

Steel angla
7.5/Sv/h Detector
holder Q4700/8

v{~. :~:::~
-..;;;:::::::S
O$. •
~-=----=-=-r-·0..
--_

Absorber plate .

Fig. 14. An absorber plate can reduce the radiation do e


rate to an acceptable value.
Fig. l6. Detectot holder mounted on ves el wall by means
of steel angle.

The detector itself is then inserted in the holder from the


side and ecured by mean of a socket-head cap screw at
the bottom of the holder.

9
5:4 Detectors of type Q 4700/9
for continuous measurement

The long detector is intended for continuous levet mea- If a number of detectors are to be installed, the
surement. Frequently, a number of detectors and a num- Q 4700/10 holders must be mounted so that they overlap
ber of source units are used to provide full coverage of the each other. The top of the lower holder must be at the
measurement range in question. The detectors are same level as the lower retainer pin on the upper holder.
mounted vertically. See Fig. 18. The deteetor shall then be inserted into the
holder from beneath and seeured by means of a socket-
head cap serew on the holder.

Frequently, the detectors can be spread out. UsuaLly,they


can be mounted one metre apart, although the resolution
requirement is the determining factor.

5:5 flectronic unit


cg - ---
c:::;------
There are two versions of the eleetronic unit:
- A. Q 4700/1,2,3:

-
This unit is housed in a grey sheet
CK metal casing that is designed for
waLl-mounting, etc.
B. Q 4700/1,2,4: This unit is designed for mounting
in a 19" Eurorack.
Fig. 17. Continuous leve! measurement
--~ -
Oj;':::.
Stainless steel hold er Q 4700/10 is provided with two
M8x25 mm bolts that are welded in place. See the dimen-
..-
sion drawings. One U -shaped steel fitting must be secured
to the vessel wall for each M8 bolt. One of these U'-shaped
fittings can be used to secure two detector holders. Se Fig.
18.

Fig. 19. E!ectronic unit mounted in sheet meta! ca sing.

A. Wall-mounting version

~ The casing is delivered with four 22.5 mm cable glands. It


U-shaped
is possible to mount an additional five cable glands in the
Deteetor
I <--
steel fitting
I bottom of the casing. The casing has four retainer screw
holder Q4700/10 holes provided with neoprene rubber seais. See also the
dimension drawings.

L M6 serew or
12 wood se rew

Fig. 18. Detector holders mounted with U-shaped steel


fittings on the vessel waJJ. Fig. 20. Sea! for retainer screw bole in casing.

10
Caution!

-
Radioactive radiation.
Fig. 21. Electronie unit designed for mounting in 19"
Eurorack.

B. 19" Eurorack version

The front panel is 128.4 mm high and 141.9 mm wide, Fig. 22. Sign, type JR 1015, stating the regulations.
and the mounting depth is 230 mm. Hales for four M3 re-
tainer crews are provided in the corner of the front pan-
el. See also the dimension drawings.

5:6 Warning signs

A number of warning signs are delivered with the equip-


ment. The radiation shield itself i delivered with all of the Dangerous!
necessary signs already mounted.
Radiation!
The user must post two signs: one stating the regulations
that apply and one at the manhole.

The sign stating the regulations that apply must be posted Radiation source must be sh ut
close (about 1 m) to the radiation source unit. The name
of the responsible overseer must appear on thi sign. off before entering into vessel.
A manhole ign must be mounted at all manhole or
Responsible works manager.
openings where it is po sible for personnel to enter the
vessel in question.

Fig. 23. Sign, type JR 1016, at the manhale.

11
6. CONNECTIONS

6:1 Connection to the mains 6:4 Connecting the detectors

The ph ase line shall be connected to BU202: 1, and the Numerous detectors can be connected to the electronic
neutral line to BU202:2. The ground line must be con- unit. Terminal board BU201 has three parallel-connect-
nected to the threaded ground terminal on the casing. For ed sections, and the detectors can be distributed as desired
the rack-rnounted version, the ground line must be con- among these. The openings in this terminal board are
nected to the rack. large enough to permit four detector cables to be connect-
ed to each section.
6:2 Relayoutputs
Cable colour coding Terminal board
The relay outputs are to be connected to threaded termi- BU20l
nals 4-12 on terminal board Bu202. See Fig. 24. Informa-
tion about the permissible load is set forth in the technical Shield Shield 3,9, 15,
specifications. The relays used for high level and low level -IN 4, 10,16
pull in when an alarm is issued. The performance rnoni-
toring relay drops out. Blue +IN 5, 11,17
Green OV 6, 12,18
6: 3 4-20 mA outpur
Red Error 7, 13,19
This output is galvanically isolated from ground. The pos- Yellow + lSV 8, 14,20
itive lead shall be connected to BU201: 1 and the negative
lead to BU201:2. A ground connection must be provided NOTE: - IN and O Vare connected by ajumper on one of the
to eliminate disturbance voltages, either at the electronic aforesaid sectiotis to permit pulse transmission. Do not re-
unit or som e other connected unit. The maximum load is move this jumper.
470 ohms.

II I I
DDD
o ~ • MAINS SWlTa<
~;: SK201

OJ
O VLl
FINE-WIRE FUSE
230V/160mA

115V/315mA ~ ~ ~

1 I2 I 3 4 I 5 I 6 7 I 8 I 9 10 111 112 N
o
N
L N E C NO NC C NO NC C NO NC ::J
MAINS NORMAL LOW HIGH al
FUNCTION LIMIT LIMIT

20

+
4 - 20 mA
o
...J
a: > o
...J
>
a:
O >
o
...J
a:
O > s
UJ Z >
~ O
O
a: ~ UJ Z ~ O a: ~ UJ Z >
~ O a: ~
N
::J
CURRENT I a: + I + a: + I + a: + al
I + UJ
I UJ
I
UJ
LOOP C/) C/) C/)

DET-INPUT 1 DET-INPUT 2 DET-INPUT 3

o
....J
W
H

~
I
Fig. 24. Terminal boards in the electronic unit.

12
6:4 A Spi icing detector cables 6:4 B Extremely long detector cable

It is possible to splice a number of detector cables to- For distances longer than 280 m between the detector and
gether. It is also possible to connect them to a junction the electronic unit, the PFM signal (+ IN) must be carrie d
box. In such case, a common cable then runs from the via a coaxial cable (68 pF/m) as shown in Fig. 26. This
spLiceor junction box to the electronic unit. See Fig. 25. perrnits the distance to be increased to 1 000 m.

Detector No. l Electronic unit

Shield 1- - - - - - - - - - - - -,
Blue 1 I
1 1
Green I I
Red 1
'O ...> 1
1 .~ Z Z >
O o LO
•..
~
I

Yellow

1
1
s:
(/) I + w+ 1
1
I
1

-
1

\tJ
I

----'
Detector Nos. 2, 3, etc.
r
I
- - f-I--
- -.,
Shield 1 1
Blue I
1
Green
Red
1
I
I
1
Yellow I

,, I
1
-------
Junction box
l· 280 m ~I
Fig. 25. Joining detector cables via a junction box.

Electronic unit

1- -
1
I
- - - - - - - - - -
-. I
1
I I
"O I
1
1
.r:.
Q) z Z 1
1
I
1
(.fl I +. I
\t.q I
I

.'- - - ---
1 o
___ -'
I
I

Detector

Shield Coaxial cable ,


L..--I-~-.f'Ii.-
---..l \ f-
D

:_{-------l
Blue
Green
T
Red
Yellow
C=-} } Standard cable
----I

1..••• '-------1000 m ------.~I


Hg. 26. Connecting the detectots via a coaxial cabJes.

13
7. INITIAL ADJUSTMENTS

7:2 Adjustment for alarm function


Q4700 gamma level indicator PHILIPS
A Set the meter response switch to the fast position.
B Using the coarse switch, set the sensitivity to "0%
Adjust". This switch is normally set to position 4
for one or two alarm leveis.
C Using the fine potentiometer, adjust to obtain 0%
scale deflection.
D Increase the level in the vessel so that it covers the
O•••.• D.JU.T

COAA8E
_lIMAl. FUNCTION J radiation beam or tum off the beam.
E Adjust to 100% scale deflection by means of the
~:
• fiMI
F
"100% Adjust" potentiometer.
Set the alarm points for the high and low levels by
tuming the radiation beam on and off. The appro-
.•.... priate lamp will light up when the alarm point is
reached. Adjust the high level by means of the high
level adjust potentiometer to provide a scale de-
Fig. 27. Front panel of the electronic unit. flection of 70-100%. Adjust the low leve! by
means of the low leve! adjust potentiometer to pro-
vide a scale deflection of 20-40%.
7:1 General

Check to see that the level of the material in the vessel is 7:3 Adjustment for continuous measure-
be!ow the radiation beam. Measure the intensity of radia- ment
tion at the detector. It must not exceed 7.5 pSv/h. Select
a suitable time eonstant by means of the meter response A Set the meter response switch to the slow position.
switch. Normally, the fast position is used for alarm leve!
B Select a sensitivity of "0% Adjust" by means of the
measurement and the slow position for continuous mea-
coarse switch. Normally, this switch is set to posi-
surement.
tion 4 for 1-3 detectors of type Q 4700/9 and to
Set the sensitivity to "0% Adjust" by means of the coar e
position 5 for 2-12 of these detectors.
switch. The table that follows presents normal settings for
different combinations of detectors. C Using the fine potentiometer, adjust to 0% scale
deflection.
D Increase the level in the vessel so that it covers the
entire distance being measured or tum off the radi-
ation beams.
E Adjust to 100% scale deflection by means of the
"100% Adjust" potentiometer.

If alarm levels are desired within the continuously mea-


sured range, adjust as set forth in step F in section 7:2.

METER RESPONSE
FAST SLOW
Cuarsc switch
Po~.

l. Not uscd in normal operation Not used in normal operation


2. l detector 04700/5 l detector O 4700/5
very low inten ity low intensity
3. l detcctor O 4700/5 l - 3 detectors 04700/5
low intensity
4. 1-3 detectors O 4700/5 l - 3 detectors 04700/9
5. l - 3 detectors 4700/9 2 - 12 detectors 04700/9
6. 2 - 12 detectors 04700/9

14
8. CIRCUITRY DESCRIPTION

8:1 General

The level monitor includes one or more detectors which, Each GM-tube is driven via a voltage divider from a 450
via detector cables, are connected to the electronic unit. V supply that is regulated and temperature-compensated
unit. in order to minirnize the detector's temperature drift.

There are two versions of the electronic unit: High-impedance pulses having an amplitude of about 50
· Q 4700/1,2,3: Circuit boards mounted in a grey sheet Vand a duration of 200 ps are obtained from the centre
metal casing designed for wall-mounting etc. tap on the voltage divider.
· Q 4700/1,2,4: Circuit boards (Q 4700/1 and 2) de-
A pulse shaping circuit con verts the pulse duration to 10
signed for mounting in a 19" Eurorack.
ps and the amplitude to ab out 10 mA. This is done to
There are two versions of the detectors: adapt the pulses to the electronic unit input.
· Q 4700/5: Single detector with one GM-tube. Active
For each GM-tube, there is a performance monitoring
iength, approx 0.15 m.
circuit. This circuit also monitors the pulse output and the
· Q 4700/9: Dual detector with two Glvl-tubes. Active supply voltage.
length, approx 0.6 m.
The output signals and error signals from the different
GM-tubes are joined by means of WlRED OR circuits.
This arrangement permits a number of detectors to be
8:2 Detector block diagram
connected in parallei with out losing any information.
The detector contains one or two Geiger-Muller (GM)
tubes (CTl1 CT2) which, when exposed to ionizing radia-
tion provide pulses having a duration of approximately
200 ps. The frequency of the pulses is proportional to the
intensity of the radiation.

C8ble to
electronic
unit
+450 V +450 V +15 V
Power supply

Out (pulses)
Single Pulse shaping
detector
Error (Leve l)
CT 1 Error detection

T = 10 us
Additional ....n. 1
ci rcuits for Pu lse shaping

CT 2 Error detection

Fig. 28. Detector block diagram

15
8:3 Description. See diagram
4031 10042180, single/dual detector

Power supply Pulse shaping


OV och + IS Vare obtained from pins C and F in connec- The signal is obtained from the centre tap on voltage di-
tor BUl. Diode GR13 is used only in explosion-proof vider Rl/R2 or RIO/RIS. The level is 4S0 V. Capacitors
equipment. GR9 provides protection against reversed C1 and C8 block the DC component. R16 and R17 pull
pola rity and negative voltage transients. GR9 lowers the up the DC level to + 14 V. The negative SOV pulses are
drive voltage to about 14 V. C7 provides additional dis- clipped at -O.S V via the protective diodes that are in-
turbance suppression. cluded in IC1 and IC2. C12 and C11 eliminate disturb-
The 450 V drive voltage is generated by a switched DC- ances, thus preventing the flip-flops from being double-
DC converter of the flyback type. It is based on the free- triggered. The monostable flip-flops are given a pulse du-
running oscillator formed by three gates in IC3. When the ration of 10 us by R7 /C2 and R12/C9. R8 and R13limit
high (drive) volta ge is less than 4S0 V, this oscillator runs the output current to 10 mA when pin D on BU 1 (the out-
at about 2S kHz with a SO% duty cycle. The frequency is put pin) is loaded by the electronic unit s optocoupler. Di-
determined by C3 and R4. R3 proteets pins 1 and 2 from odes GR7 and GRll provide a WIRED OR circuit.
damaging input currents. The oscillator output (pin 4) When the output is high, the signal can pass through.
drives switch transistor TS2 (MOSFET). When the output is low, the diod e provides blocking so
that the pulses on the parallel channels are not shunted to
Transformer TRI receives +14 V via pin 2 and it is ground. Thanks to this arrangement numerous detectors
"charged" when pin 3 is short-circuited to ground via TS2 can be connected in paralIeI.
when its V GS is high.
Performance monitoring
When V GS goes low, TS2 is cut off and the transformer s The output pulses from pin 6 on IC2 trigger the next flip-
energy is "discharged" from terminal 4 via GR6 and GRS flop in the same circuit via pin 11. It is retriggerable with
across smoothing capacitor C6. a pulse duration of 10 (CS x R9). Since the pulses ob-
tained from the G M-tube have a frequency of l.S Hz even
Regulation When the output voltage is low, regulating in response to background radiation, the flip-flop (when
transistor TS 1 is cut off when its gate voltage en is functioning normally) will always provide a high
is lowered to OV by R6. When the peak va- level at the output. This level is equal to the supply vol-
lue ofthe voltage at TRI (4) reaches 4S0 V, tage.
the output voltage across TRI (3) becomes
great er than ISO V, whereupon current If the supply voltage drops beneath about 12 V or if pulses
flows through GR4 and GR3 and charges are missing for a period longer than 10 s, a lower potential
RC circuit R6-C4. TS 1 commences to con- is applied to pin 10, thus pulling down (via diode GR8)
duct (as a variable resistance) thus moving the leve! on pin E in connector BU 1 far enough to activate
the oscillator's DC level and frequency up- the electronic unit s performance alarm. If the Error sig-
wards. As a result, the output voltage is li- nals for other connected detectors have a higher voltage,
mited about to 4S0 V, regardless of the in- their serial diodes (corresponding to GR8) prevent the
put voltage. Error signal from providing any current. Regardless of
how many detectors are connected in paralle!, only one
Soft start Is provided by GR1 and RS. These prevent flip-flop has to go low to activate (via the WIRED OR cir-
the oscillator from oscillating when the in- cuit) the performance alarm.
put voltage is lower than S V.
IC1 functions in a similar manner.

16
8:4 Electronic unit block diagram

Board 2 Board 1 Board 2


JI-+----- .• 4-20 mA

0-100 Z
v
IN----11---1
u
- (from
Detee-
ror)
Error

f
-I o
High limit adj.
I __ --4, NO
I
I
I
O Z
adj.
[I J~:::,:~
1
I V
+
I I
low lillli
t adj.
1__ -
Meter
response
._-J
V
+ I
I
Hyst.
I -
IV
(t rom
I • NO

[I~~
Detee-
tor ) h.
V
ret
(V +27 V) +14,5 V -15 V I f tunet ion
C
+15
(to
vl
I
- - - - - - - - - - - -
+
V__

-.. S-
V -lV
+

I
l
I

tor ,
Det ee-
1
I
Power +15 V, 1 A
f'V supply
I -15 V, 1 A

Fig. 29. Schema tic circuit diagram.

Operation
Pulses from the connected detectors are sent to a frequcn- To obtain a "non-inverted' ignal, an offset is thus sub-
cy/voltage converter. Its sensitivity i controlled hy "O'X, tracted from the LP filters output ignal. This offset corre-
adjust" and "Meter response". The average frcquency of sponds to the maximum output voltage of the LP filter.
the detector pulses is proportional to the intensity of the The signal that i obtained then drives the pointer in the
radiation, but the tirnc-differcnce betwecn the pulscs is instrument, the currcnt output and the Schmitt triggers
randomly divided (Poisson division). As a rcsult, the F IV uscd for the high-levet and low-level alarms.
converter has high ripple, which is limited hy the low-pass
Pcrforrnance monitoring is carricd out by means of a corn-
(LP) filter that follows. The frequcncy limit of this filter is
parator, and it issucs an alarm if "Error" ~ V· + 27 V.
adapted to the selected sensitivity (0% adjust ). The out-
Since the Error signal never exceeds V+. the monitoring
put voltage from the LP filter is highest whcn the vessel is
system also checks to see that V+ does not drop bclow
crnpty and lowest when the vessel is full (lhus providing
+12 V.
maximum attenuation of thc radiation).
orrnally, "Error" is + 14V. Conscquently, V· must be
~ 12 V for the cornparator to change tatc.

17
8:5 Physical description
All of the electronic circuitry is mounted on two circuit F/V converter
boards. All connections proceed via the base board
Each pulse that arrives at the input (pin 4 on IC102) gives
(board 2). This board also contains the relay and linear
rise to an output pulse having a definite amplitude (ap-
power supply.
prox 14 V) and duration (R x C). The avcrage value ofthe
The other electronic circuitry, light-emitting diodes, DC at TP6 is thus proportional to the input frequency
pointer instrument, trimmer points and front panel are x RC, where C is determined by the meter response
mounted on the panel board (board 2). switch:
When this switch is at the slow position, C = 680 pF.
Board l and board 2 are connected via a 26-conductor
When this switch is at the fast position, C = 2.88 nF. R is
flat cable (double wires are used for each signal).
controlled by the "0% adj. coarse" switch which cuts in
R105 R106, ... RllO.
8:6 Board 2 (see diagram
lP filter
4031 10042060)
The circuit between TP6 and TP7 con sist s of an active
low-pass filter (LP filter) which has a variable frequency
Connections for the mains voltage and relay outputs are
limit fo and gain G. This filter con verts the irregular pulses
made on terminal boards BU202 (threaded terminals).
arriving at TP6 to a fluctuating DC at TP7. To make cer-
The 4- 20 mA current outputs and the detector inputs are
tain that the ripple is independent of the preset sensitivity ,
on BU201. The line fuse, designated YL1, shall be 160
fo is affected by both the gain in the V IF converter (0%
mA (slow-blow) for 230 Vand 315 mA (slow-blow) for
coarse) and the gain in the LP filter (0% fine).
115 V. You can change back and forth between a mains
voltage of 115 Vand 230 V by means of switch SK201. IC103 functions as an inverter, where:
The secondary voltage from TR201 is rectified in bridge G = R(OZ fine) + 68.1k where
GR201, and it charges smoothing capacitors C201 and 7.5k
C202 to about +23 Vand -23 V respectively. ± 15
Vand ± 0.6 Vare obtained after regulators IC201 and f O = ~2T=-'r(-;:;R7(
l O:::-:Z'--:-f-:-i
n-e""""')-+ -:60"8'::-k-:-)
-;C~( ~OZ;;--c-o-a-rs-e"7)
IC202 respectively. GR202 is in series with + 15 V (sent
to board 1) in order to prevent negative transients from RIl3 does not affect the gain since the input (pin 2 on
reaching board 1. (These negative transients are obtained IC103) has high impedance and no current flows through
when the detectors are connected.) The diode voltage the resistor. However, it proteets the input against over-
drop lowers the voltage to 14.5 V. currents that occur when the drive (supply) voltage is
turned off.
Each ofrelays 201 and 203 has one end ofits coil connect-
ed to + 15 V. Consequently, an inverted signal (-15 V) is
Offset
needed to pull in a relay (HINV, NFINV). Relay 202 is
pulled in by -15 Vand a positive signal (L). The signal at TP7 is "reversed", When instrument B101
shows 0%, the voltage is about -10 V. At 100%, the vol-
8:7 Board 1 (see diagram tage (U) is about O V. An inverter (pins 8, 9 and 10 on
IC104) is used to "unreverse" the signal. It has two addi-
4031 10042030).
tive inputs (R115 and Rl16) and the gain is 1. A voltage
Input obtained from VR102 (about 8.5-14.5 V) is added to in-
The input signal from the detector consists of 10 mA put R115 (-10 V to O V for O - 100%). This voltage is
pulses having duration s of 10 us. They are obtained via added across R116. The result is an "unreversed" signal
PFM+ and PFM-. Normally, PFM- is connected to O V. that is sent via TP8 (O to -10 V for 0- 100%). If VR102 is
set to its minimum resistance, + 14.5 V is obtained across
R383 reduces the effect of cable capacitance and disturb-
ances. The input current drives a light-emitting diode in R1l6.
optocoupler IClO 1. To increase the optocoupler's speed,
it is driven by +5 V via R103 and GR101, and it provides
a low output signal of max 0.7 V across R 102 and the base
ofTSlO1. The collector provides 15 V pulses having a du-
ration of 10 ~s (TP5). This triggers the F IV converter
(frequency /voltage converter).

18
o to -10 V at TP8 corresponds to an input voltage range at The ST input signal (TP8) isO VatO% and -10 Vat 100°/c
TP7 of -14.5 V. Since trimming to 100% can take place of full-seale deflection. The ST output (pin 14 on IC104)
at an input voltage of -4.5 V, a background radiation or normally provides -13.5 V. After changeover to the high
residual radiation corresponding to 30% of full deflection level, it provides -13.5 V, whereupon the emitter on
(0% at -14.5 V) can be trim med out. TS103 goes to 12.8 V. Re102 is pulled in via light-emitt-
ing diade GR107.
4-20 mA output
Pins 5, 6 and 7 on IC104 comprise an inverter in which Low limit indication
pins 5 and 6 are at O V. Pins 1,2 and 3 on IC104 form aSchmitt trigger (ST) that
. _ U(TP9) _ R123 is used for the low limit. VR104 can be used to vary the
Ga l n - U <TP8 ) - "'R-'-'l
2::":0'-/'"""'/-=-R
1:-:2::"71 working point between about 20% and 40%.
2.61k = 0.317
10k/4.64k Relative hysteresis = R129 (Swing~out)
R131+R132 (Swing-in)
The output (TP9) generates current via R110 and R123.
10 V in (TP8) provides an output current of With SK101 open (slow) the hysteresis is:

28.7k x 27 V x 100 Z = 10 1 Z
10 V x 0.317 = 16.0 mA 766k x 10 V •
215 ohmsl/2.61k
With SK 101 closed (fast) the hysteresis is: 20.2%.

The ST input signal is the same as that described in under


"High limit" , while the output signal is normally -13.5
OV provides 0.0 mA. Vand, after changeover to the low level, + 13.5 V. The
To provide 4-20 mA, an offset current is added via R122 emitter on TS 104 then goes to +12.8 Vand Re202 is
to -15 V, thus providing an output current of: puIled in via light-ernitting diode GR108.

Error indications
-15 V x 2.61k x (-1) = 3.95 mA
49.9k(215 ohmsI12.61k) The Error signal (TP15) normally has a potential of
V-+V (GR103)+VBE(TS105) = -15 V + 24 V + O.7V
= 9.7Y. Normally, a current of 0.6 mA is driven through
0-10 V at TP8 thus provides an output signal of 3.95- R 134, GR103 and thebaseofTS105. TSI05 has B= 100.
19.95 mA. Here, the deviation from the desired 4-20 mA When the transistor is operating under saturated condi-
is low compared with the galvanometer's deviation (dass tions, the collector current is = 25 mA. Consequently
2.5) and the resistance network's deviation (1 %). 0.25 mA is sufficient to cause the transistor to enter the
saturated state. During normal operation, Re203 is pulled
High limit indication in via light-ernitting diode GR109 and TS105.
Pins 12, 13 and 14 on IC104 form aSchmitt trigger (ST) All Error outputs in the detector and electronic unit are
based on a feedback network. YR 103 can be used to vary normally at + 14.5 V, but this does not increase the poten-
the working point of the Schmitt trigger between about tial at TP15 since every output is provided with serial-di-
60% and 100%. ode blocking ( ee GR102). When any Error output drops
beneath 9.0 V, it begins to draw current via the serial di-
Relative hysteresis = R124 (Swing-out) ade, whereupon GR103 is shunted out, TS105 is cut off,
R126 + R127 (Swing-in) light-ernitting diode GR109 goes out and Re203 drops
Swing-in is 10 V out.
Swing-out is V+ - V- - 2 V = 27 V
R 127 can be short-circuited by means of SK 10 1 when the
system is in the fast mode.

When SK101 is open, the hysteresis is:

lOk x 27 V x 100 Z = 6 3 Z
430k x 10 V •

When SK101 is closed, the hysteresis is: 12.6%.

19
9. FAUL T TRACING

9:1 General 9:4 Remedying a fault

Level monitor O 4700 is designed and constructed to The fastest and easiest way to remedya fauIt is to replace
meet very stringent quaiity requirements. Both the detec- the faulty unit.
tors and the electronic unit are provided with perform-
ance monitoring circuits that ensure highly reliable opera- The user can easily repair base board O 4700/2 by follow-
tion and facilitate fault tracing. ing the instructions set forth in section 8:6 (circuitry de-
scription ).
9:2 Simple fault tracing There is also a circuit description for panel board
O 4700/1 and detectors Q 4700/5 and 04700/9, butre-
A. If the electronic unit is "dead" , check fuse VL201. pairing these units is more difficult, and we thus recom-
B. If the green "normal function" indicator lamp has mend that they be sent to the Philips service centre.
gone out and its relay has dropped out, replace the
detector or detectors one at a time until the green
indicator lamp is lighted again.
C. If the equipment does not respond to level changes,
use a radiation monitor to check whether radiation
from the source unit is striking the detector.

9:3 Complete fault tracing

If a fault cannot be found using the simple fauIt tracing


measures set forth above, you can carry out more detailed
fault tracing using two flowcharts. The diagram in Fig. 30
is for faults that cause the green "normal function" indica-
tor lamp to go out and its relay to drop out. The diagram in
Fig. 31 is used in situations where the green "normal func-
tion" indicator lamp remains lighted but the equipment
still does not function properly.
In most cases, the panel indications suffice for fault trac-
ing. However, it will sometimes be necessary to remove
the panel in order to access the testpoints on the underly-
ing circuit board.
See separate drawings showing the locations of the test-
points on panel board O 4700/1 and base board
04700/2.
The detectors never have to be opened in order to trace
fauIts in the system.

20
)

Fault tracing, Q4700


- active oerformance alarm
Green lamp "Normal Function" NOT lighted

Opan circuit. Check all


cables and connections

~
\..J
~
! -C RePlace)
relay

~
g.
Yes
~
C"l
> ~( Replace detector
~.
c,
tv ~. No
~ Check connections to BU201.
~ Unscrew and remove front panel
~ (5 screwsl and test TP2 and TP3.
~ (TPl is grounded.l
...•
C"l

~.
].,
O- Replace
~
Il>
panel board
::J
@
Il>
~
~ Disconnect flat cable from
base board and test again

Replace or repair
base board
Fault tracing, Q4700 - inactive performance alarm
Green lamp "Normal Function" lighted

4-20 mA current loop 'Abnormal pointe Normal Function


is not
g
malfunctioning deflection
lighted
~CI:I
~
c::
CI:I

§
.Q
Replace green
~
Q..
LED <GR109l
or the
panel board
0-•..~
u
CI:I
No Yes Yes .E;
El
~ ~
bO ~
:6
bO
Yes
°5g
Yes Replace Re201j202
or the base board
No
-•..
~
::l

•..•..
Replace instrument ("')

No
Yes
Lt
1
(Wall-mounting version: Yes
Unscrew and remove the
screws in the bottom of
the casing and pull out
Replace panel board the electronic unitl.
Check that the instrument's
input impedance is 60 ohms.
During operation:
O mV ( Uinstr < 60 mV No
No
9:5 Replacing panel board 4700/1 9:6 Replacing base board Q 4700/2
Wall-mounting version: Wall-mounting version:

- Unscrew and rem ove the five countersunk retainer - Check to see that no external voltages are applied to the
screws that hold the panel and lift it off. unit.
- Unscrew and rem ove the two upper screws in the bot- - Disconnect all cables that are connected to terminal
tom frame and pivot out the entire electronic unit boards BU201 and BU202. Also disconnect the separ-
somewhat. ate ground line that runs from the base board and is
- Disconnect the flat cable connector from the base board connected to the casing.
and pull the panel board out and up. - Dismount the panel board as instructed in section 9:5.
- When you replace a panel board, it is important to low- - Unscrew and remove the two upper screws in the bot-
er it into the slots in the side panels. Then continue by tom frame if they are not already removed. Pivot out
performing the above steps in reverse sequence. and unhook the base board together with the bott om
frame.
Rack-mounting version: - Unscrew and remove the seven Philips (cross-slotted)

-. - Loosen the electronic unit from the rack and pull the
entire unit out somewhat.
screws from the long sides of the base board and lift out
the board.
To reassemble, perform the above steps in reverse se-
- Unscrew and remove the five countersunk retainer quence.
screws that hold the panel and lift off the panel.
- Disconnect the flat cable connector from the base board Rack-mounting version:
and pull the panel board out and up.
When you replace a panel board, it is important to lower it - Check to see that no externai voltages are applied to the
into the slots in the side panels. Then continue by per- uDit.
forming the above steps in reverse sequence. - Disconnect all cables that are connected to terminal
boards BU201 and BU202. Also disconnect the separ-
ate ground line running from the base board that is con-
nected to the chassis.
- Pull the entire unit out of the rack and disconnect the
flat cable connector.
- Unscrew and rem ove the seven Philips (cross-slotted)
screws from the long sides of the base board and lift out
the board.
To reassemble, perform the above steps in reverse sequ-
ence.

23
10. ABCs OF RADIOACTIVITY

All material is composed of atoms which, in tum, consist The number of radioactive disintegrations per unit of time
of a nucleus containing a number of positively charged in a given amount of radioactive matter is measured in
protons. The nucleus is surrounded by a cloud of nega- Becquerel (Bq). One Bq corresponds to one disintegra-
tively charged electrons, equal in number to the protons. tion per second. Previously, this was measured in Curies
The number of protons (or electrons ) is referred lo as the (C). Bach atom in the radiation source disintegrates only
atomic number of the material. Bach element has a differ- once, so that the activity decays (diminishes) with time.
ent atomic number, and they range from 1for hydrogen to The time required to reduce the radioactivity of
92 for uranium. a material to one-half is referred to as the half-life. Any
given source of radioactivity thus has a specific half-life.

+.
-.

O
Electron
Proton
Neutron
The half-life of radioisotopes varies from a fraction of
a seeond up to iliillions of years.

Another propert y of isotopes is the energy with which the


radioactive radiation is emitted.

888
The energy of nuclear radiation is express ed in electron-
volts, this unit being defined as the energy which one elec-
tron gains or loses on passing across a potential difference
of 1 V. It is equivalent to only 3.6 x 10-12 Watt-seconds.

Hl Hydrogen H
2
Deuterium H} Tritium Norrnally, alarger unit is used, namely the MeV (on e mil-
(radioactive) lion electron-volts).

Fig. 32. Isotopes of hydrogen The great er the energy ofthe radiation, the more penetra-
tive power it has.

The nucleus also contains a varying number of neutrons.


Bach neutron number corresponds to an isotope of the
element in question. Som e of these isotopes are unstable
and undergo disintegration, accompanied by the emission
of radioactive radiation.
(3
Radioactive material is composed of atoms which disin-
tegrate spontaneously and emit radiation regardless of
their environment. The radiation may be of three kinds: +
alpha, beta and gamma. The first two kinds consist of par-
ticles. Alpha rays consist of positively charged helium
nuclei, and beta rays consist of positive or negative elec-
trons. Gamma rays, which often occur together with the
other two kinds, are electromagnetic waves of short wave-
length and of the same nature as X-rays. Gamma radia-
tion possesses great penetrative power. Fig. 33. DefJection of alpha, beta and gamma rays in
an electric field.

24
The alpha and beta rays, both of which consist of particles, Gamma radiation is measured in Sieverts (Sv). A Sievert
have a range in air of several centimetres and several me- is a radiation dose measured in Gy multiplied by a special
tres respectively. However, such rays are completely ab- quaiity factor to obtain the equivalent dose in Sieverts.
sorbed by an aluminium sheet that is a few millimetres
thick (for example). Gamma rays, on the other hand, have The intensity of radiation, also called the dose rate, is
a considerably greater range and can penetrate even very measured in Sieverts per hour (Sv/h) or microsieverts
thick steel walls. hour (PSv/h). Previously, it was measured in Röntgens
per hour (R/h).

1 mR/h = 10 pSv/h.
Radiation intensity varies with the distance from the radi-
oactive ubstance and also depends upon the activity and
energy of the emitted radiation.

Note that the dose rate varies inversely with the square of

- the distance from the source. Doubling the distance will


thus reduce the dose rate to a quarter of its original value.

Thin 1-2 mm of About 10 cm


paper aluminium of iron

Hg. 34. Absorbtion of alpha, beta and gamma rays.


~-t-------
Dose
rate
An element that is normally inactive, such as cobalt, can 100
be made radioactive by neutron bombardment in a reac-
tor. Certain materials undergo fission in areactor, where-
by one heavy element is transmuted in to two light ele-
ments. Different kinds of isotopes, such as cesium 137,
are obtained from these fission products. Cobalt (Co-60)
and cesium (Cs-137) are the radioactive sources most
commonly used in level indicating equipment. When ra-
Ii 4
dioactive rays pass through a material, it is ionized to som e
extent.
Here, e\ectrons are separated from the atoms. It is possi-
ble to measure the dose rate, i.e. the amount of ionizing
radiation absorbed in an irradiated substance. The unit
used to measure an absorbed dose is the Grey (Gy).

16 ~ 8:// 4 2t% 1

k'
I>c

4
~ '~~--.--.--.-~==~=T==~~-
r- b•om
~
1
r
~
2'
7-
'2
~
"2
I 7
2 l 5
• Distance
I 10

~ ~ ~ ~
Hg. 36. The dose rate varies inversely as the square of
Hg. 35. The absorbtion of gamma rays is exponential the distance

25
The first table overleaf shows the dose rate at various dis- The tables shown below present the shielding capacity of
tances from an unshielded radioactive source. The dose three materials. The absorption is an exponential func-
rate is expressed in bot h new and old units. tion, so that two half-valne layers will reduce the dose rate
to a quarter, etc. The tables show the thicknesses in mm of
New units: the half-valne and tenth-value layers for som e common
shielding materials.
Distance from source lOcm Im 2m Sm 10m
Shielding thickness in mm
,uSv/h from 40 MBq C060 1350 I 13.5 I 3.4 I 0.54 I 0.14 Source
Lead Iron Concrete
.uSv/h from 40 MBqCSIJ7 350 I 3.5 I 0.9 I 0.14 I 0.04
S=2.4
S=11.6 S=7.8
Old units:
1/2 1/10 1/2 l/lO 1/2 1/H
--
Distance from source lOcm lm 2m Sm 10m C060 12 41 22 74 60 230
mR/h from l mC C060 135 I 1.35 I 0.34 10.054 10.0135
CSl37
mR/h from l mC CSl37 35 I 0.35 I 0.09 10.014 10.0035
6.5 21 17 57 53 180

It is c1ear from the above tables that the intensity is very S = density in kg/dm! or g/cm''.
great at points near the surface of a source. As a general
rule, it is necessary to shield the source with a material that
is capable of absorbing most of the radiation. Among the
available materials, lead is the most serviceable. Since it
has a high specific gravity, it is easy to work with. More-
over it is inexpensive.

26
)
==~----==------)I
)
)===----=-------------
~

"(")~ '"
199.00 o

•e is-is M' -- i
i g ~ !lo R c"~"
I

...a
15.00 •. •.
l l•.

r _ '.00 '''.00 ,0/, " - '00 ".00 I


...a
gfJ9~'3
~I o i.so '''00
~------~1~60~.0~0--------~


~L:t=, "m' _ L ' -
o ~:'m~w'o~:~~hJ
~~,'?""" ~
t Z-profile mm.
Z-profile flotten
~~LL O O
J
o ••., ('"

o ~o~s
o .\'j..\~G

N ~~

.
~ ~I'O",~S ~~.'"

I ~
j,--LJ-=~
~r- S' ~~O
-I~------
"'... .. ~ "
"

~ o
o
g
~ Q) ~ g
~
o ~
o
~
8
g

-
N

I •
(N'
o 000' 00 the
Clomp
'-"0"" "
under the clomp, due to

~ _ "" ~,.,"',. <O""""OO,~ ~


240.00 155.00 g ~ ((~~~~~~~~.;; •••~.d~
r-------- I ci
""00 I~ [l>-$)~ ~-~">=-;;:/---~===~ ~ ,

I I 200.00

II ~
POS
I
DENOMINACION II CHAPA ACERO F.~03
MATERIAL I T
-+- ~ l ,""""'".
Y.BUENO: . (
ned ~'""ra/u/os ,,,ru,,· . "'
''', L 7032
o'"~~"
ESCALA: 1/
4 I "'~""o
FECHA: 18/11/05 SUSnTUYE A' --- F .:

, L I I " ~L nMA REVISION: 06/04/06


,",,,rulO' ,~ .
~ -' -=
~ TOLERANC'AS GENERALES

'"T 'oo'"'~''" :' I , I ' I il/JOIv KGT 360x240x155 SEGUN NORMA ISO 2768 1

FECHA I NOMBRE! No I MODIFICACION I FECHA II NOMBRij FSPANA


~ X KGT3215 101 PLAN O NO:
1----- 141
- ----

N
W
O

i
I
I

~
r
I
~ ~

128
, 122
r l
,
I~' , 1__ - ___ .-: . I
L :~
-'
l....-

~
N
...,

II
II
II
II
II
O,
r-----'l
'__ r------~G
. , I--
J

Fig. 38. Q 4700/4 sheet meta! casing for reck-tnounting electronie unit.

28
475

l 200

* Drainage hole Mounting bolts

BEAM
t
DIRECTION

"* Hole in detector holder


must be at bottom

o 4700/8

Hg. 39. Detector bolder. short version.

850
IL.oo4._------ ------

230 600 20
2 pcs MS x 25
ACTlVE LENGTH 600 I

- - - - T -.,:- == -=--: = ~-=:: =- ':. = = = = = = == = = .:-~_---


Jll n
.•. - -
.•..•. , 1- ,
: r~
, ~----
11 _
"
~4 ,
____ J _'o-~ = = = =-=-=.-=~-_-_-:=-= _=_-::..-=-~-_-_-=
==- k ========--:-=--=--------~~-=-j
I

95

o 4700/10
Fig. 40. Detector holder, long version.

29
)

Four holes
Source

~
~
~

'a."
i:l:>
;;;;-
g.
::J
'"
O
.- ~. --tr~=;::MA RAY li\-~-Hr 01 °1
c-...
~
Lf)
~
r-
U1
N

W
O
..,
:::
(")
(1)

:::
e.
...,.
O

~r
.;::..
Vj

l~
Co
120
~ I I 165 150

215 l
--1

NaTE! The ON/OFF handle is shown at the OFF position.


It is ON when the green dots correspond.
Four holes
Sourcr - = 12

----11-+-.
- - - -
-GAMMA RAY-
- -
uu--

o
~
o
~
'"
N

10 120
165 150
215

NOTEI The ON/OFF hand le is shown at the OFF position.


It is ON when the green dots correspond.

Four holes
_ a 12
Sourct

10°
---+-I---GAMMA RAY- -- o o '"
~ '" N

<,
<,
<,
<, 120
<,
165 <, 150
.....
215 <,

NOTE! The ON/OFF handle is shown at the OFF position.


It is ON when the green dots correspond.

Fig. 42. Radiation source units Q 4621 (at top) and Q 46215.

31
Four holes

-j GAMMA RAY

--TaO

12
210 210

260

NOTE! The ON/OFF hand le is shown at the OFF posi.tion.


It is ON when the green dots correspond.

Four holes
~=1'

12
210 210

260

r~)TEI The ON/OFF handle is shown at the OFF position.


It is ON when the green dots correspond.

Hg. 43. Radiation source units Q 4583 (at top) and Q 45835.

32
Four holes
12 4 =14

l 8°
-----l;~, -- , --++-'----GAMMA RAY

--- , --------i -"f

120 60 200
220 245
315

NOTE! The ON/OFF handle is shown at the OFF position.


It is ON when the green dots correspond.

Four holes
12 II = 14
Sourc ~

- - - 5° o o ~
-----l;~, -- , --++-- GAMMARAY--- :::: ~ ""
--- ,--------1

120 60
220 245
315

NOTE! The ON/OFF handle is shown at the OFF position.


It is ON when the green dots correspond.

Hg, 44. Radiation source units Q 4584 (at top) and Q 45845.

33
Six holes
Source - __ ~ 10

r ,.,o'"'
-T-'-"+;- . --- .
---r
-Gamna ray

335

NOTEI The ON/OFF handle is shown at the OFF position.


It is ON when the green dots correspond.

Six holes
_ e 14
Source --_-.,. 10

- - - - - - SO· wi o o
Gamna ray· - •.. ...o ,.,'"'
••

13°

300
335

NOTEI The ON/OFF handle is shown at the OFF position.


It is ON when the green dots correspond.

Fig. 45. Radiation source unit Q 4610 (at top) and Q 46105.

34
12. COMPONENTS LIST

Panel board Q 4700/1

Item Description CataJogue Number

Resistors (1% 0.4 W MR 25)


R 101 383 ohms 2322 151 53831
R 102 681 ohm 232215156811
R 103, 104 1 kohm 2322 151 51002
R 105 1 Mohm 2322 151 51005
R 106 562 kohms 2322 151 55624
R 107 383 kohms 2322151 53834
R 108 90.9 kohms 232215159093
R 109 21.5 kohm 2322 151 52153
R 110 5.11 kohm 2322 151 55112
Rl11 1 Mohm 232215151005
R 112 7.50 kohms 232215157502
RI13 2.61 kohms 232215152612
R 114 68.1 kohms 2322 151 56813
R 115 28.7 kohms 2322 151 52873
R 116 117 28.7 kohms 2322 151 52873
R 118 10 kohms 2322 151 51003
R 119 215 kohms 232215152151
R 120 46.4 kohms 2322 151 54643
R 121 10 kohms 2322 151 51003
R 122 5.11 kohm 2322 151 55112
R 123 2.61 kohms 2322 151 52612
R 124 10 kohms 2322151 51003
R 125 2.7 kohms 2322 15152373
R 126,127 215 kohms 2322 15152154
R 128 14.7 kohms 2322151 51473
R 129 28.7 kohms 2322 151 52873
R 130 21.5 kohms 2322 151 52153
R 131, 132 383 kohms 2322 15153834
R 133 110 kohms 2322 151 51104
R 134 7.5 kohms 2322 151 57502
R 135 215 ohm 2322 151 1473
Trimmer pot (10% 0.5W)

YR 101 500 kohms 212236200735


YR 102, 103, 104 20 kohms 212236200147
Capacitors

C 101 Folie 2,20 nF 2,5% 2012326 10024


C 102 Folie 680 pF 1% 2222 431 86801
C 103 Elyt 10 pF 16Y 2222 122 25109
C 104 Elyt 10 pF 16Y 2222 122 25109
C 105 Elyt lO,uF 16 Y 2222 122 25109
C 106 Keramik 33 pF 2% 2222 679 10339
C 107 Elyt 100pF 25Y 2222 108 3610 l
C 108 Elyt 33 pF 63Y 2222 108 38339
C 109 Elyt 10 pF 16Y 2222 122 25109
C 110 Ely t 2,2,uF 25Y 2222 12226228
C 111 Ely t l /JF 40Y 2222 122 27108

35
Item Description CataJogue Number
Diodes
GR 101 Zener BZX79/C5Vl 9331 177 20701
GR 102 BAW62/75 933101220701
GR 103 Zener BZX79/C24 933117880701
GR 104 BAW62/75 933101220701
GR 105 BAW62/75 9331 01220701
GR 106 BAW62/75 933101220701
GR 107 Red LED 4031 11631950
GR 108 Red LED 4031 11631950
GR 109 Green LED 4031 10570880
Transistors and le
TS 101, 102 BC 337 933149200701
TS 103 BC 327 9331 491 80701
TS 104, 105 BC 337 9331492 00701
IC 101 Optocoupler CNY 1711 9334311 80701
IC 102 CMOS Hef 4538 BP 933507950701
IC 103 OP. LM 301 AN 933192320701
IC 104 OP. LM 324 N QUAD. 9334405 50701
Other
BU 101 Flat cable 4031 10042190
SK 101 Sliding switch 2422 126 01278
SK 102 Rotary switch 2419 13000058
B 101 Pointer instrument 4031 100 42170

Baseboard 4700/2

Item Description Catalogue Number


Capacitors
C 201 Electrolytic 2200 uF 40V 2222 033 17222
C 202 Electrolytic 330 uF 40V 2222 108 37331
Other
GR 201 Bridge SKB2/04L5A 2412 265 02079
GR 202 Diode BYV27/200 9335 526 80701
IC 201 IC-regulator MC 7815 CT 933470420701
IC 202 IC-regulator LM 7915 CT 9335 26740701
SK 201 Switch 115/230V 2422 12700162
VL 201 Fuse holder 2422088 00156
Insett 2422088 00157
Fuse 5x20 160mA Slow-blow 242208601008
RE 201,202,203 Re\ays 24V 2422 132 05885
TR 201 Line transformer 4031 10042150
BU 203 Flat cable connector 2432 022 19002

36
Detector Q 4700/5

Item Description Catalogue Number


Resistors (l % 0.4 W MR 25)
R 1, R 2 3.90 Mohms 5% 0.25 W 2322241 13395
R3 2.15 kohms 2322 151 52152
R 4, R 5, R 6 82.50 kohms 2322 151 58253
R7 10 kohms 2322151 51003
R8 1 kohm 232215151002
R 15, R 16 3.90 Mohms 5% 0.25 W 2322241 13395
Capacitors
C 1 Ceramic 330 pF 10% 500V 2013 554 03635
C 2 Ceramic 1 nF 10% 222263053102
C 3 Ceramic 220 pF 2% 2222679 58221
C 4 Ceramic 1,5 nF 10% 222263053152
C 5 Electrolytic 10 p..1F16V 2222 12225109
C 6 Plastic film 10 nF 10% 600V 222234461103
C 7 Electrolytic 10 uF 16V
I
2222 12225109
Diodes
GR 1 Zener BZX79/C3V3 933117670701
GR2 BAW62/75 933101220701
GR 3, GR 4 Zener BZX79/B75 933167080701
GR 5, GR6 BY5841500V 9336 123 20701
GR 7, GR 8, GR 9 BAW62/75 933101220701
Transistors and ICs
TS 1 FET BF256A 9331 905 20701
TS 2 MOS VN2406M 9337 270 70682
IC 2 C MOS HEF4538BP 933507950701
IC 3 C MOS 4011PC 9332764 10701
Other
TR 1 Transformer 4031 10042160
TR 5 Fuse 100 mA Slow-blow 2422 086 00436
CT GM-tube ZP 1210 9300 198 91394
BU 1 Connector PTO 2E-1O-6P 2422 026 03424

37
Detector Q 4700/9
Item Description CataJogue Number
Resistors 1 % 004 W MR 25
R 1, R 2 3.90 Mohms 5% 0.25 W 2322241 13395
R3 2.15 kohms 2322 151 52152
R 4, R 5, R 6 82.5 kohms 2322 151 58253
R7 10 kohms 2322 151 51003
R8 1kohm 2322 151 51002
R9 1 Mohm 2322 151 51005
RIO 3.90 Mohms 5% 0.25 W 2322241 13395
R 12 10 kohms 2322 151 51003
R13 1 kohm 2322 151 51002
R 14 1 Mohm 2322 151 51005
R 15, R 16, R17 3.90 Mohms 5% 0.25 W 2322241 13395

- C 1 Ceramic
Capacitors
330 pF 10% 500 V 2013 554 03635
C 2 Ceramic 1 nF 10% 222263053102
C 3 Ceramic 220 pF2% 2222 679 58221
C 4 Ceramic 1,5 nF 10% 222263053152
C 5 Electrolytic 10 pF 16 V 2222 12225109
C 6 Plastic film 10 nF 10% 600 V 2222 344 61103
C 7 Electrolytic 10 J.1F16 V 2222 122 25109
C 8 Ceramic 330 pF 10% 500 V 2013 55403635
C 9 Ceramic 1 nF 10% 222263053102
C 10 Electrolytic lOpF 16 V 2222 12225109
C 11, C12 Ceramic 47 pF 2222679 10479
Diodes
GR 1 Zener BZX79/C3V3 933117670701
GR2 BAW62/75 933101220701
GR 3, 4 Zener BZX79/B75 933167080701
- GR5,6
GR 7,8,9
GR 11, 12
BY 5851500 V
BAW62175
BAW62/75
9336 123 20701
933101220701
933101220701
Transistors and ICs
TS 1 FET BF 256 A 9331 905 20701
TS 2 MOS VN2406M 9337 270 70682
IC 1, 2 CMOS HEF 4538P 933507950701
IC 3 CMOS 4011 PC 9332764 10701
Other
TR 1 Transformer 4031 10042160
TR 5 Fuse 100 mA Slow-blow 2422 086 00436
CT 1, 2 GM-tube ZP 1220 930020001394
BU 1 Connector PT02E-10-6P 2422 026 03424

38
13. CIRCUIT DIAGRAMS

'""'

39
A B ( D E

FLAT (A8lE TO 80ARD 2


~I" +14.5V
+11,.5t~--.----.:....:...:::...:...::..:._-----------y----------

6 + 1 I, • 5'~}-o-5=------J
l BU10l
I
1
1--------- -------1
1 I
1
O~ ADJ.

±r
1
(OARSE
1 0$ ADJ. 1(IO'l
I1E7ER RESPONSE SlOW
1 FAS1 C:OARSE SK102~ 100U
1 tfoK1 '3
o ~rll(10
1 DIPS~I,P ~ '33U
I
t l 12 cre
1 O 13 ~I,OU
1 o.. O '~, r ~I(110
1 2.2U
(101
I
I 2.2N ~----------~~
l U-4
(102 21.5K
I
680P Rl10
I 0$ ADJ. FINE
I 5.111<

4
I
1
2
.n.
1(102 hRC
TP6
~ __ ~3 I-'~__~ Rl1

I
JL I J, R112 VR101
500K
68.

I 7.5K
I
I R113
I 2.611('
2 C>oo
L-----------'3::-i
0'/ + +
1=10US Rl01,
+14.5V ll1301
JlL'4V lK
OV
PF M+ )-0....;...,:1 8'-.--., L---~0~V-----r----;~TP5

PF 1'1 + )..o..-'-"-- --.:-_---+----, U05


6
10U-16V
S
l, 1(102

t1
PF 11-I}-o-:::...::....----<~+---+--' TS101 12
I 8(337
2 PFI1_1 21
I BU10l Rl02 4538
681
1
(103
1 GR10l
I 10U-16V
aZX"'9C5Vl
OV I )-o...6=____----,
I OV
ov IHr7~-J~~--~------------~--~----~-------r~--------~---
I 8Ul01
I 16
TP1~ (iRl0?
+ C1 04
EINVI~ BAW62
I ro--!2---J 10U-16'/ ;gI5~
E:NVI~-------------------------------
1
I.~8~----<~ __-~1~5V~ ~ _
-15VIH
I 9
-t5VI~'01
1

A B [ D
F H .J K

FLAT CABLE
BOARD 1 I
BOA~O 2
I
+14.5V 4 I +
I
OV ~119 lTP9 5 I
I +14. 5V 6
BU101
215 R122 -15V +14.5V I 4-20"A
I
R120 49.91<
22 I
R123
I
107 23 I
I (IL
[)OU-25V BU101
(108 lOK T5102 I
BU-63'1 B(337 I
(109 lM324 I 5
+15V
10U-16'/ I
RE
110 RESPONSE SLOW ~ TP2..+14.5V I
METER 201
.2U-25V FAST I
GR104
111 11<1 '1 I
BAW62
1!-40V Dl-lEVEL. O IPS'M4P 10 I
I H INV
R:PPLEI Rl27 ~TPllGR107
5-20~ 11 I
215K l' BU101 I
f-- R126 lPl0 HIGH
I
2151(13 1(10 II MI T
12 -[> 14 TS103 HIGH I 4
R124 (ENERGIZEO)
+ BC327 L IM IT I
lOK LM32'
100~
VR102 AOJ. 2
1 3
1(10 20K
23.7K VR103 14.7K
20K
6 HIGH LIMIT AOJ.
+ 60-100"- -15V +14.5V
11
OV 3
15104
lP8 METER RESPONSE SlOW BC337 LOW LOW
R115
28.71<
Rl17 J, ~Kl
FAST
II M: T L IMI T
'2 GR10S (ENERGIZEO)
28.71< OlPSW4P 12
9 1(104 R132
10 -[> 8 13
L
+ ~TP13 BU101
~11 GR105
lOK BAW62 2
RE
r- TP3.-15V
.. -15V
202

SA52 GR106
21.5K 110K
TP1 OV BAW62
S15 f- TP14 + 15V RE
OV NO~HAl
FUN(TION 203
R134 GR109
14
7.5K NFINV
ER~O~ GR103 TS10 '5
BZX79C24 B(337 215 BU1m NORMAL
-15V
FUNCTION
(ENERGIZEO)

Q4700jl BOARD 1 IiEVISION


04700 ANORING
(PART OF Q4700 ELECTRONIC UNITl 03 850520

OATE SIGN. SUPERS./ERS.


ORAWN 84-02-24 TOEO 4031 100 ~2030
(HECK. SH./ B~. 1
PREl. PHiliPS
FINAL E ~EKTRON IK INDUSTR IER AB
F G H K

Fig. 46. Electronie unit, PC board No. 1.


41
A B [ D E
y
BOA
8
c
(ONNE
6 TERMINAL BOARD BU202
TP

LIVE
, VL201
TR201
111
G
BU202 B
T160mA

"SV

230V
1
TP203 -7
2 2
NEUTRAL
BU202
791S

RE2013 HIGH +1SV

- '/~I
10
4 C }-<lBU202
HIGH
11
LIMIT NO }-<lBU202
12
NC }-<lBU202

RE2023 LOW
7

LO"
LIMIT
(: BU202
NO }-<l
:U202 '~I -1SV

N( BU202 OV
RE2033 NORMAL FUNCTION

:-J
I,
C I, S RE203
NORMAL BU202
5 =--
FUNCT ION NO}-<lBU202
6
N( 3
BU202 EARTH BU202
--------------------
2 3
TERMINAL BOARD BU201 SHIELD
BU201 1 ;
9 P1
8
BU201 OiASSIS GNO
BU201
, 1S
11, ,
TP+l SV BU201
BU201
20 +lSV
BU201
1 +1SV
+
4-20 BU201
MA 2
BU201

6
BU201
12
TPOV BU201
18 OV OV
BU201
O 111 W HEAT SINK 12 e/w
112 W HEAT SINK 20 e/w

A B [ D E
E F G H j K
I
80ARD2 : HAT CABLE
TO
BU203 I BOARDI
CABLE I
INNECTOR I
FLAT 6
" I
,+It..SV CABLE
...--=<:S>-{+ 14. SV TO
80ARD 2 BOARD l
GR202 I
l;> BYV27 I 8U201
SCREW ~
TP+lsV
I
TERMINAL
7
8U201
8U203
CA8LE
CONNECTOR
I
_~IOV
ERROR')-O--::-'8U"--:2:--::0...,.,
13 ....•--- ~'6 I EINV 5
~OV
I ~~19~~~E_R_R_0_R ~~1~7~EINV
, BU201 I
~1-lsV

I
I
+--+-41 99- _ l 5 V
>-"'-(>-{,
5 I -
TP 'I I
I ~~201
~PF-P1.
I 8U201
17 PFM INPUT +
+ : ~PFI1+
- ~rINV 8U201 I

I
IN
1,,_ , H I NV I
I
I
I
I : ~U201
10
~PFP1-
2 IL 8U201
16 PFH INPUT -
- {;: 13 ~PFP1-
8U201 I
L
I
I
I
I
I
I 3
-vsv I
I
- I
I
-
t: 15
NFINV
4
I
NF I NV
I
I
f--

I
I 2
I
I
I
I
I
I
- I
I

~IUL

123 'UL

-
CIRCUIT DIAGRAM ~VISION
ANDRING
04700/2. MAIN UNIT. BOARD 2 850520

DATE
I SIGN. SUPERS./ERS. o
DRAWN 84-03-06 TOED
SH./8L. 1
4031 100 42060t-+_-+-I
CHECK.
PREL. PHILIPS
FINAL ELEKTRON I K I NDUSTR I ER AB I I I A3
I 1\ F I G I H I j I K

Fig. 47. Electronie unit. PC board No. 2.


42
A B c o E

CHASSIS PCB
H.V. POWER SUPPLY
6
+14'1

GR2

401 l 401 l
GRl
BZX7ge3V3 RS
82.SK
(SOFT START) 401 l
OV 0'1
4 +4S0V

R7
lOK

1(2

R8
l K

+ l
3
- l 0'1
+14'1
eOUNTER
TUBE
-,- I

I +4S0V
NO l I
RlO
TPS ....• R12
I
(erl )
I 3.9M lOK
2 I
I
1(1
I
IH3
I
I 1K
I
el l
47P
0'1
+14'1

eOUNTER
TUBE
NO 2 OUTPUT PULSE (IR(UIT ERI
(eT2)

OV +14'1
lel PIN8 PIN16
o SUPPLIES:
1(2 PIN8 PIN16
1(3 PIN7 PIN14

A B c o E
F G H j K

PCB CHASSIS

eONDUCTORS BUl
G~r3 G~r4 >-----I> + l4V
BZX79B75 BZX79B75 TRl 2
r-=-
o
TP1\,G~9 ~
VL1 ..;.. F +15V 1
FCItL c IRCULAR
"" '----J
BAW62 100mAT I
OV C~ 6-POLE
1
~
• 1 , CHASS IS 5
OUT D M•..
~ 1!O11 ~ ±.P I --- CONNECTOR
H.V.XFMR -~ I ERROR
~~M 10U-16V ,E R:'d.. (P INS)
I
+450V
1 C6
~~5
BY584
N BY584
N
G~6

~OV
I
I
I
I
11ON~600V ov I C
.4.

'I 4
TP3 ~G~7 OUT I D
v
R9 BAW62 I
11+ C5 I
II 10U-16V I 1'i1 I
I
15 14 IC2 I

-tt<~1
11
--"-
EJ .Il

910 I
p2-r TP4".. G,~8
....-
----
ERROR
~
I
I E
3
BAW62
I
~R 4538 I --
I CASE
- - - - - - - -- - 1- - -- -

TP6 ~G~11
BAW62
11+ el O 3.!! ADDITIONAL COMPONENTS
II 10U-16V l 1M
+14V
2

l 2 ICl FOR DUAL DETECTOR PCB


.Il

~~15
'--'-
EJ ~
76 I TP7"..GR] 2
~

r R
4538
BAW62

ERROR DET. CIRCUIT

04700 04700 GAMMA LEVEL INDICATOR


04700/9 DUAL DETECTOR PCB
04700/5 SINGLE DETECTOR PCB
~---'~D7AT~E~--r.S~I~G~N-.~S~U~PE~RvS~.~f~ER"S~.--~----------------------~~~~~~O
DRAWN
CHECK.
840213 TOED
SH. f BL . 1
4031 100 42180PT~~
PREL. PHILIPS
FINAL ELEKTRONIKINDUSTRIER AB
F G H K

Fig. 48. PC boards: gamma level indicetor, dual detector and single detector.
43
Fig. 49. Testpoints in Q 4700, PC board No. 1.

44
--
~ , I
-O !

~+
.... -! 1,,-
I

~~fl
+

I
!

~r.l
:
n
~I e
~' e,
~// ~ ~
i I
V'1 , I
< !
L--I _.1 ,
I
I
+ ~
~.I· I
I

~~
,

I
III
I
~y!
i
I I

I'
, '

•.. _-- ..
l,
-- - -- ---------- - -- ---

I ,
I
~L '
~ I

l i~ ~
I~
i ~
< -~ =v lB
JI~ 0,1: 1 I~

Li"
LJI

r
?Jev lse ~ T

1 ~ I
;
i
I
N E I C NO NC C NO
NC I C
NO
I L MPINS NORMPL LOiJ HIGH

i I FUNCTlON LIMIT i LIMIT

1 ~ I~

! I I i I 1 l i l l l

, ,
I <4-20 +MP-
lfl
I
iTI
I

Z
+ IS)
< mi
::tl -+
::tl(J\
lfl
I
iTI Z
+ IS)
< mi
::tl -+
::tl (J\
lfl
I
iTI Z
+ IS)
< mi
::tl -+
::tl (J\
r o < r o < r O <
::tl ::tl o ::tl
O o
(URREN
LOOP DET. -INPUT I DE T. -INPUT 2 DE T. -INPUT 3

Hg_ 50. Testpoints in Q 4700, re board No_ 2 (besebosrd].

45
GF?9

-l~
...J

>
~

el Vy"Ä'
,I-
1\
!c.c hl!
~
~ TB l., tJ~ rJLJ
-
"
f:(

--'
~ ~
~ ~!)

CIJ
'01
~' 5~
l-
~ ~

'------'
I- l
7
.--J
n
•••
.
1'-"1 I
I

I
I

.
~-J
TRI

: -........--.
c=J
c:rc;
\

)
!
(
~
Qe
!'JIJ.
i
il
Il

R2
I
I

Single detector PCS 4031 100 42120-03


Enkel detektor kretskort 4031 100 42120-03

GR9

- ... ,
V y..tt
~~

, A"
-
~"-
r' ...,
C5
IS'

•...~./
~

~
ru
9
~
r-
l-

--'
le

-
lo!
u
"'!
r-
I
li',S3
,
TB ..,~~

r
I- ~oO
::;
c.
~
I
TRI

'ud
[ITJ
(
I
<R6
.R5
GO
Fhe
I
)I
II

Re
G
I
!
!

Dual detector PCB 4031 100 42130-03


Dubbel detektor kretskort 4031 100 42130-03

Fig. 51. Detector re boards: Q 4700/5 (at top) and Q 4700/9.


46

You might also like