You are on page 1of 2

R1 2.

5 MM2 LEGENDS
L1 : R-PHASE
Y1 L2 : Y-PHASE
L3 : B-PHASE
B1 L4 : DRYER ON-GREEN
L5 : FAN ON-GREEN
L6 : ANTIFREEZE TRIP-RED
MCB3 C2 MCB2 C1
OLR2 OLR1 L7 : LP TRIP-RED
R1 R4 R5 R2 R3 L8 : HP TRIP-RED
L9 : COMP. ON-GREEN
Y1 Y4 Y5 Y2 Y3 L10 : DRYER MANUAL ON- GREEN
FAN COMP.
L11 : DRYER AUTO ON- GREEN
B1 B4 B5 B2 B3
SW : LOCAL & REMOTE MODE
DTI1 : DRYER INLET H2 GAS TEMP.
DTI2 : DRYER OUTLET H2 GAS TEMP.
DTC1 : DEW POINT TEMP.

CTX-1
CTX-2
CTX-3

AM ASS DTC2 : ANTIFREEZE TEMP.


TS : LOCAL MODE ON/OFF
MCB4 MCB5
R1 0.75 MM2 CR2 DT C1
OLR2 DTC-1 DTC-2 LP HP OLR1

R6
01 3 3 4 5 7 9 10 12 14 15 16
B1
Y1
R1

10SEC
60 64 DTC-2 DELAY

24VDC OUTPUT
CR4
Y6
Y1

00 0 LP HP
DTI-1 65 DTC-1 (+) 8
61 PS
TFR 66 67 240VAC 11 13
L6
62 TO 9
CCH

4A 68 DTC-2 L4 6 L7 L8 C1 SV L9
C1

ANTIFREEZE
DTI-2 24VDC
Y1

02

69 (0)

DRYER ON
C2 DT

COMP ON
63

FAN ON
CT

HP TRIP
2.5 MM2

LP TRIP
L5

TRIP
6A

0 0 0

L1 R
MANUAL ON
20A N
L2 Y 0.75 MM2 L10
CR1
17 F4 18 19 20 CR1 24 24 AS BUILT DRG.
L3 B (+)
TS
SW
CR3
CT CR2 25
MCB1 22 CR3 23 24 77 77 77 77 77
70

OLR-2

OLR-1
F3 21

CR3

CR5

CR1

CR2

CR2
CR4 REMOTE
OFF
F2 27 26
VSS

CR4
OUTPUT

VM
AUTO ON

N
24VDC

REMOTE CR5 CR6


CR6

CR4

F3 ON 73 74 75 76

CR6
L11 CR1 CR2 SET POINTS
71 72
6 MM2
28 DTC-1 = 3°C, 2°C DIFF.
DTC-2 = 0°C
CR5

HP = 215-220 PSIG
(-)
LP = 20-24 PSIG
R Y B
N PS = 130-170 PSIG
INPUT SUPPLY
415VAC, 3-PHASE 2 1 3 4 5 6 7 8
50Hz
REMOTE TB32 TB33 TB34 TB35 TB36 TB37 TB38 TB39 DT = 10 SEC.
CONNECTION &
INPUT/OUTPUT TO
24VDC C 24VDC DRYER DRYER DRYER DRYER
OFF ON
C CT = 1 HOUR ON/.
OFF ON LOCAL OVER
PLANT DCS CMD CMD MODE LOAD F/B F/B 1 HOUR OFF
BHEL TECHNICAL SPEC. - TG60327 REV.14
MATERIAL CODE - W90414907353

OUT SIDE THE CONTROL PANEL SHEET 1 OF 2


TERMINAL BLOCK POTENTIAL FREE CONTACTS

TERMNAL NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45

FERRUL. NO. R Y B R3 Y3 B3 R5 Y5 B5 60 61 62 63 64 65 66 67 68 69 5 6 16 0 02 0 10 11 13 14 71 70 72 73 74 75 76 77 R6 Y6 01 00 E

COMPONENT DTI-1 DTI-2 DTC-1 DTC-2 24VDC COM. 24VDC DRYER DRYER DRYER DRYER COM.
IN PUT SUPPLY COMPR. FAN PS SV CCH HP LP OFF POINT ON LOCAL OVER OFF ON SPARE TRX INPUT TRX OUTPUT
SENSOR SENSOR SENSOR SENSOR POINT EARTH
CMD CMD MODE LOAD F/B F/B 415 V 220 VAC
VSS VOLTMETER SELECTOR 1 SALZER/KAYCEE 6A
SWITCH
V VOLTMETER 1 AE/MICO/IMP POWER 0-500V AC

TS TOGGLE SWITCH 1 SALZER/KAYCEE 6A

TFR CONTROL TRANSFORMER 1 LOGIC STAT/INDOCOIL 415V AC/220V AC, 100VA


TB TERMINAL BLOCK 35 CONNECTWELL STD

SW SELECTOR SWITCH 1 KAYCEE/SALZER 6A, 3 WAY SV SOLENOID VALVE 1 CASTEL/DANFOSS 3/8", MOC BRASS,220VAC

SMPS SWITCHED MODE POWER 1 SIEMENS/EAPL/SELECTRON 230VAC TO 24VDC CCH CRANK CASE HEATER 1 EMERSON/DANFOSS 58WATTS
SUPPLY
OLR2 OVER LOAD RELAY 1 SIEMENS/L&T/HAVELLS 0.8-1.25A ITEM DESCRIPTION QTY. MAKE SIZE
OLR1 OVER LOAD RELAY 1 SIEMENS/L&T/HAVELLS 4-6.3A
MCB4-5 MIN. CIRCUIT BREAKER 2 HAVELLS/SIEMENS/L&T 2A-2P
MCB3 MIN. CIRCUIT BREAKER 1 HAVELLS/SIEMENS/L&T 4A-3P

MCB2 MIN. CIRCUIT BREAKER 1 HAVELLS/SIEMENS/L&T 10A-3P

MCB1 MIN. CIRCUIT BREAKER 1 HAVELLS/SIEMENS/L&T 16A-3P

L10-11 INDICATING LAMP 2 ESSBEE/L&T/BCH PTR-AFLED


24VDC
L1-9 INDICATING LAMP 9 ESSBEE/L&T/BCH PTR-AFLED
230VAC

F4 FUSE 1 C&S/L&T/SIEMENS/HAVELLS 5 Amp


F1-3 FUSE 3 C&S/L&T/SIEMENS/HAVELLS 20/2A

DTC1-2 DIGITAL TEMP. CONTROLLER 2 MASIBUS/SUBZERO/SELECTRON 1 SET POINT 220VAC,RTD I/P

DTI1-2 DIGITAL TEMP. INDICATOR 2 MASIBUS/SUBZERO/SELECTRON 7505, 220VAC/EQ. AS BUILT DRG.


DT DELAY TIMER 1 SELECTRON/EAPL 3 SEC.-30 MIN.,220V AC

CTX1-3 CURRENT TRANSFORMER 3 RISHABH 20/5 A

0-24HRS, 220VAC
CT CYCLIC TIMER 1 GIC/EAPL/SELECTRON 1 HRS ON/1 HRS OFF

CR1-6 CONTROL RELAY 6 SALZER/OMRON/SIEMENS 24VDC

C1-2 CONTACTOR 2 SIEMENS/L&T/HAVELLS 3TF30-9A.,220VAC

ASS AMMETER SELECTOR SWITCH 1 KAYCEE/SALZER 6A

AM AMMETER 1 AE/MICO/IMP POWER 0-20 AMP

ITEM DESCRIPTION QTY. MAKE SIZE BHEL TECHNICAL SPEC. - TG60327 REV.14
MATERIAL CODE - W90414907353