FILTRATION PERFORMANCE TEST OF

A PANEL FILTER FOR GENERAL


VENTILATION APPLICATIONS

Pleated filter
592 x 592 x 50 [mm]
Synthetic media / Sandler filtration medium
Sawaloom Plus 8757

ISO ePM10 80% (0,944 m³/s)

TEST REPORT: SFM 230901-PL2


November 13th, 2023

According to ISO 16890-2, -3 and -4

Initiated by:

SFM Filtry Luczak Sp. z o.o.


Requested by: SFM Filtry Luczak Sp. z o.o.xx
Grodziska 45Land
STARA WIES (NADARZYN), 05 830
POLAND

Contact person: Agniesszka Zareba

Subject: Performance test of a panel filter utilizing synthetic media according to


ISO 16890-2, -3 and -4.

Test specimen: Panel filter in metal frame


Model / Parts ID: Pleated filter
Media type / ID: Synthetic / Sandler filtration medium Sawaloom Plus 8757
Serial- or batch number: Not indicated
Flow direction: Arrow direction on filter label
Printing: See picture below
Dimensions (total): 592 x 592 x 50 mm
Pleat height: 45 mm
Nominal air flow: 3400 m³/h
Ambient pressure: 964 / 950 mbar
Samples received: October 20th, 2023
Filter test performed: October 24th, November 2nd + 8th, 2023

Test method: Test has been performed according to the procedures as defined in
ISO 16890-2, -3 and -4 “Air filter for general ventilation”.

Variations from the test standard: No.

General remarks: This test report consists of 13 pages and may only be published in its
entirety. Publications of excerpts from this report are only permitted with
written permission of Fiatec experts.

Report SFM 230901-PL2, Page 2 of 13


fiatec Filter & Aerosol Technologie GmbH, Burgkunstadter Str. 3, 95336 Mainleus, Germany
Results: The detailed findings are summarized on pages 4 through 13.

The results apply to the tested filter only at the test conditions mentioned
above. Filtration performance data of related filters of the same design and
media will be similar. Filtration performance under certain application
conditions cannot necessarily be predicted from these data.

According to the classification requirements described in ISO 16890-1 the filter element complies
with the grade ISO ePM10 80% at a nominal air flow of 3400 m³/h (media velocity of 62,0 cm/s).

The net effective filtering area of 1,5 m² was calculated using the following measured
approximate dimensions:

Note: This calculated value can differ from the total used media area as calculated by the
manufacturer of the filter. Also for example small variations in the pleat height can cause some
percental difference.

Effective width of pleats: 584 mm


Effective number of pleats: 29
Pleat height: 45 mm

Steffan Trnetschek
(Managing Director)

This document is electronically signed and valid without personal signature. The verification of this
signature can be assured with any PDF application having online access to the Adobe Approved Trust List
(AATL), e.g. Adobe or Foxit Reader

Report SFM 230901-PL2, Page 3 of 13


fiatec Filter & Aerosol Technologie GmbH, Burgkunstadter Str. 3, 95336 Mainleus, Germany
ISO 16890-1:2016 - AIR FILTER TEST RESULT SUMMARY

Testing organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
GENERAL
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Supervisor: Steffan Trnetschek Device obtained on: 20.10.2023
Test requested by: SFM Filtry Luczak Sp. z o.o. Device obtained from: SFM Filtry Luczak Sp. z o.o.
DEVICE TESTED
Model: Manufacturer: Construction:

Pleated filter SFM Filtry Luczak Sp. z o.o. Panel filter in metal frame

Type of media / media ID: Net effective filtering area [m²]: Filter dimensions (width × height × depth) [mm]:
Synthetic / Sandler filtration medium Sawaloom Customer data: 592 x 592 x 50 mm
1,5
Plus 8757 Measured dimension: 592 x 592 x 50 mm
TEST DATA AND ATTACHED TEST REPORTS
Test air flow rate [m³/s]: 0,944 Additional information
Test air flow rate [m³/h]: 3400 Test report to ISO 16890-Part 2 Yes -Part 3 Yes -Part 4 Yes
RESULTS
Initial pressure differential [Pa]: Initial grav. arrestance [%]: ePM1, min [%] ePM2,5, min [%]
ISO rating
205 75,5 29,7 ± 1,2 47,3 ± 1,9
Final test pressure diff. [Pa] Average grav. arrestance [%]:ePM1 [%] ePM2,5 [%] ePM10 [%] ISO ePM 10
300 90,9 28,5 ± 1,9 46,8 ± 2 80,3 ± 1,6 80 %
Test dust capacity [g]: 12,3 Remarks:

100
90 Conditioned
fractional
Fractional efficiency [%]

80 KCl efficiency efficiency ED,i


(ISO 16890-4)
70
60 Average
50 fractional
efficiency EA,i
40 (ISO 16890-1)
30
DEHS efficiency Initial
20 fractional
10 efficiency Ei
(ISO 16890-2)
0
0,1 1,0 10,0
Particle size [μm]

Dust fed [g]


0 2 4 6 8 10 12 14
350 100 Pressure
differential as a
90 function of the
300
80 test dust load
Pressure differential [Pa]

(ISO 16890-3)
250 70
Arrestance [%]

60 Pressure
200
differential as a
50
function of the
150 40 air flow rate
30 (clean filter)
100 (ISO 16890-2)
20 Grav.
50
10 arrestance as a
function of the
0 0
test dust load
0 500 1000 1500 2000 2500 3000 3500 4000 4500 (ISO 16890-3)
Air flow rate [m³/h]
NOTE: The results of this test relate only to the test device in the condition stated herein. The performance results cannot by themselves
be quantitatively applied to predict filtration performance in all "real life" environments.

14.11.2023
Date Signature Report SFM 230901-PL2, Page 4 of 13
ISO 16890-1:2016 - FRACTIONAL EFFICIENCY VALUES

Testing Organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Model: Pleated filter Manufacturer: SFM Filtry Luczak Sp. z o.o.
Test air flow [m³/h]: 3400 Efficency aerosol PM1 / PM2,5: DEHS / KCl

di d i+1 d m,i Δln d i


i E i [%] E D,i [%] E A,i [%]
[μm] [μm] [μm] [μm]

1 0,30 0,40 0,35 0,29 11,5 13,8 12,7

2 0,40 0,60 0,49 0,41 21,7 23,2 22,5

3 0,60 0,70 0,65 0,15 39,4 43,1 41,3

4 0,70 1,00 0,84 0,36 56,1 59,4 57,8

5 1,00 1,30 1,14 0,26 81,7 80,1 80,9

6 1,30 1,60 1,44 0,21 84,8 83,5 84,2

7 1,60 2,20 1,88 0,32 88,8 87,2 88,0

8 2,20 3,00 2,57 0,31 92,2 91,0 91,6

9 3,00 4,00 3,46 0,29 94,5 93,5 94,0

10 4,00 5,50 4,69 0,32 96,3 95,4 95,8

11 5,50 7,00 6,20 0,24 97,6 96,4 97,0

12 7,00 10,00 8,37 0,36 98,1 97,3 97,7

di Lower limit particle diameter in a size range i, μm


d i+1 Lower limit particle diameter in a size range i, μm
d m,i Geometric mean diameter of a size range i, μm
Δln d i Logarithmic width of a particle diameter size range i; ln is the natural logarithm to the base of e, where e is
an irrational and transcendental constant approximately equal to 2,718281828, dimensionless Δln di = ln (di+1/di)
Ei Initial fractional efficiency of particle size range i of the untreated and unloaded filter element, %
E D,i Fractional efficiency of particle size range i of the filter element after an artificial conditioning step, %
E A,i Average fractional efficiency (Ei+ED,i)/2 of particle size range i, %

Report SFM 230901-PL2, Page 5 of 13


ISO 16890-1:2016 – Calculation of PM-efficiencies

Testing Organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Model: Pleated filter Manufacturer: SFM Filtry Luczak Sp. z o.o.
Test air flow [m³/h]: 3400 Efficency aerosol PM1 / PM2,5: DEHS / KCl
urban
d m,i Δln d i q3u (dm,i) E D,i x q3u (dm,i) E A,i x q3u (dm,i) ePMx, min ePMx
i distribut.
x Δln d i x Δln d i x Δln d i [%] [%]
[μm] [μm] q3u (dm,i)

1 0,35 0,29 0,2263 0,06509 0,900246 0,825478

2 0,49 0,41 0,1932 0,07833 1,819148 1,761006

3 0,65 0,15 0,1517 0,02339 1,007701 0,964694

4 0,84 0,36 0,1152 0,04110 2,440845 2,373532 ePM 1, min ePM 1

Σ line 1-4 0,20791 6,16794 5,92471 29,7 28,5

5 1,14 0,26 0,0850 0,02231 1,787728 1,805131

6 1,44 0,21 0,0762 0,01582 1,320711 1,331221

7 1,88 0,32 0,0802 0,02555 2,228346 2,248434

8 2,57 0,31 0,0998 0,03097 2,818051 2,836139 ePM 2,5, min ePM 2,5

Σ line 1-8 0,30255 14,32278 14,14563 47,3 46,8

rural
d m,i Δln d i q3r (dm,i) E A,i x q3r (dm,i) ePMx
i distribut.
x Δln d i x Δln d i [%]
[μm] [μm] q3r (dm,i)

1 0,35 0,29 0,0941 0,02708 0,343365

2 0,49 0,41 0,0823 0,03337 0,750156

3 0,65 0,15 0,0732 0,01128 0,465489

4 0,84 0,36 0,0701 0,02502 1,444780

5 1,14 0,26 0,0763 0,02001 1,619361

6 1,44 0,21 0,0883 0,01834 1,543524

7 1,88 0,32 0,1080 0,03441 3,028311

8 2,57 0,31 0,1373 0,04257 3,899225

9 3,46 0,29 0,1671 0,04807 4,518265

10 4,69 0,32 0,1954 0,06223 5,962686

11 6,20 0,24 0,2167 0,05226 5,071012

12 8,37 0,36 0,2314 0,08254 8,064147 ePM 10

Σ line 1-12 0,45718 36,71032 80,3

Report SFM 230901-PL2, Page 6 of 13


ISO 16890-2:2016 - AIR FILTER TEST RESULT SUMMARY

Testing organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
GENERAL
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Operator: Susanne Weiß Date of test: 24.10.2023
Test requested by: SFM Filtry Luczak Sp. z o.o. Test sample obtained from: SFM Filtry Luczak Sp. z o.o.
Particle counter information Airflow measurement:
Manufacturer: Model: Coincidence value [p/dm³]: Wilson Grid
Klotz Abakus ca. 700.000 ( Prandtl Tube princible)
DEVICE TESTED
Model: Manufacturer: Construction:

Pleated filter SFM Filtry Luczak Sp. z o.o. Panel filter in metal frame

Type of media / media ID: Net effective filtering area [m²]: Filter dimensions (width × height × depth) [mm]:
Synthetic / Sandler filtration medium Sawaloom Customer data: 592 x 592 x 50 mm
1,5
Plus 8757 Measured dimension: 592 x 592 x 50 mm
Filter / media electrostatic charge: Media colour: Media adhesive / additive:
Not available White Not available
Device condition: (clean/initial, used, conditioned per ISO 16890-4, dust loaded per ISO 16890-3, etc.) (If dust loaded, include dust type)
Clean / Initial
Other descriptive information:
TEST DATA SUMMARY
Air flow [m³/h]: Temperature [ºC]: Abs.press. [mbar] Test air RH [%]: Test aerosol: Loading dust or conditioning method:

3400 22 963 55 DEHS / KCl (see report sheets ISO 16890-3 and 4)

RESULTS
Initial resistance to airflow Rated final resistance to
205 300
(Pressure drop ) [Pa] airflow [Pa]
Fractional Efficiency at rated air flow [%]
d m,i Measured initial efficiency 95 % Uncertainty Totoal upstream
Range [μm] Test aerosol:
[μm] Ei [%] e ps [%] conc. (raw counts)
0,30 – 0,40 0,35 11,5 1,30 765.681 DEHS
0,40 – 0,60 0,49 21,7 1,53 804.507 DEHS
0,60 – 0,70 0,65 39,4 1,35 106.948 DEHS
0,70 – 1,00 0,84 56,1 1,10 212.180 DEHS
1,00 – 1,30 1,14 81,7 1,06 85.667 KCl
1,30 – 1,60 1,44 84,8 0,93 82.764 KCl
1,60 – 2,20 1,88 88,8 0,65 125.113 KCl
2,20 – 3,00 2,57 92,2 0,47 88.418 KCl
3,00 – 4,00 3,46 94,5 0,38 65.011 KCl
4,00 – 5,50 4,69 96,3 0,33 66.946 KCl
5,50 – 7,00 6,20 97,6 0,34 15.180 KCl
7,00 – 10,0 8,37 98,1 0,24 3.069 KCl

Remarks:

NOTE: The results of this test relate only to the test device in the condition stated herein. The performance results cannot by themselves
be quantitatively applied to predict filtration performance in all "real life" environments.

Report SFM 230901-PL2, Page 7 of 13

ISO 16890-2:2016 - AIR FILTER TEST RESULT DETAILS


ISO 16890-2:2016 - AIR FILTER TEST RESULT DETAILS

Testing Organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Operator: Susanne Weiß Date of test: 24.10.2023

TEST DATA DETAILS


Air flow Air flow Mass flow rate
% of rated Media velocity Resistance to
[kg/h], Density 1,20
air flow [m3/s] [m3/h] kg/m³
[m/s] airflow Δp 1,20 [Pa]
29 0,278 1000 1200 0,182 54
44 0,417 1500 1800 0,273 84
59 0,556 2000 2400 0,364 111
74 0,694 2500 3000 0,456 143
88 0,833 3000 3600 0,547 176
100 0,944 3400 4080 0,620 205
118 1,111 4000 4800 0,729 248
125 1,181 4250 5100 0,775 266

Resistance to airflow Δp 1,20


300

250
Resistance to airflow [Pa]

200

150

100

50

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
Air flow [m³/h]

Initial fractional efficiencies Ei by particle size


100

90
KCl efficiency
80

70
Fractional efficiency [%]

60

50

40
DEHS efficiency
30

20

10

0
0,1 1 10
Particle size [µm]

NOTE: The results of this test relate only to the test device in the condition stated herein. The performance results cannot by themselves
be quantitatively applied to predict filtration performance in all "real life" environments.

Report SFM 230901-PL2, Page 8 of 13


ISO 16890-4:2016 - AIR FILTER TEST RESULT SUMMARY

Testing organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
GENERAL
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Operator: Susanne Weiß Date of test: 02.11.2023
Test requested by: SFM Filtry Luczak Sp. z o.o. Test sample obtained from: SFM Filtry Luczak Sp. z o.o.
Particle counter information Airflow measurement:
Manufacturer: Model: Coincidence value [p/dm³]: Wilson Grid
Klotz Abakus ca. 700.000 ( Prandtl Tube princible)
DEVICE TESTED
Model: Manufacturer: Construction:

Pleated filter SFM Filtry Luczak Sp. z o.o. Panel filter in metal frame

Type of media / media ID: Net effective filtering area [m²]: Filter dimensions (width × height × depth) [mm]:
Synthetic / Sandler filtration medium Sawaloom Customer data: 592 x 592 x 50 mm
1,5
Plus 8757 Measured dimension: 592 x 592 x 50 mm
Filter / media electrostatic charge: Media colour: Media adhesive / additive:
Not available White Not available
Device condition: (clean/initial, used, conditioned per ISO 16890-4, dust loaded per ISO 16890-3, etc.) (If dust loaded, include dust type)
Conditioned per ISO 16890-4
Other descriptive information:
TEST DATA SUMMARY
Air flow [m³/h]: Temperature [ºC]: Abs.press. [mbar] Test air RH [%]: Test aerosol: Conditioning method:

3400 21 948 50 DEHS / KCl ISO 16890-4, Annex A.3

CONDITIONING INFORMATIONS:
Temp. range rel.hum. range barom. pressure Time of exposure / Conditioning cabinet
Purity of IPA liquid
[°C] [%] [mbar] conditioning [h] dimensions [mm]
22 - 24 43 - 56 963 - 948 > 99,5 % 24 810 x 750 x 1070
Conditioning Evaporated Volume [dm³]
Topas - Model TDC 584 200
cabinet descript. amount of IPA (ml) 650
Test device weight before conditioning / new (g) 1570,2
Test device weight after conditioning (g) 1571,6
RESULTS
Initial resistance to (rated) Resistance to test airflow
205 207
test airflow [Pa] after conditioning [Pa]
Fractional efficiency after conditioning at rated air flow [%]
d m,i Measured conditioned 95 % Uncertainty Totoal upstream
Range [μm] Test aerosol:
[μm] Efficiency ED [%] e ps [%] conc. (raw counts)
0,30 – 0,40 0,35 13,8 0,70 548.668 DEHS
0,40 – 0,60 0,49 23,2 0,38 569.355 DEHS
0,60 – 0,70 0,65 43,1 0,77 78.790 DEHS
0,70 – 1,00 0,84 59,4 0,56 155.451 DEHS
1,00 – 1,30 1,14 80,1 1,66 107.768 KCl
1,30 – 1,60 1,44 83,5 1,44 101.911 KCl
1,60 – 2,20 1,88 87,2 1,16 147.082 KCl
2,20 – 3,00 2,57 91,0 0,81 100.043 KCl
3,00 – 4,00 3,46 93,5 0,64 69.109 KCl
4,00 – 5,50 4,69 95,4 0,57 66.098 KCl
5,50 – 7,00 6,20 96,4 0,60 12.734 KCl
7,00 – 10,0 8,37 97,3 0,80 2.099 KCl

Remarks:

NOTE: The results of this test relate only to the test device in the condition stated herein. The performance results cannot by themselves
be quantitatively applied to predict filtration performance in all "real life" environments.

Report SFM 230901-PL2, Page 9 of 13

ISO 16890-4:2016 - AIR FILTER TEST RESULT DETAILS


ISO 16890-4:2016 - AIR FILTER TEST RESULT DETAILS

Testing organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Operator: Susanne Weiß Date of test: 02.11.2023

TEST DATA DETAILS (AFTER CONDITIONIONG)


Air flow Air flow Mass flow rate
% of rated Media velocity Resistance to air Init. Resistance to
[kg/h], Density 1,20
air flow [m3/s] [m3/h] [m/s] kg/m³
flow Δp 1,20 [Pa] air flow Δp 1,20 [Pa]
29 0,278 1000 0,182 1200 58 54
44 0,417 1500 0,273 1800 88 84
59 0,556 2000 0,364 2400 114 111
74 0,694 2500 0,456 3000 145 143
88 0,833 3000 0,547 3600 180 176
100 0,944 3400 0,620 4080 207 205
118 1,111 4000 0,729 4800 251 248
125 1,181 4250 0,775 5100 269 266

Resistance to air flow Δp 1,20 after conditionion per ISO 16890-4


300

250
Resistance to air flow [Pa]

200

150

100

50

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
Air flow [m³/h]

Fractional efficiencies after conditioning by particle size


100

90
Efficiency after Conditioning ED
80
KCl efficiency
70 Efficiency DEHS after Conditioning
Fractional efficiency [%]

at 50% Airflow
60

50

40

30

20
DEHS efficiency
10

0
0,1 1 10
Particle size [µm]

NOTE: The results of this test relate only to the test device in the condition stated herein. The performance results cannot by themselves
be quantitatively applied to predict filtration performance in all "real life" environments.

Report SFM 230901-PL2, Page 10 of 13


ISO 16890-3:2016 - AIR FILTER TEST RESULT SUMMARY

Testing organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
GENERAL
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Operator: Susanne Weiß Date of test: 08.11.2023
Test requested by: SFM Filtry Luczak Sp. z o.o. Test sample obtained from: SFM Filtry Luczak Sp. z o.o.
Air flow measurement: Wilson Grid ( Prandtl Tube princible)
DEVICE TESTED
Model: Manufacturer: Construction:

Pleated filter SFM Filtry Luczak Sp. z o.o. Panel filter in metal frame

Type of media / media ID: Net effective filtering area [m²]: Filter dimensions (width × height × depth) [mm]:
Synthetic / Sandler filtration medium Sawaloom Customer data: 592 x 592 x 50 mm
1,5
Plus 8757 Measured dimension: 592 x 592 x 50 mm
Filter / media electrostatic charge: Media colour: Media adhesive / additive:
Not available White Not available
Device condition: (clean/initial, used, conditioned per ISO 16890-4, dust loaded per ISO 16890-3, etc.) (If dust loaded, include dust type)
Conditioned per ISO 16890-4, Test Dust ISO 12103-1 A2
Other descriptive information:
TEST DATA SUMMARY
Air flow [m³/h]: Temperature [ºC]: Abs.press. [mbar] Test air RH [%]: Air density [kg/m³] Loading dust:
ISO 15957 - L2 (ISO 12103-A2)
3400 21 948 50 1,118
140 ± 14 mg/m³
RESULTS
Resistance to (rated) test airflow [Pa] Dust loading results
Initial measured: Initial arrestance Average arrestance Test dust capacity
205 / 207
new / conditioned [%] [%] [g]

Final: 300 75,5 90,9 12,3

Test Device Photo

Remarks:

NOTE: The results of this test relate only to the test device in the condition stated herein. The performance results cannot by themselves
be quantitatively applied to predict filtration performance in all "real life" environments.

Report SFM 230901-PL2, Page 11 of 13

ISO 16890-3:2016 - AIR FILTER TEST RESULT DETAILS


ISO 16890-3:2016 - AIR FILTER TEST RESULT DETAILS

Testing organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Operator: Susanne Weiß Date of test: 08.11.2023

TEST DATA DETAILS


Air flow Air flow Mass flow rate
% of rated Media velocity Resistance to air
[kg/h], Density 1,20
air flow [m3/s] [m3/h] kg/m³
[m/s] flow Δp 1,20 [Pa]
29 0,278 1000 1200 0,182 54
44 0,417 1500 1800 0,273 84
59 0,556 2000 2400 0,364 111
74 0,694 2500 3000 0,456 143
88 0,833 3000 3600 0,547 176
100 0,944 3400 4080 0,620 205
118 1,111 4000 4800 0,729 248
125 1,181 4250 5100 0,775 266

Resistance to air flow new filter Δp 1,20


300

250
Resistance to air flow [Pa]

200

150

100

50

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
Air flow [m³/h]

350

300

250
Resistance [Pa]

200

150

100

50

0
0 2 4 6 8 10 12 14 16
Dust load [g]

NOTE: The results of this test relate only to the test device in the condition stated herein. The performance results cannot by themselves
be quantitatively applied to predict filtration performance in all "real life" environments.

Report SFM 230901-PL2, Page 12 of 13

ISO 16890-3:2016 - AIR FILTER TEST RESULT DETAILS


Testing organization: fiatec GmbH, Germany, Burgkunstadterstr. 3 , 95336 Mainleus, +49(0)9229 99390
Report no.: SFM 230901 Sample no.: PL2 Date of report: 14.11.2023
Operator: Susanne Weiß Date of test: 08.11.2023

100

90

80
at mid-points of weight increments

70

60
Arrestance [%]

50

40

30

20

10

0
0 2 4 6 8 10 12 14 16
Dust load [g]

Pressure drop and arrestance vs. dust loading to filter and dust collection at test air flow
Mass gain of final filter
Mass of tested device

to filter (Cumulative)
Mass of loaded dust

Mass of loaded dust

Mass of loaded dust


to filter (differential)
+ dust in duct after

Average arrestance
to filter (Cum), mid
at various loading

Dust collected on

Dust collected on
device ( Δmff)

tested device

tested device
(Cumulative)
(differential)

Arrestance
Dp 1,20

points
steps

Δm

[Pa] [g] [g] [g] [g] [g] [g] [g] [%] [%]
205 1571,9 0,0 0,0 0,0 0,0 0,0
227 1574,1 0,7 2,9 2,9 1,5 2,2 2,2 75,5 75,5
262 1579,3 0,3 5,5 8,4 5,7 5,2 7,5 95,1 88,3
300 1584,2 0,3 5,1 13,6 11,0 4,9 12,3 95,1 90,9

Note: The mass balance might deviate slightly due to the rounding of the last digits of the weight measurements.

Dust holding capacity [g] at 300 Pa: 12,3

Initial gravimetric arrestance [%]: 75,5

Average arrestance [%] at 300 Pa: 90,9

Report SFM 230901-PL2, Page 13 of 13