Table Of Contents

TYPE DESCRIPTION PAGE

Cu/PVC 450/750 V (NYA) Copper Conductor Building Wire 2

Cu/PVC/PVC 300/500 V (NYM) Copper Conductor PVC Insulated and PVC Sheathed Indoor Cable 3-5

Cu/PVC 450/750 V (NYAF) Single Core Flexible Copper Conductor PVC Insulated 6

Cu/PVC/PVC 300/500 V (NYMHY) Multi Core Flexible Copper Conductor PVC Insulated & PVC Sheathed 7

Cu/PVC/PVC 0.6/1 kV (NYY) Copper Conductor PVC Insulated & PVC Sheathed 8 - 12
non Armoured Power Cable

Cu/PVC/PVC 0.6/1 kV Control Cable (NYY) Copper Conductor PVC Insulated & PVC Sheathed 13 - 14
non Armoured Control Cable

Cu/PVC/SFA/PVC 0.6/1 kV (NYFGbY) Copper Conductor PVC Insulated & PVC Sheathed 15 - 18
Armoured Power Cable

Cu/PVC/SFA/PVC 0.6/1 kV Control Cable (NYFGbY) Copper Conductor PVC Insulated & PVC Sheathed 19 - 20
Armoured Control Cable

Cu/PVC/SWA/PVC 0.6/1 kV (NYRGbY) Copper Conductor PVC Insulated & PVC Sheathed 21 - 24
Armoured Power Cable

Cu/PVC/SWA/PVC 0.6/1 kV Control Cable (NYRGbY) Copper Conductor PVC Insulated & PVC Sheathed 25 - 26
Armoured Control Cable

Cu/PVC/CTS/PVC 0.6/1 kV (NYSY) Copper Conductor PVC Insulated, Copper tape Screened and 27 - 30
PVC Sheathed Power Cable

Cu/PVC/CTS/PVC 0.6/1 kV Control Cable (NYSY) Copper Conductor PVC Insulated, Copper tape Screened and 31 - 32
PVC Sheathed Cotrol Cable

Cu/PVC/CWS/PVC 0.6/1 kV (NYCY) Copper Conductor PVC Insulated, Concentric Copper wire Screened 33 - 35
and PVC Sheathed Power Cable

Cu/PVC/CWS/PVC 0.6/1 kV Control Cable (NYCY) Copper Conductor PVC Insulated, Concentric Copper wire Screened 36 - 37
and PVC Sheathed Control Cable

Cu/PVC/DSTA/PVC 0.6/1 kV (NYBY) Copper Conductor PVC Insulated & PVC Sheathed 38 - 41
Armoured Power Cable

Cu/PVC/DSTA/PVC 0.6/1 kV Control Cable (NYBY) Copper Conductor PVC Insulated & PVC Sheathed 42 - 43
Armoured Control Cable

Derating Factors 44 - 48

Conversion Table of Conductor Size 49

Standards 50

www.kabelindo.co.id
Copper Conductor PVC Insulated Building Wire
Cu/PVC 450/750 V (NYA)
Specification :
SPLN 42-1 : 1991
IEC 227
SNI 04-6629 : 3-2006

Constructions: Applications:
1. Conductor: Permanent installation in conduit or exposed wiring in dry location.
Annealed plain copper round solid or round circular stranded
according to SPLN 4 2 - 3 ; IEC 60228 Note : [re] round solid conductor
[rm] circular stranded conductor
2. Insulation:
Extruded layer of Polyvinyl Chloride (PVC) complied with Packing : [C] Coil
SPLN 41-2 [D] Drum

Identification:
Yellow/Green strip, Light Blue, Black, Yellow, Red colour

DC. Resistance Current Carrying Short Circuit Current


Conductor Nominal Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
Nominal thickness Diameter of Cable bending delivery
crosssection Insulation (approx) (approx] radius Conductor Insulation in Pipe in Air 0.1 0.5 1.0 length
area Max Min second second
sq.mm mm mm kg/km mm Ohm/km M.Ohm. A A kA kA kA mm
1.5 re 0.7 3.3 19 59 12.1 50 15 24 0.55 0.24 0.17 100/C
1.5 rm 0.7 3.4 20 61 12.1 50 15 24 0.55 0.24 0.17 100/C
2.5 re 0.8 3.9 31 70 7.41 50 19 32 0.91 0.41 0.29 100/C
2.5 rm 0.8 4.2 33 76 7.41 50 19 32 0.91 0.41 0.29 100/C
4 re 0.8 4.4 45 79 4.61 50 25 42 1.45 0.65 0.46 100/C
4 rm 0.8 4.7 48 85 4.61 50 25 42 1.45 0.65 0.46 100/C
6 re 0.8 4.9 65 88 3.08 50 33 54 2.18 0.98 0.69 100/C
6 rm 0.8 5.4 71 97 3.08 50 33 54 2.18 0.98 0.69 100/C
10 rm 1.0 6.8 108 122 1.83 40 45 73 3.64 1.63 1.15 100/C
16 rm 1.0 8.0 175 144 1.15 40 61 98 5.82 2.60 1.84 3000/D
25 rm 1.2 9.8 273 176 0.727 40 83 129 9.09 4.07 2.88 3000/D
35 rm 1.2 11 367 198 0.524 40 103 158 12.73 5.69 4.03 2000/D
50 rm 1.4 13 523 234 0.387 30 132 197 18.18 S.13 5.75 1000/D
70 rm 1.4 15 692 270 0.268 30 165 245 25.46 11.38 8.05 1000/D
95 rm 1.6 17 962 306 0.193 30 197 290 34.55 15.45 10.93 1000/D
120 rm 1.6 19 1192 342 0.153 30 235 345 43.64 19.52 13.80 500/D
150 rm 1.8 21 1511 378 0.124 20 - 390 54.5 24.40 17.25 500/D
185 rm 2.0 23.5 1844 423 0.0991 20 - 445 67.28 30.09 21.28 500 /D
240 rm 2.2 26.5 2430 477 0.0754 20 - 525 87.28 39.03 27.60 500 /D
300 rm 2.4 29.5 3015 531 0.0601 20 - 605 109.10 48.79 34.50 500/D
400 rm 2.6 33.5 3863 603 0.0470 20 - 725 145.46 65.05 46.00 500/D

sales@kabelindo.co.id 1
Copper Conductor PVC Insulated & PVC Sheathed Indoor Cable
Cu/PVC/PVC 300/500 V (NYM)
Specification :
SPLN 42-2 : 1992
IEC 227
SNI : 04-6629.4-2006

Constructions: Applications:
1. Conductor: Permanent installation in conduit under plaster or exposed wiring
Annealed plain copper round solid or round circular in dry location.
stranded according to SPLN 42 - 2 ; IEC 60228
Note : [re] round solid conductor
2. Insulation: [rm] circular stranded conductor
Extruded layer of Polyvinyl Chloride (PVC] complied with
SPLN 41-2 Packing : [C] Coil
[D] Drum
Identification of core Identification of core
Light Blue, Black (SPLN) Ligh Blue, Brown (SNI)

3. Inner Covering / filler:


Extruded Polyvinyl Chloride [PVC], Black colour

4. Outer sheath:
Extruded Polyvinyl Chloride [PVC], White colour

Nominal DC. Resistance Current Carrying Short Circuit Current


Conductor Thickness Overall Weight Minimum at 20°C Capacity in air Capacity at Standard
Nominal Diameter of Cable bending delivery
crosssection Insulation Outer radius Conductor Insulation 30°C 40°C 0.1 0.5 1.0 length
area (approx) (approx) Max Min second second second
Sheath
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
2x1.5 re 0.7 1.2 8.8 112 158 12.1 50 19 16 0.55 0.24 0.17 100/C
2x 1.5 rm 0.7 1.2 9.1 119 164 12.1 50 19 16 0.55 0.24 0.17 100/C
2x2.5 re 0.8 1.2 9.6 145 173 7.41 50 25 22 0.91 0.41 0.29 100/C
2x2.5 rm 0.8 1.2 10.1 157 182 7.41 50 25 22 0.91 0.41 0.29 100/C
2x4 re 0.8 1.2 11.3 209 203 4.61 50 34 30 1.45 0.65 0.46 100/C
2x4 rm 0.8 1.2 11.9 227 210 4.61 50 34 30 1.45 0.65 0.46 100/C
2x6 re 0.8 1.2 12.3 267 221 3.08 50 44 39 2.18 0.98 0.69 100/C
2x6 rm 0.8 1.2 13.1 291 236 3.08 50 44 39 2.18 0.98 0.69 100/C
2x 10 rm 1.0 1.4 16 453 326 1.83 50 61 53 364 1.63 1.15 100/C
2x 16 rm 1.0 1.4 18.1 621 401 1.15 40 82 71 5.82 2.60 1.84 1000/D
2x25 rm 1.2 1.4 22.3 958 401 0.727 40 108 94 9.09 4.07 2.88 1000/D
2x35 rm 1.2 1.6 24.9 1249 448 0.524 40 134 117 12 73 5.69 4.03 1000/D

2 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Indoor Cable
Cu/PVC/PVC 300/500 V (NYM)
Specification :
SPLN 42-2 : 1992
IEC 227
SNI : 04-6629.4-2006

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular
stranded according to SPLN 4 1 - 1 ; IEC 60228
3. Inner Covering / filler:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour
Extruded layer of Polyvinyl Chloride (PVC] complied with
SPLN 41-2 4. Outer sheath:
Extruded Polyvinyl Chloride [PVC], White colour
Identification of core (SPLN)
Applications:
Colour of insulation Permanent installation in conduit under plaster or exposed wiring
No. of cores in dry location.
System - i System - o
Three Yellow/Green strip, Light Blue, Black Light Blue, Yellow, Black
Four Yellow/Green strip, Light Blue, Yellow, Black Light Blue, Red, Yellow, Black
Note : [re] round solid conductor
[rm] circular stranded conductor

Identification of core (SNI) Packing : [C] Coil


[D] Drum
No. of cores Colour of insulation
Three Yellow/Green strip, Light Blue, Brown
Four Yellow/Green strip, Light Blue, Black, Brown

Nominal DC. Resistance Current Carrying Short Circuit Current


Conductor Thickness Overall Weight Minimum at 20°C Capacity in air Capacity at Standard
Nominal Diameter of Cable bending delivery
crosssection Insulation Outer radius Conductor Insulation 30°C 40°C 0.1 0.5 1.0 length
(approx) (approx) Max Min second second second
area Sheath
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
3x1.5 re 0.7 1.2 9.2 132 166 12.1 50 19 16 0.55 0.24 0.17 100/C
3x1.5 rm 0.7 1.2 9.6 140 173 12.1 50 19 16 0.55 0.24 0.17 100/C
3x2.5 re 0.8 1.2 10.1 175 182 7.41 50 25 22 0.91 0.41 0.29 100/C
3x2.5 rm 0.8 1.2 10.6 188 191 7.41 50 25 22 0.91 0.41 0.29 100/C
3x4 re 0.8 1.2 11.9 254 214 4.61 50 34 30 1.45 0.65 0.46 100/C
3x4 rm 0.8 1.2 12.6 274 227 4.61 50 34 30 1.45 0.65 0.46 100/C
3x6 re 0.8 1.4 13 331 234 3.08 50 44 39 2.18 0.98 0.69 100/C
3x6 rm 0.8 1.4 13.8 359 248 3.08 50 44 39 2.18 0.98 0.69 100/C
3x10 rm 1.0 1.4 17 562 306 1.83 50 61 53 364 1.63 1.15 100/C
3x16 rm 1.0 1.4 19.2 784 346 1.15 40 82 71 5.82 2.60 1.84 1000/D
3x25 rm 1.2 1.6 23.6 1214 425 0.727 40 108 94 9.09 4.07 2.88 1000/D
3x35 rm 1.2 1.6 26.4 1593 475 0.524 40 134 117 12 73 5.69 4.03 1000/D

4x1.5 re 0.7 1.2 9.9 159 178 12.1 50 19 16 0.55 0.24 0.17 100/C
4x1.5 rm 0.7 1.2 10.3 169 185 12.1 50 19 16 0.55 0.24 0.17 100/C
4x2.5 re 0.8 1.2 10.9 214 196 7.41 50 25 22 0.91 0.41 0.29 100/C
4x2.5 rm 0.8 1.2 11.5 230 207 7.41 50 25 22 0.91 0.41 0.29 100/C
4x4 re 0.8 1.4 12.9 313 232 4.61 50 34 30 1.45 0.65 0.46 100/C
4x4 rm 0.8 1.4 13.6 338 245 4.61 50 34 30 1.45 0.65 0.46 100/C
4x6 re 0.8 1.4 14.1 411 254 3.08 50 44 39 2.18 0.98 0.69 100/C
4x6 rm 0.8 1.4 15 446 270 3.08 50 44 39 2.18 0.98 0.69 100/C
4x10 rm 1.0 1.4 18.5 701 333 1.83 50 61 53 364 1.63 1.15 100/C
4x16 rm 1.0 1.4 21 987 378 1.15 40 82 71 5.82 2.60 1.84 1000/D
4x25 rm 1.2 1.6 25.9 1,530 466 0.727 40 108 94 9.09 4.07 2.88 1000/D
4x35 rm 1.2 1.6 28.9 2,014 520 0.524 40 134 117 12 73 5.69 4.03 1000/D

sales@kabelindo.co.id 3
Copper Conductor PVC Insulated & PVC Sheathed Indoor Cable
Cu/PVC/PVC 300/500 V (NYM)
Specification :
SPLN 42-2 : 1992
IEC 227
SNI : 04-6629.4-2006

Constructions: Applications:
1. Conductor: Permanent installation in conduit under plaster or exposed wiring in
Annealed plain copper round solid or round circular stranded dry location.
according to SPLN 4 1 - 1 ; IEC 60228
Note : [re] round solid conductor
2. Insulation: [rm] circular stranded conductor
Extruded layer of Polyvinyl Chloride [PVC] complied with
SPLN 41-2 Packing : (C) Coil
(D) Drum
Identification of core: [SPLN]
Yellow/Green strip, Light Blue, Red, Yellow, Black,

Identification of core: [SNI]


Yellow/Green,Light Blue, Black, Brown and Grey

3. Inner Covering / filler:


Extruded Polyvinyl Chloride [PVC], Black colour

4. Outer sheath:
Extruded Polyvinyl Chloride [PVC], White colour

Nominal DC. Resistance Current Carrying Short Circuit Current


Conductor Thickness Overall Weight Minimum at 20°C Capacity in air Capacity at Standard
Nominal Diameter of Cable bending delivery
crosssection Insulation Outer radius Conductor Insulation 30°C 40°C 0.1 0.5 1.0 length
(approx) (approx) Max Min second second second
area Sheath
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
5x1.5 re 0.7 1.2 10.7 189 193 12.1 50 19 16 0.55 0.24 0.17 100/C
5x1.5 rm 0.7 1.2 11.1 201 200 12.1 50 19 16 0.55 0.24 0.17 100/C
5x2.5 re 0.8 1.2 11.8 256 212 7.41 50 25 22 0.91 0.41 0.29 100/C
5x2.5 rm 0.8 1.2 12.5 276 225 7.41 50 25 22 0.91 0.41 0.29 100/C
5x4 re 0.8 1.4 14 377 252 4.61 50 34 30 1.45 0.65 0.46 100/C
5x4 rm 0.8 1.4 14.8 407 266 4.61 50 34 30 1.45 0.65 0.46 100/C
5x6 re 0.8 1.4 15.4 499 277 3.08 50 44 39 2.18 0.98 0.69 100/C
5x6 rm 0.8 1.4 16.4 540 295 3.08 50 44 39 2.18 0.98 0.69 100/C
5x10 rm 1.0 1.4 20.2 854 364 1.83 50 61 53 3.64 1.63 1.15 100/C
5x16 rm 1.0 1.6 23 1208 414 1.15 40 82 71 5.82 2.60 1.84 1000/D
5x25 rm 1.2 1.6 28.3 1874 509 0.727 40 108 94 9.09 4.07 2.88 1000/D
5x35 rm 1.2 1.6 31.7 2471 571 0.524 40 134 117 12.73 5.69 4.03 1000/D

4 www.kabelindo.co.id
Single Core Flexible Copper Conductor PVC Insulated
Cu/PVC/PVC 450/750 V (NYAF)
Specification :
SPLN 42-3 : 1992
IEC 227
SNI : 04-6629.5-2006

Constructions: Applications:
1. Conductor: Used for fixed installation inside appliances, switchgear and
Annealed plain copper wires bunch stranded, according to controlgear.
SPLN 41-1; IEC 60228 Note : [f] Flexible bunched wire

2. Insulation: Packing : [C] Coil


Extruded layer of Polyvinyl Chloride [PVC] complied with [D] Drum
SPLN 41-2

Identification:
Yellow/Green strip, Light Blue, Black, Yellow, Red colour

DC. Resistance Current Carrying Short Circuit Current


Conductor
Nominal Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
Nominal No. of wire thickness Diameter of Cable bending delivery
crosssection and Insulation (approx) radius Conductor Insulation in Pipe in Air 0.1 0.5 1.0
(approx] length
area Diameter Max Min second second second
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
0.5 f 16/0.2 0.6 2.6 10 47 39.0 50 2.5 - 0.18 0.08 0.06 100/C
0.75 f 24/0.2 0.6 2.8 13 50 26.0 50 7 - 0.27 0.12 0.09 100/C
1.0 f 32/0.2 0.6 3 16 54 19.5 50 11 19 0.36 0.16 0.12 100/C
1.5 f 30/0.25 0.7 3.5 23 63 13.3 50 15 24 0.55 0.24 0.17 100/C
2.5 f 50/0.25 0.8 4.2 36 76 7.98 50 20 32 0.91 0.41 0.29 100/C
4f 56/0.3 0.8 5 51 90 4.95 50 25 41 1.45 0.65 0.46 100/C
6f 84/0.3 0.8 6.3 73 113 3.30 50 33 53 2.18 0.98 0.69 100/C
10 f 84/0.4 1.0 7.4 116 133 1.91 50 45 72 3.64 1.63 1.15 100/C
16 f 126/0.4 1.0 8.6 180 155 1.21 40 61 97 5.82 2.60 1.84 100/C
25 f 196/0.4 1.2 10.8 275 194 0.780 40 82 128 9.09 4.07 2.88 500/D
35 f 278/0.4 1.2 12 385 216 0.554 40 102 156 12.73 5.69 4.03 500/D
50 f 398/0.4 1.4 14.5 550 261 0.386 40 131 195 18.18 8.13 5.75 500/D
70 f 360/0.5 1.4 16.5 750 297 0.272 30 164 243 25.46 11.38 8.05 500/D
95 f 475/0.5 1.6 19.5 1000 351 0.206 30 205 287 34.55 15.45 10.93 500/D
120 f 608/0.5 1.6 21 1240 378 0.161 30 233 342 43.64 19.52 13.80 500/D
150 f 760/0.5 1.8 23.5 1550 423 0.129 30 - 386 54.5 24.40 17.25 500/D
185 f 925/0.5 2 26 1900 468 0.106 20 - 441 67.28 30.09 21.28 500/D
240 f 1221/0.5 2.2 29.5 2450 531 0.0801 20 - 525 87.28 39.03 27.60 500/D
300 f 1517/0.5 2.4 32.5 3025 585 0.0641 20 - 605 109.10 48.79 34.50 500/D

sales@kabelindo.co.id 5
Multi-Core Flexible Copper Conductor PVC Insulated & PVC Sheathed
Cu/PVC/PVC 300/500 V (NYMHY)
Specification :
SPLN 42-6 : 1991
IEC 227
SNI : 04-6629.5-2006

Constructions: Identification of core [SNI]


1. Conductor: No. of cores Colour of insulation
Annealed plain copper wires bunch stranded, according to Two Light Blue, Brown
SPLN 4 1 - 1 ; IEC 60228 Three Yellow/Green strip, Light Blue, Brown
Four Yellow/Green strip, Light Blue, Black, Brown
2. Insulation: Five Yellow/Green, Light Blue, Black, Brown, and Grey
Extruded layer of Polyvinyl Chloride [PVC] complied with SPLN 41-2
3. Outer Sheath:
Identification of core [SPLN] Extruded Polyvinyl Chloride [PVC] White colour

No. of cores Colour of insulation Applications:


System - i System - O These cables are useful for use in dry or damp locations for medium
Two - Light Blue, Black duties in domestic premises, kitchens, offices, washing machines,
Three Yellow/Green strip, Light Blue, Black Light Blue, Yellow, Black refrigerators, etc. Can be used for cooking and heating appliances
Four Yellow/Green strip, Light Blue, Yellow, Black Light Blue, Red, Yellow, Black
provided that the cable does not come in contact with the hot parts.
Five Yellow/Green strip, Light Blue, Red, Yellow, Black -
Note : [f] Flexible bunched wire
Packing : [C] Coil

Conductor Nominal thickness DC. Resistance Current Carrying Short Circuit Current
Weight Minimum at 20°C Capacity in air Capacity at Standard
Nominal No. of wire Overall of Cable bending
cross and Insulation Outer Diameter radius radius Conductor Insulation delivery
30°C 40°C 0.1 sec 0.5 sec 1.0 sec
section Diameter Sheath (approx) Max Min
length
area of wire
sq.mm mm mm mm mm mm mm Ohm/km M.Ohm.km A A kA kA kA m
2 x 0.5 f 16/0.2 0.6 0.8 6 56 108 39 40 2 1.8 0.18 0.08 0.06 100/C
2 x 0.75 f 24/0.2 0.6 O.B 6.5 56 117 26 40 6 5.5 0.27 0.12 0.09 100/C
2 x 1.0 f 32/0.2 0.6 0.8 6.7 66 121 19.5 40 10 9.2 0.36 0.16 0.12 100/C
2 x 1.5 f 30/0.25 0.7 0.9 7.7 90 139 13.3 40 15 13.8 0.55 0.24 0.17 100/C
2 x 2.5 f 50/0.25 0.8 1.0 9.4 140 169 7.98 40 20 18.4 0.91 0.41 0.29 100/C
2x4f 56/0.3 O.B 1.0 11.3 209 203 4.95 40 27.5 25.3 1.45 0.65 0.46 100/C
3 x 0.5 f 16/0.2 0.6 0.8 6.4 60 115 39 40 2 1.8 0.18 O.OB 0.06 100/C
3 x 0.75 f 24/0.2 0.6 0.8 6.8 77 122 26 40 6 5.5 0.27 0.12 0.09 100/C
3 x 1.0 f 32/0.2 0.6 0.8 7.1 90 128 19.5 40 10 9.2 0.36 0.16 0.12 100/C
3 x 1.5 f 30/0.25 0.7 O.B 8.3 147 149 13.3 40 15 13.8 0.55 0.24 0.17 100/C
3 x 2.5 f 50/0.25 0.8 1.0 10.2 190 184 7.98 40 20 18.4 0.91 0.41 0.29 100/C
3x4f 56/0.3 0.8 1.0 12 265 216 4.95 40 27.5 25.3 1.45 0.65 0.46 100/C
4 x 0.5 f 16/0.2 0.6 0.8 7 70 126 39 40 2 1.8 0.18 0.08 0.06 100/C
4 x 0.75 f 24/0.2 0.6 O.B 7.4 96 133 26 40 6 5.5 0.27 0.12 0.09 100/C
4 x 1.0 f 32/0.2 0.6 O.B B 121 144 19.5 40 10 9.2 0.36 0.16 0.12 100/C
4 x 1.5 f 30/0.25 0.7 0.9 9.1 167 164 13.3 40 15 13.B 0.55 0.24 0.17 100/C
4 x 2.5 f 50/0.25 0.8 1.0 11.2 237 202 7.98 40 20 18.4 0.91 0.41 0.29 100/C
4x4f 56/0.3 0.8 1.0 13.1 330 236 4.95 40 27.5 25.3 1.45 0.65 0.46 100/C
5 x 0.5 f 16/0.2 0.6 O.B 7.B 90 140 39 40 2 1.8 0.18 O.OB 0.06 100/C
5 x 0.75 f 24/0.2 0.6 O.B B.3 116 149 26 40 6 5.5 0.27 0.12 0.09 100/C
5 x 1.0 f 32/0.2 0.6 0.8 8.7 139 157 19.5 40 10 9.2 0.36 0.16 0.12 100/C
5 x 1.5 f 30/0.25 0.7 0.9 10.3 194 185 13.3 40 15 13.8 0.55 0.24 0.17 100/C
5 x 2.5 f 50/0.25 0.8 1.0 12.4 291 223 7.98 40 20 18.4 0.91 0.41 0.29 100/C
5x4f 56/0.3 0.8 1.0 14.3 391 257 4.95 40 27.5 25.3 1.45 0.65 0.46 100/C

6 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed non Armoured Power Cable
Cu/PVC/PVC 0.6/1 kV (NYY)
Specification :
SPLN 43-1 : 1994
IEC 60502-1 : 2004
SNI IEC :60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded Applications:
according to SPLN 4 1 - 1 ; IEC 60228 Indoor and outdoor induct installation or of laying in the ground
where not sustain mechanical damage.
2. Insulation:
Extruded layer of Polyvinyl Chloride [PVC] complied with SPLN Note : [re] round solid conductor
41- 2: IEC 60502-1 [rm] Circular stranded conductor

Identification of core Packing : [D] Drum


Light Blue

3. Outer Sheath:
Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite
and/or special flame retardant. PVC sheath can be provided on
request.

Nominal DC. Resistance Current Carrying Short Circuit Current


No. of cores Thickness Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
and cross Diameter of Cable bending delivery
section area Insulation Outer radius Conductor Insulation In Ground In Air 0.1 0.5 1.0 length
Sheath (approx) (approx) Max Min second second second
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
1 x 1.5 re 0.8 1.4 5.8 50 104 12.1 50 33 26 0.55 0.24 0.17 1000/D
1 x 1.5 rm 0.8 1.4 6 52 108 12.1 50 33 26 0.55 0.24 0.17 1000/D
1 x 2.5 re 0.8 1.4 6.2 63 112 7.41 50 45 35 0.91 0.41 0.29 1000/D
1 x 2.5 rm 0.8 1.4 6.5 67 117 7.41 50 45 35 0.91 0.41 0.29 1000/D
1 x 4 re 1.0 1.4 7.1 87 128 4.61 50 58 46 1.45 0.65 0.46 1000/D
1 x 4 rm 1.0 1.4 7.4 92 133 4.61 50 58 46 1.45 0.65 0.46 1000/D
1 x 6 re 1.0 1.4 7.6 110 137 3.08 50 74 58 2.18 0.98 0.69 1000/D
1 x 6 rm 1.0 1.4 8 117 144 3.08 50 74 58 2.18 0.98 0.69 1000/D
1 x 10 rm 1.0 1.4 8.8 163 158 1.83 50 98 80 3.64 1.63 1.15 1000/D
1 x 16 rm 1.0 1.4 9.9 227 178 1.15 40 129 105 5.82 2.60 1.84 1000/D
1 x 25 rm 1.2 1.4 11.6 336 209 0.727 40 169 140 9.09 4.07 2.88 1000/D
1 x 35 rm 1.2 1.4 12.7 437 229 0.524 40 210 175 12.73 5.69 4.03 1000/D
1 x50 rm 1.4 1.4 14.3 562 257 0.387 30 250 215 18.18 8.13 5.75 1000/D
1 x 70 rm 1.4 1.4 16 768 288 0.268 30 310 270 25.46 11.38 8.05 1000/D
1 x 95 rm 1.6 1.5 18.5 1049 333 0.193 30 375 335 34.55 15.45 10.93 1000/D
1 x 120 rm 1.6 1.5 20 1280 360 0.153 30 425 390 43.64 19.52 13.80 1000/D
1 x 150 rm 1.8 1.6 22.2 1275 400 0.124 20 480 445 54.55 24.40 17.25 1000/D
1 x 185 rm 2.0 1.7 24.6 1959 443 0.0991 20 550 510 67.28 30.09 21.28 1000/D
1 x 240 rm 2.2 1.8 27.7 2538 499 0.0754 20 640 620 87.28 39.03 27.60 1000/D
1 x 300 rm 2.4 1.9 30.7 3157 553 0.0601 20 730 710 109.10 48.79 34.50 1000/D
1 x 400 rm 2.6 2.0 34.2 3995 616 0.0470 20 855 850 145.46 65.05 46.00 1000/D
1 x 500 rm 2.8 2.1 38.1 5075 686 0.0366 20 990 1000 181.83 81.32 57.50 1000/D
1 x 630 rm 2.8 2.3 42.4 6449 763 0.0283 20 1126 1195 229.11 102.46 72.45 500/D

sales@kabelindo.co.id 7
Copper Conductor PVC Insulated & PVC Sheathed non Armoured Power Cable
Cu/PVC/PVC 0.6/1 kV (NYY)
Specification :
SPLN 43-1 : 1994
IEC 60502-1 : 2004
SNI IEC :60502-1 : 2009

Constructions: 3. Inner covering / filler :


1. Conductor: Extruded Polyvinyl Chloride (PVC) Black colour
Annealed plain copper round solid or round circular stranded
according to SPLN 4 1 - 1 ; IEC 60228 4. Outer Sheath:
Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite and/or
2. Insulation: special flame retardant. PVC sheath can be provided on request.
Extruded layer of Polyvinyl Chloride [PVC] complied with SPLN
41- 2: IEC 60502-1 Applications:
Indoor and outdoor induct installation or of laying in the ground where not
Identification of core (SPLN) sustain mechanical damage.
Light Blue, Black
Note : [re] round solid conductor
(SNI IEC) [rm] Circular stranded conductor
Light Blue, Brown
Packing : [D] Drum
DC. Resistance Current Carrying Short Circuit Current
No. of cores Nominal Thickness Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
and cross Diameter of Cable bending delivery
section area Insulation Outer radius Conductor Insulation In Ground In Air 0.1 0.5 1.0 length
Sheath (approx) (approx) Max Min second second second
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
2x1.5 re 0.8 1.8 10.8 159 194 12.1 50 27 21 0.55 0.24 0.17 1000/D
2x1.5 rm 0.8 1.8 11.1 168 200 12.1 50 27 21 0.55 0.24 0.17 1000/D
2x2.5 re 0.8 1.8 11.6 196 209 7.41 50 36 29 0.91 0.41 0.29 1000/D
2x2.5 rm 0.8 1.8 12.1 209 218 7.41 50 36 29 0.91 0.41 0.29 1000/D
2x4 re 1.0 1.8 13.3 269 239 4.61 50 47 38 1.45 0.65 0.46 1000/D
2x4 rm 1.0 1.8 13.9 289 250 4.61 50 47 38 1.45 0.65 0.46 1000/D
2x6 re 1.0 1.8 14.3 333 257 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x6 rm 1.0 1.8 15.1 359 272 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x10 rm 1.0 1.8 16.8 485 302 1.83 50 78 66 3.64 1.63 1.15 1000/D
2x16 rm 1.0 1.8 18.9 657 340 1.15 40 102 90 5.82 2.60 1.84 1000/D
2x25 rm 1.2 1.8 22.3 959 401 0.727 40 134 120 9.09 4.07 2.88 1000/D
2x35 rm 1.2 1.8 24.5 1224 441 0.524 40 160 150 12.73 5.69 4.03 1000/D
2x50 rm 1.4 1.8 27.7 4578 499 0.387 30 187 180 18.18 8.13 5.75 1000/D
2x70 rm 1.4 1.9 31.4 2131 565 0.268 30 230 230 25.46 11.38 8.05 1000/D
2x95 rm 1.6 2 36.4 2905 655 0.193 30 280 275 34.55 15A5 10.93 1000/D
2x120 rm 1.6 2.1 39.7 3531 715 0.153 30 320 320 43.64 19.52 13.80 500/D
2x150 rm 1.8 2.2 43.7 4321 787 0.124 20 355 379 54.55 24.40 17.25 500/D
2x185 rm 2.0 2.4 48.6 5368 875 0.0991 20 409 430 67.28 30.09 21.28 500/D
2x240 rm 2.2 2.6 55.1 6964 992 0.0754 20 472 510 87.28 39 03 27.60 500/D
2x300 rm 2.4 2.7 60.8 8605 1,094 0.0601 20 525 590 109.10 48.79 34.50 500/D

8 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed non Armoured Power Cable
Cu/PVC/PVC 0.6/1 kV (NYY)
Specification :
SPLN 43-1 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions: 3. Inner covering / filler :


1. Conductor: Extruded Polyvinyl Chloride (PVC) Black colour
Annealed plain copper round solid or round circular stranded
or sector shaped according to SPLN 4 1 - 1 ; IEC 60228 4. Outer Sheath:
Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite and/
2. Insulation: or special flame retardant. PVC sheath can be provided on request.
Extruded layer of Polyvinyl Chloride [PVC] complied with SPLN
41- 2: IEC 60502-1 Applications:
Indoor and outdoor induct installation or of laying in the ground where
Identification of core : (SPLN) not sustain mechanical damage.

Note : [re] round solid conductor


Colour of insulation [rm] Circular stranded conductor
System - i System - o (sm) sector shaped conductor
Yellow/Green strip, Light Blue, Black Light Blue, Yellow, Black
Packing : [D] Drum
Identification of core : [SNI]
Yellow/Green, Light Blue, Brown.

Nominal DC. Resistance Current Carrying Short Circuit Current


No. of cores Overall Weight Minimum Capacity at 30°C Capacity at
Thickness at 20°C Standard
and cross Diameter of Cable bending delivery
section area
Insulation Outer (approx) (approx) radius Conductor Insulation In Ground In Air 0.1 0.5 1.0 length
Sheath Max Min second second second
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
3 x 1.5 re 0.8 1.8 11.2 181 202 12.1 50 24 18 0.55 0.24 0.17 1000/D
3 x 1.5 rm 0.8 1.8 11.6 191 209 12.1 50 24 18 0.55 0.24 0.17 1000/D
3 x 2.5 re 0.8 1.8 12.1 229 218 7.41 50 32 25 0.91 0.41 0.29 1000/D
3 x 2.5 rm 0.8 1.8 12.6 245 227 7.41 50 32 25 0.91 0.41 0.29 1000/D
3x4 re 1.0 1.8 14 319 252 4.61 50 41 34 1.45 0.65 0.46 1000/D
3x4 rm 1.0 1.8 14.6 342 263 4.61 50 41 34 1.45 0.65 0.46 1000/D
3x6 re 1.0 1.8 15.1 401 272 3.08 50 52 44 2.18 0.98 0.69 1000/D
3x6 rm 1.0 1.8 15.9 433 286 3.08 50 52 44 2.18 0.98 0.69 1000/D
3 x 10 rm 1.0 1.8 17.8 596 320 1.83 50 69 60 3.64 1.63 1.15 1000/D
3 x 16 rm 1.0 1.8 20 822 360 1.15 40 89 80 5.82 2.60 1.84 1000/D
3 x 25 rm 1.2 1.8 23.6 1213 425 0.727 40 116 105 9.09 4.07 2.88 1000/D
3 x 35 rm 1.2 1.8 26 15.65 468 0.524 40 138 130 12.73 5.69 4.03 1000/D
3 x 50 sm 1.4 1.8 25.3 1898 455 0.387 30 165 160 18.18 8.13 5.75 1000/D
3 x 70 sm 1.4 2 28.6 2580 515 0.268 30 205 200 25.46 11.38 8.05 1000/D
3 x 95 sm 1.6 2.1 32.7 3485 589 0.193 30 245 245 34.55 15.45 10.93 1000/D
3 x 120 sm 1.6 2.2 35.5 4312 639 0.153 30 285 285 43.64 19.52 13.80 500/D
3 x 150 sm 1.8 2.3 39.2 5300 706 0.124 20 315 325 54.55 24.40 17.25 500/0
3 x 185 sm 2.0 2.5 43.8 6478 788 0.0991 20 355 370 67.28 30.09 21.28 500/D
3 x 240 sm 2.2 2.7 49.3 8491 887 0.0754 20 415 435 87.28 39.03 27.60 500/D
3 x 300 sm 2.4 3.1 55 10652 990 0.0601 20 535 600 109.10 48.79 34.50 500/D

sales@kabelindo.co.id 9
Copper Conductor PVC Insulated & PVC Sheathed non Armoured Power Cable
Cu/PVC/PVC 0.6/1 kV (NYY)
Specification :
SPLN 43-1 : 1994
IEC 60502-1 : 2004
SNI IEC :60502-1 : 2009

Constructions: 3. Inner covering / filler :


1. Conductor: Extruded Polyvinyl Chloride (PVC) Black colour
Annealed plain copper round solid or round circular stranded or
sector shaped according to SPLN 4 1 - 1 ; IEC 60228 4. Outer Sheath:
Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite and/or
2. Insulation: special flame retardant. PVC sheath can be provided on request.
Extruded layer of Polyvinyl Chloride [PVC] complied with SPLN 41- 2:
IEC 60502-1 Applications:
Indoor and outdoor induct installation or of laying in the ground where not
Identification of core : (SPLN) sustain mechanical damage.

Colour of insulation Note : [re] round solid conductor


System - i System - 0
[rm] Circular stranded conductor
Yellow/Green strip, Light Blue, Yellow, Black Light Blue, Red, Yellow, Black
(sm) sector shaped conductor

Packing : [D] Drum


Identification Core : (SNI IEC)
Yellow/Green Strip, Light Blue, Brown

DC. Resistance Current Carrying Short Circuit Current


No. of cores Nominal Thickness Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
and cross Diameter of Cable bending delivery
section area Insulation Outer radius Conductor Insulation In Ground In Air 0.1 0.5 1.0 length
(approx) (approx) Max Min second second second
Sheath
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
4 x 1.5 re 0.8 1.8 12 213 216 12.1 50 24 18 0.55 0.24 0.17 1000/D
4 x 1.5 rm 0.8 1.8 12.4 224 223 12.1 50 24 18 0.55 0.24 0.17 1000/D
4 x 2.5 re 0.8 1.8 13 273 234 7.41 50 32 25 0.91 0.41 0.29 1000/D
4 x 2.5 rm 0.8 1.8 13.6 292 245 7.41 50 32 25 0.91 0.41 0.29 1000/D
4x4 re 1.0 1.8 15.1 385 272 4.61 50 41 34 1.45 0.65 0.46 1000/D
4x4 rm 1.0 1.8 15.8 413 284 4.61 50 41 34 1.45 0.65 0A6 1000/D
4x6 re 1.0 1.8 16.3 490 293 3.08 50 52 44 2.18 0.98 0.69 1000/D
4x6 rm 1.0 1.8 17.2 527 310 3.08 50 52 44 2.18 0.98 0.69 1000/D
4 x 10 rm 1.0 1.8 21 743 349 1.83 50 69 60 3.64 1.63 1.15 1000/D
4 x 16 rm 1.0 1.8 24 1035 392 1.15 40 89 80 5.82 2.60 1.84 1000/D
4 x 25 rm 1.2 1.8 28 1541 466 0.727 40 116 105 9.09 4.07 2.88 1000/D
4 x 35 rm 1.2 1.8 30 1999 515 0.524 40 138 130 12.73 5.69 4.03 1000/D
4 x 50 sm 1.4 1.9 32 2498 540 0.387 30 165 160 18.18 8.13 5.75 1000/D
4 x 70 sm 1.4 2.1 36 3374 614 0.268 30 205 200 25.46 11.38 8.05 1000/D
4 x 95 sm 1.6 2.2 40 4536 697 0.193 30 245 245 34.55 15.45 10.93 1000/D
4 x 120 sm 1.6 2.3 44 5676 767 0.153 30 285 285 43.64 19.52 13.80 500/D
4 x 150 sm 1.8 2.5 49 6910 833 0.124 20 315 325 54.55 24.40 17.25 500/D
4 x 185 sm 2.0 2.7 53 8596 940 0.0991 20 355 370 67.28 30.09 21.28 500/D
4 x 240 sm 2.2 2.9 60 11087 1,053 0.0754 20 415 435 87.28 39.03 27.60 500/D
4 x 300 sm 2.4 3.1 66 13549 1,177 0.0601 20 465 500 109.10 48.79 34.50 500/D

10 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed non Armoured Power Cable
Cu/PVC/PVC 0.6/1 kV (NYY)
Specification :
SPLN 43-1 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions: 4. Outer sheath


1. Conductor: Extruded Polyvinyl Chloride (PVC) Black colour, Anti termite
Annealed plain copper round solid or round circular stranded and / or special flame retardant, PVC sheath can be provided
according to SPLN 4 1 - 1 ; IEC 60228 on request.

2. Insulation: Applications:
Extruded layer of Polyvinyl Chloride (PVC) complied with SPLN Indoor and outdoor induct installation or of laying in the ground
41-2 : IEC 60502-1 where not sustain mechanical damage.

Identification of core : (SPLN) Note : [re] round solid conductor


Yellow/Green strip, Light Blue, Red, Yellow, Black [rm] circular stranded conductor

(SNI IEC) : Packing : [D] Drum


Yellow/Green strip, Light Blue, Black, Brown, Grey.

3. Inner covering / filler


Extruded Polyvinyl Chloride (PVC) Black colour

DC. Resistance Current Carrying Short Circuit Current


No. of cores Nominal Thickness Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
and cross Diameter of Cable bending
delivery
section area Insulation Outer radius Conductor Insulation In Ground In Air 0.1 0.5 1.0 length
(approx) (approx)
Sheath Max Min second second second
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
5 x 1.5 re 0.8 1.8 12.8 255 230 12.1 50 24 18 0.55 0.24 0.17 1000/D
5 x 1.5 rm 0.8 1.8 13.3 268 239 12.1 50 24 18 0.55 0.24 0.17 1000/D
5 x 2.5 re 0.8 1.8 14 329 252 7.41 50 32 25 0.91 0.41 0.29 1000/D
5 x 2.5 rm 0.8 1.8 14.6 352 263 7.41 50 32 25 0.91 0.41 0.29 1000/D
5 x 4 re 1.0 1.8 16.3 470 293 4.61 50 41 34 1.45 0.65 0.46 1000/D
5 x 4 rm 1.0 1.8 17.1 505 308 4.61 50 41 34 1.45 0.65 0.46 1000/D
5 x 6 re 1.0 1.8 17.7 602 319 3.08 50 52 44 2.18 0.98 0.69 1000/D
5 x 6 rm 1.0 1.8 18.6 650 335 3.08 50 52 44 2.18 0.98 0.69 1000/D
5 x 10 rm 1.0 1.8 21.1 912 380 1.83 50 69 60 3.64 1.63 1.15 1000/D
5 x 16 rm 1.0 1.8 23.8 1279 428 1.15 40 89 80 5.82 2.60 1.84 1000/D
5 x 25 rm 1.2 1.8 28.3 1914 509 0.727 40 116 105 9.09 4.07 2.88 1000/D
5 x 35 rm 1.2 1.9 31.5 2505 567 0.524 40 138 130 12.73 5.69 4.03 1000/D
5 x 50 rm 1.4 2.0 36.4 3273 655 0.387 30 165 160 18.18 8.13 5.75 1000/D

sales@kabelindo.co.id 11
Copper Conductor PVC Insulated & PVC Sheathed non Armoured Control Cable
Cu/PVC/PVC 0.6/1 kV (NYY)
Specification :
SPLN 43-1 : 1994
IEC 60502-1 : 2004
SNI IEC :60502-1 : 2009

Constructions:
1. Conductor: 3. Inner Covering / filler:
Annealed plain copper round solid or round circular stranded Extruded Polyvinyl Chloride [PVC], Black colour
according to SPLN 4 1 - 1 ; IEC 60228
4. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite and/or
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : special flame retardant. PVC sheath can be provided on request
IEC 60502-1
Applications:
Identification of core (SPLN) Indoor and outdoor induct : installation or of laying in the ground where
not sustain mechanical damage.
Colour of insulation
System - i System - 0
Note : [re] round solid conductor
Yellow/Green strip, Black with White number Black with White number
[rm] circular stranded conductor

(SNI IEC): Black, with White Number Packing : (D) Drum

DC. Resistance Current Carrying Short Circuit Current


No. of cores Nominal Thickness Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
and cross Diameter of Cable bending delivery
section area Insulation Outer radius Conductor Insulation In Ground In Air 0.1 0.5 1.0 length
Sheath (approx) (approx) Max Min second second second
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x1.5 re 0.8 1.8 14.5 324 261 12.1 50 17 13 0.55 0.24 0.17 1000/D
7x1.5 rm 0.8 1.8 15 341 270 12.1 50 17 13 0.55 0.24 0.17 1000/D
8x1.5 re 0.8 1.8 15.5 362 279 12.1 50 16 12 0.55 0.24 0.17 1000/D
8x1.5 rm 0.8 1.8 16 381 288 12.1 50 16 12 0.55 0.24 0.17 1000/D
10x1.5 re 0.8 1.8 17.4 434 313 12.1 50 15 12 0.55 0.24 0.17 1000/D
10x1.5 rm 0.8 1.8 18.1 458 326 12.1 50 15 12 0.55 0.24 0.17 1000/D
12x1.5 re 0.8 1.8 17.9 480 322 12.1 50 14 11 0.55 0.24 0.17 1000/D
12x1.5 rm 0.8 1.8 18.6 506 335 12.1 50 14 11 0.55 0.24 0.17 1000/D
14x1.5 re 0.8 1.8 18.7 542 337 12.1 50 13 11 0.55 0.24 0.17 1000/D
14x1.5 rm 0.8 1.8 19.5 572 351 12.1 50 13 11 0.55 0.24 0.17 1000/D
16x1.5 re 0.8 1.8 19.5 599 351 12.1 50 12 10 0.55 0.24 0.17 1000/D
16x1.5 rm 0.8 1.8 20.3 632 365 12.1 50 12 10 0.55 0.24 0.17 1000/D
19x1.5 re 0.8 1.8 20.4 670 367 12.1 50 12 9 0.55 0.24 0.17 1000/D
19x1.5 rm 0.8 1.8 21.3 707 383 12.1 50 12 9 0.55 0.24 0.17 1000/D
21x1.5 re 0.8 1.8 21.4 728 385 12.1 50 11 9 0.55 0.24 0.17 1000/D
21x1.5 rm 0.8 1.8 22.3 768 401 12.1 50 11 9 0.55 0.24 0.17 1000/D
24x1.5 re 0.8 1.8 23.4 821 421 12.1 50 11 8 0.55 0.24 0.17 1000/D
24x1.5 rm 0.8 1.8 24.4 866 439 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 re 0.8 1.8 24.6 970 443 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 rm 0.8 1.8 25.7 1024 463 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 re 0.8 1.8 27.3 1226 491 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 rm 0.8 1.8 28.5 1294 513 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 re 0.8 1.9 32 1585 576 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 rm 0.8 1.9 33.4 1673 601 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 re 0.8 2.0 33 1815 594 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 rm 0.8 2.0 34.6 1916 623 12.1 50 11 8 0.55 0.24 0.17 1000/D

12 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed non Armoured Control Cable
Cu/PVC/PVC 0.6/1 kV (NYY)
Specification :
SPLN 43-1 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions: 4. Outer sheath:


1. Conductor: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
Annealed plain copper round solid or round circular stranded and/or special flame retardant. PVC sheath can be provided on
according to SPLN 4 1 - 1 ; IEC 60228 request

2. Insulation: Applications:
Extruded layer of Polyvinyl Chloride (PVC] complied with Indoor and outdoor induct : installation or of laying in the
SPLN 41-2 : IEC 60502-1 ground where not sustain mechanical damage.

Identification of core (SPLN) Note : [re] round solid conductor


[rm] circular stranded conductor
Colour of insulation
System - i System - 0 Packing : (D) Drum
Yellow/Green strip, Black with White number Black with White number

(SNI IEC): Black, with White Number

3. Inner Covering / filler:


Extruded Polyvinyl Chloride [PVC], Black colour
DC. Resistance Current Carrying Short Circuit Current
No. of cores Nominal Thickness Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
and cross Diameter of Cable bending delivery
section area Insulation Outer radius Conductor Insulation In Ground In Air 0.1 0.5 1.0 length
Sheath (approx) (approx) second second second
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x2.5 re 0.8 1.8 15.8 421 284 7.41 50 26 21 0.91 0.41 0.29 1000/D
7x2.5 rm 0.8 1.8 16.5 450 297 7.41 50 26 21 0.91 0.41 0.29 1000/D
8x2.5 re 0.8 1.8 16.9 471 304 7.41 50 23 18 0.91 0.41 0.29 1000/D
8x2.5 rm 0.8 1.8 17.7 505 319 7.41 50 23 18 0.91 0.41 0.29 1000/D
10x2.5 re 0.8 1.8 19.1 570 344 7.41 50 21 17 0.91 0.41 0.29 1000/D
10x2.5 rm 0.8 1.8 20.1 611 362 7.41 50 21 17 0.91 0.41 0.29 1000/D
12x2.5 re 0.8 1.8 19.7 637 355 7.41 50 20 16 0.91 0.41 0.29 1000/D
12x2.5 rm 0.8 1.8 20.7 682 373 7.41 50 20 16 0.91 0.41 0.29 1000/D
14x2.5 re 0.8 1.8 20.5 724 369 7.41 50 18 15 0.91 0.41 0.29 1000/D
14x2.5 rm 0.8 1.8 21.6 777 389 7.41 50 18 15 0.91 0.41 0.29 1000/D
16x2.5 re 0.8 1.8 21.5 804 387 7.41 50 17 14 0.91 0.41 0.29 1000/D
16x2.5rm 0.8 1.8 22.6 863 407 7.41 50 17 14 0.91 0.41 0.29 1000/D
19x2.5 re 0.8 1.8 22.5 907 405 7.41 50 17 13 0.91 0.41 0.29 1000/D
19x2.5 rm 0.8 1.8 23.6 974 425 7.41 50 17 13 0.91 0.41 0.29 1000/D
21x2.5 re 0.8 1.8 23.6 989 425 7.41 50 16 12 0.91 0.41 0.29 1000/D
21x2.5 rm 0.8 1.8 24.9 1062 448 7.41 50 16 12 0.91 0.41 0.29 1000/D
24x2.5 re 0.8 1.8 25.9 1118 466 7.41 50 15 11 0.91 0.41 0.29 1000/D
24x2.5 rm 0.8 1.8 27.3 1200 491 7.41 50 15 11 0.91 0.41 0.29 1000/D
30x2.5 re 0.8 1.8 27.3 1335 491 7.41 50 14 11 0.91 0.41 0.29 1000/D
30x2.5 rm 0.8 1.8 28.8 1433 518 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2.5 re 0.8 1.9 30.5 1718 549 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2.5 rm 0.8 1.9 32.3 1846 581 7.41 50 14 11 0.91 0.41 0.29 1000/D
52x2.5 re 0.8 2.0 35.8 2220 644 7.41 50 14 11 0.91 0.41 0.29 1000/D
52x2.5 rm 0.8 2.0 37.9 2384 682 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 re 0.8 2.1 37 2552 666 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 rm 0.8 2.1 39.1 2741 704 7.41 50 14 11 0.91 0.41 0.29 1000/D

sales@kabelindo.co.id 13
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/SFA/PVC 0.6/1 kV (NYFGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC :60502-1 : 2009

Constructions: 4. Armour :
1. Conductor: A layer of galvanized flat steel wires with a counter helix layer of
Annealed plain copper round solid or round circular stranded galvanized steel tape.
according to SPLN 4 1 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite and/
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : or special flame retardant, PVC sheath can be provided on request.
IEC 60502-1
Applications:
Identification of core (SPLN) For general purpose power distribution in dry or wet location, best
Light Blue, Black suitable for direct burying in ground.

( SNI IEC ) Note : [re] round solid conductor


Light Blue, Brown. [rm] circular stranded conductor

3. Inner Covering / filler: Packing : [D] Drum


Extruded Polyvinyl Chloride [PVC], Black colour

DC. Resistance Current Carrying Short Circuit Current


No. of Thickness Armour Thickness Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
cores of Flat of outer Diameter of Cable bending delivery
and cross Insulation Steel sheath (approx) (approx] radius Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
section (nom) Size (nom) Max Min second second second
mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
2x25 rm 1.2 4x0.8 1.8 24.9 1383 448 0.727 40 134 120 9.09 4.07 2.88 1000/D
2x 35 rm 1.2 4x0.8 1.8 27.1 1709 448 0.524 40 160 150 12.73 5.69 4.03 1000/D
2x50 rm 1.4 4x0.8 1.9 30.5 2170 549 0.387 30 187 180 18.18 8.13 5.75 1000/D
2x70 rm 1.4 4x0.8 2.0 34.5 2846 621 0.268 30 230 230 25.46 11.38 8.05 1000/D
2x95 rm 1.6 4x0.8 2.1 39.2 3702 706 0.193 30 280 275 34.55 15.45 10.93 1000/D
2x120rm 1.6 4x0.8 2.2 42.5 4423 765 0.153 30 320 320 43.84 19.52 13.80 1000/D
2x150rm 1.8 4x0.8 2.3 46.9 5347 844 0.124 20 355 379 54.55 24.40 17.25 500/D
2x185rm 2.0 4x0.8 2.5 51.8 6501 932 0.0991 20 409 430 67.28 30.09 21.28 500/D
2x240rm 2.2 4x0.8 2.7 58 8231 1.044 0.0754 20 472 510 87.28 39.03 27.60 250/D
2x300rm 2.4 4x0.8 2.8 64.1 10081 1.154 0.0601 20 525 590 109.10 48.79 34.50 250/D

14 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/SFA/PVC 0.6/1 kV (NYFGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC 60902-1 : 2009

Constructions: 4. Armour :
1. Conductor: A layer of galvanized flat steel wires with a counter helix layer
Annealed plain copper round solid or round circular stranded or of galvanized steel tape.
sector shape according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : and/or special flame retardant, PVC sheath can be provided on
IEC 60502-1 request.

Identification of core (SPLN) Applications:


For general purpose power distribution in dry or wet location,
Colour of insulation best suitable for direct burying in ground.
System - i System - 0
Yellow/Green strip, Light Blue, Black Light Blue, Yellow, Black Note : [re] round solid conductor
[rm] circular stranded conductor
( SNI IEC ) [sm] sector shaped conductor
Yellow/Green Strip, Light Blue, Brown.
Packing : [D] Drum
3. Inner Covering / filler:
Extruded Polyvinyl Chloride [PVC], Black colour

DC. Resistance Current Carrying Short Circuit Current


No. of Thickness Armour Thickness Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
cores of Flat of outer Diameter of Cable bending delivery
and cross Insulation Steel sheath (approx) (approx] radius Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
section (nom) Size (nom) second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
3 x16 rm 1.0 4x0.8 1.8 22.6 1010 407 1.15 40 89 80 5.82 2.60 1.84 1000/D
3 x 25 rm 1.2 4x0.8 1.8 26.2 1695 472 0.727 40 116 105 9.09 4.07 2.88 1000/D
3 x 35 rm 1.2 4x0.8 1.8 28.6 2084 515 0.524 40 138 130 12.73 5.69 4.03 1000/D
3 x 50 sm 1.4 4x0.8 1.9 28.1 2403 506 0.387 30 165 160 18.18 8.13 5.75 1000/D
3 x 70 sm 1.4 4x0.8 2.0 31.3 3112 563 0.268 30 205 200 25.46 11.38 8.05 1000/D
3 x 95 sm 1.6 4x0.8 2.2 35.6 4151 641 0.193 30 245 245 34.55 15.45 10.93 1000/D
3 x120 sm 1.6 4x0.8 2.3 38.4 5041 691 0.153 30 285 285 43.64 19.52 13.80 1000/D
3 x150 sm 1.8 4x0.8 2.4 42.2 6121 760 0.124 20 315 325 54.55 24.40 17.25 500/D
3 x185 sm 2.0 4x0.8 2.6 46.8 7377 842 0.0991 20 355 370 67.28 30.09 21.28 500/D
3 x 240 sm 2.2 4x0.8 2.8 52.3 9536 941 0.0754 20 415 435 87.28 39.03 27.60 250/D
3 x 300 sm 2.4 4x0.8 3.0 57.4 11717 1.033 0.0601 20 465 500 109.10 48.79 34.50 250/D

sales@kabelindo.co.id 15
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/PVC 0.6/1 kV (NYFGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC :60502-1 : 2009

Constructions: 4. Armour :
1. Conductor: A layer of galvanized flat steel wires with a counter helix layer
Annealed plain copper round solid or round circular stranded or of galvanized steel tape.
sector shape according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : and/or special flame retardant, PVC sheath can be provided on
IEC 60502-1 request.

Identification of core : (SPLN) Applications:


For general purpose power distribution in dry or wet location,
Colour of insulation
best suitable for direct burying in ground.
System - i System - 0
Yellow/Green strip, Light Blue, Yellow, Black Light Blue, Red, Yellow, Black Note : [re] round solid conductor
[rm] circular stranded conductor
( SNI IEC ) Yellow/Green Strip, Light Blue, Black, Brown. [sm] sector shaped conductor

3. Inner Covering / filler: Packing : [D] Drum


Extruded Polyvinyl Chloride [PVC], Black colour

DC. Resistance Current Carrying Short Circuit Current


No. of Thickness Armour Thickness Overall Weight Minimum at 20°C Capacity at 30°C Capacity at Standard
cores of Flat of outer Diameter of Cable bending delivery
and cross Insulation Steel sheath (approx) (approx] radius Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
section (nom) Size (nom) Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
4 x10 rm 1.0 4 x 0.8 1.8 23 1101 349 1.83 50 69 80 3.64 1.63 1.15 1000/D
4 x 16 rm 1.0 4 x 0.8 1.8 26 1455 392 1.15 40 89 80 5.82 2.60 1.84 1000/D
4 x 25 rm 1.2 4 x 0.8 1.8 30 2093 466 0.727 40 116 105 9.09 48.79 2.88 1000/D
4 x 35 rm 1.2 4 x 0.8 1.9 33 2602 515 0.524 40 138 130 12.73 4.07 4.03 1000/D
4 x 50 sm 1.4 4 x 0.8 2.0 35 3080 541 0.387 30 165 160 18.18 5.69 5.75 1000/D
4 x 70 sm 1.4 4 x 0.8 2.1 38 4093 614 0.268 30 205 200 25.46 8.13 8.05 1000/D
4 x 95 sm 1.6 4 x 0.8 2.3 43 5370 697 0.193 30 245 245 34.55 11.38 10.93 500/D
4 x120 sm 1.6 4 x 0.8 2.4 47 6563 767 0.153 30 285 285 43.64 15.45 13.80 500/D
4 x150 sm 1.8 4 x 0.8 2.6 51 7938 833 0.124 20 315 325 54.55 19.52 17.25 500/D
4 x 185 sm 2.0 4 x 0.8 2.8 56 9756 940 0.0991 20 355 370 67.28 24.40 21.28 500/D
4 x 240 sm 2.2 4 x 0.8 3.0 62 12409 1.053 0.0754 20 415 435 87.28 30.09 27.60 250/D
4 x 300 sm 2.4 4 x 0.8 3.2 68 15104 1.177 0.0601 20 465 500 109.10 39.03 34.50 250/D

16 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/SFA/PVC 0.6/1 kV (NYFGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions: 4. Armour :
1. Conductor: A layer of galvanized flat steel wires with a counter helix layer
Annealed plain copper round solid or round circular stranded of galvanized steel tape.
according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
Extruded layer of Polyvinyl Chloride (PVC] complied with and/or special flame retardant, PVC sheath can be provided on
SPLN 41-2 : IEC 60502-1 request.

Identification of core : (SPLN) Applications:


Yellow/Green Strip, Light Blue, Red, Yellow, Black. For general purpose power distribution in dry or wet location,
best suitable for direct burying in ground.
( SNI IEC )
Yellow/Green Strip, Light Blue, Black, Brown, Grey. Note : [re] round solid conductor
[rm] circular stranded conductor
3. Inner Covering / filler:
Extruded Polyvinyl Chloride [PVC], Black colour Packing : [D] Drum

DC. Resistance Current Carrying Conductor Short Circuit


No. of Thickness Armour Thickness Overall Weight Minimum at 20°C Capacity at 30°C Current Capacity at Standard
cores of Flat of outer Diameter of Cable bending delivery
and cross Insulation Steel sheath (approx) (approx] radius Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
section (nom) Size (nom) Max Min second second second
sq.mm mm mm mm mm kg/ mm Ohm/km M.Ohm.km A A kA kA kA m
5 x10 rm 1.0 4 x 0.8 1.8 24.1 1323 434 1.83 50 69 60 3.64 1.63 1.15 1000/D
5 x 16 rm 1.0 4 x 0.8 1.8 26.8 1750 482 1.15 40 89 80 5.82 2.60 1.84 1000/D
5 x 25 rm 1.2 4 x 0.8 1.9 31.3 2519 563 0.727 40 116 105 9.09 4.07 2.88 1000/D
5 x 35 rm 1.2 4 x 0.8 2.0 34.7 3158 625 0.524 40 138 130 12.73 5.69 4.03 1000/D
5 x 50 sm 1.4 4 x 0.8 2.1 39.7 4117 715 0.387 30 165 160 18.18 8.13 5.75 1000/D

sales@kabelindo.co.id 17
Copper Conductor PVC Insulated & PVC Sheathed Armoured Control Cable
Cu/PVC/SFA/PVC 0.6/1 kV (NYFGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC :60502-1 : 2009

Constructions:
1. Conductor: 4. Armour :
Annealed plain copper round solid or round circular stranded or A layer of galvanized flat steel wires with a counter helix layer
sector shape according to SPLN 41 - 1 ; IEC 60228 of galvanized steel tape.

2. Insulation: 5. Outer sheath:


Extruded layer of Polyvinyl Chloride (PVC] complied with Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
SPLN 41-2 : IEC 60502-1 and/or special flame retardant, PVC sheath can be provided
on request.
Identification of core : (SPLN)
Applications:
Colour of insulation For general purpose power distribution in dry or wet location,
System - i System - 0 best suitable for direct burying in ground.
Yellow/Green strip, Black with White number Black with White number
Note : [re] round solid conductor
( SNI IEC ) Black with White number [rm] circular stranded conductor

3. Inner Covering / filler: Packing : [D] Drum


Extruded Polyvinyl Chloride [PVC], Black colour

Thickness Armour Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
No. of of Flat of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
cores Insulation Steel sheath radius delivery
and cross Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
Size (approx) (approx]
section Max Min second second second
(nom) (nom)
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x1.5 re 0.8 4x0.8 1.8 18.6 727 335 12.1 50 17 13 0.55 0.24 0.17 1000/D
7x1.5 rm 0.8 4x0.8 1.8 19.2 777 346 12.1 50 17 13 0.55 0.24 0.17 1000/D
8x1.5 re 0.8 4x0.8 1.8 19.7 792 355 12.1 50 16 12 0.55 0.24 0.17 1000/D
8x1.5 rm 0.8 4x0.8 1.8 20.3 848 365 12.1 50 16 12 0.55 0.24 0.17 1000/D
10x1.5 re 0.8 4x0.8 1.8 21.7 929 391 12.1 50 15 11 0.55 0.24 0.17 1000/D
10x1.5 rm 0.8 4x0.8 1.8 22.6 997 407 12.1 50 15 11 0.55 0.24 0.17 1000/D
12x1.5 re 0.8 440.8 1.9 23 1117 414 12.1 50 14 11 0.55 0.24 0.17 1000/D
12x1.5 rm 0.8 4x0.8 1.8 23.8 1199 428 12.1 50 14 11 0.55 0.24 0.17 1000/D
14x1.5 re 0.8 4x0.8 1.8 24 1197 432 12.1 50 13 10 0.55 0.24 0.17 1000/D
14x1.5 rm 0.8 4x0.8 1.8 24.7 1287 445 12.1 50 13 10 0.55 0.24 0.17 1000/D
16x1.5 re 0.8 4x0.8 1.8 25 1310 450 12.1 50 12 10 0.55 0.24 0.17 1000/D
16x1.5 rm 0.8 4x0.8 1.9 25.6 1382 461 12.1 50 12 10 0.55 0.24 0.17 1000/D
19x1.5 re 0.8 4x0.8 1.8 26 1391 468 12.1 50 12 9 0.55 0.24 0.17 1000/D
19x1.5 rm 0.8 4x0.8 1.8 26.6 1504 479 12.1 50 12 9 0.55 0.24 0.17 1000/D
21x1.5 re 0.8 4x0.8 1.8 27 1496 486 12.1 50 11 9 0.55 0.24 0.17 1000/D
21x1.5 rm 0.8 4x0.8 1.8 27.7 1611 499 12.1 50 11 9 0.55 0.24 0.17 1000/D
24x1.5 re 0.8 4x0.8 1.9 28.2 1629 508 12.1 50 11 9 0.55 0.24 0.17 1000/D
24x1.5 rm 0.8 4x0.8 1.8 29.3 1766 527 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 re 0.8 4x0.8 1.8 30 1857 540 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 rm 0.8 4x0.8 1.8 31.4 2020 565 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 re 0.8 4x0.8 1.9 33.7 2420 607 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 rm 0.8 4x0.8 1.9 35.2 2635 634 12.1 50 11 9 0.55 0.24 0.17 1000/D
52x1.5 re 0.8 4x0.8 2.0 37.6 2932 677 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 rm 0.8 4x0.8 2.0 39.3 3190 707 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 re 0.8 4x0.8 2.1 39.5 3215 711 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 rm 0.8 4x0.8 2.1 41.3 3518 743 12.1 50 11 8 0.55 0.24 0.17 1000/D

18 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Armoured Control Cable
Cu/PVC/SFA/PVC 0.6/1 kV (NYFGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded 4. Armour :
according to SPLN 41 - 1 ; IEC 60228 A layer of galvanized flat steel wires with a counter helix layer
of galvanized steel tape.
2. Insulation:
Extruded layer of Polyvinyl Chloride (PVC] complied with 5. Outer sheath:
SPLN 41-2 : IEC 60502-1 Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
and/or special flame retardant, PVC sheath can be provided on
Colour of insulation request.
System - i System - 0
Yellow/Green strip, Black with White number Black with White number Applications:
For general purpose power distribution in dry or wet location,
(SNI IEC) best suitable for direct burying in ground.
Black with White number
Note : [re] round solid conductor
3. Inner Covering / filler: [rm] circular stranded conductor
Extruded Polyvinyl Chloride [PVC], Black colour
Packing : [D] Drum

DC. Resistance Current Carrying Conductor Short Circuit


No. of Thickness Armour Thickness Overall Weight Minimum at 20°C Capacity at 30°C Current Capacity at Standard
cores of Flat of outer Diameter of Cable bending delivery
and cross Insulation Steel sheath (approx) (approx] radius Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
section (nom) Size (nom) Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x2.5 re 0.8 4x0.8 1.8 19.7 848 335 7.41 50 26 21 0.91 0.41 0.29 1000/D
7x2.5 rm 0.8 4x0.8 1.8 20.6 918 371 7.41 50 26 21 0.91 0.41 0.29 1000/D
8x2.5 re 0.8 4x0.8 1.B 21 928 378 7.41 50 23 18 0.91 0.41 0.29 1000/D
8x2.5 rm 0.8 4x0.8 1.8 21.8 1007 392 7.41 50 23 18 0.91 0.41 0.29 1000/D
10x2.5 re 0.8 4x0.8 1.8 24 1228 432 7.41 50 21 17 0.91 0.41 0.29 1000/D
10x2.5 rm 0.8 4x0.8 1.8 25.2 1332 454 7.41 50 21 17 0.91 0.41 0.29 1000/D
12x2.5 re 0.8 440.8 1.8 24.6 1317 443 7.41 50 20 16 0.91 0.41 0.29 1000/D
12x2.5 rm 0.8 4x0.8 1.8 25.7 1431 463 7.41 50 20 16 0.91 0.41 0.29 1000/D
14;2.5 re 0.8 4x0.8 1.8 25.4 1421 457 7.41 50 18 15 0.91 0.41 0.29 1000/D
14x2.5 rm 0.8 4x0.8 1.8 26.7 1548 481 7.41 50 18 15 0.91 0.41 0.29 1000/D
16x2.5 re 0.8 4x0.8 1.8 26.9 1561 484 7.41 50 17 14 0.91 0.41 0.29 1000/D
16x2.5 rm 0.8 4x0.8 1.8 27.7 1671 499 7.41 50 17 14 0.91 0.41 0.29 1000/D
19x2.5 re 0.8 4x0.8 1.8 27.5 1675 495 7.41 50 17 13 0.91 0.41 0.29 1000/D
19x2.5 rm 0.8 4x0.8 1.8 28.9 1833 520 7.41 50 17 13 0.91 0.41 0.29 1000/D
21x2.5 re 0.8 4x0.8 1.8 28.6 1800 515 7.41 50 16 12 0.91 0.41 0.29 1000/D
21x2.5 rm 0.8 4x0.8 1.8 30.2 1973 544 7.41 50 16 12 0.91 0.41 0.29 1000/D
24x2.5 re 0.8 4x0.8 1.8 30.4 1980 547 7.41 50 15 11 0.91 0.41 0.29 1000/D
24x2.5 rm 0.8 4x0.8 1.8 31.9 2173 574 7.41 50 15 11 0.91 0.41 0.29 1000/D
30x2.5 re 0.8 4x0.8 1.9 32.5 2280 585 7.41 50 14 11 0.91 0.41 0.29 1000/D
30x2.5 rm 0.8 4x0.8 1.9 35.5 2823 639 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2.5 re 0.8 4x0.8 2.0 37.3 3167 671 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2.5 rm 0.8 4x0.8 2.0 39.5 3389 711 7.41 50 14 11 0.91 0.41 0.29 1000/D
52x2.5 re 0.8 4x0.8 2.1 41.6 3704 749 7.41 50 14 11 0.91 0.41 0.29 1000/D
52x2.5 rm 0.8 4x0.8 2.1 43.2 4002 778 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 re 0.8 4x0.8 2.2 43.9 4121 790 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 rm 0.8 4x0.8 2.2 46.3 4970 833 7.41 50 14 11 0.91 0.41 0.29 1000/D

sales@kabelindo.co.id 19
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/SWA/PVC 0.6/1 kV (NYRGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC :60502-1 : 2009

Constructions: 4. Armour :
1. Conductor: A layer of galvanized round steel wires with a counter helix
Annealed plain copper round solid or round circular stranded or layer of galvanized steel tape.
according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : and/or special flame retardant, PVC sheath can be provided on
IEC 60502-1 request.

Identification of core (SPLN) Applications:


Light Blue, Black For general purpose power distribution in dry or wet location,
best suitable for direct burying in ground.
( SNI IEC )
Light Blue, Brown Note : [re] round solid conductor
[rm] circular stranded conductor
3. Inner Covering / filler:
Extruded Polyvinyl Chloride [PVC], Black colour Packing : [D] Drum

Armour DC. Resistance Current Carrying Conductor Short Circuit


No. of Thickness Thickness Overall Weight Minimum at 20°C Capacity at 30°C Current Capacity at Standard
Round
cores of of outer Diameter of Cable bending delivery
Steel
and cross Insulation sheath (approx) (approx] radius Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
Wire Max Min second second second
section (nom) (nom)
Diameter
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
2x1.5 re 0.8 0.9 1.8 13.9 374 250 12.1 50 27 21 0.55 0.24 0.17 1000/D
2x1.5 rm 0.8 0.9 1.8 14.3 375 257 12.1 50 27 21 0.55 0.24 0.17 1000/D
2x2.5 re 0.8 0.9 1.8 14.6 406 263 7.41 50 36 29 0.91 0.41 0.29 1000/D
2x2.5 rm as 0.9 1.8 15.2 430 274 7.41 50 36 29 0.91 0.41 0.29 1000/D
2x4 re in 0.9 1.8 16.4 503 295 4.61 50 47 38 1.45 0.65 0.46 1000/D
2x4 rrn 10 02 1.8 17 536 306 4.61 50 47 38 1.45 0.65 0.46 1000/D
2x6 re 10 125 1.8 18 674 324 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x6 rm 1.0 1.25 1.8 18.9 734 340 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x10 rm 1.0 1.25 1.8 20.8 908 374 1.83 50 78 66 3.64 1.63 1.15 1000/D
2x16 rm in 1.6 1.8 23.4 1296 421 1.15 40 102 90 5.82 2.60 1.84 1000/D
2x25 rm 12 1.6 1.8 26.6 1688 479 0.727 40 134 120 9.09 4.07 2.88 1000/D
2x35 rm 1.2 1.6 1.8 2E9 2030 520 0.524 40 160 150 12.73 5.69 4.03 1000/D
2x50 rm 1.4 2.0 1.9 33.6 2812 605 0.387 30 187 180 18.18 8.13 5.75 1000/D
2x70 rm 1.4 2.0 2.0 36.8 3430 662 0.268 30 230 230 25.46 11.28 8.05 1000/D
2x95 rm 1.6 2.0 2.1 42.2 4470 760 0.193 30 280 275 34.55 15.45 10.93 1000/D
2x120 rm 1.6 2.5 2.2 46.5 5648 837 0.153 30 320 320 43.64 19.52 13.80 1000/D
2x150 rm 1.8 2.5 2.3 50.6 6650 911 0.124 20 355 375 54.45 24.40 17.25 500/D
2x185 rm 2.0 2.5 2.5 55.8 8007 1,004 0.0991 20 409 430 67.28 30.09 21.28 500/D
2x240 rm 2.2 2.5 2.7 62.2 9952 1,120 0.0754 20 472 510 8728 39.03 27.60 250/D
2x300 rm 2.4 2.5 2.8 58.5 11918 1,233 0.0601 20 525 590 109.10 48.79 34.50 250/D

20 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/SWA/PVC 0.6/1 kV (NYRGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions: 4. Armour :
1. Conductor: A layer of galvanized round steel wires with a counter helix
Annealed plain copper round solid or round circular stranded layer of galvanized steel tape.
according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : and/or special flame retardant, PVC sheath can be provided on
IEC 60502-1 request.

Identification of core : (SPLN) Applications:


For general purpose power distribution in dry or wet location,
Colour of insulation
best suitable for direct burying in ground.
System - i System - o
Yellow/Green strip, Light Blue, Brown Light Blue, Yellow, Black Note : [re] round solid conductor
[rm] circular stranded conductor
(SNI IEC) (sm) sector shaped conductor
Yellow/Green Strip, Light Blue,Brown.
Packing : [D] Drum
3. Inner Covering / filler:
Extruded Polyvinyl Chloride [PVC], Black colour

DC. Resistance Current Carrying Conductor Short Circuit


No. of Thickness Armour Thickness Overall Weight Minimum at 20°C Capacity at 30°C Current Capacity at Standard
cores of Flat of outer Diameter of Cable bending delivery
and cross Insulation Steel sheath radius Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
section Size (approx) (approx] Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
3x1.5 re 0.8 0.9 1.8 14.3 390 257 12.1 50 24 18 0.55 0.24 0.17 1000/D
3x1.5 rm 0.8 0.9 1.8 14.8 410 266 12.1 50 24 18 0.55 0.24 0.17 1000/D
3x2.5 re 0.8 0.9 1.8 15.2 451 274 7.41 50 32 25 0.91 0.41 0.29 1000/D
3x2.5 rm 0.8 0.9 1.8 15.8 479 284 7.41 50 32 25 0.91 0.41 0.29 1000/D
3x4 re 1.0 0.9 1.8 17.8 655 320 4.61 50 41 34 1.45 0.65 0.46 1000/D
3x4 rm 1.0 0.9 1.8 18.5 699 333 4.61 50 41 34 1.45 0.65 0.46 1000/D
3x6 re 1.0 1.25 1.8 18.8 762 338 3.08 50 52 44 2.18 0.98 0.69 1000/D
3x6 rm 1.0 1.25 1.8 19.7 819 355 3.08 50 52 44 2.18 0.98 0.69 1000/D
3x10 rm 1.0 1.25 1.8 21.8 1044 392 1.83 50 69 60 3.64 1.63 1.15 1000/D
3x16 rm 1.0 1.6 1.8 24.5 1416 441 1.15 40 89 80 5.82 2.60 1.84 1000/D
3x25 rm 1.2 1.6 1.8 28.1 1894 506 0.727 40 116 105 9.09 4.07 2.88 1000/D
3x35 rm 1.2 1.6 1.8 30.5 2321 369 0.524 40 138 130 12.73 5.69 4.03 1000/D
3x50 sm 1.4 2.0 1.9 32.7 2784 589 0.387 30 165 160 18.18 8.13 5.75 1000/D
3x70 sm 1.4 2.0 2.0 36.7 3806 661 0.268 30 205 200 25.46 1128 8.05 1000/D
3x95 sm 1.6 2.0 2.2 41 4882 738 0.193 30 245 245 34.55 15.45 10.93 1000/D
3x120 sm 1.6 2.5 2.3 43.7 5853 787 0.153 30 285 285 43.64 19.52 13.80 1000/D
3x150 sm 1.8 2.5 2.4 48.9 7407 880 0.124 20 315 325 54.45 24.40 17.25 500/D
3x185 sm 2.0 2.5 2.6 52.5 8774 945 0.0991 20 355 370 67.28 30.09 21.28 500/D
3x240 sm 2.2 2.5 2.8 57.9 11036 1,042 0.0754 20 415 435 87.28 39 03 27.60 250/D
3x300 sm 2.4 2.5 3.0 62.47 13137 1,124 0.0601 20 465 500 109.10 48.79 34.50 250/D

sales@kabelindo.co.id 21
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/SWA/PVC 0.6/1 kV (NYRGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions: 4. Armour :
1. Conductor: A layer of galvanized round steel wires with a counter helix
Annealed plain copper round solid or round circular stranded or layer of galvanized steel tape.
sector shape according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : and/or special flame retardant, PVC sheath can be provided on
IEC 60502-1 request.

Identification of core : (SPLN) Applications:


For general purpose power distribution in dry or wet location,
Colour of insulation
best suitable for direct burying in ground.
System - i System - o
Yellow/Green strip, Light Blue, Yellow, Black Light Blue, Red, Yellow, Black Note : [re] round solid conductor
[rm] circular stranded conductor
(SNI IEC) Yellow/Green Strip, Light Blue, Black, Brown. (sm) sector shaped conductor

3. Inner Covering / filler: Packing : [D] Drum


Extruded Polyvinyl Chloride [PVC], Black colour

Armour
No. of Thickness Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
Round
cores of of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
Steel
and cross Insulation sheath radius delivery
Wire
section Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
Diameter
area (nom) (nom) (approx) (approx) Max Min second second second
(nom)
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
4x1.5 re 0.8 0.9 1.8 15.2 433 274 12.1 50 24 18 0.55 0.24 0.17 1000/D
4x1.5 rm 0.8 0.9 1.8 15.6 455 281 12.1 50 24 18 0.55 0.24 0.17 1000/D
4x2.5 re 0.8 0.9 1.8 16 515 288 7.41 50 32 25 0.91 0.41 0.29 1000/D
4x2.5 rm 0.8 0.9 1.8 16.7 538 301 7.41 50 32 25 0.91 0.41 0.29 1000/D
4x4 re 1.0 0.9 1.8 18.8 740 338 4.61 50 41 34 1.45 0.65 0A6 1000/D
4x4 rm 1.0 0.9 1.8 19.7 790 355 4.61 50 41 34 1.45 0.65 0A6 1000/D
4x6 re 1.0 1.25 1.8 20.8 870 374 3.08 50 52 44 2.18 0.98 0.69 1000/D
4x6 rm 1.0 1.25 1.8 21 925 378 3.08 50 52 44 2.18 0.98 0.69 1000/D
4x10 rm 1.0 1.25 1.8 24 1317 432 1.83 50 69 60 3.64 1.63 1.15 1000/D
4x16 rm 1.0 1.6 1.8 26.3 1548 473 1.15 40 89 80 5.82 2.60 1.84 1000/D
4x25 rm 1.2 1.6 1.8 30A 2241 547 0.727 40 116 105 9.09 4.07 2.88 1000/D
4x35 rm 1.2 1.6 1.9 32.9 2933 592 0.524 40 138 130 12.73 5.69 4.03 1000/D
4x50 sm 1.4 2.0 2.0 33.9 2934 610 0.387 30 165 160 18.18 8.13 5.75 1000/D
4x70 sm 1.4 2.0 2.1 38.7 4148 697 0.268 30 205 200 25.46 11.38 8.05 1000/D
4x95 sm 1.6 2.0 2.3 43.9 5489 790 0.193 30 245 245 34.55 15.45 10.93 1000/D
4x120 sm 1.6 2.5 2.4 48.2 7163 868 0.153 30 285 285 43.64 19.52 13.80 1000/D
4x150 sm 1.8 2.5 2.6 52.5 8637 945 0.124 20 315 325 54.45 24.40 17.25 500/D
4x185 sm 2.0 2.5 2.8 57.2 10354 1,030 0.0991 20 355 370 67.28 30.09 21.28 500/D
4x240 sm 2.2 2.5 3.0 64.3 13347 1,157 0.0754 20 415 435 87.28 39.03 27.60 250/D
4x300 sm 2.4 2.5 3.2 72.5 16702 1,305 0.0601 20 465 500 109.10 48.79 34.50 250/D

22 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/SWA/PVC 0.6/1 kV (NYRGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions: 4. Armour :
1. Conductor: A layer of galvanized round steel wires with a counter helix
Annealed plain copper round solid or round circular stranded layer of galvanized steel tape.
according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : and/or special flame retardant, PVC sheath can be provided on
IEC 60502-1 request.

Identification of core : (SPLN) Applications:


Yellow/Green Strip, Light Blue, Red, Yellow, Black For general purpose power distribution in dry or wet location,
best suitable for direct burying in ground.
( SNI IEC )
Yellow/Green Strip, Light Blue, Black, Brown, Grey Note : [re] round solid conductor
[rm] circular stranded conductor
3. Inner Covering / filler:
Extruded Polyvinyl Chloride [PVC], Black colour Packing : [D] Drum

No. of Thickness Armour Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of Round of outer Diameter of Cable bending
at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation Steel sheath radius delivery
section Wire Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) Diameter (nom) (approx) (approx) Max Min second second second
(nom)
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
5x1.5 re 0.8 0.9 1.8 16 484 288 12.1 50 24 18 0.55 0.24 0.17 1000/D
5x1.5 rm 0.8 0.9 1.8 16.5 509 297 12.1 50 24 18 0.55 0.24 0.17 1000/D
5x2.5 re 0.8 0.9 1.8 17.7 647 319 7.41 50 32 25 0.91 0.41 0.29 1000/D
5x2.5 rm 0.8 1.25 1.8 18.5 687 333 7.41 50 32 25 0.91 0.41 0.29 1000/D
5x4 re 1.0 1.25 1.8 20 839 360 4.61 50 41 34 1.45 0.65 0.46 1000/D
5x4 rm 1.0 1.25 1.8 21 897 378 4.61 50 41 34 1.45 0.65 0.46 1000/D
5x6 re 1.0 1.25 1.8 21.4 996 385 3.08 50 52 44 2.18 0.98 0.69 1000/D
5x6 rm 1.0 1.25 1.8 22.5 1069 405 3.08 50 52 44 2.18 0.98 0.69 1000/D
5x10 rm 1.0 1.6 1.8 25.7 1527 463 1.83 50 69 60 3.64 1.63 1.15 1000/D
5x16 rm 1.0 1.6 1.8 28.3 1928 509 1.15 40 89 80 5.82 2.60 1.84 1000/D
5x25 rm 1.2 1.6 1.9 33.2 2641 598 0.727 40 116 105 9.09 4.15 2.96 1000/D
5x35 rm 1.2 2.0 2.0 37.4 3520 673 0.524 40 138 130 12.73 5.69 4.03 1000/D
5x50 rm 1A 2.0 2.1 43 4921 774 0.387 30 165 160 18.18 8.13 5.75 1000/D

sales@kabelindo.co.id 23
Copper Conductor PVC Insulated & PVC Sheathed Armoured Control Cable
Cu/PVC/SWA/PVC 0.6/1 kV (NYRGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions: 4. Armour :
1. Conductor: A layer of galvanized round steel wires with a counter helix
Annealed plain copper round solid or round circular stranded or layer of galvanized steel tape
according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite and/or
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : special flame retardant, PVC sheath can be provided on request.
IEC 60502-1
Applications:
Identification of core (SPLN) For general purpose power distribution in dry or wet location, best
Colour of insulation
suitable for direct burying in ground.
System - i System - 0
Note : [re] round solid conductor
Yellow/Green strip, Black with White number Black with White number
[rm] circular stranded conductor
(SNI IEC) : Black with White number
Packing : [D] Drum
3. Inner Covering / filler:
Extruded Polyvinyl Chloride [PVC], Black colour

No. of Thickness Armour Thickness Overall Weight Minimum


DC. Resistance Current Carrying Conductor Short Circuit
cores of Round of outer Diameter of Cable bending
at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation Steel sheath radius
section Wire delivery
Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
area Diameter (approx) (approx) Max Min second second second
(nom) (nom) (nom)
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x1.5 re 0.8 1.25 1.8 18.6 727 335 12.1 50 17 13 0.55 0.24 0.17 1000/D
7x1.5 rm 0.8 1.25 1.8 19.2 777 346 12.1 50 17 13 0.55 0.24 0.17 1000/D
8x1.5 re 0.8 1.25 1.8 19.7 792 355 12.1 50 16 12 0.55 0.24 0.17 1000/D
8x1.5 rm 0.8 1.25 1.8 20.3 848 365 12.1 50 16 12 0.55 0.24 0.17 1000/D
10x1.5 re 0.8 1.25 1.8 21.7 929 391 12.1 50 15 11 0.55 0.24 0.17 1000/D
10x1.5 rm 0.8 1.25 1.8 22.6 997 407 12.1 50 15 11 0.55 0.24 0.17 1000/D
12x1.5 re 0.8 1.6 1.8 23 1117 414 12.1 50 14 11 0.55 0.24 0.17 1000/D
12x1.5 rm 0.8 1.6 1.8 23.8 1199 428 12.1 50 14 11 0.55 0.24 0.17 1000/D
14x1.5 re 0.8 1.6 1.8 24 1197 432 12.1 50 13 10 0.55 0.24 0.17 1000/D
14x1.5 rm 0.8 1.6 1.8 24.7 1287 445 12.1 50 13 10 0.55 0.24 0.17 1000/D
16x1.5 re 0.8 1.6 1.8 25 1310 450 12.1 50 12 10 0.55 0.24 0.17 1000/D
16x1.5 rm 0.8 1.6 1.8 25.6 1382 461 12.1 50 12 10 0.55 0.24 0.17 1000/D
19x1.5 re 0.8 1.6 1.8 26 1391 468 12.1 50 12 9 0.55 0.24 0.17 1000/D
19x1.5 rm 0.8 1.6 1.8 26.6 1504 479 12.1 50 12 9 0.55 0.24 0.17 1000/D
21x1.5 re 0.8 1.6 1.8 27 1496 486 12.1 50 11 9 0.55 0.24 0.17 1000/D
21x1.5 rm 0.8 1.6 1.8 27.7 1611 499 12.1 50 11 9 0.55 0.24 0.17 1000/D
24x1.5 re 0.8 1.6 1.8 28.2 1629 508 12.1 50 11 8 0.55 0.24 0.17 1000/D
24x1.5 rm 0.8 1.6 1.8 29.3 1766 527 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 re 0.8 1.6 1.8 30 1857 540 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 rm 0.8 1.6 1.8 31.4 2020 565 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 re 0.8 2.0 1.9 33.7 2420 607 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 rm 0.8 2.0 1.9 35.2 2635 634 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 re 0.8 2.0 2.1 37.6 2932 677 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 rm 0.8 2.0 2.1 39.3 3190 707 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 re 0.8 2.0 2.1 39.5 3215 711 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 rm 0.8 2.0 2.1 41.3 3518 743 12.1 50 11 8 0.55 0.24 0.17 1000/D
24 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Armoured Control Cable
Cu/PVC/SWA/PVC 0.6/1 kV (NYRGbY)
Specification :
SPLN 43-2 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
4. Armour :
Annealed plain copper round solid or round circular stranded or
A layer of galvanized round steel wires with a counter helix layer of
sector shape according to SPLN 41 - 1 ; IEC 60228
galvanized steel tape
2. Insulation:
5. Outer sheath:
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite and/
IEC 60502-1
or special flame retardant, PVC sheath can be provided on request.
Identification of core (SPLN)
Applications:
Colour of insulation For general purpose power distribution in dry or wet location, best
System - i System - 0 suitable for direct burying in ground.
Yellow/Green strip, Black with White number Black with White number
Note : [re] round solid conductor
(SNI IEC) : Black with White number
[rm] circular stranded conductor
3. Inner Covering / filler:
Packing : [D] Drum
Extruded Polyvinyl Chloride [PVC], Black colour

No. of Thickness Armour Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of Round of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation Steel sheath radius delivery
section Wire Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) Diameter (nom) (approx) (approx] second second second
sq.mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x2.5 re 0.8 1.25 1.8 19.7 848 335 7.41 50 26 21 0.91 0.41 0.29 1000/D
7x2.5 rm 0.8 1.25 1.8 20.6 918 371 7.41 50 26 21 0.91 0.41 0.29 1000/D
8x2.5 re 0.8 1.25 1.8 21 928 378 7.41 50 23 18 0.91 0.41 0.29 1000/D
8x2.5 rm 0.8 1.25 1.8 21.8 1007 392 7.41 50 23 18 0.91 0.41 0.29 1000/D
10x2.5 re 0.8 1.6 1.8 24 1228 432 7.41 50 21 17 0.91 0.41 0.29 1000/D
10x2.5 rm 0.8 1.6 1.8 25.2 1332 454 7.41 50 21 17 0.91 0.41 0.29 1000/D
12x2.5 re 0.8 1.6 1.8 24.6 1317 443 7.41 50 20 16 0.91 0.41 0.29 1000/D
12x2.5 rm 0.8 1.6 1.8 25.7 1431 463 7.41 50 20 16 0.91 0.41 0.29 1000/D
14x2.5 re 0.8 1.6 1.8 25.4 1421 457 7.41 50 18 15 0.91 0.41 0.29 1000/D
14x2.5 rm 0.8 1.6 1.8 26.7 1548 481 7.41 50 18 15 0.91 0.41 0.29 1000/D
16x2.5 re 0.8 1.6 1.8 26.9 1561 484 7.41 50 17 14 0.91 0.41 0.29 1000/D
16x2.5 rm 0.8 1.6 1.8 27.7 1671 499 7.41 50 17 14 0.91 0.41 0.29 1000/D
19x2.5 re 0.8 1.6 1.8 27.5 1675 495 7.41 50 17 13 0.91 0.41 0.29 1000/D
19x2.5 rm 0.8 1.6 1.8 28.9 1833 520 7.41 50 17 13 0.91 0.41 0.29 1000/D
21x2.5 re 0.8 1.6 1.8 28.6 1800 515 7.41 50 16 12 0.91 0.41 0.29 1000/D
21x2.5 rm 0.8 1.6 1.8 30.2 1973 544 7.41 50 16 12 0.91 0.41 0.29 1000/D
24x2.5 re 0.8 1.6 1.9 30.4 1980 547 7.41 50 15 11 0.91 0.41 0.29 1000/D
24x2.5 rm 0.8 1.6 1.9 31.9 2173 574 7.41 50 15 11 0.91 0.41 0.29 1000/D
30x2.5 re 0.8 1.6 1.9 32.5 2280 585 7.41 50 14 11 0.91 0.41 0.29 1000/D
30x2.5 rm 0.8 2.0 1.9 35.5 2823 639 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2.5 re 0.8 2.0 2.1 37.3 3167 671 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2.5 rm 0.8 2.0 2.1 39.5 3389 711 7.41 50 14 11 0.91 0.41 0.29 1000/D
52x2.5 re 0.8 2.0 2.2 41.6 3704 749 7.41 50 14 11 0.91 0.41 0.29 1000/D
52x2.5 rm 0.8 2.0 2.2 43.2 4002 778 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 re 0.8 2.0 2.3 43.9 4121 790 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 rm 0.8 2.5 2.3 46.3 4970 833 7.41 50 14 11 0.91 0.41 0.29 1000/D

sales@kabelindo.co.id 25
Copper Conductor PVC Insulated, Copper tape Screened & PVC Sheathed Power Cable
Cu/PVC/CTS/PVC 0.6/1 kV (NYSY)
Specification : SNI IEC 60502-1: 2009

Constructions: 5. Outer sheath:


1. Conductor: Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite
Annealed plain copper round solid or round circular stranded or and/or special flame retardant. PVC sheath can be provided on
according to SPLN 41 - 1 ; IEC 60228 request

2. Insulation: Applications:
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : For indoor installations, in power and switching stations. As un-
IEC 60502-1 derground cable, for difficult installation where the low weight is
particularly
Identification of core : advantageous.

(SNI IEC) : Light Blue, Brown Note : [re] round solid conductor
[rm] circular stranded conductor
3. Inner sheath: Polyvinyl Chloride [PVC], Black colour
Packing : [D] Drum
4. Shield: Hellically copper tape
No. of Thickness Thickness Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of of of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation Copper sheath radius delivery
section tape Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) screened (nom) (approx) (approx] Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
2x1.5 re 0.8 0.1 1.8 12.1 218 218 12.1 50 27 21 0.55 0.24 0.17 1000/D
2x1.5 rm 0.8 0.1 1.8 12A 231 223 12.1 50 27 21 0.55 0.24 0.17 1000/D
2x2.5 re 0.8 0.1 1.8 12.8 263 230 7.41 50 36 29 0.91 0.41 0.29 1000/D
2x2.5 rm 0.8 0.1 1.8 13.4 280 241 7.41 50 36 29 0.91 0.41 0.29 1000/D
2x4 re 1.0 0.1 1.8 14.5 348 261 4.61 50 47 38 1.45 0.65 0.46 1000/D
2x4 rm 1.0 0.1 1.8 15.2 369 274 4.61 50 47 38 1.45 0.65 0.46 1000/D
2x6 re 1.0 0.1 1.8 16.5 417 297 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x6 rm 1.0 0.1 1.8 18.1 445 326 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x10 rm 1.0 0.1 1.8 20.2 582 364 1.83 50 78 66 3.64 1.63 1.15 1000/D
2x16 rm 1.0 0.1 1.8 23.6 771 425 1.15 40 102 90 5.82 2.60 1.84 1000/D
2x25 rm 1.2 0.1 1.8 25.8 1095 464 0.727 40 134 120 9.09 4.07 2.88 1000/D
2x35 rm 1.2 0.1 1.8 29.2 1368 526 0.524 40 180 150 12.73 5.69 4.03 1000/D
2x50 rm 1.4 0.1 1.9 32.7 1748 589 0.387 30 210 180 18.18 8.13 5.75 1000/D
2x70 rm 1.4 0.1 2.0 38.4 2336 691 0.268 30 260 230 25.46 11.38 8.05 1000/D
2x95 rm 1.6 0.1 2.2 41.6 3159 749 0.193 30 315 280 34.55 15.45 10.93 1000/D
2x120 rm 1.6 0.1 2.3 45.5 3807 819 0.153 30 320 320 43.64 19.52 13.80 1000/D
2x150 rm 1.8 0.1 2.4 50.6 4647 911 0.124 20 355 375 54.55 24.40 17.25 500/D
2x185 rm 2.0 0.1 2.6 53.5 5756 909 0.0991 20 409 430 67.28 30.09 21.28 500/D
2x240 rm 2.2 0.1 2.8 57.3 7366 1,031 0.0754 20 472 510 87.28 39.03 27.60 250/D
2x300 rm 2.4 0.1 3.0 63.3 9117 1,139 0.0601 20 525 590 109.10 48.79 34.50 250/D

26 www.kabelindo.co.id
Copper Conductor PVC Insulated, Copper tape Screened & PVC Sheathed Power Cable
Cu/PVC/CTS/PVC 0.6/1 kV (NYSY)
Specification :
SNI IEC 60902-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or 5. Outer sheath:
sector shape according to SPLN 41 - 1 ; IEC 60228 Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
and/or special flame retardant, PVC sheath can be provided on
2. Insulation: request.
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
IEC 60502-1 Applications:
For indoor installations, in power and switching stations.
Identification of core : As underground cable, for difficult installation where the low
weight is particularly advantageous.
(SNI IEC) : Yellow/Green Strip, Light Blue, Brown
Note: (re) round solid conductor
3. Inner Covering / filler: (rm) circular stranded conductor
Extruded Polyvinyl Chloride [PVC], Black colour (sm) sector shaped conductor

4. Shield: Hellically copper tape Packing : [D] Drum

No. of Thickness Thickness Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of of Copper of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation tape sheath radius delivery
section screened Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A m
3x1.5 re 0.8 0.1 1.8 12.4 246 223 12.1 50 24 18 0.55 0.24 0.17 1000/D
3x1.5 rrn 0.8 0.1 1.8 12.9 262 232 12.1 50 24 18 0.55 0.24 0.17 1000/D
3x2.5 re 0.8 0.1 1.8 13.3 296 239 7.41 50 32 25 0.91 0.41 0.29 1000/D
3x2.5 rm 0.8 0.1 1.8 13.9 323 250 7.41 50 32 25 0.91 0.41 0.29 1000/D
3x4 re 1.0 0.1 1.8 15.3 398 275 4.61 50 41 34 1.45 0.65 0A6 1000/D
3x4 rm 1.0 0.1 1.8 15.8 432 284 4.61 50 41 34 1.45 0.65 0.46 1000/D
3x6 re 1.0 0.1 1.8 16.4 492 295 3.08 50 52 44 2.18 0.98 0.69 1000/D
3x6 rm 1.0 0.1 1.8 17.2 524 310 3.08 50 52 44 2.18 0.98 0.69 1000/D
3x10 rm 1.0 0.1 1.8 19.1 698 344 1.83 50 69 60 3.64 1.63 1.15 1000/D
3x16 rm 1.0 0.1 1.8 21.4 940 385 1.15 40 89 80 5.82 2.60 1.84 1000/D
3x25 rm 1.2 0.1 1.8 24.7 1359 445 0.727 40 116 105 9.09 4.07 2.88 1000/D
3x35 rm 1.2 0.1 1.8 27.5 1720 495 0.524 40 138 130 12.73 5.69 4.03 1000/D
3x50 sm 1.4 0.1 1.9 28.7 2018 517 0.387 30 165 160 18.18 8.13 5.75 1000/D
3x70 sm 1A 0.1 2.0 30.2 2671 544 0.268 30 205 200 25A6 11.38 8.05 1000/D
3x95 sm 1.6 0.1 2.2 34.6 3641 623 0.193 30 245 245 34.55 15.45 10.93 1000/D
3x120 sm 1.6 0.1 2.3 37.8 4478 680 0.153 30 285 285 43.64 19.52 13.80 1000/D
3x150 sm 1.8 0.1 2.4 41.3 5486 743 0.124 20 315 325 54.55 24.40 17.25 500/D
3x185 sm 2.0 0.1 2.6 45.6 6693 821 0.0991 20 355 370 67.28 30.09 21.28 500/D
3x240 sm 2.2 0.1 2.8 51.2 8727 922 0.0754 20 415 435 87.28 39.03 27.60 250/D
3x300 sm 2.4 0.1 3.0 57.2 10869 1,030 0.0601 20 465 500 109.10 48.79 34.50 250/D

sales@kabelindo.co.id 27
Copper Conductor PVC Insulated, Copper tape Screened & PVC Sheathed Power Cable
Cu/PVC/CTS/PVC 0.6/1 kV (NYSY)
Specification :
SNI IEC 60502-1: 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or 5. Outer sheath:
sector shape according to SPLN 41 - 1 ; IEC 60228 Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite
and/or special flame retardant. PVC sheath can be provided on
2. Insulation: request
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
IEC 60502-1 Applications:
For indoor installations, in power and switching stations. As
Identification of core: underground cable, for difficult installation where the low weight
is particularly advantageous.
(SNI IEC) :
Yellow/Green Strip, Light Blue, Black, Brown Note : [re] round solid conductor
[rm] circular stranded conductor
3.Inner covering / filler: [sm) sector shaped conductor
Extruded Polyvinyl Chloride (PVC), Black colour
Packing : [D] Drum
4. Shield: Hellically copper tape

No. of Thickness Thickness Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of of Copper of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation tape sheath radius delivery
section screened Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
4x1.5 re 0.8 0.1 1.8 13.1 281 236 12.1 50 24 18 0.55 0.24 0.17 1000/D
4x1.5 rm 0.8 0.1 1.8 13.4 296 241 12.1 50 24 18 0.55 024 0.17 1000/D
4x2.5 re 0.8 0.1 1.8 14.2 348 256 7.41 50 32 25 0.91 0.41 0.29 1000/D
4x2.5 rm 0.8 0.1 1.8 14.8 373 266 7.41 50 32 25 0.91 0.41 0.29 1000/D
4x4 re 1.0 0.1 1.8 16.3 470 293 4.61 50 41 34 1.45 0.65 0.46 1000/D
4x4 rm 1.0 0.1 1.8 17.1 509 308 4.61 50 41 34 1.45 0.65 0.46 1000/D
4x6 re 1.0 0.1 1.8 17.6 585 317 3.08 50 52 44 2.18 0.98 0.69 1000/D
4x6 rm 1.0 0.1 1.8 18.5 627 333 3.08 50 52 44 2.18 0.98 0.69 1000/D
4x10 rm 1.0 0.1 1.8 20.4 847 367 1.83 50 69 60 3.64 1.63 1.15 1000/D
4x16 rm 1.0 0.1 1.8 23.1 1158 416 1.15 40 89 80 5.82 2.60 1.84 1000/D
4x25 rm 1.2 0.1 1.8 27.2 1683 490 0.727 40 116 105 9.09 4.07 2.88 1000/D
4x35 rm 1.2 0.1 1.9 30.2 2452 544 0.524 40 138 130 12.73 5.69 4.03 1000/D
4x50 sm 1.4 0.1 2.0 31.8 2640 572 0.387 30 165 160 18.18 8.13 5.75 1000/D
4x70 sm 1.4 0.1 2.1 35.7 3519 643 0.268 30 205 200 25.46 11.38 8.05 1000/D
4x95 sm 1.6 0.1 2.3 40.8 4717 734 0.193 30 245 245 34.55 15.45 10.93 1000/D
4x120 sm 1.6 0.1 2.4 44.6 5879 803 0.153 30 285 285 43.64 19.52 13.80 1000/D
4x150 sm 1.8 0.1 2.6 48.1 7135 866 0.124 20 315 325 54.55 24.40 17.25 500/D
4x185 sm 2.0 0.1 2.8 53.8 8847 968 0.0991 20 355 370 67.28 30.09 21.28 500/D
4x240 sm 2.2 0.1 3.0 60.4 11363 1.087 0.0754 20 415 435 87.28 39.03 27.60 250/D
4x300 sm 2.4 0.1 3.2 66.8 13858 1.202 0.0601 20 465 500 109.10 48.79 34.50 250/D

28 www.kabelindo.co.id
Copper Conductor PVC Insulated, Copper tape Screened & PVC Sheathed Power Cable
Cu/PVC/CTS/PVC 0.6/1 kV (NYSY)
Specification :
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or 5. Outer sheath:
according to SPLN 41 - 1 ; IEC 60228 Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
and/or special flame retardant, PVC sheath can be provided on
2. Insulation: request.
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
IEC 60502-1 Applications:
For indoor installations, in power and switching stations. As un-
Identification of core : derground cable, for difficult installation where the low weight is
particularly advantageous.
(SNI IEC) :
Yellow/Green strip, Light Blue, Black, Brown, Grey Note : (re) round solid conductor
(rm) circular stranded conductor
3. Inner Covering / filler:
Extruded Polyvinyl Chloride [PVC], Black colour Packing : [D] Drum

4. Shield: Hellically copper tape

No. of Thickness Thickness Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of of Copper of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation tape sheath radius delivery
section screened Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
5x1.5 re 0.8 0.1 1.8 14.2 327 256 12.1 50 24 18 0.55 0.24 0.17 1000/D
5x1.5 rm 0.8 0.1 1.8 14.7 345 265 12.1 50 24 18 0.55 0.24 0.17 1000/D
5x2.5 re 0.8 0.1 1.8 15.5 408 279 7.41 50 32 25 0.91 0.41 0.29 1000/D
5x2.5 rm 0.8 0.1 1.8 16.2 435 292 7.41 50 32 25 0.91 0.41 0.29 1000/D
5x4 re 1.0 0.1 1.8 17.4 564 313 4.61 50 41 34 1.45 0.65 0A6 1000/D
5x4 rm 1.0 0.1 1.8 18.5 606 333 4.61 50 41 34 1.45 0.65 0.46 1000/D
5x6 re 1.0 0.1 1.8 18.9 708 340 3.08 50 52 44 2.18 0.98 0.69 1000/D
5x6 rm 1.0 0.1 1.8 19.8 761 356 3.08 50 52 44 2.18 0.98 0.69 1000/D
5x10 rm 1.0 0.1 1.8 22.4 1036 403 1.83 50 69 60 3.64 1.63 1.15 1000/D
5x16 rm 1.0 0.1 1.8 25.2 1415 454 1.15 40 89 80 5.82 2.60 1.84 1000/D
5x25 rm 1.2 0.1 1.8 29.7 2079 535 0.727 40 116 105 9.09 4.07 2.88 1000/D
5x35 rm 1.2 0.1 1.8 32.6 2685 587 0.524 40 138 130 12.73 5.69 4.03 1000/D
5x50 rm 14 0.1 1.9 37.8 3497 680 0.387 30 165 160 18.18 8.13 5.75 1000/D

sales@kabelindo.co.id 29
Copper Conductor PVC Insulated, Copper tape Screened & PVC Sheathed Control Cable
Cu/PVC/CTS/PVC 0.6/1 kV (NYSY)
Specification :
SNI IEC 60502-1: 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or 5. Outer sheath:
according to SPLN 41 - 1; IEC 60228 Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite
and/or special flame retardant. PVC sheath can be provided on
2. Insulation: request
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
IEC 60502-1 Applications:
For indoor installations, in power and switching stations. As un-
Identification of core: derground cable, for difficult installation where the low weight is
Black with White printed number particularly
advantageous.
3.Inner covering /filler:
Extruded Polyvinyl Chloride (PVC), Black colour Note : [re] round solid conductor
[rm] circular stranded conductor
4. Shield: Hellically copper tape
Packing : [D] Drum

No. of Thickness Thickness Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of of Copper of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation tape sheath radius delivery
section screened Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x1.5 re 0.8 0.1 1.8 14.9 357 268 12.1 50 17 13 0.55 0.24 0.17 1000/D
7x1.5 rm 0.8 0.1 1.8 15.5 372 279 12.1 50 17 13 0.55 0.24 0.17 1000/D
8x1.5 re 0.8 0.1 1.8 16.1 394 290 12.1 50 16 12 0.55 0.24 0.17 1000/D
8x1.5 rm 0.8 0.1 1.8 16.5 418 297 12.1 50 16 12 0.55 0.24 0.17 1000/D
10x1.5 re 0.8 0.1 1.8 18.2 475 328 12.1 50 15 11 0.55 0.24 0.17 1000/D
10x1.5 rm 0.8 0.1 1.8 18.6 496 335 12.1 50 15 11 0.55 0.24 0.17 1000/D
12x1.5 re 0.8 0.1 1.8 18.7 518 337 12.1 50 14 11 0.55 0.24 0.17 1000/D
12x1.5 rm 0.8 0.1 1.8 19.2 545 346 12.1 50 14 11 0.55 0.24 0.17 1000/D
14x1.5 re 0.8 0.1 1.8 19.4 586 349 12.1 50 13 10 0.55 0.24 0.17 1000/D
14x1.5 rm 0.8 0.1 1.8 20.2 613 364 12.1 50 13 10 0.55 0.24 0.17 1000/D
16x1.5 re 0.8 0.1 1.8 20.4 642 367 12.1 50 12 10 0.55 0.24 0.17 1000/D
16x1.5 rm 0.8 0.1 1.8 20.8 675 374 12.1 50 12 10 0.55 0.24 0.17 1000/D
19x1.5 re 0.8 0.1 1.8 21.2 718 382 12.1 50 12 9 0.55 0.24 0.17 1000/D
19x1.5 rm 0.8 0.1 1.8 21.8 757 392 12.1 50 12 9 0.55 0.24 0.17 1000/D
21x1.5 re 0.8 0.1 1.8 22.2 778 400 12.1 50 11 9 0.55 0.24 0.17 1000/D
21x1.5 rm 0.8 0.1 1.8 22.8 820 410 12.1 50 11 9 0.55 0.24 0.17 1000/D
24x1.5 re 0.8 0.1 1.8 23.8 872 428 12.1 50 11 8 0.55 0.24 0.17 1000/D
24x1.5 rm 0.8 0.1 1.8 25 928 450 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 re 0.8 0.1 1.8 25.3 1026 455 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 rm 0.8 0.1 1.8 26.7 1085 481 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 re 0.8 0.1 1.8 27.6 1288 497 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 rm 0.8 0.1 1.8 29A 1356 529 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 re 0.8 0.1 1.9 31.8 1656 572 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 rm 0.8 0.1 1.9 33.4 1752 601 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 re 0.8 0.1 2.0 33.7 1893 607 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 rm 0.8 0.1 2.0 35.2 1990 634 12.1 50 11 8 0.55 0.24 0.17 1000/D

30 www.kabelindo.co.id
Copper Conductor PVC Insulated, Copper tape Screened & PVC Sheathed Control Cable
Cu/PVC/CTS/PVC 0.6/1 kV (NYSY)
Specification :
SNI IEC 60502-1:2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or 5. Outer sheath:
according to SPLN 41 - 1; IEC 60228 Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
and/orspecial flame retardant, PVC sheath can be provided on
2. Insulation: request.
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
IEC 60502-1 Applications:
For indoor installations, in power and switching stations.
Identification of core : As underground cable, for difficult installation where the low
Black with White printed number weight is particularly advantageous.

3. Inner Covering / filler: Note : (re) round solid conductor


Extruded Polyvinyl Chloride [PVC], Black colour (rm) circular stranded conductor

4. Shield: Hellically copper tape Packing : [D] Drum

No. of Thickness Thickness Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of of Copper of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation tape sheath radius delivery
section screened Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x2.5 re 0.8 0.1 1.8 15.8 458 284 7.41 50 23 18 0.91 0.41 0.29 1000/D
7x2.5 rm 0.8 0.1 1.8 16.6 486 299 741 50 23 18 0.91 0.41 0.29 1000/D
8x2.5 re 0.8 0.1 1.8 17.1 509 308 7.41 50 21 17 0.91 0.41 0.29 1000/D
8x2.5 rm 0.8 0.1 1.8 18.3 545 329 7.41 50 21 17 0.91 0.41 0.29 1000/D
10x2.5 re 0.8 0.1 1.8 19.3 617 347 7.41 50 20 16 0.91 0.41 0.29 1000/D
10x2.5 rrn 0.8 0.1 1.8 20.5 656 369 7.41 50 20 16 0.91 0.41 0.29 1000/D
12x2.5 re 0.8 0.1 1.8 20.7 682 373 7.41 50 18 15 0.91 0.41 0.29 1000/D
12x2.5 rm 0.8 0.1 1.8 21.5 432 387 7.41 50 18 15 0.91 0.41 0.29 1000/D
14x2.5 re 0.8 0.1 1.8 21.8 775 392 7.41 50 17 14 0.91 0.41 0.29 1000/D
14x2.5 rm 0.8 0.1 1.8 22.5 826 405 7.41 50 17 14 0.91 0.41 0.29 1000/D
16x2.5 re 0.8 0.1 1.8 22.6 854 407 7.41 50 17 13 0.91 0.41 0.29 1000/D
16x2.5 rm 0.8 0.1 1.8 23.4 918 421 741 50 17 13 0.91 0.41 0.29 1000/D
19x2.5 re 0.8 0.1 1.8 23.6 962 425 7.41 50 16 13 0.91 0.41 0.29 1000/D
19x2.5 rm 0.8 0.1 1.8 24.8 1027 446 7.41 50 16 13 0.91 0.41 0.29 1000/D
21x2.5 re 0.8 0.1 1.8 25.1 1055 452 7.41 50 15 12 0.91 0.41 0.29 1000/D
21x2.5 rrn 0.8 0.1 1.8 25.8 1136 464 7.41 50 15 12 0.91 0.41 0.29 1000/D
24x2.5 re 0.8 0.1 1.8 26.2 1210 472 7.41 50 14 11 0.91 0.41 0.29 1000/D
24x2.5 rm 0.8 0.1 1.8 26.8 1292 482 7.41 50 14 11 0.91 0.41 0.29 1000/D
30x2.5 re 0.8 0.1 1.9 28.3 1426 509 7.41 50 14 11 0.91 0.41 0.29 1000/D
30x2.5 rm 0.8 0.1 1.9 30.2 1535 544 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2 5 re 0.8 0.1 2.0 31.7 1840 571 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2.5 rm 0.8 0.1 2.0 33.5 1973 603 7.41 50 14 11 0.91 0.41 0.29 1000/D
52)(2.5 re 0.8 0.1 2.1 37.4 2358 673 7.41 50 14 11 0.91 0.41 0.29 1000/D
52x2.5 rm 0.8 0.1 2.1 38.6 2534 695 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 re 0.8 0.1 2.1 40.6 2701 731 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 rrn 0.8 0.1 2.1 41.4 2895 745 7.41 50 14 11 0.91 0.41 0.29 1000/D

sales@kabelindo.co.id 31
Copper Conductor PVC Insulated, Concentric Copper wire Screened & PVC Sheathed Power Cable
Cu/PVC/CWS/PVC 0.6/1 kV (NYCY)
Specification:
SPLN 43-4 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or 5. Outer sheath:
according to SPLN 41 - 1 ; IEC 60228 Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite
and/or special flame retardant. PVC sheath can be provided on
2. Insulation: request
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
IEC 60502-1 Applications:
Indoor, in ducts, in the open, underground, if mechanical damage
Identification of core: (SPLN) is not expected
Light Blue and Brown Light Blue and Red or Light Blue and
Yellow or Light Blue and Black Note : [re] round solid conductor
[rm] circular stranded conductor
(SNI IEC) :
Light Blue and Brown Packing : [D] Drum

3.Inner sheat:
Polyvinyl Chloride (PVC), Black colour

4. Screen:
Annealed copper wire with transverse helix of Annealed copper tape

No. of Thickness Cross Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of section of of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulationconcentric sheath radius delivery
section shield Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm sq.mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
2x1.5 re/1.5 0.8 1.5 1.8 13.5 230 243 12.1 50 27 21 0.55 0.24 0.17 1000/D
2x1.5 rm/1.5 0.8 1.5 1.8 13.9 242 250 12.1 50 27 21 0.55 0.24 0.17 1000/D
2x2.5 re/2.5 0.8 2.5 1.8 14.5 281 261 7.41 50 36 29 0.91 0.41 0.29 1000/D
2x2.5 rm/2.5 0.8 2.5 1.8 16.2 290 292 7.41 50 36 29 0.91 0.41 0.29 1000/D
2x4 re/4 1.0 4 1.8 16.8 370 302 4.61 50 47 38 1.45 0.65 0.46 1000/D
2x4 rm/4 1.0 4 1.8 17.2 395 310 4.61 50 47 38 1.45 0.65 0.46 1000/D
2x6 re/6 1.0 6 1.8 17.8 454 320 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x6 rm/6 1.0 6 1.8 18.1 485 326 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x10 rm/10 1.0 10 1.8 20.2 658 364 1.83 50 78 66 3.64 1.63 1.15 1000/D
2x16 rm/16 1.0 16 1.8 22 891 396 1.15 40 102 90 5.82 2.60 1.84 1000/D
2x25 rm/16 1.2 16 1.8 25.6 1207 461 0.727 40 134 120 9.09 4.07 2.88 1000/D
2x35 rm/16 1.2 16 1.8 27.8 1476 500 0.524 40 180 150 12.73 5.69 4.03 1000/D
2x50 rm/25 1.4 25 1.9 31.3 1928 563 0.387 30 210 180 18.18 8.13 5.75 1000/D
2x70 rm/35 14 35 2.0 35.8 2605 644 0.268 30 260 230 25.46 11.38 8.05 1000/D
2x95 rm/50 1.6 50 2.2 40.4 3557 727 0.193 30 315 280 34.55 15.45 10.93 1000/D
2x120 rm/70 1.6 70 2.3 43.6 4376 785 0.153 30 320 320 43.64 19.52 13.80 1000/D
2x150 rm/70 1.8 70 2.4 48.5 5208 873 0.124 20 355 375 54.55 24.40 17.25 500/D
2x185 rm/95 2.0 95 2.6 53.8 6546 968 0.0991 20 409 430 67.28 30.09 21.28 500/D
2x240 rm/120 2.2 120 2.8 60.6 8368 1,091 0.0754 20 472 510 87.28 39.03 27.60 250/D
2x300 rm/150 2.4 150 3.0 67.5 10385 1,215 0.0601 20 525 590 109.10 48.79 34.50 250/D

32 www.kabelindo.co.id
Copper Conductor PVC Insulated, Concentric Copper wire Screened & PVC Sheathed Power Cable
Cu/PVC/CWS/PVC 0.6/1 kV (NYCY)
Specification :
SPLN 43-4 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or
sector shape according to SPLN 41 - 1 ; IEC 60228

2. Insulation: 5. Outer sheath:


Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
IEC 60502-1 and/or special flame retardant, PVC sheath can be provided on
request.
Identification of core :
Light Blue, Red, Yellow or Light Blue, Red, Black or Light Blue, Yellow, Applications:
Black Indoor, in ducts, in the open, underground, if mechanical damage is
not expected.
(SNI IEC) :
Yellow/Green strip, Light Blue, Brown Note : (re) round solid conductor
(rm) circular stranded conductor
3. Inner Covering / filler: (sm) sector shaped conductor
Extruded Polyvinyl Chloride [PVC], Black colour
Packing : [D] Drum
4. Shield: Annealed copper wire with transverse helix of Annealed
copper tape

No. of Thickness Cross Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of section of of outer Diameter of Cable bending Capacity at 30°C Current Capacity at Standard
and cross Insulation concentric sheath radius delivery
section shield Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
area (nom) (nom) (approx) (approx] Min second second second
sq.mm mm sq.mm mm mm kg/km mm Ohm/km M.Ohm. A A kA kA kA m
3x1.5 re/1.5 0.8 1.5 1.8 14.1 260 253 12.1 50 24 18 0.55 0.24 0.17 1000/D
3x1.5 rm/1.5 0.8 1.5 1.8 144 271 259 12.1 50 24 18 0.55 0.24 0.17 1000/D
3x2.5 re/2.5 0.8 2.5 1.8 14.9 322 268 7.41 50 32 25 0.91 0.41 0.29 1000/D
3x2.5 rm/2.5 0.8 2.5 1.8 15.5 339 279 7.41 50 32 25 0.91 0.41 0.29 1000/D
3x4 re/4 1.0 4 1.8 16.9 427 304 4.61 50 41 34 145 0.65 0.46 1000/D
3x4 rm/4 1.0 4 1.8 17.5 456 315 4.61 50 41 34 1.45 0.65 0.46 1000/D
3x6 re/6 1.0 6 1.8 18.2 535 328 3.08 50 52 44 2.18 0.98 0.69 1000/D
3x6 rm/6 1.0 6 1.8 19.1 568 344 3.08 50 52 44 2.18 0.98 0.69 1000/D
3x10 rm/10 1.0 10 1.8 21.3 787 383 1.83 50 69 60 3.64 1.63 1.15 1000/D
3x16 rm/16 1.0 16 1.8 23.2 1068 418 1.15 40 89 80 5.82 2.60 1.84 1000/D
3x25 rm/16 1.2 16 1.8 26.8 1476 482 0.727 40 116 105 9.09 4.07 2.88 1000/D
3x35 rm/16 1.2 16 1.8 29.5 1438 531 0.524 40 138 130 12.73 5.69 4.03 1000/D
3x50 sm/25 1.4 25 1.9 29.7 2216 535 0.387 30 165 160 18.18 8.13 5.75 1000/D
3x70 sm/35 1.4 35 2.0 324 2985 583 0.268 30 205 200 25.46 11.38 8.05 1000/D
3x95 sm/50 1.6 50 2.2 36.6 4065 659 0.193 30 245 245 34.55 15.45 10.93 1000/D
3x120 sm/70 1.6 70 2.3 40.2 5073 724 0.153 30 285 285 43.64 19.52 13.80 1000/D
3x150 sm/70 1.8 70 24 43.7 6082 787 0.124 20 315 325 54.45 24.40 17.25 500/D
3x185 sm/95 2.0 95 2.6 494 7516 889 0.0991 20 355 370 67.28 30.09 21.28 500/D
3x240 sm/120 2.2 120 2.8 54.8 9768 986 0.0754 20 415 435 87.28 39.03 27.60 250/D
3x300 sm/150 2.4 150 3.0 61.3 12186 1,103 0.0601 20 465 500 109.10 48.79 34.50 250/D

sales@kabelindo.co.id 33
Copper Conductor PVC Insulated, Concentric Copper wire Screened & PVC Sheathed Power Cable
Cu/PVC/CWS/PVC 0.6/1 kV (NYCY)
Specification :
SPLN 43-4 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or 5. Outer sheath:
sector shape according to SPLN 41 - 1 ; IEC 60228 Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite
and/or special flame retardant. PVC sheath can be provided on
2. Insulation: request
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
IEC 60502-1 Applications:
Indoor, in ducts, in the open, underground, if mechanical damage
Identification of core: (SPLN) is not expected
Light Blue, Red,Yellow, Black
Note : [re] round solid conductor
(SNI IEC) : [rm] circular stranded conductor
Yellow/Green strip, Light Blue, Black, Brown (sm) sector shaped conductor

3. Inner covering /filler: Packing : [D] Drum


Extruded Polyvinyl Chloride (PVC), Black colour

4. Shield:
Annealed copper wire with transverse helix of Annealed copper tape

No. of cores Thickness Cross Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
and cross of section of of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
section area Insulation concentric sheath radius delivery
shield Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm sq.mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
4x1.5 re/1.5 0.8 1.5 1.8 14.7 236 265 12.1 50 24 18 0.55 0.24 0.17 1000/D
4x1.5 rm/1.5 0.8 1.5 1.8 15.2 249 274 12.1 50 24 18 0.55 0.24 0.17 1000/D
4x2.5 re/2.5 0.8 2.5 1.8 15.8 303 284 7.41 50 32 25 0.91 0.41 0.29 1000/D
4x2.5 rm/2.5 0.8 2.5 1.8 16.4 324 295 7.41 50 32 25 0.91 0.41 0.29 1000/D
4x4 re/4 1.0 4 1.8 18.1 428 326 4.61 50 41 34 1.45 0.65 0.46 1000/D
4x4 re/4 1.0 4 1.8 18.9 457 340 4.61 50 41 34 145 0.65 0.46 1000/D
4x6 re/6 1.0 6 1.8 19.3 546 347 3.08 50 52 44 2.18 0.98 0.69 1000/D
4x6 rm/6 1.0 6 1.8 20.2 585 364 3.08 50 52 44 2.18 0.98 0.69 1000/D
4x10 rm/10 1.0 10 1.8 22.7 817 409 1.83 50 69 60 3.64 1.63 1.15 1000/D
4x16 rm/16 1.0 16 1.8 25.3 1155 455 1.15 40 89 80 5.82 2.60 1.84 1000/D
4x25 rm/16 1.2 16 1.8 29.2 1648 526 0.727 40 116 105 9.09 4.07 2.88 1000/D
4x35 rm/16 1.2 16 1.8 31.8 2095 572 0.524 40 138 130 12.73 5.69 4.03 1000/D
4x50 sm/25 1.4 25 2.0 33.7 2664 607 0.387 30 165 160 18.18 8.13 5.75 1000/D
4x70 sm/35 1.4 35 2.1 40.2 3573 724 0.268 30 205 200 25.46 11.38 8.05 1000/D
4x95 sm/50 1.6 50 2.3 42.6 4880 767 0.193 30 245 245 34.55 1545 10.93 1000/D
4x120 sm/70 1.6 70 2.4 47.4 6153 853 0.153 30 285 285 43.64 19.52 13.80 1000/D
4x150 sm/70 1.8 70 2.6 50.6 7377 911 0.124 20 315 325 54.45 24.40 17.25 500/D
4x185 sm/95 2.0 95 2.8 57.5 9195 1 ,035 0.0991 20 355 370 67.28 30.09 21.28 500/D
4x240 sm/120 2.2 120 3.0 63.8 11865 1,148 0.0754 20 415 435 87.28 39.03 27.60 250/D
4x300 sm/150 2.4 150 3.2 71.6 14420 1,289 0.0601 20 465 500 109.10 48.79 34.50 250/D

34 www.kabelindo.co.id
Copper Conductor PVC Insulated, Concentric Copper wire Screened & PVC Sheathed Control Cable
Cu/PVC/CWS/PVC 0.6/1 kV (NYCY)
Specification :
SPLN 43-4 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or
according to SPLN 41 - 1 ; IEC 60228 5. Outer sheath:
Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite
2. Insulation: and/or special flame retardant, PVC sheath can be provided on
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : request.
IEC 60502-1
Applications:
Identification of core : For indoor installations, in power and switching stations.
Black with White printed number As underground cable, for difficult installation where the low
weight is particularly advantageous.
3. Inner Covering / filler:
Extruded Polyvinyl Chloride [PVC], Black colour Note: (re) round solid conductor
(rm) circular stranded conductor
4. Shield:
Annealed copper wire with transverse helix of Annealed copper tape Packing : [D] Drum

Thickness Cross Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
No. of cores of section of of outer Diameter of Cable Current Capacity at
bending at 20°C Capacity at 30°C Standard
and cross Insulation concentric sheath
radius delivery
section area shield Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm sq.mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
5x1.5 re/2.5 0.8 2.5 1.8 16.4 361 295 12.1 50 19 15 0.55 0.24 0.17 1000/D
5x1.5 rm/2.5 0.8 2.5 1.8 16.6 372 299 12.1 50 19 15 0.55 0.24 0.17 1000/D
7x1.5 re/2.5 0.8 2.5 1.8 17 407 306 12.1 50 17 13 0.55 0.24 0.17 1000/D
7x1.5 rm/2.5 0.8 2.5 1.8 17.6 441 317 12.1 50 17 13 0.55 0.24 0.17 1000/D
8x1.5 re/2.5 0.8 2.5 1.8 18 445 324 12.1 50 16 12 0.55 0.24 0.17 1000/D
8x1.5 rm/2.5 0.8 2.5 1.8 18.7 485 337 12.1 50 16 12 0.55 0.24 0.17 1000/D
10x1.5 re/2.5 0.8 2.5 1.8 20.1 542 362 12.1 50 15 11 0.55 0.24 0.17 1000/D
10x1.5 rm/2.5 0.8 2.5 1.8 20.9 592 376 12.1 50 15 11 0.55 0.24 0.17 1000/D
12x1.5 re/2.5 0.8 2.5 1.8 20.6 594 371 12.1 50 14 11 0.55 0.24 0.17 1000/D
12x1.5 rm/2.5 0.8 2.5 1.8 21.5 649 387 12.1 50 14 11 0.55 0.24 0.17 1000/D
14x1.5 re/2.5 0.8 2.5 1.8 21.4 647 385 12.1 50 13 10 0.55 0.24 0.17 1000/D
14x1.5 rm/2.5 0.8 2.5 1.8 22.3 710 401 12.1 50 13 10 0.55 0.24 0.17 1000/D
16x1.5 re/4 0.8 4 1.8 22.7 721 409 12.1 50 12 10 0.55 0.24 0.17 1000/D
16x1.5 rm/4 0.8 4 1.8 23.3 775 419 12.1 50 12 10 0.55 0.24 0.17 1000/D
19x1.5 re/4 0.8 4 1.8 23.2 784 418 12.1 50 12 9 0.55 0.24 0.17 1000/D
19x1.5 rm/4 0.8 4 1.8 24.3 865 437 12.1 50 12 9 0.55 0.24 0.17 1000/D
21x1.5 re/6 0.8 6 1.8 24.2 866 436 12.1 50 11 9 0.55 0.24 0.17 1000/D
21x1.5 rm/6 0.8 6 1.8 25.3 955 455 12.1 50 11 9 0.55 0.24 0.17 1000/D
24x1.5 re/6 0.8 6 1.8 25.8 958 464 12.1 50 11 8 0.55 0.24 0.17 1000/D
24x1.5 rm/6 0.8 6 1.8 27 1058 486 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 re/6 0.8 6 1.8 27.7 1125 499 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 rm/6 0.8 6 1.8 29 1247 522 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 re/10 0.8 10 1.8 30.7 1417 553 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 rm/10 0.8 10 1.8 32.2 1576 580 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 re/10 0.8 10 1.9 34.8 1785 626 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 rm/10 0.8 10 1.9 36.5 1988 657 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 re/10 0.8 10 2.0 37 2025 666 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 rm/10 0.8 10 2.0 38.7 2259 697 12.1 50 11 8 0.55 0.24 0.17 1000/D

sales@kabelindo.co.id 35
Copper Conductor PVC Insulated, Concentric Copper wire Screened & PVC Sheathed Control Cable
Cu/PVC/CWS/PVC 0.6/1 kV (NYCY)
Specification :
SPLN 43-4 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or
according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite and/or
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : special flame retardant. PVC sheath can be provided on request
IEC 60502-1
Applications:
For indoor installations, in power and switching stations.
Identification of core: (SPLN)
As underground cable, for difficult installation where the low weight is
Black with White printed number particularly advantageous.

3. Inner covering /filler: Note : [re] round solid conductor


Extruded Polyvinyl Chloride (PVC), Black colour [rm] circular stranded conductor

4. Shield: Packing : [D] Drum


Annealed copper wire with transverse helix of Annealed copper tape

No. of Thickness Cross Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of section of of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulationconcentric sheath radius delivery
section shield Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm sq.mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
5x2.5 re/2.5 0.8 2.5 1.8 17.5 432 315 7.41 50 26 21 0.91 0.41 0.29 1000/D
5x2.5 rm/2.5 0.8 2.5 1.8 17.8 453 320 7.41 50 26 21 0.91 0.41 0.29 1000/D
7x2.5 re/2.5 0.8 2.5 1.8 18.1 514 326 7.41 50 23 18 0.91 0.41 0.29 1000/D
7x2.5 rm/2.5 0.8 2.5 1.8 18.9 564 340 7.41 50 23 18 0.91 0.41 0.29 1000/D
8x2 5 re/2.5 0.8 2.5 1.8 19.3 565 347 7.41 50 21 17 0.91 0.41 0.29 1000/D
8x2.5 rm/2.5 0.8 2.5 1.8 20.2 620 364 7.41 50 21 17 0.91 0.41 0.29 1000/D
10x2.5 re/4 0.8 4 1.8 21.6 672 389 7.41 50 20 16 0.91 0.41 0.29 1000/D
10x2.5 rm/4 0.8 4 1.8 22.7 741 409 7.41 50 2D 16 0.91 0.41 0.29 1000/D
12x2.5 re/4 0.8 4 1.8 22.2 743 400 7.41 50 18 15 0.91 0.41 0.29 1000/D
12x2.5 rm/4 0.8 4 1.8 23.3 822 419 7.41 50 18 15 0.91 0.41 0.29 1000/D
14x2.5 re/6 0.8 6 1.8 23.1 818 416 7.41 50 17 14 0.91 0.41 0.29 1000/D
14x2.5 rm/6 0.8 6 1.8 24.3 907 437 7.41 50 17 14 0.91 0.41 0.29 1000/D
16x2.5 re/6 0.8 6 1.8 24.5 914 441 7.41 50 17 13 0.91 0.41 0.29 1000/D
16x2.5 rm/6 0.8 6 1.8 25.4 997 457 7.41 50 17 13 0.91 0.41 0.29 1000/D
19x2.5 re/6 0.8 6 1.8 25.2 1007 454 7.41 50 16 13 0.91 0.41 0.29 1000/D
19x2 5 rm/6 0.8 6 1.8 26.5 1122 477 7.41 50 16 13 0.91 0.41 0.29 1000/D
21x2.5 re/10 0.8 10 1.8 26.4 1153 475 7.41 50 15 12 0.91 0.41 0.29 1000/D
21x2.5 rm/10 0.8 10 1.8 27.8 1281 500 7.41 50 15 12 0.91 0.41 0.29 1000/D
24x2.5 re/10 0.8 10 1.8 28.1 1278 506 7.41 50 14 11 0.91 0.41 0.29 1000/D
24x2.5 rm/10 0.8 10 1.8 29.7 1338 535 7.41 50 14 11 0.91 0.41 0.29 1000/D
30x2.5 re/10 0.8 10 1.8 30.3 1510 545 7.41 50 14 11 0.91 0.41 0.29 1000/D
30x2.5 rm/10 0.8 10 1.8 32 1687 576 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2.5 re/10 0.8 10 1.9 34.1 1917 614 7.41 50 14 11 0.91 0.41 0.29 1000/D
40x2.5 rm/10 0.8 10 1.9 36.1 2145 650 7.41 50 14 11 0.91 0.41 0.29 1000/D
52x2.5 re/10 0.8 10 2.1 38.4 2402 691 7.41 50 14 11 0.91 0.41 0.29 1000/D
52x2.5 rm/10 0.8 10 2.1 40.7 2694 733 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 re/10 0.8 10 2.1 40.5 2716 729 7.41 50 14 11 0.91 0.41 0.29 1000/D
61x2.5 rm/10 0.8 10 2.1 43 3053 774 7.41 50 14 11 0.91 0.41 0.29 1000/D

36 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/DSTA/PVC 0.6/1 kV (NYBY)
Specification :
SPLN 43-3 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or
according to SPLN 41 - 1 ; IEC 60228

2. Insulation:
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : 5. Outer sheath:
IEC 60502-1 Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite and/or
special flame retardant, PVC sheath can be provided on request.
Identification of core: (SPLN)
Light Blue, Black Applications:
For installations as underground, outdoor, indoor in ducts and where
(SNI IEC) mechanical protection is required or for higher tensile stresses during
Light Blue, Brown installation and operation.

3. Inner Covering / filler: Note : [re] round solid conductor


Extruded Polyvinyl Chloride [PVC], Black colour [rm] circular stranded conductor

4. Armour
Two layers of galvanized steel tape helically applied Packing : [D] Drum

No. of Thickness Armour Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of Steel of outer Diameter of Cable bending Capacity at 30°C Current Capacity at Standard
and cross Insulation Tape sheath radius delivery
section thickness Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx) second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
2x6 re 1.0 0.3 1.8 16.7 557 301 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x6 rm 1.0 0.3 1.8 17.5 587 315 3.08 50 59 48 2.18 0.98 0.69 1000/D
2x10 rm 1.0 0.3 1.8 19.4 709 349 1.83 50 78 66 3.64 1.63 1.15 1000/D
2x16 rm 1.0 0.3 1.8 21.3 894 383 1.15 40 102 90 5.82 2.60 1.84 1000/D
2x25 rm 1.2 0.3 1.8 24.8 1248 446 0.727 40 134 120 9.09 4.07 2.88 1000/D
2x35 rm 1.2 0.3 1.8 27.2 1555 490 0.524 40 160 150 12.73 5.69 4.03 1000/D
2x50 rm 1.4 0.3 1.8 30.3 1952 545 0.387 30 187 180 18.18 8.13 5.75 1000/D
2x70 rm 1.4 0.3 1.9 34.5 2600 621 D.268 30 230 230 25.46 11.38 8.05 1000/D
2x95 rm 1.6 0.5 2.1 40.4 3745 727 0.193 30 280 275 34.55 15A5 10.93 1000/D
2x120 rm 1.6 0.5 2.2 43.8 4476 788 0.153 30 320 320 43.64 19.52 13.80 1000/D
2x150 rm 1.8 0.5 2.4 48.4 541 8 871 0.124 20 355 379 54.55 24.40 17.25 500/D
2x185 rm 2.0 0.5 2.5 53.3 6649 959 0.0991 20 409 430 67.28 30.09 21.28 500/D
2x240 rm 2.2 0.5 2.7 59.7 8524 1,075 0.0754 20 472 510 87.28 39.03 27.60 250/D
2x300 rm 2.4 0.5 2.9 65.8 10229 1,184 0.0601 20 525 590 109.10 48.79 34.50 250/D

sales@kabelindo.co.id 37
Copper Conductor PVC Insulated, & PVC Sheathed Armoured Power Cable
Cu/PVC/DSTA/PVC 0.6/1 kV (NYBY)
Specification :
SPLN 43-3 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or
sector shape according to SPLN 41 - 1 ; IEC 60228

2. Insulation:
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : 5. Outer sheath:
IEC 60502-1 Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite
and/or special flame retardant. PVC sheath can be provided on
Identification of core: (SPLN) request

Colour of insulation Applications:


System - i System - o For indoor installations, in power and switching stations.
Yellow/Green strip, Light Blue, Black Light Blue, Yellow, Black As underground cable, for difficult installation where the low
weight is particularly advantageous.
(SNI IEC)
Yellow/Green strip, Light Blue, Brown Note : [re] round solid conductor
[rm] circular stranded conductor
3. Inner covering /filler: (sm) sector shaped conductor
Extruded Polyvinyl Chloride (PVC), Black colour
Packing : [D] Drum
4. Armour:
Two layers of galvanized steel tape helically applied

No. of Thickness Armour Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of Steel of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation Tape sheath radius delivery
section thickness Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
3x4 re 1.0 0.3 1.8 16.4 499 295 4.61 50 41 34 145 0.65 0.46 1000/D
3x4 rm 1.0 0.3 1.8 17.2 534 310 4.61 50 41 34 145 0.65 0.46 1000/D
3x6 re 1.0 0.3 1.8 17.5 591 315 3.08 50 52 44 2.18 0.98 0.69 1000/D
3x6 rm 1.0 0.3 1.8 18.4 638 331 3.08 50 52 44 2.18 0.98 0.69 1000/D
3x10 rm 1.0 0.3 1.8 20.4 835 367 1.83 50 69 60 3.64 1.63 1.15 1000/D
3x16 rm 1.0 0.3 1.8 22.5 1159 405 1.15 40 89 80 5.82 2.60 1.84 1000/D
3x25 rm 1.2 0.3 1.8 26.2 15.17 472 0.727 40 116 105 9.09 4.07 2.88 1000/D
3x35 rm 1.2 0.3 1.8 28.6 1894 515 0.524 40 138 130 12.73 5.69 4.03 1000/D
3x50 sm 1.4 0.3 1.9 30.5 2238 549 0.387 30 165 160 18.18 8.13 5.75 1000/D
3x70 sm 1.4 0.3 2.0 33.9 3007 610 0.268 30 205 200 25.46 11.38 8.05 1000/D
3x95 sm 1.6 0.5 2.2 38.9 4256 700 0.193 30 245 245 34.55 15.45 10.93 1000/D
3x120 sm 1.6 0.5 2.3 41.6 5124 749 0.153 30 285 285 43.64 19.52 13.80 1000/D
3x150 sm 1.8 0.5 2.4 45.6 6223 821 0.124 20 315 325 54.55 24.40 17.25 500/D
3x185 sm 2.0 0.5 2.6 49.4 7613 889 0.0991 20 355 370 67.28 30.09 21.28 500/D
3x240 sm 2.2 0.5 2.8 54.8 9623 986 0.0754 20 415 435 87.28 39.03 27.60 250/D
3x300 sm 2.4 0.5 3.0 59.7 11588 1.075 0.0601 20 465 500 109.10 48.79 34.50 250/D

38 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/DSTA/PVC 0.6/1 kV (NYBY)
Specification :
SPLN 43-3 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or
sector shape according to SPLN 41 - 1 ; IEC 60228
5. Outer sheath:
2. Insulation: Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite and/or
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : special flame retardant, PVC sheath can be provided on request.
IEC 60502-1

Identification of core : (SPLN)


Applications:
For installations as underground, outdoor, indoor in ducts and where
Colour of insulation mechanical protection is required or for higher tensile stresses during
System - i System - o installation and operation.
Yellow/Green strip, Light Blue, Yellow, Black Light Blue, Red, Yellow, Black
Note : [re] round solid conductor
(SNI IEC) : [rm] circular stranded conductor
Yellow/Green Strip, Light Blue, Black, Brown (sm) sector shaped conductor

3. Inner Covering / filler: Packing : [D] Drum


Extruded Polyvinyl Chloride [PVC], Black colour

4. Armour
Two layers of galvanized steel tape helically applied

No. of Thickness Armour Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of Steel of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation Tape sheath radius delivery
section thickness Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
4x2.5 re 0.8 0.3 1.8 16.4 499 295 7.41 50 32 25 0.91 0.41 0.29 1000/D
4x2.5 rm 0.8 0.3 1.8 17.2 534 310 7.41 50 32 25 0.91 0.41 0.29 1000/D
4x4 re 1.0 0.3 1.8 16.4 499 295 4.61 50 41 34 1.45 0.65 0.46 1000/D
4x4 rm 1.0 0.3 1.8 17.2 534 310 4.61 50 41 34 1.45 0.65 046 1000/D
4x6 re 1.0 0.3 1.8 17.5 591 315 3.08 50 52 44 2.18 0.98 0.69 1000/D
4x6 rm 1.0 0.3 1.8 18.4 638 331 3.08 50 52 44 2.18 0.98 0.69 1000/D
4x10 rm 1.0 0.3 1.8 19.4 1101 349 1.83 50 69 60 3.64 1.63 1.15 1000/D
4x16 rm 1.0 0.3 1.8 21.8 1455 392 1.15 40 89 80 5.82 2.60 1.84 1000/D
4x25 rm 1.2 0.3 1.8 25.9 2093 466 0.727 40 116 105 9.09 4.07 2.88 1000/D
4x35 rm 1.2 0.3 1.9 28.6 2602 515 0.524 40 138 130 12.73 5.69 4.03 1000/D
4x50 sm 1.4 0.3 2.0 30 3080 540 0.387 30 165 160 18.18 8.13 5.75 1000/D
4x70 sm 1.4 0.5 2.2 34.1 4093 614 0.268 30 205 200 25.46 11.38 8.05 1000/D
4x95 sm 1.6 0.5 2.4 38.7 5370 697 0.193 30 245 245 34.55 15.45 10.93 1000/D
4x120 sm 1.6 0.5 2.5 42.6 6563 767 0.153 30 285 285 43.64 19.52 13.80 1000/D
4x150 sm 1.8 0.5 2.6 46.3 7938 833 0.124 20 315 325 54.55 2440 17.25 500/D
4x185 sm 2.0 0.5 2.8 52.2 9756 940 0.0991 20 355 370 67.28 30.09 21.28 500/D
4x240 sm 2.2 0.5 3.0 58.5 12409 1,053 0.0754 20 415 435 87.28 39.03 27.60 250/D
4x300 sm 2.4 0.5 3.2 65.4 15104 1,177 0.0601 20 465 500 109.10 48.79 34.50 250/D

sales@kabelindo.co.id 39
Copper Conductor PVC Insulated & PVC Sheathed Armoured Power Cable
Cu/PVC/DSTA/PVC 0.6/1 kV (NYBY)
Specification :
SPLN 43-3 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or 5. Outer sheath:
according to SPLN 41 - 1 ; IEC 60228 Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite
and/or special flame retardant. PVC sheath can be provided on
2. Insulation: request
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
IEC 60502-1 Applications:
For indoor installations, in power and switching stations.
Identification of core: (SPLN) As underground cable, for difficult installation where the low
Yellow/Green strip, Light Blue, Red, Yellow, Black weight is particularly advantageous.

(SNI IEC) Note : [re] round solid conductor


Yellow/Green strip, Light Blue, Black, Brown, Grey [rm] circular stranded conductor

3. Inner covering /filler: Packing : [D] Drum


Extruded Polyvinyl Chloride (PVC), Black colour

4. Armour:
Two layers of galvanized steel tape helically applied

No. of Thickness Armour Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of Steel of outer Diameter of Cable bending Capacity at 30°C Current Capacity at Standard
and cross Insulation Tape sheath radius delivery
section thickness Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
5x4 re 1.0 0.3 1.8 18.7 656 337 4.61 50 41 34 1.45 0.65 0.46 1000/D
5x4 rm 1.0 0.3 1.8 19.7 704 355 4.61 50 41 34 1.45 0.65 0.46 1000/D
5x6 re 1.0 0.3 1.8 20.1 842 362 3.08 50 52 44 2.18 0.98 0.69 1000/D
5x6 rm 1.0 0.3 1.8 21.2 857 382 3.08 50 52 44 2.18 0.98 0.69 1000/D
5x10 rm 1.0 0.3 1.8 23.7 1149 427 1.83 50 69 60 3.64 1.63 1.15 1000/D
5x16 rm 1.0 0.3 1.8 26.3 1498 473 1.15 40 89 80 5.82 2.60 1.84 1000/D
5x25 rm 1.2 0.3 1.8 31 2365 558 0.727 40 116 105 9.09 4.07 2.88 1000/D
5x35 rm 1.2 0.3 2.0 34.6 2803 623 0.524 40 138 130 12.73 5.69 4.03 1000/D
5x50 rm 1.4 0.5 2.2 40.4 3909 727 0.387 30 165 160 18.18 8.13 5.75 1000/D

40 www.kabelindo.co.id
Copper Conductor PVC Insulated & PVC Sheathed Armoured Control Cable
Cu/PVC/DSTA/PVC 0.6/1 kV (NYBY)
Specification :
SPLN 43-3 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or
according to SPLN 41 - 1 ; IEC 60228
4. Armour
2. Insulation: Two layers of galvanized steel tape helically applied
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 :
IEC 60502-1 5. Outer sheath:
Extruded Polyvinyl Chloride [PVC], Black colour, Anti termite and/or
Identification of core : (SPLN) special flame retardant, PVC sheath can be provided on request.
Colour of insulation
System - i System - o
Applications:
Yellow/Green strip, Black with White number Black with White number
For installations as underground, outdoor, indoor in ducts and where
mechanical protection is required or for higher tensile stresses during
(SNI IEC) : installation and operation.
Black with White number
Note : [re] round solid conductor
3. Inner Covering / filler: [rm] circular stranded conductor
Extruded Polyvinyl Chloride [PVC], Black colour
Packing : [D] Drum

No. of Thickness Armour Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
cores of Steel of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
and cross Insulation Tape sheath radius delivery
section thickness Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (nom) (approx) (approx] Max Min second second second
sq.mm mm sq.mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x1.5 re 0.8 0.3 1.8 15.9 458 286 12.1 50 17 13 0.55 0.24 0.17 1000/D
7x1.5 rm 0.8 0.3 1.8 16.4 483 295 12.1 50 17 13 0.55 0.24 0.17 1000/D
8x1.5 re 0.8 0.3 1.8 16.9 508 304 12.1 50 16 12 0.55 0.24 0.17 1000/D
8x1.5 rm 0.8 0.3 1.8 17.5 537 315 12.1 50 16 12 0.55 0.24 0.17 1000/D
10x1.5 re 0.8 0.3 1.8 18.8 609 338 12.1 50 15 11 0.55 0.24 0.17 1000/D
10x1.5 rm 0.8 0.3 1.8 19.6 642 353 12.1 50 15 11 0.55 0.24 0.17 1000/D
12x1.5 re 0.8 0.3 1.8 19.3 657 347 12.1 50 14 11 0.55 0.24 0.17 1000/D
12x1.5 rm 0.8 0.3 1.8 20.1 695 362 12.1 50 14 11 0.55 0.24 0.17 1000/D
14x1.5 re 0.8 0.3 1.8 20.2 721 364 12.1 50 13 10 0.55 0.24 0.17 1000/D
14x1.5 rm 0.8 0.3 1.8 20.9 763 376 12.1 50 13 10 0.55 0.24 0.17 1000/D
16x1.5 re 0.8 0.3 1.8 21 785 378 12.1 50 12 10 0.55 0.24 0.17 1000/D
16x1.5 rm 0.8 0.3 1.8 21.8 831 392 12.1 50 12 10 0.55 0.24 0.17 1000/D
19x1.5 re 0.8 0.3 1.8 22 857 396 12.1 50 12 9 0.55 0.24 0.17 1000/D
19x1.5 rm 0.8 0.3 1.8 22.8 907 410 12.1 50 12 9 0.55 0.24 0.17 1000/D
21x1.5 re 0.8 0.3 1.8 22.7 924 409 12.1 50 11 9 0.55 0.24 0.17 1000/D
21x1.5 rm 0.8 0.3 1.8 23.7 972 427 12.1 50 11 9 0.55 0.24 0.17 1000/D
24x1.5 re 0.8 0.3 1.8 24.2 1027 436 12.1 50 11 8 0.55 0.24 0.17 1000/D
24x1.5 rm 0.8 0.3 1.8 25.3 1087 455 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 re 0.8 0.3 1.8 26 1205 468 12.1 50 11 8 0.55 0.24 0.17 1000/D
30x1.5 rm 0.8 0.3 1.8 27.2 1277 490 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 re 0.8 0.3 1.9 28.6 1488 515 12.1 50 11 8 0.55 0.24 0.17 1000/D
40x1.5 rm 0.8 0.3 1.9 30.1 1577 542 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 re 0.8 0.3 2.0 32.3 1871 581 12.1 50 11 8 0.55 0.24 0.17 1000/D
52x1.5 rm 0.8 0.3 2.0 33.9 1882 610 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 re 0.8 0.3 2.0 34 2110 612 12.1 50 11 8 0.55 0.24 0.17 1000/D
61x1.5 rm 0.8 0.3 2.0 36.6 2428 659 12.1 50 11 8 0.55 0.24 0.17 1000/D

sales@kabelindo.co.id 41
Copper Conductor PVC Insulated & PVC Sheathed Armoured Control Cable
Cu/PVC/DSTA/PVC 0.6/1 kV (NYBY)
Specification :
SPLN 43-3 : 1994
IEC 60502-1 : 2004
SNI IEC 60502-1 : 2009

Constructions:
1. Conductor:
Annealed plain copper round solid or round circular stranded or
according to SPLN 41 - 1 ; IEC 60228 4. Armour:
Two layers of galvanized steel tape helically applied
2. Insulation:
Extruded layer of Polyvinyl Chloride (PVC] complied with SPLN 41-2 : 5. Outer sheath:
IEC 60502-1 Extruded Polyvinyl Chloride [PVC] Black colour, Anti termite
and/or special flame retardant. PVC sheath can be provided on
Identification of core: (SPLN) request
Colour of insulation
System - i System - o Applications:
Yellow/Green strip, Black with White number Black with White number For indoor installations, in power and switching stations.
As underground cable, for difficult installation where the low
(SNI IEC) weight is particularly advantageous.
Black with White number
Note : [re] round solid conductor
3. Inner covering /filler: [rm] circular stranded conductor
Extruded Polyvinyl Chloride (PVC), Black colour
Packing : [D] Drum

No. of cores Thickness Armour Thickness Overall Weight Minimum DC. Resistance Current Carrying Conductor Short Circuit
and cross of Steel of outer Diameter of Cable bending at 20°C Capacity at 30°C Current Capacity at Standard
section area Insulation Tape sheath radius delivery
thickness Conductor Insulation in Ground in Air 0.1 0.5 1.0 length
(nom) (nom) (nom) (approx) (approx) Max Min second second second
sq.mm mm sq.mm mm mm kg/km mm Ohm/km M.Ohm.km A A kA kA kA m
7x2.5 re 0.8 0.3 1.8 17 561 306 7.41 50 23 13 0.91 0.41 0.29 1000/D
7x2.5 rm 0.8 0.3 1.8 17.8 597 320 7.41 50 23 13 0.91 0.41 0.29 1000/D
8x2.5 re 0.8 0.3 1.8 18.1 624 326 7.41 50 21 12 0.91 0.41 0.29 1000/D
8x2.5 rm 0.8 0.3 1.8 19 666 342 7.41 50 21 12 0.91 0.41 0.29 1000/D
10x2.5 re 0.8 0.3 1.8 20.3 752 365 7.41 50 20 11 0.91 0.41 0.29 1000/D
10x2.5 rm 0.8 0.3 1.8 21.4 803 385 7.41 50 20 11 0.91 0.41 0.29 1000/D
12x2.5 re 0.8 0.3 1.8 21.8 822 392 7.41 50 18 11 0.91 0.41 0.29 1000/D
12x2.5 rm 0.8 0.3 1.8 22 878 396 7.41 50 18 11 0.91 0.41 0.29 1000/D
14x2.5 re 0.8 0.3 1.8 21.7 909 391 7.41 50 17 10 0.91 0.41 0.29 1000/D
14x2.5 rm 0.8 0.3 1.8 23 971 414 7.41 50 17 10 0.91 0.41 0.29 1000/D
16x2.5 re 0.8 0.3 1.8 22.7 996 409 7.41 50 17 10 0.91 0.41 0.29 1000/D
16x2.5 rm 0.8 0.3 1.8 24 1063 432 7.41 50 17 10 0.91 0.41 0.29 1000/D
19x2.5 re 0.8 0.3 1.8 23.7 1097 427 7.41 50 16 9 0.91 0.41 0.29 1000/D
19x2.5 rm 0.8 0.3 1.8 25 1164 450 7.41 50 16 9 0.91 0.41 0.29 1000/D
21x2.5 re 0.8 0.3 1.8 24.8 1188 446 7.41 50 15 9 0.91 0.41 0.29 1000/D
21x2.5 rm 0.8 0.3 1.8 26.1 1267 470 7.41 50 15 9 0.91 0.41 0.29 1000/D
24x2.5 re 0.8 0.3 1.8 26.2 1327 472 7.41 50 14 8 0.91 0.41 0.29 1000/D
24)x2.5 rm 0.8 0.3 1.8 26.3 1415 473 7.41 50 14 8 0.91 0.41 0.29 1000/D
30x2.5 re 0.8 0.3 1.9 27.9 1472 502 7.41 50 14 8 0.91 0.41 0.29 1000/D
30x2.5 rm 0.8 0.3 1.9 28A 1677 511 7.41 50 14 8 0.91 0.41 0.29 1000/D
40x2.5 re 0.8 0.3 2.0 31.4 1965 565 7.41 50 14 8 0.91 0.41 0.29 1000/D
40x2.5 rm 0.8 0.3 2.0 33.4 2095 601 7.41 50 14 8 0.91 0.41 0.29 1000/D
52x2.5 re 0.8 0.5 2.2 36.2 2722 652 7.41 50 14 8 0.91 0.41 0.29 1000/D
52x2.5 rm 0.8 0.5 2.2 38.5 2904 693 7.41 50 14 8 0.91 0.41 0.29 1000/D
61x2.5 re 0.8 0.5 2.2 39.1 3144 704 7.41 50 14 8 0.91 0.41 0.29 1000/D
61x2.5 rm 0.8 0.5 2.2 40.6 3278 731 7.41 50 14 8 0.91 0.41 0.29 1000/D

42 www.kabelindo.co.id
DERATING FACTORS

sales@kabelindo.co.id 43
DERATING FACTORS

44 www.kabelindo.co.id
DERATING FACTORS

sales@kabelindo.co.id 45
DERATING FACTORS

46 www.kabelindo.co.id
DERATING FACTORS

sales@kabelindo.co.id 47
Conversion Table of Conductor Size

IEC JIS AMERICAN STANDARD

48 www.kabelindo.co.id
STANDARDS

sales@kabelindo.co.id 49
NOTES