You are on page 1of 19

1.

2 VIEW EXAMPLE
*Now we have the next project and is a school building consisting of
three floors in addition to parking :

In the following information we need:

node Diameter fitting Length (feet) Fitting Total C factor


( inch) length length (gpm\inch-
(feet) (feet) psi)
1-2 1 E 11.81 3 14.81 120
2-3 1 T 5.91 5 10.91 120
3-6 1.5 T 12.2 8 20.2 120
6-11 2 T 12.2 2 22.2 120
11-12 2.5 2E3T 56.8 48 104.8 120
12-13 3 T 87.43 120 207.4 120
13-14 3 E3T 37.4 76 113.4 120
14-15 4 2T 9.84 59 68.84 120
15-16 4 E2T 11.81 50 61.81 120
16-17 4 ET 49.21 32 81.21 120

13
1.3 Distribution of sprinklers
*Now we have the next project and is a school building consisting of
three floors in addition to parking :

 Distribution for parking:

L=14.3m
W=48.7m
Area = 696.41𝑚

width:
.
- Number of Sprinklers = = = 12.17 =13 spr
.
- Distance between two sprinklers S = = 3.746
m
.
- Distance between sprinkler and wall = = = 1.87 𝑚

Length:

.
- Number of Sprinklers = = = 3.575 = 4𝑠𝑝𝑟
.
- Distance between two sprinklers S = = 3. 57m
.
- Distance between sprinkler and wall = = = 1.79 𝑚

14
 Distribution for second floor:

F2-R1

L=5.5m
W=6m
Area = 33𝑚

width:
- Number of Sprinklers = = = 1.5=2 spr
- Distance between two sprinklers S = =2m
- Distance between sprinkler and wall = = =1𝑚

Length:
.
- Number of Sprinklers = = = 1.3 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.38 𝑚

F2-R2

15
L=5.5m
W=5.5m
Area = 30.25𝑚

width:
.
- Number of Sprinklers = = = 1.38=2 spr
.
- Distance between two sprinklers S = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.375 𝑚

Length:

.
- Number of Sprinklers = = = 1.3 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.38 𝑚

F2-R3

Room number three the same with room number two .

F2-R4

L=5.5m
W=3.7m
Area =20.35 𝑚

width:
.
- Number of Sprinklers = = .925=1 spr
.
- Distance between two sprinklers S = = 3.7m
.
- Distance between sprinkler and wall = = = 1.85 𝑚

Length:

16
.
- Number of Sprinklers = = = 1.3 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.38 𝑚

F2-R5

The room number five the same with room number One .

F2-R6

The room number six the same with room number one.

F2-R7

L=5.5m
W=10.76m
Area = 59.18𝑚

width:
.
- Number of Sprinklers = = = 2.69=4 spr
.
- Distance between two sprinklers S = = 2.69 m
.
- Distance between sprinkler and wall = = = 1.34 𝑚

Length:

.
- Number of Sprinklers = = = 1.3 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.38 𝑚

F2-R8

17
The room number eight the same with room number two.

F2-R9

The room number nine the same with room number two.

F2-R10

The room number ten the same with room number two.

F2-R11

The room number eleven the same with room number five.

F2-R12

The room number twelve the same with room number five.

F2-R13

L=14.3m
W=7.75m
Area = 33𝑚

width:

.
- Number of Sprinklers = = = 1.9=2 spr
.
- Distance between two sprinklers S = = 3.875 m
.
- Distance between sprinkler and wall = = = 1.94 𝑚

Length:

18
.
- Number of Sprinklers = = = 3.57 = 4𝑠𝑝𝑟
.
- Distance between two sprinklers S = = = 3.57 m
.
- Distance between sprinkler and wall = = = 1.78 𝑚

19
Distribution for first floor :

F1-R1

L=5.5m
W=6m
Area = 33𝑚

width:
- Number of Sprinklers = = = 1.5 =2 spr
- Distance between two sprinkler S= = =3m
- Distance between sprinkler and wall = = = 1.5 𝑚

Length:

.
- Number of Sprinklers = = = 1.3 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.38 𝑚

20
F1-R2

L=5.5m
W=5.5m
Area = 30.25𝑚

width:
.
- Number of Sprinklers = = = 1.375 =2 spr
.
- Distance between two sprinklers S = = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.375 𝑚

Length:

.
- Number of Sprinklers = = = 1.375 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.375 𝑚

F1-R3

Room number three the same with room number two

F1-R4

L=5.5m
W=3.7m
Area = 20.35𝑚

width:
.
- Number of Sprinklers = = = 0.9256 =1 spr
.
- Distance between two sprinklers S = = = 3.7 m
.
- Distance between sprinkler and wall = = = 1.85 𝑚

21
Length:

.
- Number of Sprinklers = = = 1.3 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = = 2.75 m

.
- Distance between sprinkler and wall = = = 1.38 𝑚

F1-R5

Room number five the same with room number one

F1-R6

Room number six the same with room number one

F1-R7

L=5.5m
W=10.76m
Area = 59.18𝑚

width:

.
- Number of Sprinklers = = = 2.69 =4 spr
.
- Distance between two sprinklers S = = = 2.69m
.
- Distance between sprinkler and wall = = = 134 𝑚

Length:

.
- Number of Sprinklers = = = 1.3 = 2𝑠𝑝𝑟

22
.
- Distance between two sprinklers S = = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.38 𝑚

F1-R8

Room number eight the same with room number two

F1-R9

Room number nine the same with room number two

F1-R10

Room number ten the same with room number two

F1-R11

L=4.45m
W=4m
Area 17.8𝑚

width:

- Number of Sprinklers = = =1 spr


- Distance between two sprinklers S = = = 4m
- Distance between sprinkler and wall = = = 2𝑚

Length:

.
- Number of Sprinklers = = = 1.11 = 2𝑠𝑝𝑟

23
.
- Distance between two sprinklers S = = = 2.22 m
.
- Distance between sprinkler and wall = = = 1.125 𝑚

F1-R12

Room number twelve the same with room number one

F1-R13

Room number thirteen the same with room number one

F1-R14

L=5.15m
W=3.15m
Area= 16.2𝑚

Width

.
- Number of Sprinklers = = =0.787 =1 spr
.
- Distance between two sprinklers S = = = 3.15m
.
- Distance between sprinkler and wall = = = 1.58𝑚

Length

.
- Number of Sprinklers = = = 1.28 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = = 2.57 m
.
- Distance between sprinkler and wall = = = 1.285 𝑚

F1-R15

24
L=7m
W=7.75m
Area= 54.25𝑚

Width:

.
- Number of Sprinklers = = =1.93 =2 spr
.
- Distance between two sprinklers S = = = 3.875m
.
- Distance between sprinkler and wall = = = 1.93𝑚

Length:

- Number of Sprinklers = = = 1.75 = 2𝑠𝑝𝑟


- Distance between two sprinklers S = = = 3.5m
.
- Distance between sprinkler and wall = = = 1.75 𝑚

F1-R16

L=7.2m
W=7.64m
Area=55𝑚

width:

.
- Number of Sprinklers = = =1.91 =2 spr
.
- Distance between two sprinklers S = = = 3.82m
.
- Distance between sprinkler and wall = = = 1.91𝑚

Length:

.
- Number of Sprinklers = = = 1.8 = 2𝑠𝑝𝑟

25
.
- Distance between two sprinklers S = = = 3.6m
.
- Distance between sprinkler and wall = = = 1.8𝑚

 Distribution for Ground floor:


GF-R1

- L=5.5 m
- W=5m
- Area = 27.5 𝑚

width:
- Number of Sprinklers = = = 1.25 =2 spr
- Distance between two sprinklers S = = 2.5 m
.
- Distance between sprinkler and wall = = = 1. .25 𝑚

Length:

.
- Number of Sprinklers = = = 1.375 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.375 𝑚

26
GF-R2

- L=5.5m
- W=5.7m
- Area = 31.35 𝑚

width:
.
- Number of Sprinklers = = = 1.4 =2 spr
.
- Distance between two sprinklers S = = 2.85 m
.
- Distance between sprinkler and wall = = = 1. .425 𝑚

Length:

.
- Number of Sprinklers = = = 1.375 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = 2.75 m
.
Distance between sprinkler and wall = = = 1.375 𝑚

GF-R3

- L=5.5 m
- W=5.1m
- Area = 28.05 𝑚

width:
.
- Number of Sprinklers = = = 1.275 =2 spr
.
- Distance between two sprinklers S = = 2.55m
.
- Distance between sprinkler and wall = = = 1.275 𝑚

Length:

.
- Number of Sprinklers = = = 1.375 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = 2.75 m

27
.
- Distance between sprinkler and wall = = = 1.375 𝑚

GF-R4

- L=5.5 m
- W=3.7 m
- Area = 20.35 𝑚

width:
.
- Number of Sprinklers = = = 0 .925 =1 spr
.
- Distance between two sprinklers S = = 3.7m
.
- Distance between sprinkler and wall = = = 1.85 𝑚

Length:
.
- Number of Sprinklers = = = 1.375 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.375 𝑚

GF-R5

- L=5.5 m
- W=6 m
- Area = 33 𝑚

width:

- Number of Sprinklers = = = 1.5 =2 spr

28
- Distance between two sprinklers S = =3m

- Distance between sprinkler and wall = = = 1.5 𝑚

Length:
.
- Number of Sprinklers = = = 1.375 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.375 𝑚

GF-R6

Room number six the same with room number five

GF-R7

- L=14.3 m
- W=7.65 m
- Area = 108.68 𝑚

width:

- Number of Sprinklers = = .
= 1.912 =2 spr
.
- Distance between two sprinklers S = = 3.82m
.
- Distance between sprinkler and wall = = = 1.91 𝑚

Length:

29
.
- Number of Sprinklers = = = 3.57 = 4𝑠𝑝𝑟
.
- Distance between two sprinklers S = = 3.575 m

.
- Distance between sprinkler and wall = = = 1.78 𝑚

GF-R8

- L=5.5 m
- W=5.4m
- Area = 29.7 𝑚

width:
.
- Number of Sprinklers = = = 1.35 =2 spr
.
- Distance between two sprinklers S = = 2.7m
.
- Distance between sprinkler and wall = = = 1.35 𝑚

Length:

.
- Number of Sprinklers = = = 1.375 = 2𝑠𝑝𝑟
.
- Distance between two sprinklers S = = 2.75 m
.
- Distance between sprinkler and wall = = = 1.375 𝑚

GF-R9

Room number nine the same with room number eight

GF-R10

Room number ten the same with room number eight


GF-R11

Room number eleven the same with room number eight

GF-R12

30
Room number twelve the same with room number eight

GF-R13

Room number Thirteen the same with room number five

GF-R14

Room number fourteen the same with room number five

- GF-R15
- L=6 m
- W=3.15m
- Area = 18.9 𝑚

width:
.
- Number of Sprinklers = = = 0.78 =1 spr
.
- Distance between two sprinklers S = = 3.15m
.
- Distance between sprinkler and wall = = = 1.57 𝑚

Length:

- Number of Sprinklers = = = 1.5 = 2𝑠𝑝𝑟


- Distance between two sprinklers S = =3m
- Distance between sprinkler and wall = = = 1.5 𝑚

31

You might also like