EQUIPMENT DETAILS

CUSTOMER NAME Reliance Projects & Property Management Services Ltd


Smart Bazar S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
CUSTOMER ADDRESS

CUSTOMER CONTACT PERSON


PROJECT NAME Reliance Projects & Property Management Services Ltd
Smart Bazar S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
PROJECT ADDRESS

INSTALLER NAME Shree SVS Systems


INSTALLER ADDRESS Galaxy Apartment, Office NO. 01, 1st Floor, Katraj Kondhwa Road, Pune - 411048
INSTALLER CONTACT NUMBER 020-24378164
PROJECT AREA MANAGER Mr. Dastagir
CONTACT NUMBER 9923567507
MULTI VRV SYSTEM 1 - 122 HP
SR NO. MODEL NUMBER CAPACITY TYPE SERIAL NUMBER LOCATION
1 JRUN140LTE5 14 HP ODU 211PHVK001247
1st Floor Front Side AHU
2 JRUN140LTE5 14 HP ODU 210PHXB001450
Room
3 AHU-8800CFM 28 HP IDU 05-23PID00432-01
4 JRUN140LTE5 14 HP ODU 212PHLU004288
5 JRUN140LTE5 14 HP ODU 211PHVK004751 1st Floor Front Side
6 AHU-8800CFM 28 HP IDU 05-23PID00432-02
7 JRUV220LTE5 22 HP ODU 212PHUP003358
Ground Floor Pantry
8 AHU-6800CFM 22 HP IDU 05-23PID00433-03
9 JRUV220LTE5 22 HP ODU 210PHXB012706
Ground Floor AHU Room ODU
10 AHU-6800CFM 22 HP IDU 05-23PID00433-01
11 JRUV220LTE5 22 HP ODU 212PHAW003360
Ground Floor AHU Room ODU
12 AHU-6800CFM 22 HP IDU 05-23PID00433-02

Shree SVS Systems


Reliance Projects and Property
Management LG Electronics Prachi Bhosale
4th Floor, Regent Plaza Mall, Baner - Pashan Link Rd,Pune - 411045
LG Electronics India Pvt.Ltd.
Email:- cac.service@lgepartner.com
COMMERCIAL AIR-CONDITIONING DIVISION Tel :-020-41474100
Toll Free-1800-180-3575

ESCALATION CHART
Sr. No FROM Dealer MOBILE NO EMAIL ID

1 Mrs. Prachi Bhosale 9168320222 service@shreesvs.com

2 MR. KHUSHBOO ALI SHAIKH 8899972555 service@shreesvs.com

3 Mr. Sachin Salunke 9960166222 sachin.shreesvs@gmail.com

Sr. No FROM LGEIL MOBILE NO EMAIL ID


1 Mr. Santosh Gunjal 7262033341 santosh.gunjal@lgepartner.com

2 Mr. Rahul Kumar 7030972989 rahul09.kumar@lge.com

3 Mr. ABHIJEET NADKAR (Manager) 9823317015 abhijeet.nadkar@lge.com

FOR LG ELECTRONICS INDIA PVT. LTD. SHREE SVS SYSTEMS

(AUTHORISED SIGNATORY) ( AUTHORISED SIGNATORY)


HANDING OVER DOCUMENT
VRF AIRCONDITIONING SYSTEM FOR
Reliance Projects & Property Management Services
Smart Bazar S No 4781 Babasaheb Paranjape Marg,
Latur, Maharashtra 413512

HVAC WORK CARRIED OUT BY

LG ELECTRONICS (I) PVT. LTD.


4th Floor, Regent Plaza Mall
Baner - Pashan Link Rd,Pune - 411045

HVAC WORK EXECUTED BY

SHREE SVS SYSTEMS

Galaxy Apartment, Office NO. 01, 1st Floor.


Katraj Kondhwa Road, Pune - 411048
Cell: +91-9168320222

For Customer for LGEIL for Dealer

(Reliance Projects and Property) (LG Electronics (I) Pvt Ltd) (Shree SVS Systems)
Management Services
MULTI VRV PRE-START UP COMMISSIONING & HAND OVER REPORT
PROJECT CODE MULTI V-5 SYSTEM NO. 28 HP
LG ELECTRONICS INDIA PVT. LTD.
12th to 20th Floor Tower 1, KP tower, Plot No. C-001B, Sector 16B, Noida, Uttar Pradesh 201301
NAME COMPANY NAME & ADDRESS CONTACT DETAILS
Reliance Projects & Property Management Services Ltd
CUSTOMER DETAIL
PERSON IN CHARGE

Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512

Reliance Projects & Property Management Services Ltd


SITE ADDRESS
Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
SHREE SVS SYSTEMS
INSTALLATION DEALER SHREE SVS SYSTEM 9168320222
Galaxy Apartment, Office NO. 01, 1st Floor, Katraj Kondhwa Road, Pune - 411048

PROJECT AREA MANAGER SERVICE AREA MANGER PROJECT AREA HEAD


FOR LG ELECTRONICS AMIT KUNDRI DIPAK CHAUDHARI DILIP SUKHWANI
9820315489 9923403744 8291103825
TYPE MODEL NO CAPACITY DESCRIPTION QTY
PRODUCT

ODU JRUN140LTE5 14 HP Outdoor Unit 14 HP 1


ODU JRUN140LTE5 14 HP Outdoor Unit 14 HP 1
IDU AHU-8800CFM 28 HP Indoor Unit 28 HP 1

ITEMS RESULT CRITERION


MAIN SLAVE 1 SLAVE 2 SLAVE 6
PRODUCT SERIAL NO.
211PHVK001247 210PHXB001450
MAIN CABLE 6 6 ARMOURED SQ.MM X 4 CORE + EARTHING
WIRE SPECS BREAKER 40 40 AMPS IP65
TRANSMISSION CABLE 1.5 SHIELDED SQ.MM X 2 CORE
OUTDOOR UNIT SERVICE AREA OK EASILY ACCESIBLE
ADDITIONAL REF. AS PER LATS 10.5 KGS R-410 (DUPONT/HONEYWELL)
MASTER SLAVE 1 SLAVE 2 SLAVE 3
CONTROL BOX DIP SWITCH
ALL OFF 1 On
PRE START UP

POWER OK
WIRING TRANSMISSION OK
CENTRAL CONTROLLER OK AC EZ
PIPE SIZE @ HEADER SUCTION 34.9 LIQUID 15.88 MM HARD DRAWN
LEAKAGE TEST @ 550 PSIG MIN 24 HRS
VACUUMING 490 MICRONS 300-600
PIPING CONDITION OK
PIPING WORK PIPE & INSULATION
INSULATION SUCTION 19 LIQUID 19 MM SUCTION (19) ; LIQUID (13)
110 TOTAL PIPE LENGTH MTR MAX. 1000 MTR
PIPING LENGTH (AS PER
3 ELEVATION (ODU ~ IDU) MTR MAX. 110 MTR
LATS)
15 1ST Y BRANCH ~ IDU MTR MAX. 40 MTR
WIRE SPECS IDU POWER CABLE 2.5 FLEXIBLE SQ.MM X 3 CORE
TOTAL NO OF IDU 26 QTY
INDOOR UNIT TOTAL INDOOR UNIT CAPACITY 126.5 Tr KW/TR
REMOTE CONTROLLER WIRED/WIRELESS
DRAIN WORK OK TESTED
FOR COOLING OPERATION ONLY
ITEMS RESULT CRITERION
ALL INDOOR UNIT DISPLAY OK ON LGMV SCREEN
T PIPE IN (AVG TEMP) 10.28 °C 8°-15°C
EEV PULSE 300 PULSE 200-600 PULSE
INDOOR UNIT
AIR DISCHARGE OK FAN OPERATING
DRAIN WORK OK NO WATER LEAKAGE
REFRIGERANT NOISE NO NOISE NO REFRIGERANT NOISE
FREQUENCY M S1 S2 S6
START UP (LGMV)

INVERTER 1 82.31 82.31 82.31 82.31 Hz FREQUENCY (60-150 Hz)


INVERTER 2
DISCHARGE TEMP
COMPRESSOR INVERTER 1 77.39 77.39 77.39 77.39 °C TEMPERATURE (60°-100° C)
INVERTER 2
CURRENT
INVERTER 1 13.38 13.38 13.38 13.38 A CURRENT (11-30 A)
OUTDOOR UNIT INVERTER 2
HIGH PRESSURE 365.72 365.72 365.72 365.72 PSIG 300-450 PSIG
PRESSURE (PSIG)
LOW PRESSURE 116.33 116.33 116.33 116.33 PSIG 100-150 PSIG
R-Y 420 R-N 230
3Ø - 380-450 V
Y-B 420 Y-N 230
VOLTAGE (V) V 1Ø - 210-250 V
R-B 420 B-N 230
N-G - 0-2 V
N-G 0.1
AIR TEMP (°C) 35 MIN -5° C MAX 48° C
DEGREE OF SUPERHEAT SUCTION (SH) 5 °C 3°C - 10°C
MAIN EEV PULSE 1944 PULSE 1944 PULSE
SITE DETAIL

CAPACITY HP: 28 HP No OUTDOOR UNIT: 2 No INDOOR U: 1


TOTAL AREA (sqft) APPLICATION : RESIDENCE / COMMERCIAL
COMMISIONING DATE ( WARRANTY START DATE): 15.12.2023

WARRANTY EXPIRY DATE: 14.12.2024


SUGESSTIONS (IF ANY) :
CUSTOMER REMARKS :

THIS IS TO CERTIFY THAT LG HAS COMPLETED THE AIRCONDITIONING WORKS AT ABOVE ADDRESS IN ALL RESPECTS. FURTHER, THE SYSTEM IS RUNNING SATISFACTORILY AND HAS BEEN HANDEDOVER TO THE CUSTOMER/ USER FOR
BENEFICIAL USE. THE PERFORMANCE PARAMETERS OF A-C SYSTEM/S ARE RECORDED AND WITNESSED BY THE UNDERSIGNED. FOR ANY BREAKDOWN/ WARRANTY SERVICES, PLEASE CONTACT OUR DEALER OR UNDERSIGNED
PROJECT/SERVICE ENGINEER.

FOR CUSTOMER NAME DEALER NAME LGEIL AMIT KUNDRI

DATE 15.12.2023

Note:
- The 'Pre-Start up' & 'Start up Report' Should be filled in by a certified person in charge.
- Under LG confirmation, warranty period will start officially.
- Without report and confirmation, LG has no responsibility for guarantee.
I, the supervisor, take all the responsibilities for this start up.
MULTI VRV PRE-START UP COMMISSIONING & HAND OVER REPORT
PROJECT CODE MULTI V-5 SYSTEM NO. 28 HP
LG ELECTRONICS INDIA PVT. LTD.
12th to 20th Floor Tower 1, KP tower, Plot No. C-001B, Sector 16B, Noida, Uttar Pradesh 201301
NAME COMPANY NAME & ADDRESS CONTACT DETAILS
Reliance Projects & Property Management Services Ltd
PERSON IN CHARGE

CUSTOMER DETAIL
Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
Reliance Projects & Property Management Services Ltd
SITE ADDRESS
Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
SHREE SVS SYSTEMS

INSTALLATION DEALER SHREE SVS SYSTEM 9168320222


Galaxy Apartment, Office NO. 01, 1st Floor, Katraj Kondhwa Road, Pune - 411048

PROJECT AREA MANAGER SERVICE AREA MANGER PROJECT AREA HEAD


FOR LG ELECTRONICS AMIT KUNDRI DIPAK CHAUDHARI DILIP SUKHWANI
9820315489 9923403744 8291103825
TYPE MODEL NO CAPACITY DESCRIPTION QTY
PRODUCT

ODU JRUN140LTE5 14 HP Outdoor Unit 14 HP 1


ODU JRUN140LTE5 14 HP Outdoor Unit 14 HP 1
IDU AHU-8800CFM 28 HP Indoor Unit 28 HP 1

ITEMS RESULT CRITERION


MAIN SLAVE 1 SLAVE 2 SLAVE 6
PRODUCT SERIAL NO.
212PHLU004288 211PHVK004751
MAIN CABLE 6 6 ARMOURED SQ.MM X 4 CORE + EARTHING
WIRE SPECS BREAKER 40 40 AMPS IP65
TRANSMISSION CABLE 1.5 SHIELDED SQ.MM X 2 CORE
SERVICE AREA OK EASILY ACCESIBLE
OUTDOOR UNIT
ADDITIONAL REF. AS PER LATS 10.5 KGS R-410 (DUPONT/HONEYWELL)
MASTER SLAVE 1 SLAVE 2 SLAVE 3
CONTROL BOX DIP SWITCH
ALL OFF 1 On
PRE START UP

POWER OK
WIRING TRANSMISSION OK
CENTRAL CONTROLLER OK AC EZ
PIPE SIZE @ HEADER SUCTION 34.9 LIQUID 15.88 MM HARD DRAWN
LEAKAGE TEST @ 550 PSIG MIN 24 HRS
VACUUMING 490 MICRONS 300-600
PIPING CONDITION OK
PIPING WORK PIPE & INSULATION
INSULATION SUCTION 19 LIQUID 19 MM SUCTION (19) ; LIQUID (13)
110 TOTAL PIPE LENGTH MTR MAX. 1000 MTR
PIPING LENGTH (AS PER
3 ELEVATION (ODU ~ IDU) MTR MAX. 110 MTR
LATS)
15 1ST Y BRANCH ~ IDU MTR MAX. 40 MTR
WIRE SPECS IDU POWER CABLE 2.5 FLEXIBLE SQ.MM X 3 CORE
TOTAL NO OF IDU 26 QTY
INDOOR UNIT TOTAL INDOOR UNIT CAPACITY 126.5 Tr KW/TR
REMOTE CONTROLLER WIRED/WIRELESS
DRAIN WORK OK TESTED
FOR COOLING OPERATION ONLY
ITEMS RESULT CRITERION
ALL INDOOR UNIT DISPLAY OK ON LGMV SCREEN
T PIPE IN (AVG TEMP) 10.28 °C 8°-15°C
EEV PULSE 300 PULSE 200-600 PULSE
INDOOR UNIT
AIR DISCHARGE OK FAN OPERATING
DRAIN WORK OK NO WATER LEAKAGE
REFRIGERANT NOISE NO NOISE NO REFRIGERANT NOISE
FREQUENCY M S1 S2 S6
START UP (LGMV)

INVERTER 1 82.31 82.31 82.31 82.31 Hz FREQUENCY (60-150 Hz)


INVERTER 2
DISCHARGE TEMP
COMPRESSOR INVERTER 1 77.39 77.39 77.39 77.39 °C TEMPERATURE (60°-100° C)
INVERTER 2
CURRENT
INVERTER 1 13.38 13.38 13.38 13.38 A CURRENT (11-30 A)
INVERTER 2
OUTDOOR UNIT
HIGH PRESSURE 365.72 365.72 365.72 365.72 PSIG 300-450 PSIG
PRESSURE (PSIG)
LOW PRESSURE 116.33 116.33 116.33 116.33 PSIG 100-150 PSIG
R-Y 420 R-N 230
3Ø - 380-450 V
Y-B 420 Y-N 230
VOLTAGE (V) V 1Ø - 210-250 V
R-B 420 B-N 230
N-G - 0-2 V
N-G 0.1
AIR TEMP (°C) 35 MIN -5° C MAX 48° C
DEGREE OF SUPERHEAT SUCTION (SH) 5 °C 3°C - 10°C
SITE DETAIL

MAIN EEV PULSE 1944 PULSE 1944 PULSE


CAPACITY HP: 28 HP No OUTDOOR UNIT: 2 No INDOOR U: 1
TOTAL AREA (sqft) APPLICATION : RESIDENCE / COMMERCIAL
COMMISIONING DATE ( WARRANTY START DATE): 15.12.2023
WARRANTY EXPIRY DATE: 14.12.2024
SUGESSTIONS (IF ANY) :

CUSTOMER REMARKS :

THIS IS TO CERTIFY THAT LG HAS COMPLETED THE AIRCONDITIONING WORKS AT ABOVE ADDRESS IN ALL RESPECTS. FURTHER, THE SYSTEM IS RUNNING SATISFACTORILY AND HAS BEEN HANDEDOVER TO THE CUSTOMER/ USER FOR
BENEFICIAL USE. THE PERFORMANCE PARAMETERS OF A-C SYSTEM/S ARE RECORDED AND WITNESSED BY THE UNDERSIGNED. FOR ANY BREAKDOWN/ WARRANTY SERVICES, PLEASE CONTACT OUR DEALER OR UNDERSIGNED
PROJECT/SERVICE ENGINEER.

FOR CUSTOMER NAME DEALER NAME LGEIL AMIT KUNDRI

DATE 15.12.2023

Note:
- The 'Pre-Start up' & 'Start up Report' Should be filled in by a certified person in charge.
- Under LG confirmation, warranty period will start officially.
- Without report and confirmation, LG has no responsibility for guarantee.
I, the supervisor, take all the responsibilities for this start up.
MULTI VRV PRE-START UP COMMISSIONING & HAND OVER REPORT
PROJECT CODE MULTI V-5 SYSTEM NO. 22 HP
LG ELECTRONICS INDIA PVT. LTD.
12th to 20th Floor Tower 1, KP tower, Plot No. C-001B, Sector 16B, Noida, Uttar Pradesh 201301
NAME COMPANY NAME & ADDRESS CONTACT DETAILS
Reliance Projects & Property Management Services Ltd
PERSON IN CHARGE

CUSTOMER DETAIL
Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
Reliance Projects & Property Management Services Ltd
SITE ADDRESS
Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
SHREE SVS SYSTEMS

INSTALLATION DEALER SHREE SVS SYSTEM 9168320222


Galaxy Apartment, Office NO. 01, 1st Floor, Katraj Kondhwa Road, Pune - 411048

PROJECT AREA MANAGER SERVICE AREA MANGER PROJECT AREA HEAD


FOR LG ELECTRONICS AMIT KUNDRI DIPAK CHAUDHARI DILIP SUKHWANI
9820315489 9923403744 8291103825
TYPE MODEL NO CAPACITY DESCRIPTION QTY
PRODUCT

ODU JRUV220LTE5 22 HP Outdoor Unit 22 HP 1


IDU AHU-6800CFM 22 HP Indoor Unit 22 HP 1

ITEMS RESULT CRITERION


MAIN SLAVE 1 SLAVE 2 SLAVE 6
PRODUCT SERIAL NO.

MAIN CABLE 6 ARMOURED SQ.MM X 4 CORE + EARTHING


WIRE SPECS BREAKER 40 AMPS IP65
TRANSMISSION CABLE 1.5 SHIELDED SQ.MM X 2 CORE
SERVICE AREA OK EASILY ACCESIBLE
OUTDOOR UNIT
ADDITIONAL REF. AS PER LATS 10.5 KGS R-410 (DUPONT/HONEYWELL)
MASTER SLAVE 1 SLAVE 2 SLAVE 3
CONTROL BOX DIP SWITCH
ALL OFF
PRE START UP

POWER OK
WIRING TRANSMISSION OK
CENTRAL CONTROLLER OK AC EZ
PIPE SIZE @ HEADER SUCTION 34.9 LIQUID 15.88 MM HARD DRAWN
LEAKAGE TEST @ 550 PSIG MIN 24 HRS
VACUUMING 490 MICRONS 300-600
PIPING CONDITION OK
PIPING WORK PIPE & INSULATION
INSULATION SUCTION 19 LIQUID 19 MM SUCTION (19) ; LIQUID (13)
110 TOTAL PIPE LENGTH MTR MAX. 1000 MTR
PIPING LENGTH (AS PER
3 ELEVATION (ODU ~ IDU) MTR MAX. 110 MTR
LATS)
15 1ST Y BRANCH ~ IDU MTR MAX. 40 MTR
WIRE SPECS IDU POWER CABLE 2.5 FLEXIBLE SQ.MM X 3 CORE
TOTAL NO OF IDU 26 QTY
INDOOR UNIT TOTAL INDOOR UNIT CAPACITY 126.5 Tr KW/TR
REMOTE CONTROLLER WIRED/WIRELESS
DRAIN WORK OK TESTED
FOR COOLING OPERATION ONLY
ITEMS RESULT CRITERION
ALL INDOOR UNIT DISPLAY OK ON LGMV SCREEN
T PIPE IN (AVG TEMP) 10.28 °C 8°-15°C
EEV PULSE 300 PULSE 200-600 PULSE
INDOOR UNIT
AIR DISCHARGE OK FAN OPERATING
DRAIN WORK OK NO WATER LEAKAGE
REFRIGERANT NOISE NO NOISE NO REFRIGERANT NOISE
FREQUENCY M S1 S2 S6
START UP (LGMV)

INVERTER 1 82.31 82.31 82.31 82.31 Hz FREQUENCY (60-150 Hz)


INVERTER 2
DISCHARGE TEMP
COMPRESSOR INVERTER 1 77.39 77.39 77.39 77.39 °C TEMPERATURE (60°-100° C)
INVERTER 2
CURRENT
INVERTER 1 13.38 13.38 13.38 13.38 A CURRENT (11-30 A)
INVERTER 2
OUTDOOR UNIT
HIGH PRESSURE 365.72 365.72 365.72 365.72 PSIG 300-450 PSIG
PRESSURE (PSIG)
LOW PRESSURE 116.33 116.33 116.33 116.33 PSIG 100-150 PSIG
R-Y 420 R-N 230
3Ø - 380-450 V
Y-B 420 Y-N 230
VOLTAGE (V) V 1Ø - 210-250 V
R-B 420 B-N 230
N-G - 0-2 V
N-G 0.1
AIR TEMP (°C) 35 MIN -5° C MAX 48° C
DEGREE OF SUPERHEAT SUCTION (SH) 5 °C 3°C - 10°C
SITE DETAIL

MAIN EEV PULSE 1944 PULSE 1944 PULSE


CAPACITY HP: 28 HP No OUTDOOR UNIT: 1 No INDOOR U: 1
TOTAL AREA (sqft) APPLICATION : RESIDENCE / COMMERCIAL
COMMISIONING DATE ( WARRANTY START DATE): 15.12.2023
WARRANTY EXPIRY DATE: 14.12.2024
SUGESSTIONS (IF ANY) :

CUSTOMER REMARKS :

THIS IS TO CERTIFY THAT LG HAS COMPLETED THE AIRCONDITIONING WORKS AT ABOVE ADDRESS IN ALL RESPECTS. FURTHER, THE SYSTEM IS RUNNING SATISFACTORILY AND HAS BEEN HANDEDOVER TO THE CUSTOMER/ USER FOR
BENEFICIAL USE. THE PERFORMANCE PARAMETERS OF A-C SYSTEM/S ARE RECORDED AND WITNESSED BY THE UNDERSIGNED. FOR ANY BREAKDOWN/ WARRANTY SERVICES, PLEASE CONTACT OUR DEALER OR UNDERSIGNED
PROJECT/SERVICE ENGINEER.

FOR CUSTOMER NAME DEALER NAME LGEIL AMIT KUNDRI

DATE 15.12.2023

Note:
- The 'Pre-Start up' & 'Start up Report' Should be filled in by a certified person in charge.
- Under LG confirmation, warranty period will start officially.
- Without report and confirmation, LG has no responsibility for guarantee.
I, the supervisor, take all the responsibilities for this start up.
MULTI VRV PRE-START UP COMMISSIONING & HAND OVER REPORT
PROJECT CODE MULTI V-5 SYSTEM NO. 22 HP
LG ELECTRONICS INDIA PVT. LTD.
12th to 20th Floor Tower 1, KP tower, Plot No. C-001B, Sector 16B, Noida, Uttar Pradesh 201301
NAME COMPANY NAME & ADDRESS CONTACT DETAILS
Reliance Projects & Property Management Services Ltd
PERSON IN CHARGE

CUSTOMER DETAIL
Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
Reliance Projects & Property Management Services Ltd
SITE ADDRESS
Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
SHREE SVS SYSTEMS
INSTALLATION DEALER SHREE SVS SYSTEM 9168320222
Galaxy Apartment, Office NO. 01, 1st Floor, Katraj Kondhwa Road, Pune - 411048

PROJECT AREA MANAGER SERVICE AREA MANGER PROJECT AREA HEAD


FOR LG ELECTRONICS AMIT KUNDRI DIPAK CHAUDHARI DILIP SUKHWANI
9820315489 9923403744 8291103825
TYPE MODEL NO CAPACITY DESCRIPTION QTY
PRODUCT

ODU JRUV220LTE5 22 HP Outdoor Unit 22 HP 1


IDU AHU-6800CFM 22 HP Indoor Unit 22 HP 1

ITEMS RESULT CRITERION


MAIN SLAVE 1 SLAVE 2 SLAVE 6
PRODUCT SERIAL NO.

MAIN CABLE 6 ARMOURED SQ.MM X 4 CORE + EARTHING


WIRE SPECS BREAKER 40 AMPS IP65
TRANSMISSION CABLE 1.5 SHIELDED SQ.MM X 2 CORE
SERVICE AREA OK EASILY ACCESIBLE
OUTDOOR UNIT
ADDITIONAL REF. AS PER LATS 10.5 KGS R-410 (DUPONT/HONEYWELL)
MASTER SLAVE 1 SLAVE 2 SLAVE 3
CONTROL BOX DIP SWITCH
ALL OFF
PRE START UP

POWER OK
WIRING TRANSMISSION OK
CENTRAL CONTROLLER OK AC EZ
PIPE SIZE @ HEADER SUCTION 34.9 LIQUID 15.88 MM HARD DRAWN
LEAKAGE TEST @ 550 PSIG MIN 24 HRS
VACUUMING 490 MICRONS 300-600
PIPING CONDITION OK
PIPING WORK PIPE & INSULATION
INSULATION SUCTION 19 LIQUID 19 MM SUCTION (19) ; LIQUID (13)
110 TOTAL PIPE LENGTH MTR MAX. 1000 MTR
PIPING LENGTH (AS PER
3 ELEVATION (ODU ~ IDU) MTR MAX. 110 MTR
LATS)
15 1ST Y BRANCH ~ IDU MTR MAX. 40 MTR
WIRE SPECS IDU POWER CABLE 2.5 FLEXIBLE SQ.MM X 3 CORE
TOTAL NO OF IDU 26 QTY
INDOOR UNIT TOTAL INDOOR UNIT CAPACITY 126.5 Tr KW/TR
REMOTE CONTROLLER WIRED/WIRELESS
DRAIN WORK OK TESTED
FOR COOLING OPERATION ONLY
ITEMS RESULT CRITERION
ALL INDOOR UNIT DISPLAY OK ON LGMV SCREEN
T PIPE IN (AVG TEMP) 10.28 °C 8°-15°C
EEV PULSE 300 PULSE 200-600 PULSE
INDOOR UNIT
AIR DISCHARGE OK FAN OPERATING
DRAIN WORK OK NO WATER LEAKAGE
REFRIGERANT NOISE NO NOISE NO REFRIGERANT NOISE
FREQUENCY M S1 S2 S6
START UP (LGMV)

INVERTER 1 82.31 82.31 82.31 82.31 Hz FREQUENCY (60-150 Hz)


INVERTER 2
DISCHARGE TEMP
COMPRESSOR INVERTER 1 77.39 77.39 77.39 77.39 °C TEMPERATURE (60°-100° C)
INVERTER 2
CURRENT
INVERTER 1 13.38 13.38 13.38 13.38 A CURRENT (11-30 A)
INVERTER 2
OUTDOOR UNIT
HIGH PRESSURE 365.72 365.72 365.72 365.72 PSIG 300-450 PSIG
PRESSURE (PSIG)
LOW PRESSURE 116.33 116.33 116.33 116.33 PSIG 100-150 PSIG
R-Y 420 R-N 230
3Ø - 380-450 V
Y-B 420 Y-N 230
VOLTAGE (V) V 1Ø - 210-250 V
R-B 420 B-N 230
N-G - 0-2 V
N-G 0.1
AIR TEMP (°C) 35 MIN -5° C MAX 48° C
DEGREE OF SUPERHEAT SUCTION (SH) 5 °C 3°C - 10°C
SITE DETAIL

MAIN EEV PULSE 1944 PULSE 1944 PULSE


CAPACITY HP: 28 HP No OUTDOOR UNIT: 1 No INDOOR U: 1
TOTAL AREA (sqft) APPLICATION : RESIDENCE / COMMERCIAL
COMMISIONING DATE ( WARRANTY START DATE): 15.12.2023
WARRANTY EXPIRY DATE: 14.12.2024
SUGESSTIONS (IF ANY) :

CUSTOMER REMARKS :

THIS IS TO CERTIFY THAT LG HAS COMPLETED THE AIRCONDITIONING WORKS AT ABOVE ADDRESS IN ALL RESPECTS. FURTHER, THE SYSTEM IS RUNNING SATISFACTORILY AND HAS BEEN HANDEDOVER TO THE CUSTOMER/ USER
FOR BENEFICIAL USE. THE PERFORMANCE PARAMETERS OF A-C SYSTEM/S ARE RECORDED AND WITNESSED BY THE UNDERSIGNED. FOR ANY BREAKDOWN/ WARRANTY SERVICES, PLEASE CONTACT OUR DEALER OR
UNDERSIGNED PROJECT/SERVICE ENGINEER.

FOR CUSTOMER NAME DEALER NAME LGEIL AMIT KUNDRI

DATE 15.12.2023

Note:
- The 'Pre-Start up' & 'Start up Report' Should be filled in by a certified person in charge.
- Under LG confirmation, warranty period will start officially.
- Without report and confirmation, LG has no responsibility for guarantee.
I, the supervisor, take all the responsibilities for this start up.
MULTI VRV PRE-START UP COMMISSIONING & HAND OVER REPORT
PROJECT CODE MULTI V-5 SYSTEM NO. 22 HP
LG ELECTRONICS INDIA PVT. LTD.
12th to 20th Floor Tower 1, KP tower, Plot No. C-001B, Sector 16B, Noida, Uttar Pradesh 201301
NAME COMPANY NAME & ADDRESS CONTACT DETAILS
Reliance Projects & Property Management Services Ltd
PERSON IN CHARGE

CUSTOMER DETAIL
Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
Reliance Projects & Property Management Services Ltd
SITE ADDRESS
Smart Bazar, S No 4781 Babasaheb Paranjape Marg, Latur, Maharashtra 413512
SHREE SVS SYSTEMS
INSTALLATION DEALER SHREE SVS SYSTEM 9168320222
Galaxy Apartment, Office NO. 01, 1st Floor, Katraj Kondhwa Road, Pune - 411048

PROJECT AREA MANAGER SERVICE AREA MANGER PROJECT AREA HEAD


FOR LG ELECTRONICS AMIT KUNDRI DIPAK CHAUDHARI DILIP SUKHWANI
9820315489 9923403744 8291103825
TYPE MODEL NO CAPACITY DESCRIPTION QTY
PRODUCT

ODU JRUV220LTE5 22 HP Outdoor Unit 22 HP 1


IDU AHU-6800CFM 22 HP Indoor Unit 22 HP 1

ITEMS RESULT CRITERION


MAIN SLAVE 1 SLAVE 2 SLAVE 6
PRODUCT SERIAL NO.

MAIN CABLE 6 ARMOURED SQ.MM X 4 CORE + EARTHING


WIRE SPECS BREAKER 40 AMPS IP65
TRANSMISSION CABLE 1.5 SHIELDED SQ.MM X 2 CORE
SERVICE AREA OK EASILY ACCESIBLE
OUTDOOR UNIT
ADDITIONAL REF. AS PER LATS 10.5 KGS R-410 (DUPONT/HONEYWELL)
MASTER SLAVE 1 SLAVE 2 SLAVE 3
CONTROL BOX DIP SWITCH
ALL OFF
PRE START UP

POWER OK
WIRING TRANSMISSION OK
CENTRAL CONTROLLER OK AC EZ
PIPE SIZE @ HEADER SUCTION 34.9 LIQUID 15.88 MM HARD DRAWN
LEAKAGE TEST @ 550 PSIG MIN 24 HRS
VACUUMING 490 MICRONS 300-600
PIPING CONDITION OK
PIPING WORK PIPE & INSULATION
INSULATION SUCTION 19 LIQUID 19 MM SUCTION (19) ; LIQUID (13)
110 TOTAL PIPE LENGTH MTR MAX. 1000 MTR
PIPING LENGTH (AS PER
3 ELEVATION (ODU ~ IDU) MTR MAX. 110 MTR
LATS)
15 1ST Y BRANCH ~ IDU MTR MAX. 40 MTR
WIRE SPECS IDU POWER CABLE 2.5 FLEXIBLE SQ.MM X 3 CORE
TOTAL NO OF IDU 26 QTY
INDOOR UNIT TOTAL INDOOR UNIT CAPACITY 126.5 Tr KW/TR
REMOTE CONTROLLER WIRED/WIRELESS
DRAIN WORK OK TESTED
FOR COOLING OPERATION ONLY
ITEMS RESULT CRITERION
ALL INDOOR UNIT DISPLAY OK ON LGMV SCREEN
T PIPE IN (AVG TEMP) 10.28 °C 8°-15°C
EEV PULSE 300 PULSE 200-600 PULSE
INDOOR UNIT
AIR DISCHARGE OK FAN OPERATING
DRAIN WORK OK NO WATER LEAKAGE
REFRIGERANT NOISE NO NOISE NO REFRIGERANT NOISE
FREQUENCY M S1 S2 S6
START UP (LGMV)

INVERTER 1 82.31 82.31 82.31 82.31 Hz FREQUENCY (60-150 Hz)


INVERTER 2
DISCHARGE TEMP
COMPRESSOR INVERTER 1 77.39 77.39 77.39 77.39 °C TEMPERATURE (60°-100° C)
INVERTER 2
CURRENT
INVERTER 1 13.38 13.38 13.38 13.38 A CURRENT (11-30 A)
INVERTER 2
OUTDOOR UNIT
HIGH PRESSURE 365.72 365.72 365.72 365.72 PSIG 300-450 PSIG
PRESSURE (PSIG)
LOW PRESSURE 116.33 116.33 116.33 116.33 PSIG 100-150 PSIG
R-Y 420 R-N 230
3Ø - 380-450 V
Y-B 420 Y-N 230
VOLTAGE (V) V 1Ø - 210-250 V
R-B 420 B-N 230
N-G - 0-2 V
N-G 0.1
AIR TEMP (°C) 35 MIN -5° C MAX 48° C
DEGREE OF SUPERHEAT SUCTION (SH) 5 °C 3°C - 10°C
SITE DETAIL

MAIN EEV PULSE 1944 PULSE 1944 PULSE


CAPACITY HP: 28 HP No OUTDOOR UNIT: 1 No INDOOR U: 1
TOTAL AREA (sqft) APPLICATION : RESIDENCE / COMMERCIAL
COMMISIONING DATE ( WARRANTY START DATE): 15.12.2023
WARRANTY EXPIRY DATE: 14.12.2024
SUGESSTIONS (IF ANY) :

CUSTOMER REMARKS :

THIS IS TO CERTIFY THAT LG HAS COMPLETED THE AIRCONDITIONING WORKS AT ABOVE ADDRESS IN ALL RESPECTS. FURTHER, THE SYSTEM IS RUNNING SATISFACTORILY AND HAS BEEN HANDEDOVER TO THE CUSTOMER/ USER
FOR BENEFICIAL USE. THE PERFORMANCE PARAMETERS OF A-C SYSTEM/S ARE RECORDED AND WITNESSED BY THE UNDERSIGNED. FOR ANY BREAKDOWN/ WARRANTY SERVICES, PLEASE CONTACT OUR DEALER OR
UNDERSIGNED PROJECT/SERVICE ENGINEER.

FOR CUSTOMER NAME DEALER NAME LGEIL AMIT KUNDRI

DATE 15.12.2023

Note:
- The 'Pre-Start up' & 'Start up Report' Should be filled in by a certified person in charge.
- Under LG confirmation, warranty period will start officially.
- Without report and confirmation, LG has no responsibility for guarantee.
I, the supervisor, take all the responsibilities for this start up.
Date: 15.12.2023

To,
Reliance Projects & Property Management Services
Smart Bazar, S No 4781 Babasaheb Paranjape Marg,
Latur, Maharashtra 413512

Subject: Handing Over of LG Make VRF Air conditioning System for Reliance Projects
& Property Management Services, Smart Bazar Latur

Dear Sir,

This is with reference to the subject matter. We have commissioned the Air conditioning
system of (28 HP x Ckts 2) (22 HP x Ckts 3) Capacity at your office and has been put into
final operation on 15.12.2023 & now submitting following documents as per LG’s
standard handing over process:

1) Commissioning Reports ( VRF)


2) Warranty Letter.
3) Warranty Terms & Conditions.
4) Dos & Don’ts of the Operation.
5) Escalation Chart

Thanking you,
Sincerely yours,

For LG Electronics (I) Pvt. Ltd. Shree SVS Systems

(Authorised Signatory) (Authorised Signatory)


LG CUSTOMER CARE CENTRE
Toll free no : 1800 180 3575 (From Landline)
Email : cac.service@lgepartner.com

Warranty Letter
DATE: - 15.12.2023
To,
Reliance Projects & Property Management Services Ltd
Smart Bazar, S No 4781 Babasaheb Paranjape Marg,
Latur, Maharashtra 413512

Dear Sir,
SUB: WARRANTY CERTIFICATE
We thank you for giving us wonderful opportunity for Supply & Installation of the Air conditioning Equipment’s at your new
premises. We are pleased to inform you that, we have successfully installed the system of our LG make.
SR
LOCATION
NO. MODEL NUMBER CAPACITY TYPE SERIAL NUMBER
1 JRUN140LTE5 14 HP ODU 211PHVK001247
1st Floor Front Side
2 JRUN140LTE5 14 HP ODU 210PHXB001450
AHU Room
3 AHU-8800CFM 28 HP IDU 05-23PID00432-01
4 JRUN140LTE5 14 HP ODU 212PHLU004288
5 JRUN140LTE5 14 HP ODU 211PHVK004751 1st Floor Front Side
6 AHU-8800CFM 28 HP IDU 05-23PID00432-02
7 JRUV220LTE5 22 HP ODU 212PHUP003358
Ground Floor Pantry
8 AHU-6800CFM 22 HP IDU 05-23PID00433-03
9 JRUV220LTE5 22 HP ODU 210PHXB012706 Ground Floor AHU
10 AHU-6800CFM 22 HP IDU 05-23PID00433-01 Room ODU
11 JRUV220LTE5 22 HP ODU 212PHAW003360 Ground Floor AHU
12 AHU-6800CFM Room ODU
22 HP IDU 05-23PID00433-02

The warranty period for the above system shall be from 15.12.2023 to 14.12.2024 (12 Months from Date of Commissioning).
During warranty period for any manufacturing defects in the system, the spare parts will be replaced at free of cost as per
LG Warranty Policy only.

Please contact our Authorized Dealer M/s SHREE SVS SYSTEMS – 9168320222 in case of any complaints.
Please feel free to contact our Customer Care Officer, for any kind of issues relating to 4 Quarterly Services & complaints
during the warranty period.

Thanking you and assuring you of our Best services and attention at all the times.
Yours Truly,
For LG Electronics (I) Pvt. Ltd. Shree SVS Systems

(Authorized Signatory) ( Authorized Signatory)


AMIT KUNDRI Prachi Bhosale
DOS AND DON’TS WHILE OPERATING LG AIRCONDITIONERS

FOLLOWING TO BE OBSERVED WHILE OPERATING LG MAKE AIRCONDITIONERS AT SITE.

DOS:

1 ALWAYS START THE OUTDOOR UNIT POWER SUPPLY FIRST.

2 INDOOR UNITS TO BE SWITCHED ON AFTER THE OUTDOOR UNITS ARE ON.

3 WAIT FOR FEW SECONDS AFTER THE BEEP TO GET THE COMMAND EXECUTED.

4 RUN THE AIRCON AT RECOMMENDED TEMP RANGE OF 23 TO 25 DEGREE C.

5 KEEP THE FLAPS / AIR SWING IN MOVING POSITION FOR BETTER AIR FLOW.

DON'TS :

1 DO NOT RUN THE INDOOR UNIT WITHOUT SWITCHING ON THE OUTDOOR UNIT.

2 DO NOT RUN THE OUTDOOR UNIT BEYOND RECOMMENDED VOLTAGE RANGE.

3 DO NOT RUN THE OUTDOOR UNIT IN CASE OF FLUCTUATING VOLTAGE.

4 DO NOT KEEP OPEN THE DOORS/ WINDOWS WHILE THE AIRCONDITIONER IS ON.

5 DO NOT SET THE TEMPERATURE AT 18 DEGREE C.

6 DO NOT SWITCH OFF THE POWER OF IDU'S FROM MAIN MCB/SWITCH


DURING NORMAL OPERATION.

FOR LG ELECTRONICS INDIA PVT. LTD.

(AUTHORISED SIGNATORY)
Warranty Policy

Warranty Terms and Conditions

1) Warranty for the equipment shall be valid for 15


months from the date of Invoice or 12 months from the
date of installation/commissioning whichever is earlier.

2) Repair/replacement of any part of the standard


equipment found defective except for the plastic parts /
sheet metal / ducting / Air Delivery Devices (grilles
diffusers )/ filters /Condenser Coil /Cooling Coil*.

3) Any number of breakdown calls shall be attended.

4) Four preventive maintenance services shall be


rendered ( One in each quarter ) .

5) The warranty will be null & void in case the


installation / modifications / shifting / repairs of unit are
carried out by any person other than the authorized
dealer of LGEIL.

6) Warranty shall be null & Void if Input Power Supply


is beyond permissible limits (i.e. 3 Phase 415 V ± 10%,
1 Phase 220 ± 10 %). Customer shall install voltage
stabilizer to ensure the same.

7) The warranty in no case shall extend to the payment


or reimbursement against failed part/system or any
monetary benefit for any repair / replacement .

8) Force majeure :- no penalty / liability shall be


attached to the LGEIL for non performance or delayed
execution as a result of force majeure , including acts of
god, flood , labor dispute ,strikes etc. and other
circumstances beyond the control of LGEIL.

You might also like