Professional Documents
Culture Documents
2021
Ross D. Montgomery, PE., TBE, CCE
ASHRAE: BEAP, HBDP,
AABC-ACG: CxA.
AEE: CEM,GBE,CSDP,CIAQP
1 LU/HSW Credit by AIA ;course # MONTGOMERY07 (TAB)
Air Balancing
Fan Laws,
Fans, Ducts,
Dampers, flow
monitors, etc.
Basic
Measurements
Instruments,
Publications,
Rules and
Procedures
Calculations
Air
calculations
for an
assorted list
of typical
tasks
A B C
A+B+C Basic Air
Balancing Calculations
Measurements
Instruments, Fan Laws, Fans, Air calculations
Publications, Ducts, for an assorted
Dampers, flow list of typical
Rules and monitors, etc. tasks
Procedures
Pumps, Pump
calculations, Series and Psychrometrics, Moisture
Parallel, Pump curves, and Latent heat
PRV’s, Expansion Tanks, calculations, Controls and
TD valves and VFD’s
BAS systems.
2
1
3
TEAM
6
BAS/Controls
4
5
Specialty Start Up
and Tuning Crew
Major Equipment and
Manufacturer Reps
Testing Adjusting Balancing……” It’s all about the numbers and calculations” !!
GPM (gallons
per minute)
6
4 RPM
(revolutions
Head Pressure 5 per minute)
2
Static Pressure
CFM 3
(cubic feet
per minute) BHP (brake
1 horsepower)
AABC (Associated Air
Who are the Balance Council)
Major
Certifying NEBB (National
Organizations Environmental Balancing
Bureau)
? For (TAB)
Testing
Adjusting and TABB (aka SMACNA) (Test
and Balancing Bureau)
Balancing in
the United
States? ?Other
TAB Icons in the Industry
Application
Education
Certification Testing
Process Interviews
Background checks
(AABC/
NEBB) Annual meeting attendance
Continuing Education
Air + EOR
Water Design
The “air” and “water” side components, devices, TAB - verifies the ENGINEER’s
equipment, and systems, try to meet the design Design and reports any
requirements. (within 5-10%), as shown in the deficiencies/problems
Design Documents
WHAT TYPE OF “AIR” SYSTEMS DO
WE PERFORM TAB SERVICES FOR?
Zoned Chilled Water AHU Systems
AHU’s HVAC
FCU-Unit ventilators
Split DX
Systems
Variable Air Volume Boxes
Exhaust fan systems
VRF
Mini
Splits
TAB PUBLICATIONS
ANSI-ASHRAE
Standards for
(TAB) Testing
Adjusting and
Balancing
ASHRAE
Performance
Measurement
Protocols
(PMP)
Fundamentals
of HVAC
Control
Systems,
I-P & SI
(2nd edition)
AABC Standards and Technician Training Manual for
(TAB) Testing Adjusting and Balancing
NEBB Testing Protocols
NEBB Cleanroom
Process/Procedures/Protocols
BASIC
Measurements
Temperature
Probes and
Instruments
Relative Humidity
Probes and Instruments
Air flow instruments / Flow Hoods
Flow Hood ( Using a Pole)
Air pressure instruments
Voltage and Amperage ++ Meters
Illuminance and Light Level Meters
Kilowatt-hour (Energy) meters
Particle Counters
CO2 measuring Instruments
Sound Meters (dBA)
Equations…
Brake Horsepower…
Electrical Measurements/
Variable Speed
Calculations Drives (VFD’s)….
• Single Phase • Voltage (V)
Alternating 110-120 • Amps (A)
volt
• Watts = (W)
• Single Phase
Alternating 220-240 • Impedance (Z)
volt
Basic Electrical • Direct Current (DC)
• Three-wire Delta 3- • Alternating Current
Measurements phase 220-240 volt (AC)
• 220-240 volt 3-wire • Frequency (Hz)
Delta 3-phase
circuit with 110-120 • Phase (ph)
volt single phase • Kilowatt-hour (KwHr)
supply
• Power factor (pf)
• Four-wire WYE
circuit 120/208 volt
3-phase
• 480/277 volt 3-
phase
• % Imbalance =
Maximum deviation from
avg. voltage x 100/Avg.
Voltage
• Solution:
Electrical * A 2% limit for a 3-phase
Measurements motor circuit is
prescribed. 1. Average voltage imbalance:
“Voltage
240 + 238 + 226 / 3 = 235 v
Imbalance”
Example: Find the voltage
imbalance of a 230 volt 3- 2. Find the maximum deviation
from the average voltage:
phase motor with phase-
to-phase readings of: L1-L2=240-235=5v
L1 to L2 = 240 v L1-L3=238-235=3v
L2-L3=235-226=9v
L1 to L3 = 238 v
From the % imbalance equation:
L2 to L3 = 226 v
% Imbalance= 9 x 100 / 235 =
3.8
• Since 3.8% is larger than 2%,-
-----IT DOES NOT PASS ---
• The AHJ/Engineer should be
notified
• Brake Horsepower (BHP) =
1.732 x RA x RV x L factor (pf
Electrical x eff) / 746
Measurements,
continued’- Example: Find the brake
“BHP (Brake horsepower for 3-phase
Horsepower)”
motor with the following
conditions:
Average amps: 54
Average volts: 235
Average power factor: 0.87
Motor efficiency: 0.83
• Answer…..
• 1.732 x 54 x 235
(.87x.83)/746= 21.25 BHP
Variable Frequency Drives
offer a great potential for
energy savings. Fan and
pump applications follow
the affinity laws, which
means that flow is
proportional to speed,
pressure is proportional to
the square of
speed, and horsepower is
proportional to the cube of
speed.
Example:
• From 100% to 80% speed; resultant
speed is .8x.8x.8
Motor Speed Hertz Savings (cube root of speed)
100% 60 0% • = .51
90% 54 27%
80% 48 49% • = 49% energy savings
70% 42 66%
60% 36 78%
Measuring Duct Air
Velocity and Flows
Rectangular + Round
+ Oval Ducts
• V(1) = 4005*SQRT(0.074)=1089
• V(1) = 4005*SQRT(0.288)=2149
• V(1) = 4005*SQRT(0.405)=2548
• V(1) = 4005*SQRT(0.511)=2862
• V(1) = 4005*SQRT(0.715)=3386
• V(1) = 4005*SQRT(0.926)=3853
• V(1) = 4005*SQRT(0.405)=2548
• V(1) = 4005*SQRT(0.511)=2862
Sample Calculation of •
•
V(1) = 4005*SQRT(0.715)=3386
V(1) = 4005*SQRT(0.926)=3853
• V(2) = 4005*SQRT(0.064)=1013
• V(2) = 4005*SQRT(0.388)=2494
• V(2) = 4005*SQRT(0.305)=2211
• V(2) = 4005*SQRT(0.411)=2567
• V(2) = 4005*SQRT(0.615)=3140
• V(2) = 4005*SQRT(0.826)=3639
• V(2) = 4005*SQRT(0.305)=2211
• V(2) = 4005*SQRT(0.411)=2567
• V(2) = 4005*SQRT(0.615)=3140
Sample Calculation of • V(2) = 4005*SQRT(0.826)=3639
Sample Calculation of
Velocity and Flow (Round
Duct) 3/4
Step-3 : Measuring Duct Air
Flows [Round Duct] Calculating
the Air flow measurements)-4/4
“traverse as rectangle”
Sample Calculation of Velocity and
Flow (OVAL Duct) 6/8
• VP (2) readings (at hole-2) = 0.064, 0.388, 0.305,
0.411, 0.615, 0.826 0.064, 0.388, 0.305, 0.411
• Use equation Velocity (V) = 4005 * SQRT (VP)
• V(2) = 4005*SQRT(0.064)=1013
• V(2) = 4005*SQRT(0.388)=2494
• V(2) = 4005*SQRT(0.305)=2211
• V(2) = 4005*SQRT(0.411)=2567
• V(2) = 4005*SQRT(0.615)=3140
• V(2) = 4005*SQRT(0.826)=3639
• V(2) = 4005*SQRT(0.305)=2211
• V(2) = 4005*SQRT(0.411)=2567
• V(2) = 4005*SQRT(0.615)=3140
• V(2) = 4005*SQRT(0.826)=3639
Sample Calculation of Velocity and
Flow (OVAL Duct) 7/8
• Take all velocity readings and take
average of all readings. (5 holes on
each side; 10 holes total= 10 readings
each= 100 readings total
• 312,000/100=3,120 fpm (OVAL)
• 2,518 fpm (Rectangular)
• Average Velocity = 3,120 + 2,518 / 2 =
2,819 fpm
Step-3 ; Measuring Duct Air Flows [OVAL Duct]
Calculating the Air flow measurements) 8/8
• Because the rectangle width is less than the diameter of the diameter of
the semi-circle, we are going to traverse this OVAL duct as a circle using
the Log Linear method across A-B and C-D in Figure 1.22a
• Insert pitot tube into duct holes and take ten (10) readings; A-B
• VP (A-B) readings = 0.074, 0.099, 0.288, 0.35, 0.405, 0.511, 0.65, 0.715,
0.88, 0.926
• V(ab) = 4005*SQRT(0.074)=1089
• V(ab) = 4005*SQRT(0.099)=1260
• V(ab) = 4005*SQRT(0.288)=2149
• V(ab) = 4005*SQRT(0.35)=2369
• V(ab) = 4005*SQRT(0.405)=2548
• V(ab) = 4005*SQRT(0.511)=2862
• V(ab) = 4005*SQRT(0.65)=3228
• V(ab) = 4005*SQRT(0.715)=3386
• V(ab) = 4005*SQRT(0.88)=3757
• V(ab) = 4005*SQRT(0.926)=3853
• V(cd) = 4005*SQRT(0.199)=1786
• V(cd) = 4005*SQRT(0.32)=2265
• V(cd) = 4005*SQRT(0.41)=2564
• V(cd) = 4005*SQRT(0.55)=2970
• V(cd) = 4005*SQRT(0.60)=3102
• V(cd) = 4005*SQRT(0.75)=3468
• V(cd) = 4005*SQRT(0.80)=3582
• V(cd) = 4005*SQRT(0.85)=3692
[Rule of Thumb:]
+ 2% correction for each 1000 feet above sea level
+/- 1% correction for each 10 DegF above/below 70 DegF]
Question? (Fan Law-3 (BHP-
Density)
• A fan is operating at 5,000
CFM and 4.2 BHP. The density
of the air is 0.062 lbs. per cubic
So, How do we use the foot. FIND the new BHP at
FAN LAWS? In practice? standard conditions (0.075)?
(BHP-Density)
Maximum
Minimum Test
Type of System Allowable
Pressure “(w.g)
Leakage (%)
1. Fractional HP, fan systems; fan
0.50" 2%
coils, small EF’s, SF’s
2. Small Systems ; Split DX- usually
1.00” 2%
under 2000 cfm
3. VAV and CAV boxes and associated
1.00” 2%
downstream ductwork
4. Single zone, multi-zone, low
pressure VAV and CAV systems,
2.00” 2%
return ducts, and exhaust duct
systems
5. All Constant volume ducts in chases
and concealed spaces, main return 3.00” 1%
ducts on supply and supply systems.
6. Supply ducts for VAV and CAV
4.00” 1%
systems
7. High Pressure Induction Systems 6.00” 0.50%
Note; Supply ducts should be tested with positive pressure; return and exhaust ducts
should be tested with negative pressure.
“Whole Building” Ducts and Whole
Building
Leakage
ASTM Standard E799-87, “Test Method for Determining Air
Leakage by Fan Pressurization.”
Measuring
and The fan laws will help you make
Changing changes to RPM, CFM, static
pressure, and Horsepower, etc.
Rotational “up and down” as you need it.
Speeds on
Fans
We can change the FAN or
MOTOR sheaves to change
those characteristics
Changing Drive components “Sheaves” to change the
RPM of the Fan
cfm2= cfm 1
(rpm2/ rpm1)
Fan Law SP2=SP1
Relationships
(rpm2/rpm1)2
BHP2=BHP1
(rpm2/rpm1)3
Measuring Rotational
Speed and its
Resultant Flows
• Motors drive the fans and pumps that produce
the air and fluid flow in HVAC systems.
• TAB professionals test, adjust, and balance the
rotational equipment.
• The “1st Fan Law” states that that the output
of the fan in cfm varies in direct proportion to
the fans rpm.
BHP2=BHP1
(rpm2/rpm1)3
• Question? (Fan • Question? (Fan
Law-1 (RPM)) Law-1(CFM))
• A fan is operating • A fan is operating
So, How do at a speed of 835 at 655 RPM and
we use the RPM. The volume delivering 12,250
of air out of the CFM. FIND the
FAN LAWS? fan is 6,000 cfm. new CFM
In practice? FIND the new fan delivered by the
(RPM-CFM) speed (RPM) fan if the fan
required to speed is
deliver 6,600 decreased to 625
cfm? RPM?
Answer: Rpm2= Answer: cfm2= cfm
Rpm 1 (cfm2/ 1 (rpm2/ rpm1)
cfm1) • = 12,250
• =835(6600/6000) (625/655)=11,690
=919 rpm cfm
• Question? (Fan Law-2 • Question? (Fan Law-
(SP-RPM)) 2(SP-CFM))
• A fan is operating at a • A fan is operating at
speed of 835 RPM. 25,000 CFM with a
So, How do we The fan discharge discharge static
static pressure is 2.25 pressure of 4.1 in.
use the FAN in. WC. Find the new WC. The air volume
LAWS? In static pressure if the is reduced to 21,250
practice? (Static fan speed is CFM. FIND the new
Pressure) increased to 920 static pressure.?
RPM?
Answer: SP2=SP1
(rpm2/rpm1)2
Answer:
SP2=SP1(rpm2/rpm1)2 • =SP2=4.1
(21,250/25,000)2
• =SP2=2.25 (920/835)2
• Centrifugal
• Forward curved
• Backward curved
• Radial
• Airfoil
• Tubular
• Axial
• Propeller
• Tube axial
• Vane axial
A set of
Parallel 10 HP
fans in an
AHU being
operated by
VFD’s
Fans
Operating in
Parallel
Parallel:
• Fans are commonly installed to
operate in parallel in the same
system , particularly when large
volumes of air must be moved.
• The combined performance curve
is obtained by adding the airflow of
each fan at the same pressure.
For example, two fans, each handling
20,000 cfm at 2 in. WC operate in
parallel; the combined curve will have
the output at 40,000 cfm at 2 in. WC.
Series:
• Sometimes multiple fans are
installed in series.
• The combined performance curve
is obtained by adding the fan
pressures at the same air flow
volume.
• For example, two fans, each
handling 20,000 cfm, operating in
series, at 2 in. WC; the combined
curve will have the output at
20,000 cfm at 4 in. WC.
Balancing
Dampers
HVAC systems use Dampers to control
temperature direction and volume of the air.
• This is a typical
splitter damper
that is installed
throughout the
duct systems that
are used for
balancing of
branch ducts.
Adjusting Duct Balancing damper
Air Balance Preparation
(+ pre-paperwork)
Mechanical Site: • Motor starters installed
with proper overloads
• REQUEST and fuses and branch
circuit protection.
STARTUP SHEETS !!!!
• VFD’s operating not
• Record nameplate of over 60 Hz? Or not over
Site motors, fans , coils,
sheaves, belts, terminals
nameplate rated rpm
rating?
Inspections boxes, controls, etc.
• Are all inlets and
• Check ductwork ; make outlets to each room
sure it is complete; is it installed?
sealed with a sealant?
• Are all paths to all
• Make sure access doors rooms installed?
are installed where
needed for concealed • Are all duct paths un-
devices. obstructed?
• Make sure balancing • Are all fire dampers?
dampers are installed in Fire –smoke dampers
ducts where needed + installed? Fire caulked?
open
• Access doors to all fire
• Filters installed and and fire smoke
clean? dampers?
• Belts adjusted; fans and • Access doors to all
pulleys aligned? smoke detector and
smoke detector tubes?
• Are the drive components
installed (sheaves)
• Air Handling Units:
o Check rotation of
fans
o Filter cleanliness
o Belt tightness and
condition
o Coil conditions
o Static pressure
profiles across fans,
filter banks,
dampers, air
monitors, coils,
heaters, etc.
o Damper conditions
o Enclosure leakage
o Duct connections
o Economizer
Inspections functions
o Control functionality
Basic Air Balance
Procedures
Building Pressurization • It is important to set up the OA air flows
involves the Outside air with the exhaust flows in mind. If you want
the building to remain positively pressurized,
and Exhaust then the OA flows need to be more than the
exhaust flows.
Air Flow Monitoring
Stations for Ducts
Design Test
Station No. Area Served Size Area Sq. Ft.
FPM CFM FPM 1 FPM 2 CFM
Air
Monitoring
Station
Data Sheet
• Air flow monitoring devices are
frequently installed and used for
HVAC systems
• They typically measure differential
Air Flow pressure across a precision orifice
plate or Venturi throat.
Monitoring • They are useful in monitoring and
understanding the on-going
and Use in performance of mechanical
equipment
Sequences of • They are often used in control
Operation sequences of ventilation, exhaust
and relief air control systems
• TAB technicians work with BAS
technicians to calibrate these
devices
Draw out the AHU and duct-diffuser layout
• Make sure all balancing
dampers are open
• Perform “preliminary
General Process: tests” to see where you
Air Balance (1) are starting at.
• Document your
VAV box findings
using a
standardized air
distribution
sheet
HVAC REFRIGERATION SYSTEMS
Direct
expansion (DX)
refrigeration
• Common systems used
for small to medium
buildings
• Uses various refrigerants
in a closed pressurized
system to produce
cooling and heating
effects
• TAB forms record all
performance parameters
• Fan/Evaporator Data:
• Manufacturer Model #/Serial #/Location
o Total CFM
o OA CFM
o RA CFM
o Entering Air temperature (Dry bulb and wet bulb)
o Leaving Air temperature (Dry bulb and wet bulb)
o Amperage
o Volts
o Phase
o Air supply TH
Refrigerant o Cooling BTU/hr coil
o Room Temperature and space humidity
100 5 3,520
1,000 6 35,200
10,000 7 352,000
100,000 8 3,520,000
United States Pharmacopeia
and The National Formulary
(USP-NF) is a compilation of
Example- drug monographs, biologics,
USP 797 medical devices, dietary
supplements, reference tests
Pharmacy and standards, and standards
Requirement for compounding of sterile and
nonsterile drug preparations.
• THE INTENT OF IS TO PREVENT HARM AND FATALITY TO
PATIENTS THAT COULD RESULT FROM MICROBIAL
CONTAMINATION (NONSTERILITY), EXCESSIVE BACTERIAL
ENDOTOXINS, LARGE CONTENT ERRORS IN THE STRENGTH OF
CORRECT INGREDIENTS, AND INCORRECT INGREDIENTS IN
COMPOUNDED STERILE PRODUCTS (CSPs).”
Typical Clean rooms-Pharma
The “crew” for TAB in “Clean rooms”
Getting ready
to enter the
clean room
Return Grille Velocity testing (with a handheld velometer)
Test Instruments
CO2
testing
Light
meter
tests
Door
Differential
Pressure
tests
Horizonal
Velocity/Draft
testing
• The airborne particle count
cleanliness classification test is
Particle performed to determine the
actual particle count level within
Count the facility at the time of the test
(As-Built, At-Rest, or Operational).
Cleanliness
tests • The size of particles to be measured for room class
certification shall be as specified in the contract’
for an ISO-8 classification, 0.5 μm 1.0 μm 5.0 μm
are a minimum.
Handheld Particle counter
Using a
Handheld
Particle
meter
Lay out
your Test
Grids
Ambient Conditions
Room-101 50 9 450 13
Room Use-Classification (Gown-Molding)
Test location 1 (raw data from instrument) 20 15 15 8 6 3
Test location 2 (raw data from instrument) 24 17 14 4 3 0
Test location 3 (raw data from instrument) 170 75 32 12 9 5
Test location 4 (raw data from instrument) 60 44 29 17 10 5
Test location 5 (raw data from instrument) 801 172 40 8 5 1
Test location 6 (raw data from instrument) 500 50 15 5 2 1
Average raw particle counts @0.1cfm 263 62 24 9 6 3
Avg. Particle counts per cubic foot (per ft3/min) 2625 622 242 90 58 25
High Particle counts per cubic foot (per ft3/min) 8010 1720 400 170 100 50
Average particle counts per square meter (cfm x 35.31) 92689 21951 8533 3178 2060 883
Maximum ISO-8 Classification allowed 3520000 832,000 29300
Status of Room relative to Code minimum Passed Passed Passed
Temperature (DegF)/Humidity (% rh) 59/64%
Grid - minimum #samples required//taken 6
Air changes per hour[ cfm/ft3 (350x60/450)] 46
Average Light Intensities (foot-candles) 46-112 fc
Carbon Dioxide (CO2) (parts per million) 460 ppm
Room Dimensions; cubic feet
Room-101 50 9 450 13
Room Use-Classification (Gown-Molding)
Test location 1 (raw data from instrument) 20 15 15 8 6 3
Test location 2 (raw data from instrument) 24 17 14 4 3 0
Test location 3 (raw data from instrument) 170 75 32 12 9 5
Test location 4 (raw data from instrument) 60 44 29 17 10 5
Test location 5 (raw data from instrument) 801 172 40 8 5 1
Test location 6 (raw data from instrument) 500 50 15 5 2 1
Average raw particle counts @0.1cfm 263 62 24 9 6 3
Avg. Particle counts per cubic foot (per ft3/min) 2625 622 242 90 58 25
High Particle counts per cubic foot (per ft3/min) 8010 1720 400 170 100 50
Average particle counts per square meter (cfm x 35.31) 92689 21951 8533 3178 2060 883
Maximum ISO-8 Classification allowed 3520000 832,000 29300
Status of Room relative to Code minimum Passed Passed Passed
Temperature (DegF)/Humidity (% rh) 59/64%
Grid - minimum #samples required//taken 6
Air changes per hour[ cfm/ft3 (350x60/450)] 46
Average Light Intensities (foot-candles) 46-112 fc
Carbon Dioxide (CO2) (parts per million) 460 ppm
Collect raw data from
particle counting device
Area of Height of Cubic Feet Cubic Meter Particle 0.3 Particle 0.5 Particle 1 Particle 3 Particle 5
Locations Value
room (ft2) Ceiling (ft) (ft3) (m3) micron micron micron micron micron
Particle 10 micron
Room-101 50 9 450 13
Room Use-Classification (Gown-Molding)
Test location 1 (raw data from instrument) 20 15 15 8 6 3
Test location 2 (raw data from instrument) 24 17 14 4 3 0
Test location 3 (raw data from instrument) 170 75 32 12 9 5
Test location 4 (raw data from instrument) 60 44 29 17 10 5
Test location 5 (raw data from instrument) 801 172 40 8 5 1
Test location 6 (raw data from instrument) 500 50 15 5 2 1
Average raw particle counts @0.1cfm 263 62 24 9 6 3
Avg. Particle counts per cubic foot (per ft3/min) 2625 622 242 90 58 25
High Particle counts per cubic foot (per ft3/min) 8010 1720 400 170 100 50
Average particle counts per square meter (cfm x 35.31) 92689 21951 8533 3178 2060 883
Maximum ISO-8 Classification allowed 3520000 832,000 29300
Status of Room relative to Code minimum Passed Passed Passed
Temperature (DegF)/Humidity (% rh) 59/64%
Grid - minimum #samples required//taken 6
Air changes per hour[ cfm/ft3 (350x60/450)] 46
Average Light Intensities (foot-candles) 46-112 fc
Carbon Dioxide (CO2) (parts per million) 460 ppm
ISO 14644-1 Cleanroom Standards
Maximum Particles/m3 FED STD
Class 209E
≥0.1µm ≥0.2µm ≥0.3µm ≥0.5µm ≥1µm ≥5µm Equivalent
ISO
10 2.37 1.02 0.35 0.083 0.0029
1
ISO
100 23.7 10.2 3.5 0.83 0.029
ISO 14644-1 2
ISO
Cleanroom 3
1,000 237 102 35 8.3 0.029 Class 1
ISO
Standard(Most 4
10,000 2,370 1,020 352 83 2.9 Class 10
current) ISO
5
100,000 23,700 10,200 3,520 832 29 Class 100
Room-101 50 9 450 13
Room Use-Classification (Gown-Molding)
Test location 1 (raw data from instrument) 20 15 15 8 6 3
Test location 2 (raw data from instrument) 24 17 14 4 3 0
Test location 3 (raw data from instrument) 170 75 32 12 9 5
Test location 4 (raw data from instrument) 60 44 29 17 10 5
Test location 5 (raw data from instrument) 801 172 40 8 5 1
Test location 6 (raw data from instrument) 500 50 15 5 2 1
Average raw particle counts @0.1cfm 263 62 24 9 6 3
Avg. Particle counts per cubic foot (per ft3/min) 2625 622 242 90 58 25
High Particle counts per cubic foot (per ft3/min) 8010 1720 400 170 100 50
Average particle counts per square meter (cfm x 35.31) 92689 21951 8533 3178 2060 883
Maximum ISO-8 Classification allowed 3520000 832,000 29300
Status of Room relative to Code minimum Passed Passed Passed
Temperature (DegF)/Humidity (% rh) 59/64%
Grid - minimum #samples required//taken 6
Air changes per hour[ cfm/ft3 (350x60/450)] 46
Average Light Intensities (foot-candles) 46-112 fc
Carbon Dioxide (CO2) (parts per million) 460 ppm
• Mini-Split and DX units
That is a general Air
• Constant Volume AHU’s
Balance Procedure; • Multizone AHU’s
There are much more • Terminal VAV Boxes
specific procedures o Single Duct Constant Volume
available for ;
o Dual Duct
o Induction Box
o Bypass Box
o With or with heaters
Pump Law
Relationships h2=h1 (rpm2/rpm1)2
BHP2=BHP1
(rpm2/rpm1)3
WATER SYSTEMS
Chillers
Hot Water Boilers
Chiller and Pumps (ONA)
Pumping Systems
Solar systems
TAB helps to calibrate
water sensing devices
BTU-Energy Meters
Water Pressure Meters
Water flow Instruments
Water Differential Pressure
Differential
Pressure gauges
• Used on Pumps to measure suction
and discharge pressures, strainer
pressure drop, flow rates across flow
meters, and pressure drop across
discharge valves.
• Differential gauges eliminate the
need for 2 separate gauges
• Can have manifolds that can be
switched to have multiple
functionality to read many different
configurations
Flow Meters
Practical Flow
(gpm)
measurement
examples
• A water chiller is rated at
30 gpm with a 4.6 feet of
pressure drop. The
entering pressure drop is
measured at 28 feet and
the leaving pressure is 25.5
feet. FIND the actual flow
rate?
• Answer>
• Gpm2 = Gpm1 √∆P2 / ∆ P1
• Gpm2 = 30 √(28-25.5) / 4.6
• =22 gpm
• Using Temperature
Difference (heat transfer
rate) through the Coil:
• Gpm=Btuh/500 x deltaT
• A chilled water coil has an
Practical Flow entering temperature of 44
DegF and a leaving
(gpm) temperature of 54 DegF. The
heat transfer rate through
the coil has been calculated
measurement at 60,000 Btuh.
Make sure:
• Pump seals are in-
tact and
operational
• Pump bearings
are smooth, quiet,
and lubricated.
• Pump couplings
are aligned
Bad things that can happen with Pumps
that TAB watches out for (2):
• Cavitation:
• A condition when inside the centrifugal pump,
the internal pressure falls below the operating
vapor pressure of the liquid, causing the liquid
to “boil and vaporize”
• Causes “snapping and crackling noises” at the
inlet; severe vibration; a drop in Head and
Brake horsepower; a reduction or stoppage of
flow.
• To eliminate cavitation, it is necessary to
maintain a minimum suction pressure at the
pump suction inlet to overcome the internal
losses in the pump. See (NPSH) Net Positive
Suction Head graph.
gpm2= gpm 1 (rpm2/
rpm1)
Pump Law
Relationships h2=h1 (rpm2/rpm1)2
BHP2=BHP1
(rpm2/rpm1)3
Theoretical Water
Horsepower formula:
Brake horsepower
• Whp = gpm x head x uses a pump
sp. Gr. / 3,960 efficiency factor.
“Theoretical” • Note: SP. Gr. =1
(water between 32- • Bhp = gpm x
head x sp. Gr. /
Water 212 DegF)
3,960 x pump
• Since all pumps are efficiency
Horsepower NOT 100% efficient,
(due to friction and • Example: FIND
turbulence losses) the BHP of a
we do not typically pump operating
use “theoretical”
and water horsepower.
at 142 feet of
head and 980
gpm, with an
efficiency of
74%.
“Brake”
Horsepower • Bhp = 980 x 142
x 1 / 3,960 x 0.74
=47.5
❑Question? (Pump Law-1 (RPM))
• A pump is operating at a flow of
100 GPM. The speed of the
motor is 1755 rpm. FIND the
So, How do we use the new GPM when the speed is
Pump LAWS? In raised to 1900 rpm?
practice? (RPM-GPM) • Answer: gpm2= gpm 1 (rpm2/
rpm1)
• =100(1900/1755)
=108.2 GPM
• Question? (Pump Law-2 • Question? (Fan Law-
So, How do we (Head-RPM)) 2(Head-GPM))
• =20 (150/100)3
• =67.5 BHP
Question? (Pump Law-3
(BHP-Density)
• A pump is operating at
20 BHP with an impeller
How do we use the diameter of 10” . FIND
Pump LAWS? In the new BHP if the
practice? impeller is increased to
(BHP-Impeller
11.5”?
Diameter)
Answer: BHP2=BHP1
(d2/d1)3
• BHP2=20 (11.5/10)3
• =30.41 BHP
Pumps Operating in
Series and Parallel
Parallel: Series:
➢ When pumps are ❑ When pumps operate
installed to operate in in Series, Heads and
parallel, in the same Horsepower's are
system, GPM’s and BHP’s additive (+++)
are additive (+++).
❑ GPM’s (Flows remain
Pumps in ➢ Heads (Pressures remain
constant.)
constant)
❑ For example: if a single
➢ For example: if a single pump operating at 60
pump operating at 60 gpm, 120 feet of head,
gpm, 120 feet of head, 3 3 BHP, is added in
SERIES Parallel
Basic Hydronic
(Pumping) Systems
Simple Example of a Hydronic (pumping) system
Simple Examples of Hydronic pumping systems
(Open + Closed)
Start the TAB • Check the settings and gauge readings for the make-up
water pressure (typical low-rise buildings;30-35 psi)
process- • Make sure all large AHU/FCU control valves are open in the
secondary systems
Prepare
• Start 2-pumps and 2-chillers (all systems on)
• Test each pump BY ITSELF (Parallel INDIVIDUALLY;;; or Series-
RUNNING TOGETHER)
Make sure pressure taps and gauges are installed and
working
Connect water pressure meter to pressure ports
Primary Secondary Chiller Plant
SET BLOCK OFF/SHUT OFF:: TO VERIFY IMPELLER SIZE
Block-0ff; Deadhead; in the Plant-
Primary side
• Block off Pump-1; Verify the impeller size of the pump by
“dead-heading” the pump and reading its pressure and
comparing it to its pump curve data.
• Block off Pump-2; Verify the impeller size of the pump by
“dead-heading” the pump and reading its pressure and
comparing it to its pump curve data.
• Throttle VFD in order to get the desired flow (GPM) -+10% of design
o After adjustments are made, record all electrical, pressure, flow,
and impeller sizes on the TAB forms. (and write in magic marker
on VFD’s)
o Set the high limit speed at the VFD control panel
o Make sure do not pump more than design flow +105%, when
VFD’s are at 60 Hz during full cooling mode (all valves open)
Note; Do not use triple duty valve (TDV) to adjust flow---use VFD.
Question?? Making adjustments to flow using VFD’s (or Triple
duty valve) to match “desired design requirements”
Balancing the Distribution System
next; Using the diagram Let’s
identify the Mains, risers,
branches and take-off at each
terminal
Typical Water
distribution
system
components
Main +
Headers
➢ Mains:
➢ Using the data obtained from
reading the pump data, determine
the “main’ common output is
delivering 100-110% of design flow
(gpm).
➢ Headers:
➢ Adjust the “headers” starting with
Balancing mains, the headers with the HIGHEST
headers… (1/4) flow. Set this headers balancing
valve until the water flow is within
10% of the desired amount for that
header.
➢ Read the other headers, set their
balancing valve to within 10% of
their design flow rates.
➢ Cont’d…….
Start at
HIGHEST
Header
Go to next
HIGHEST
Header
➢ Risers:
➢ Go to the “highest riser” (WITH THE
MOST FLOW) and adjust risers
balancing valve until the water flow
is within 10% of the desired amount
for that riser.
➢ Continue to balance all of the
Balancing risers, branches and coils on that branch
(proportional)
and
➢ Read the other risers, Go to tbe
branches/Coils.. “Next Highest Riser” (most flow); set
(2/4) their balancing valve to within 10%
of their design flow rates.
➢ Continue to balance all of the
branches and coils on that branch
(proportional)
➢ Next….Cont’d…….
Risers
➢Branches:
➢Go to the “highest branch” and
adjust branch balancing valve
until the water flow is within 10%
of the desired amount for that
branch.
➢Read the other branches, starting
from the highest to its lowest,
Balancing and then set their balancing valve
to within 10% of their design
branches/Coils.. flow rates.
(3/4) ➢After all branches are adjusted;
go back and re-check them. This
will usually take going back 2-3
times.
➢Cont’d…….
Pick the
highest Riser;
then balance
the branches
and coils
Go to the
next highest
Riser; then
balance the
branches and
coils
Finish the
entire Riser;
then move to
the next
Risers
• Many times….