You are on page 1of 3

TYCO Fire Protection Products Technical Support

October 15, 2016

Software Release

Product: 4100ES, 4010ES


Programmer: ESProgrammer_3.05.exe
Executive: ES_3.05.bin
Slaves included: 4010idnetplus_3.12.10
(new files in bold) Amp_20203 (cards 566-205, -206, -208 use with > 28 speakers/circuit)
Amp_2.03.03 (cards 566-205, -206, -208 use with up to 28 speakers/circuit)
Amp2_3.02.05 (cards 566-521, -523, -524)
AudAna_20101
AudDig_10502 (card 566-033)
AudDig2_20102 (card 566-409)
BMUX_10102
BNIC_1.01.02
CPUBoot_2.02.02
EBOOT_1.01.03
EOS_1.01.02
EPS_1.05.02
ESS_1.05.02
FUI_1.05
FUIBoot_104
idnet_3.12.10
idnet1plus_3.12.10
idnet2_1.03
idnetplus_3.12.10
LMC_3.01.01
MSS_31208
mssi_3.12.10
mxdloop_2.01.03
Phone_1.04.01
RPS_31208
SPS_204 (for Rev E and earlier boards)
sps_3.12.10
TFXLoop_10103
TIC_3.01.01
TIC2_1.01.01
TPS_1.05.05
XALIC_10105
XBC_10604
XPS_31208
XSIG_101

Compatibility See SB11002 (in C:\4100ESINFO)

After downloading:
Find the Programmer installation file in C:\4100ESProg
Find the BIN files in C:\4100ubin\Rev3-05
Find the documentation in C:\4100ESinfo
To Install the Programmer go to C:\4100ESProg and double click on ESProgrammer_3.05.exe
ES Programmer 3.05
DBF Revision = 174

Functional Changes:
 This release is synchronized with the release of the AutoPulse Programmer (version 3.05).

Fixed Defects:
755204 4100ESI NDU jobs are missing the Network Interface and Repeater Cards as
selectable cards

Other Changes:
 None

4100/4010ES Executive 3.05


Functional Changes
 Add support for panel branding (no branding available for 4100ES)

Fixed Defects
 None

Other Changes
 None

Usage Notes
 Requires revision 2.02.02 or greater of CPU Bootloader.
 Revision 3.04.03 of the ESSupport tools should be used with this release.
 Requires EPS revision 1.05.02 or later
 Requires InfoAlarm revision 1.04 and InfoAlarm Bootloader revision 1.04.
FUI_1.05.bin

Functional Changes
 Added support for NXNA Symbolic Name (SIGx-y) direct point call up.

Fixed Defects
 None

Other Changes
 None

TIC2_1.01.01.bin

Functional Changes
 None

Fixed Defects
747704 TIC2 does not generate broadcast alarm message in local mode.

Other Changes
 None

You might also like