THAI ROTARY ENGINEERING PUBLIC COMPANY LIMITED

MECHANICAL DATASHEET
FOR CHILLER UNIT

RETURN STATUS

 (1) REJECT
 (2) COMMENT
 (3) APPROVED WITH COMMENT
 (4) APPROVED / NO COMMENT

IMPORTANT: Permission to proceed does not constitute


acceptance or approval of design detail, calculation, analysis,
test method or material developed or selected by the supplier
and does not relieve supplier from full compliance with
contractual obligations.

REVIEWED/
COMMENTED BY:

DATE:

CLIENT :

THAI TANK TERMINAL LIMITED

PROJECT TITLE:
PO & POLYOLS PROJECT

CONTRACTOR:

THAI ROTARY ENGINEERING PUBLIC COMPANY LIMITED

DOCUMENT NO.:

8-13-836

PROJECT NO.:

P11P3351

ISSUED FOR
0A POOM 02-08-2018 SIP 02-08-2018 API 02-08-2018 PAGE NO.:
APPROVAL

REV. INTIAL
MADE BY INTIAL DATE CHK'D BY INTIAL DATE APP' D BY PURPOSE 1 OF 5
NO. DATE
Sheet No. : 2 of 5
MECHANICAL DATASHEET
PROJECT NO.: P11P3351

TREL Doc. No. :


FOR CHILLER UNIT
8-13-836

Date:02-08-2018 Rev. No.: 0A

REVISION LOG

REV NO REV DATE REVISED PAGE/S REVISION DESCRIPTION


0A 02-08-2018 - ISSUED FOR APPROVAL

0 00/01/1900 4 to 6 0
Sheet No. : 3 of 5
MECHANICAL DATASHEET
PROJECT NO.: P11P3351

TREL Doc. No. :


FOR CHILLER UNIT
8-13-836

Date:02-08-2018 Rev. No.: 0A

TABLE OF CONTENTS

NO DESCRIPTION PAGE

1 MECHANICAL DATASHEET FOR CHILLER UNIT


4
Sheet No. : 4 of 5
MECHANICAL DATASHEET PROJECT NO.: P11P3351
TREL Doc. No. :
FOR CHILLER UNIT 8-13-836
Date:02-08-2018 Rev.No.: 0A

SERVICE PROPYLENE OXIDE(PO) CIRCULATION SYSTEM EQUIPMENT TAG NO.: R-1704

NO. REQUIRED: 01 SET

DESIGN DATA

TOTAL SYSTEM HEAT DUTY CAPACITY: 170 kW MASS FLOW RATE INLET / OUTLET: 84,050 / 84,050 Kg/Hr

DESIGN PRESSURE: 8.8 Bar G. SPECIFIC GRAVITY AT 10 Deg C INLET / OUTLET: 0.84 / 0.84

TEST PRESSURE: 13.2 Bar G. SPECIFIC HEAT INLET / OUTLET: 0.456 / 0.456 kcal/Kg-C

AMBIENT TEMP.: 35 Deg C PROPYLENE OXIDE TEMP.INLET / OUTLET: 13 / 10 Deg C

DESIGN TEMP.: 93 Deg C VELOCITY INLET / OUTLET: 1.49 / 1.49 m/s

PRESSURE DROP: 0.69 Bar G.

CONSTRUCTION

MODEL: MAKE: CARRIER NOTE 2 HEAT DUTY CAPACITY PER UNIT: 85 kW/SET NOTE 2

TYPE: AIR COOLED WATER CHILLER REFRIGERANT: R - 407C ( NON CFC) NOTE 2

CONFIGURATION: 3(THREE) UNIT X 50% BY PARALLEL LOCATION: ( )INDOOR, ( X )OUTDOOR

IN 1(ONE) SEIRIES

CONNECTION

PROPYLENE OXIDE NOZZLE SIZE / FLANGE RATING INLET: 6'' / 150#

PROPYLENE OXIDE NOZZLE SIZE / FLANGE RATING OUTLET: 6'' / 150#

HEAT EXCHANGER COMPRESSOR

MODEL: NO. OF REQ.: 1 SET NOTE 1 MODEL: NO. OF REQ.: 3 SETS NOTE 2

MAKE: NOTE 1 MAKE: CARLYLE (CARRIER MAKE) NOTE 2

TYPE: PLATE HEAT EXCHANGER TYPE: TWIN SCREW NOTE 2

PO.VOLUME FLOW RATE: GMP NOTE 1 POWER: kW NOTE 1

WATER VOLUME FLOW RATE: GMP NOTE 1

Cp. WATER: kJ/Kg-C NOTE 1

WATER PUMP CONDENSER

MODEL: NO. OF REQ.: SETS NOTE 1 MODEL: NO. OF REQ.: 3 SETS NOTE 1

MAKE: NOTE 1 MAKE: NOTE 1

TYPE: RATED BHP: kW NOTE 1 TYPE: NOTE 1

CAPACITY: m3/Hr NOTE 1 POWER: kW NOTE 1

SPEED: RATED EFF: % NOTE 1 NO. OF FAN: AIR FOLW RATE: CFM NOTE 1

MOTOR TYPE: NOTE 1 FAN SPEED: NOTE 1

MOTOR ENCLOSURE: NOTE 1 PHASE : HZ: VOLT: NOTE 1

PHASE : HZ: VOLT: NOTE 1 FULL LOADS AMPS. AMPS NOTE 1

OPERATING PRESSURE: NOTE 1

NOZZLE SIZE RATING FACE LOCATION

SUCTION

DISCH.
Sheet No. : 4 of 5
MECHANICAL DATASHEET PROJECT NO.: P11P3351
TREL Doc. No. :
FOR CHILLER UNIT 8-13-836
Date:02-08-2018 Rev.No.: 0A

MIXING TANK EVAPORATOR

MODEL: NO. OF REQ.: SET NOTE 1 MODEL: NO. OF REQ.: 3 SETS NOTE 1

MAKE: CAPACITY: m3 NOTE 1 MAKE: NOTE 1

WATER VOLUME FLOW RATE INLET/OUTLET: GMP NOTE 1 TYPE: NOTE 1

WATER TEMP.INLET/OUTLET: Deg C NOTE 2 WATER CONTENT: L NOTE 1


WATER FLOW RATE: L/S NOTE 1
PRESSURE DROP: Bar G. NOTE 1
TEST

TEST WITNESS

HYDRO TEST YES NO

PNEUMATIC TEST YES NO

PERFORMANCE TEST OF COMPLETE SYSTEM YES NO

MECH.RUNNING TEST YES NO

DISMANTLE & INSPECTION AFTER TEST YES NO

VISUAL INSPECTION YES NO

DIMENSIONAL INSPECTION YES NO

NDT YES NO

VIBRATION MESUREMENT YES NO

FIELD TEST YES YES

NOISE LEVEL TEST YES NO

NOTES: 1. DATASHEET SHALL BE COMPLETED BY VENDOR

2. VENDOR TO CONFIRM

3. FULLY COMPLY TO CLIENT SPECIFICATION NO.

4. REQUIRE 135 kW TO COOL TEMPERATURE OF PO. DOWN TO 1 Deg C AT 7,300 M3 WITHIN 24 Hr AND 35 kW IS LOSING THE ENERGY IN TANK

AND PIPING SYSTEM