Professional Documents
Culture Documents
Software Release
After downloading:
Find the Programmer installation file in C:\4100ESProg
Find the BIN files in C:\4100ubin\Rev3-07-01
Find the documentation in C:\4100ESinfo
To Install the Programmer go to C:\4100ESProg and double click on ESProgrammer_3.07.01.exe
1
ES Programmer 3.07.01
DBF Revision = 177
Functional Changes
This version supports NXNA Horn Strobe Ceiling Mount Devices and Advanced Earth Fault Diagnostic
Feature
Fixed Defects:
788334 Copy and paste of NXNA point broken in Point Editing tab
788282 Unable to perform Remote Download via BNIC using 3.01 and later programmers if mDNS is
disabled or target is on different subnet.
793909 Program memory checksum error occurs with DACT with External IDNAC REPEATER Point
800016 Binary S-Record job file is built incorrectly
803711 Copy/Paste is broken for NXNA point on the ESS
Other Changes:
793160 3000-Point 4100ES support
796016 No warning is shown when you configure a switch to an unassociated VNAC
Fixed Defects
793880 Panel may incorrectly report "will alarm" when enabling AMZ device from external node
793879 AMZ points are on the install mode list at the NDU but not at the owning node or TSW
796035 the Heat sensitivity threshold shown on front panel is invalid in centigrade format
793177 Strobe and Relay appliances of an SV do not operate independently
Other Changes
None
Usage Notes
Revision 3.07 of the ESSupport tools should be used with this release.
Requires revision 2.02.02 or greater of CPU Bootloader.
Requires InfoAlarm revision 1.04 and InfoAlarm Bootloader revision 1.04.
Requires EPS revision 1.05.03 or later
2
EPS_1.06.bin
ESS_1.06.bin
Functional Changes
This is the first version that supports Ceiling Mount Devices and Advanced Earth Fault Diagnostic
Feature.
Fixed Defects
751875 Wrong EPS trouble LEDs indication after removal of earth fault on IDNAC
788332 EPS LED does not display any errors when the earth fault is removed even if missing devices
troubles exist
791715 EPS 1.05.03 when IDNAC Channel is only programmed with MTAA (CM A/V) device, going to
Alarm won't activate these MTAA (CM A/V) devices
793177 Strobe and Relay appliances of an SV do not operate independently
Other Changes
Should be used with ES programmer/ Master 3.07 or higher to use Ceiling Mount devices and Advanced
Fault Diagnostic Feature.
TIC2_1.01.02.bin
Functional Changes
None
Fixed Defects
796009 Cannot clear the Primary receive trouble on the DARIC card.
Other Changes
None