Item Material Description Brand/ Model Country of Test report / Certification no. Location of Use
Origin
Washable Panel Type Air Filter
1. Washable Panel Type Air Filter Wing Shing/ PRC Report on Filter Test Whole building
WAF-25-6LHD & No. RALC00183
WAF47-12L (Page 4)
Page1/27
Page2/27
CONTRACT TITLE: The Hong Kong Document No. EQ-AC-005
Palace Museum
CONTRACT No.: CC/2018/04/068
Description : Washable Panel Type Air Filter
Page3/27
Page4/27
Page5/27
Page6/27
Page7/27
Page8/27
Page9/27
3040 Cornwallis Rd. PO Box 12194 Research Triangle Park, NC 27709
Telephone 919 541 6941 Fax 919 541 6936 www.rti.org
Test Laboratory:
RTI
3040 Cornwallis Road
Research Triangle Park, NC 27709
919-541-6941
mko@rti.org
Page10/27
ASHRAE Std. 52.2-2012 Air Cleaner Performance Report Summary
This report applies to the tested device only.
Laboratory Data
RTI Report No. BX07291401 Date 29-Jul-14
Test Laboratory Research Triangle Institute
Operator Pope Supervisor Owen/Hanley
Particle Counter(s): Brand Climet Model 500 Spectrometer
Device Description
Nominal Dimensions (in.): 24 x 24 x 1 (height x width x depth) 610 x 610 x 25 mm
Generic name flat panel Media color silver
Amount and type of adhesive NA
Other attributes NA
Test Conditions
Airflow (cfm) 1180 Temperature (F) 76 RH (%) 44
Face Velocity (fpm) 295 Final Pressure Drop (in. wg) 0.48
Test aerosol type: KCl
Remarks
Page11/27
Report No. BX07291401
Research Triangle Institute
100
90 Initial Efficiency
50
40
30
20
10
0
0.1 1 10
(in. H2O)
Resistance (in. H2O)
70
60 0.3
50
40 0.2
30
20 0.1
10
0 0
0.1 1 10 0 500 1000 1500
Particle Diameter (µm) Air Flow (cfm)
Page12/27
TABULATED DATA SUMMARY
Report No. BX07291401
Research Triangle Institute
Run No.
Initial efficiency BX07291402 0 0 1 0 3 5 7 11 21 25 31 28
after first dust load BX07291403 1 0 1 2 7 12 15 27 44 58 72 80
after second dust load BX07291404 2 1 4 7 16 23 29 39 55 65 79 86
after third dust load BX07301401 5 4 6 9 18 26 34 43 60 70 77 87
after fourth dust load BX07301402 3 4 7 13 20 30 41 50 64 73 83 87
after fifth dust load BX07301403 7 4 9 15 27 34 45 54 63 74 82 89
E1 = 0
E2 = 6
E3 = 26
MERV = 5
Resistance to Airflow:
Initial 0.18 44
After first dust load 0.19 47 30.0
After second dust load 0.25 63 101.1
After third dust load 0.33 82 46.6
After fourth dust load 0.41 101 31.4
After fifth dust load 0.48 120 28.5
Page14/27
Page15/27
Page16/27
Page17/27
Page18/27
CONTRACT TITLE: The Hong Kong Document No. EQ-AC-005
Palace Museum
CONTRACT No.: CC/2018/04/068
Description : Washable Panel Type Air Filter
AC GS – B1.2 Comply
AC GS – C1.3 Comply
MERV comply with ASHRAE 52 and EN779.
PS.BS01 – 3.5.3 Comply
Page19/27
Page20/27
Page21/27
Page22/27
Page23/27
Page24/27
Page25/27
CONTRACT TITLE: The Hong Kong Document No. EQ-AC-005
Palace Museum
CONTRACT No.: CC/2018/04/068
Description : Washable Panel Type Air Filter
1. The pressure drop from the submitted test report cannot According to ACGS, the final
comply with General Specification. Please clarify. resistance for 25mm & 50mm filter
shall be 75Pa & 100Pa respectively.
Page26/27
WEST KOWLOON CULTURAL DISTRICT AUTHORITY
RESPONSE to CONTRACTOR’S SUBMISSION FORM
Contract No. CC/2018/04/068
Main Contract for the Hong Kong Palace Museum
Document Title: HVAC Installation – Material Submission of Washable Panel Type Air Filter
1. The pressure drop from the submitted test report cannot be complied to General
Specification. Please clarify.
2. Sample submission is required for approval.
Status*: C
Signed by (CA/CAR):_______________(Date)_________________
*STATUS as per G.S. Clause 11.2.2. “A – Notice of No-Objection”; “B – Notice of No-Objection but subject to comments and no re-
submission is Required”; “C – Notice of No-Objection but subject to comments and a re-submission is required to address comments”; “D –
Notice of Objection, please resubmit” that he has objections, which shall be resubmitted.
Page27/27