You are on page 1of 2

TYCO Fire Protection Products Technical Support

November 10, 2015

Software Release

Product: 4100ES, 4010ES


Programmer: ESProgrammer_3.03.exe
Executive: ES_3.03.bin
Slaves included: 4010idnetplus_3.12.10
(new files in bold) Amp_20203 (cards 566-205, -206, -208 use with > 28 speakers/circuit)
Amp_2.03.03 (cards 566-205, -206, -208 use with up to 28 speakers/circuit)
Amp2_3.02.05 (cards 566-521, -523, -524)
AudAna_20101
AudDig_10502 (card 566-033)
AudDig2_20102 (card 566-409)
BMUX_10102
BNIC_1.01.02
CPUBoot_2.02.02
EBOOT_1.01.03
EOS_1.01.02
EPS_1.05
ESS_1.04.01
FUI_104
FUIBoot_104
idnet_3.12.10
idnet1plus_3.12.10
idnet2_1.01.05
idnetplus_3.12.10
LMC_3.01.01
MSS_31208
mssi_3.12.10
MXDLoop_2.01.01
Phone_1.04.01
RPS_31208
SPS_204 (for Rev E and earlier boards)
sps_3.12.10
TFXLoop_10103
TIC_3.01.01
TPS_1.05.05
XALIC_10105
XBC_10604
XPS_31208
XSIG_101
Compatibility See SB11002 (in C:\4100ESINFO)

After downloading:
Find the Programmer installation file in C:\4100ESProg
Find the BIN files in C:\4100ubin\Rev3-03
Find the documentation in C:\4100ESinfo

To Install the Programmer go to C:\4100ESProg and double click on ESProgrammer_3.03.exe


ES Programmer 3.03
DBF Revision = 169

Functional Changes
 Added support for NXNA addressable speaker

Fixed Defects
 None

Other Changes
 None

4100/4010ES Executive 3.03


Functional Changes
 Added support for NXNA addressable speaker.

Fixed Defects
664851 Master crashes Error 97 invalid device type function when browsing All Points list backward
668621 "CSHOW" on an NXNA Addressable Speaker device via Teraterm command prompt returns
inconsistent label.
676794 Warm start clears self test trouble for speaker and led strobe devices

Other Changes
 None

Usage Notes
 Requires revision 2.02.02 or greater of CPU Bootloader.
 Revision 3.03 of the ESSupport tools should be used with this release.
 Requires InfoAlarm revision 1.04 and InfoAlarm Bootloader revision 1.04.
 Requires EPS Upgrade to version 1.05 or better

EPS_1.05

Functional Changes
 Added support for NXNA addressable speaker

Fixed Defects
621265 LED Strobes Devices does not flash or sound under Test Mode.
667835 The system did not exit the Manual Selftest by itself after eight hours.
678078 EPS does not handle multiple answer/bad answer detection properly during Device
configuration phase

Other Changes
 None