Professional Documents
Culture Documents
Emotron ACDriveFDU2.0 OM
Emotron ACDriveFDU2.0 OM
0
AC drive
ffi
Trry
H
lnstruction manual
Engl ish
{-
ils
step to previous menu on the same level 1
13
2
Reference 14
3
4-2O mA 15
5
to
17
6
19
I
20
I
21
Remote control 10
11
22
Change settings using the keys on the control panel. Default toggle loop
Menu [100], Preferred View is displayed when started. Figure 3 shows the default toggle loop. This loop contains
the necessary menus that need to be set before starting. Press
1. *
Press to display menu [200], Main Setup.
Toggle to enter menu l2ll] then use the Next k.y to enter
2. Press ;{ and then * to display menu L220), Moror the sub menus ITLZ) to l21A] and enter the parameters.
'When
Data. you press the Toggle key again, menu l22l] is dis-
played.
3. Press ;{ to display menu 1221] and set moror voltage.
4. Change the value using the + and keys. Confirm
with *.
0-l0 v
4"20 mA
/./
Anlnl
Function (Default)
S1
Terminal Name Current (default) U
Anln2
I Digln 2 RunR; rotation right
Cu rrent (defa u lt)
S2 U
s{
O
13 AnOut 1 Min speed to max speed (lf desired) Anln3 rl
I
S3 r{
Current (default) U o
t4 AnOut 2 0 to max torque (lf desired) c!
cf)
t-
r{
22 Digln 8 Reset S4 o
Voltage U
O)
I
(o
Anln4 O)
cr)
S4 I
Current (default) U rl
o
m
C
o
l-
P
o
E
lrJ
Emotron AB, Mdrsaregatan 12, SE-250 24 Helsingbor& Tel: +46 42 76 99 OO, Fax: +46 42 16 99 49
www.gmotron.com
Emotron FDU 2.O
INSTRUCTION MANUAL - ENGLISH
Emotron AB OL-4428-01r3
Condensation
Ifthe AC drive is moved from a cold (storage) room ro a
room where it will be installed, condensation can occur.
This can result in sensitive components becoming damp. Do
not connect the mains voltage until all visible dampness has
evaporated.
lncorrect connection
The AC drive is not protected against incorrect connection
of the mains voltage, and in particular against connection of
the mains voltage to the motor outlets U, V and \W. The AC
drive can be damaged in this way.
Transport
To avoid darnxge, keep the AC drive in its original
packaging during transport. This packaging is specially
designed to absorb shocks during transport.
lT Mains supply
The AC drives can be modified for an IT mains supply,
(non-earthed neutral), please contact your supplier for
details.
Heat warning
HOT SURFACE!
Be aware of specific parts on the AC drive
having high temperature.
WARNING!
After switching off the mains supply,
dangerous voltage can stlll be present in the
AC drive. When opening the AC drive for
installi ng and/or commissioning activities
wait at least 7 minutes. ln case of malfunc'tion a
gualified technician should check the Dc-link or wait for
one hour before dismantling the AC drive for repair.
Emotron AB OL-4428-01r3
Gontents
3
5. GgttinB Staft(Bd.........!r..r.rrrrrrr..:r...r.rrrrttr....... 29
COntgntS rrrrrrr..:rr.r..r.rrrr.rr.trrr.rr.rrrrrr.rrrrrrrrrrrrr....
5.1 Connect the mains and motor cables 29
t-. lntfOdUCtiOn..tr.r.!rrr.r.rrrrrrtrr.:rrrrrr..!rr.!:.rr..rr.......5 5.1.1 Mains cables 29
L1, Delivery and unpacking.. 5 5.I.2 Motor cables 29
1,.2 Using of the instruction manual...... ........ 5 5.2 Using the function keys 29
1.3 Type code number.. 5 5.3 Remote control ..... 30
1,.4 Standards.. 6 5.3.1 Connect control cables 30
I.4.7 Product standard for EMC 6 5.3.2 Switch on the mains .. 30
1.5 Dismantling and scrapping.. 7 5.3.3 Set the Motor Data ........ 30
1,.5.1, Disposa! of old electrical and electronic 5.3.4 Run the AC drive 30
equipment 7
5.4 Local control ....,.. . 31
1.6 Glossary... 8
5.4.7 Switch on the mains .. 31
1.6.1 Abbreviations and symbols. 8
5.4.2 Select manual control...... 31
I.6.2 Definitions. 8
5.4.3 Set the Motor Data 31
2. MOUnting rrrr..r.r....rrr..rrr.r.rrrrrrrrrrrrrr:r.r.!rr........r.. 9 5.4.4 Enter a Reference Value ..-.. 31
Emotron AB OL-4428-01r3
9.1 General ..... 53 11.6 Logical Functions and Timers t6001 ...... L4I
9.2 The control panel 53 71,.6.L Comparators [610] ... I4I
9.2.7 The display 53 1,r.6.2 Logic Output Y [620] L51,
9.2.2 lndications on the display 54 11.6.3 Logic Output Z [630] ... LS
9.2.3 LED indicators... 54 1"1,.6.4 Timerl t6401 .. 155
9.2.4 Control keys 54 11.6.5 Timer2 [650] ..... 156
9.2.5 The Toggle and LoclRem Key ... 54 1,L.7 View Operation/Status [700] .. . 158
9.2.6 Function keys 56 LT.7.T Operation [710]. .. 158
9.3 The menu structure.. 56 I1_.7.2 Status l2Al . 160
9.3.1 The main menu ..... . 56 LL.7.3 Stored values [730] ... 163
9.4 Programming during operation.. 57 11.8 View Trip Log [800] ... 165
9.5 Editing values in a menu ..... 57 11.8.1 Trip Message log t8101 ... 165
9.6 Copy current parameter to all sets 57 1,1-.8.2 Trip Messages [820] - t8901 .... ..... 1Go
9.7 ProSramming example 58 11.8.3 t8A0l
Reset Trip Log ... 106
10. Sgrial communlcation r.rrr.!r.rrr.!r.r..r.r.rrrrrrrrrt 59 11.9 System Datat9001 ,.. 167
7!.9.7 VSD Data [920] ..
10.1 Modbus RTU 59 LGT
LI.2.2
13.2 Handheld Control Panel 2.O.. ... LTs
Remote Signal Level/Edge 121,A) 68
13.3 EmoSoftCom I7S
17.2.3 Mains supply voltage l21.B) 68 L3.4 Brakechopper...... ... LTG
LL.2.4 Motor Data t22oj . 69 13.5 l/O Board... ... L7T
11,.2.5 Motor Protection [230] .. 74 13.6 Encoder..... L77
1,I.2.6 Parameter Set Handling t24}l 77 13.7 PTC/PT100 . 777
II.2.7 Trip Autoreset/Trip Conditions t2501 ....... 80 13.8 Serial communication and fieldbus..... .. r.78
L1.2.8 Serial Communication [260] ..... 88 13.9 Standby supply board option..... 1-78
11.3 Process and Application Parameters [300] 91 13.10 Safe Stop option L79
7I.3.I Set/View Reference Value t3101 ...... 91 13.11 Output chokes ..... 181
II.3.2 Process Settings [320] .. 91 73.r2 Liquid cooling.. ..... 181
L1.3.3 Start/Stop settings t3301 .... 95 L4. TgChnical Data ...r.!,.rrr.rrr.rrrrrrr.rrr.rrrrrrrrrrr.rrr 183
11-.3.4 Mechanical brake control... 99
L4.T Electrical specifications related to model 183
11-.3.5 Speed t3401 103 14.2 General electrical specifications... r87
11.3.6 Torques [350]... . 105 14.3 Operation at higher temperatures .. 188
L1.3.7 Preset References [360].. 7O7 1,4.4 Operation at higher switching frequency. 188
11.3.8 PID Process Control t3801 109 L4.5 Dimensions and Weights.... 189
11.3.9 Pump/Fan Control [390] ..... ..... 1,I2 74.6 Envi ron mental conditions 190
1,!.4 Load Monitor and Process Protection t4001 118 L4.7 Fuses, cable cross-sections and glands L91,
LI.A.I Load Monitor t4101 ..... 118 1,4.7 .1, According IEC ratings 191
7!.4.2 Process Protection 14201..... .... !23 74.7,2 Fuses and cable dimensions according to
NEMA ratings
11.5 l/Os and Virtual Connections [500] ...... L25 193
1,4.8 Control signals.... 195
11.5.1 Analogue Inputs [510] ..... 1'25
7L.5.2 Digital lnputs t5201 .... 131 15. MenU LiSt rrrrr.rr.rr.rr.r.rrrrr.r.r..rrrt.r!.r.rrrrrr....rrrr L97
l-1.5.3 Analogue Outputs t53ol .. l-33
7I.5.4 Digital Outputs [540] ..... ... L37 lndeX ...rrr!!rrrrrrrr.rrrrrrrrrrrrrrrrrrr..r.r.r.rr.rrrrrr.r.... 2Os
Emotron AB OI-4428-01r3
!-. lntroduction
Emotron FDU is used most commonly to control and
protect pump and fan applications that put high demands
7..2 Using of the instruction
on flow control, process uptime and low maintenance costs. manual
It can also be used for e.g. compressors and blowers. The \Within this instruction manual the abbreviation 'AC drive"
used moror control method is V/Hz-control. Several options is used to indicate the complete variable speed drive as a
are available, listed in chapter 13. page 175, that enable you single unit.
to customize the AC drive for your specific needs.
Check that the sofrware version number on the first page of
this manual matches the sofnryare version in the AC drive.
NOTE: Read this instrustion manual carefully before See chapter 1 1.9 page 167
starting installation, connestion or working with the AC
drive. \7ith help of the index and the table of contents it is easy to
track individual functions and to find out how to use and set
them.
Users The Quick Setup Card can be put in a cabinet door, so that
This instruction manual is intended for: it is always easy to access in case of an emergency.
. installation engineers
o maintenance engineers 1.3 Type code number
o oPerators Fig. 1 gives an example of the rype code numbering used on
o all AC drives. \7ith this code number the exact type of the
service engineers
drive can be determined. This identification will be required
fur .ype specific information when mounting and installing.
Motors The code number is located on the product label, on the
The AC drive is suitable for use with stand ard 3-phase front of the unit.
asynchronous motors. Under certain conditions it is possible
to use other types of motors. Contact your supplier for
details.
FDU48-T75-54CE A NNNNA N
Position number:
1, 2 3 4 56 7 8 910LLL2L3L4 15 16 t7 L8
48=4OO V mains
2 2 Supply voltage 52=525 V mains
69:690 V mains
-003=2.5 A
Rated current (A)
3 3
contin uous
-1K5=1500 A
2O=lP20
4 4 Protection class
54=1P54
-=Blank panel
5 5 Control panel
C=Standard panel
E=Standard EMC
(Category C3)
6 6 EMC option F=Extended EMC
(Category C2)
!=lT-Net
8 8
Stand-by power -=No SBS t-.4.1 Product standard for EMC
supply option S=SBS included
Product standard EN(IEC)61800-3, second edition of 2oo4
Safe stop option defines the:
-=No safe stop
I (Only valid for
T-Safe stop incl. First Environment (Extended EMC) as environmenr that
090-1500)
includes domestic premises. It also includes establishments
9 10 Brand label A=Emotron directly connected without intermediate transformers ro a
Painted AC drive A-Sta ndard paint low voltage power supply nerwork that supplies buildings
10 (Only valid for B=White paint used for domestic purposes.
003-074) RAL9OlO
Catego ry C2: Power Drive System (PDS) of rated
Coated boards, - =Standard boards voltage< 1.000 V which is neither a plug in device nor a
LL !1,
option V-Coated boards movable device and, when used in the first environmenr, is
intended to be installed and commissioned only by
T2 t2 Option position 1 N=No option "
C-Crane l/O professional.
13 13 Option position 2
E=Encoder Second environment (Srandard EMC) includes all other
P=PTC/ PT100 establishments.
l=Extended I/O
T4 T4 Option position 3 Catego ry C3: PDS of rated voltage < I .000 V intended for
S-Safe Stop (only
003-074) use in the second environment and not intended for use in
the ftrst environmenr.
N-No option
D=DeviceNet Catego ry C4: PDS or rated voltage equal or above I .000 V
Option position,
15 15 P-Profibus or rated current equal to or above 400 A, or intended for use
comm unication
S=RS232/485 in complex systems in the second environment.
M=Modbus/TCP
The AC drive complies with the product standard
16 16 Software type A=Sta ndard EN(IEC) 61 800-3 :2004 (A,ry kind of metal screened cable
Motor PTC. (Only N-No option may be used). The standard AC drive is designed to meet the
L7
valid for OO3-A74) P=PTC requirements according ro caregory C3.
--Glands not By using the optional "Exrended EMC" filter the AC drive
Gland kit.
i ncl uded fulfils requirements according ro caregory C2,
18 (Only valid for
G=Gland kit
003-074)
i ncl uded
WARNING!
ln a domestic environment this product may
cause radio inteffetence, in whlch case it
may be necessary to take adequate
additional measutes.
WARNING!
The standard AC drive, complying with
category C3, is not lntended to be used on a
low-voltage publlc network whlch supplies
domestic premises; radio lnterference is
expected if used in such a network. Contact
your supplier if you need additional
measuJes.
Sync
Synchronous speed of the motor rpm
speed
Load: 56 lo 74 kg
Fig. 3 Remoue the roof unit and use the lfiing eyes to lifi
r ingle unit 600mm and 900mm.
450 4800N
60" 6400N
90' 13 600N
300-1500
oo3-018 026-074 090-250
cabinet
a 200 200 200 100
Fig. 6 Cable interface for mains, motor and communica-
FDU-FDU b 200 200 200 0 tion,FDU4S/52: Model 003 ro 0lS (B)
(mm) c 0 0 o 0
d 0 0 0 0
FDU-wall, a 1-00 100 100 100
wall-one b 100 100 100 0
side c 0 0 o o
(mm) 0
d 0 0 0
o o
Or
Lr) r.r)
Glands Glands
M25 (026-031 M20 M50
M32 (037-046
Glands
Glands M40
M32 (026-031)
M4O (037-046)
r
e)> ei G}
@t
osl o
Loo
L) r'l
rq
I
C1
I
!O
o)
l* (o
ii
Fig I2 FDU4S: Model 090 to 175 (E) including cable inter- Fig. l3 FDU4S: Model 210 to 250 (F)
mdins, mntor dnd communication FDU69: Model 90 to 175 (F69) including cable
face for interface mains, motor and communici.tion
for
Dimension in mm
Frame FDU model
A B c
F 2LO - 250 925 950 920
c
Frame FDU Model Flow rate lm3Ttrourl
B 003-018 75
C 026 - 031 L20
C 037 - 046 !70
D 06r-074 L70 I
I
I
2400 I
NOTE: For the models 860 to 15OO the mentioned Fig. 14 Recommend.edfee spdce infiont of the cabinet
mounted AC driue
amount of air flow should be divided equally over the two
cablnets.
o
rr)
N
N
600
Fig. 15 FDU4S: Mode I 300 ro 500 (G and H) Fig. 17 FDU4S: Modtl 560 to 1000 (l)
FDU69: Model 210 ro 375 (H69) FDU69: Model 600 to 650 (169)
o
lr)
c.,l
ot
il,ll
Fig 16 FDU48: Modrl 600 to 750 (I) Fig 18 FDU4S: Model 1200 to 1500 (K)
FDU69: Modrl 430 to 500 (169) FDU69: Model 750 to 1000 (K69)
Screen connection
Output coil (option)
of signal cables
Screened cables
Mains
(L1, L2,L3,PE)
Brake resistor
(option)
Mains
Cable interface
Motor cable
DC+, DC-, R (optional)
Mains cable
Motor connection
U
V
W
Mains Connection
L1
L2
L3
Mains
x4 1'
-****;_# Option
'L*or.****,,o,***'.o.**o.o.*"1#
Comn6unication
.,#1+1ff1<\ -
Y|.-*'""{\
b.+qts+l'.d.c
ti''+la-so{'::ldr*{
--6""ry\
ET" JS
\i ""tx' ,'
'\,t${g'r,
Switches
+1OV Al1 A,2 Al3 Al4 -1OV r Dl1 Dl2 Dl3 +24V x3
The terminal strip for connecting the control signals is Terminal Name Functlon (Default)
accessible after opening the front panel.
31 N/C 1
The table describes the default functions for the signals. The Relay 1 output
inputs and outputs are programmable for other functions as 32 COM 1 Trip, active when the AC drive is
in a TRIP condition.
described in chapter 11. page 63. For signal specifications 33 N/O 1
refer to chapter 1 4. page 183.
4L N/C 2
Relay 2 output
42 COM 2 Run, active when the AC drive is
NOTE: The maximum total combined current for outputs
sta rted.
Lt ,2O and 21 is 1OOmA. 43 N/O 2
51 COM 3 Relay 3 output
NOTE: lt is possible to use external 24V if connection to 52 N/O 3 off
Common (15).
Outputs
+10 v
4.3 lnputs configuration
+10 VDC supply voltage
T
with the switches
6 -10 v -10 VDC supply voltage
The switches S I to 54 are used ro ser the input configuration
7 Common Signal ground for the 4 analogue inputs Anlnl, Anln2, AnIn3 and AnIn4
+24Y +24 VDC supply voltage as described in table 15. See Fig.30 for the location of the
T7
switches.
!2 Common Signal ground
iffii
':{4'i:fi
4 Anln 3 off configured uslng the software. See menus [5L21, [515],
t5181 and t51BI in section 11.5, page L25.
5 Anln 4 off
Analogue outputs
NOTE: the 2 analogue outputs Anout 1. and An0ut 2 can
13 AnOut 1 Min speed to max speed be configured using the software. See menu [53O]
section 11.5.3, page 133
L4 AnOut 2 0 to max torque
Relay outputs
Alternative for :
potentiometer cofitrol * *
+10 VDC
Anln 1: Reference
0-10v
4-20mA Anln 2
Anln 3 Common
Anln 4 AnOut 1
Common Digout 1
Digln Z:RunR*
Fieldbus option
Option board
or PC
* Default setting
** The switch 51 is set to U NG_06-F27
4.5.1Cables
The standard control signal connections are suitable for
stranded flexible wire up to 1.5 mm2 andfor solid wire up to
2.5 mm2.
OCfOOCfOO
OOOOC]OOO
OOCfOCOC)
OC)OOOOCJ-
OOC]OO
Control signals
Control signals
Control signa ls
signa ls
Fig. 3i Connecting tlte control signals, 026 to 046 Fig. 35 Connecting the control signals, 090 to 250
Analogue inputs
Voltage or current signals, (0-10 V, 014-20 mA) normally NOTE: Each installation must be examlned carefully
used as control signals for speed, torque and PID feedback before applying the proper EMC measurements.
signals.
Analogue outputs
Voltage or current signals, (0-10 V 014-20 mA) which
change slowly or only occasionally in value. In general, these
are control or measurement signals.
Digital
Voltage or current signals (0-10 V 0-24Y,014-20 mA)
which can have only rwo values (high or low) and only o
ccasion ally change in value.
Data
Usually voltage signals (0-5 V O-10 V) which change rapidly
and at a high frequenry, generally data signals such as
RS232, RS485, Profibus, etc.
Relay
Relay contacts (0-250 VAC) can switch highly inductive
loads (auxiliary relay,lamp, valve, brake, etc.).
Signal Tightening
Maximum wire size Gable type
type torque EKerna! control
(e.9. in metal housing)
Example:
The relay output from a AC drive which controls an aaa
auxiliary relay can, at the moment of switching, form a
source of interference (emission) for a measurement signal
Fig. 36 Electro Magnetic (EM) screening of control signal
cables.
from, for example, a pressure sensor. Therefore it is advised
to separate wiring and screening to reduce disturbances.
H:J"!'i-ff 1 #,il J:ff I:t iffi.r :f[' :n 3 "" of the option cards are connected in the same way as other
control signals.
fI*:
4.5.6Twisted cables
Analogue and digital signals are less sensitive to interference
if the cables carrying them are "rwisted". This is certainly to
be recommended if screening cannot be used. By rwisting
the wires the exposed areas are minimised. This means that
in the current circuit for any possible High Frequency (HF)
interference fields, no voltage can be induced. For a PLC it
is therefore important that the return wire remains in
proximiqy to the signal wire. It is important that the pair of
wires is fully rwisted over 360'.
5.1 Gonnect the mains and 5.2 Using the function keys
motor cables
Dimension the mains and motor cables according to local
regulations. The cable must be able to carry the AC drive
load current.
i:i:::i::i;::;:t::::l::::::::ii
Screened cables
Metal housing
Output
coils
(option)
Mains
.
mon) and 2 (AnIn 1) as in Fig. 39.
4. Connect an external start button berween terminal 1 I
5. Set motor frequency 1222).
(+24 VDC) and 9 (Digln2, RUNR) as in Fig. 39. 6. Set motor power [223).
Fig. 39 Wiring
5.3.4 Run the AC drive
Now the installation is finished, and you can press the
5.3.2 Switch on the mains external start button to start the motor.
Close the door to the AC drive. Once the mains is switched
on, the internal fan in the AC drive will run for 5 seconds.
\[hen the motor is running the main connections are OK.
6.1.tPumps
Challenge Emotron FDU solution Menu
Dry-running, cavitation and overheating damage Pump Curve Protection detects deviation. Sends
4L!-4L9,4LCL- 4rC9
the pump and cause downtime. warning or activates safety stoP.
Sludge sticks to impeller when pump has been Automatic pump rinsing function: pump is set to
running at low speed or been stationary for a while. run at full speed at certain intervals, then return 362-368, 560, 640
Reduces the pump's efficiency. to normal speed.
Motor runs at same speed despite varying PID continuously adapts pressure/flow to the
demands in pressure/flow. Energy is lost and level required. Sleep function activated when 320,380,342,354
equipment stressed. none is needed.
Process inefficiency due to e.g. a blocked pipe, a Pump Curve Protection detects deviation.
4L7-4L9, 47C1--41C9
valve not fully opened or a worn impeller. Warning is sent or safety stop activated.
Water hammer damages the pump when stopped. Smooth linear stops protect the equipment. 331-336
Mechanical stress on pipes, valves, gaskets, seals. Eliminates need for costly motorized valves.
6.!..2Fans
Challenge Emotron FDU solution Menu
Starting afan rotating in the wrong direction can be Fan is started at low speed to ensure correct 219,341"
critical, e.g. a tunnel fan in event of a fire. direction and proper function.
Regulating pressure/flow with dampers causes Automatic regulation of pressure/flow with motor
321-,354
high energy consumption and equipment wear. speed gives more exact control.
Compressor is damaged when cooling media Overload situation is quickly detected and safety
enters the compressor screw. 41,I_4TA
stop can be activated to avoid breakdown.
Pressure is higher than needed, causing leaks, Load Curve Protection function detects deviation.
stress on the equipment and excessive air use. Warning is sent or safety stop activated.
4I7-4I9, 4!Ct-4LCg
Motor runs at same speed when no air is
PID continuously adapts to the level required.
compressed. Energy is lost and equipment 320,390, 342,354
Sleep function activated when none is needed.
stressed.
Process inefficiency and energy wasted due to e.g. Load Curve Protection quickly detects deviation.
the compressor idling. Warning is sent or safety stop activated.
4L7-4L9, 4IC1,-41C9
6.l..[Blowers
Challenge Emotron FDU solution Menu
Difficult to compensate for pressure fluctuations. PID function continuously adapts pressure to the
Wasted energy and risk of production stop. level required.
320,390
Motor runs at same speed despite varying PID continuously adapts air flow to level required.
demands. Energy is lost and equipment stressed. Sleep function activated when none is needed.
320,390, 342,354
Process inefficiency due to e.g. a broken damper, a Load Curve Protection quickly detects deviation.
valve not fully opened or a worn belt. Warning is sent or safety stop activated.
47r-4L9, 4LCL-41C9
D L 1,
Define parameter sets
til7hen using parameter sets you first decide how to select
different parameter sets. The parameter sets can be selected NOTE: The selection via the digital inputs is immedlately
via the control panel, via digital inputs or via serial ac,tivated. The new parameter settings will be astivated
communication. AJI digital inputs and virtual inputs can be on-line, also during Run.
configured to select parameter set. The function of the
digital inputs is defined in the menu [520]. NOTE: The default parameter set is parameter set A.
Fig. 40 shows the way the parameter sets are activated via
any digital input configured to Set Ctrl I or Set Ctrl 2. Examples
Different parameter sets can be used to easily change the
Parameter Set A setup of a AC drive to adapt quickly to difFerent application
Run/Stop
requirements. For example when
. a process needs optimized settings in different stages of
Torques
the process, to
- increase the process qualiry
Controllers - increase control accu racy
- lower maintenance costs
Limits/Prot. - increase operator safery
'S7ith
these settings a large number of options are available.
-Max Alarm Some ideas are given here:
3. Enter the settings for other paramerers e.g. inputs and . Activate Moto r I2t to be automatically reser; set menu
outPuts. l25[l to 300 s.
4. If there are only minor differences berween the settings . Set relay 1, menu [551] to AutoRst Tlip; a signal will be
in the parameter sets, /ou can copy parameter set A to available when the maximum number of restarts is
parameter set B, menu 1242). reached and the AC drive srays in fault condition.
5. Enter the settings for parameters e.g. inputs and ourpurs. . The reset input musr be constantly activated.
\7ith
these settings, the AC drive switched on and a RUN -"i:
command given, the speed will be: f.ii
tS
Enable Edge-control
Input must be active (HI) to allow any Run signal. If the After the Reset command is given a new Run command
input is made LO\f, the output of the AC drive is must be applied to start the AC drive again.
immediately disabled and the motor will coast. Autoreset is enabled if the Reset input is continuously active.
The Autoreset functions are programmed in menu Autoreset
CAUTIONI l25o).
lf the Enable functlon is not programmed to a
dlgltal input, it is considered to be active
NOTE: lf the control commands are programmed for
internally.
Keyboard control or Com, Autoreset is not possible.
Stop
If the input is low then
the AC drive will stop according to
the selected stop mode set in menu t3fg] Stop Mode. Fig.
42 shows the function of the Enable and the Stop input and
the Stop Mode=Decel [338].
STOP
(STOP=DECEL)
OUTPUT
SPEED
ENABLE
OUTPUT
SPEED
rNrlls_ _l
ENABLE
STOP
RUN R
RUN L
OUTPUT
Fig. 43 Example of wiringfor Run/Stop/Enabb/Reset inputs
STATUS
\rt I ,-a I Vr\J
]
ENABLE
STOP
RUN R
RUN L
The max and min alarm can be set for a trip condition. The
NOTE: Load from and copy to the AC drive is only pre-alarms act as a warning condition. All the alarms can be
possible when the AC drive is ln stop mode.
monitored on the digital or relay ourpurs.
The autoset function auromatically sers the 4 alarm levels
whilst running: maximum alarm, maximum pre-alarm,
minimum alarm and minimum pre-alarm.
AC drive @
Fig. 7 .6 gives an example of the monitor functions for
constant torque applications
7.6.1 lntroduction
A maximum of 4 pumps can be controlled with the standard
FDU AC drive.
R:SlavePumpl
If I/O Board options are installed, a ma:rimum of 7 pumps R:SlavePump2
Stop pump
P6=on FLOW/
PRESSURE
TIM E
(50-PC-3_1)
the pumps depending on the run time history of each pump. R: Ma6terPump6
R: MasterPump5
R: MasterPump4
R: MastcrPump3
R: MasterPump2
R: MastcrPumpl
See menu:
t3e3l to [3e6]
t5531 to [55C]
R:SlavePump3
R:SlavePump2
R:SlavePumpl
feedback Dl:PumplFeedb
Dl:Pump2Feedb
inputs Dl:Pump3Feedb
7.6.5 Fail safe operation obtained by using the NC conracrs of the pump control
relays. These can be programmed for each individual addi-
Some pump systems must always have a minimum flow or
pressure level, even if the frequenry inverter is tripped or
tional pump. In this example pumps P5 and P6 will run ar
damaged. So at least 1 or 2 (or maybe all) additional pumps
maximum power if the inverrer fails or is powered down.
must keep running after the inverter is powered down or
tripped. This kind of "safe" pump operation can be
See menu:
t5541 to [55C] Relays
[55D4] to [55DC] Mode
R:SlavePump6
R:SlavePump5
R:SlavePump4
R:SlavePump3
R:SlavePump2
R:SlavePumpl
See menu:
t3811 to [3851
t5531 to [55C]
l{L]-lto [41C]
R:SlavePump6
R:SlavePump5
R:SlavePump4
R:SlavePump3
Set R:SlavePump2
R:SlavePumpl
Value
Feedback
Value
ow / l'ressu re
measurement (NG_5O-PC-8_1)
PE
L1
L2
L3
(NG_50-PC-11_3)
1. Main Func'tions
2. Number of pumps/drives
lf the system consists oi 2 or 3 pumps the l/O Board option is not needed. However, this does mean that the following
functions are notthen possible:
- "Alternating MASTER" function
- With isolated inputs
With the l/O Board option installed, the maximum number of pumps is:
- 6 pumps if "Alternating MASTER- function is selected. (see section 7.6.3 on page 41)
- 7 pumps if "Fixed MASTER'function is selected. (see section 7.6.2, page 41)
3. Pump size
lf the digital inputs are used, the digital input function must be set to Drive feedback.
After the Pump controller is switched on in menu 1391] the number of drives (pumps, fans, etc.) must be set in menu [392]
(Number of Drives). The relays themselves must be set to the function SlavePumpl-6 and if Alternate master is used,
MasterPumpl-6 as well.
6. Equal Pumps
lf all pumps are equal in power size it is likely that the Upper band is much smaller than the Lower band, because the
maximum pump discharge of the master pump is the same if the pump is connected to the mains (SOHz). This can give a
very narrow hysteresis causing an unstable control area in the flovpressure. By setting the maximum frequency of the
inverter only slightly above 5OHz it means that the master pump has a slightly bigger pump discharge than the pump on
the mains. Of course caution is essential in order to prevent the master pump running at a higher frequency for a longer
period of time, which in turn prevents the master pump from overloading.
7. Minimum Speed
With pumps and fans it is normal to use a minimum speed, because at lower speed the discharge of the pump or fan will
be low until 30-50% of the nominal speed (depending on size, power, pump properties, etc.). When using a minimum
speed, a much smoother and better control range of the whole system will be achieved.
\f Feedback Ftow
time
Master pump
Speed
Max speed
t3431 Upper band
I
I
I
Transition Speed Start
t3eEl
Min speed
l34rl
H! H time
Start delay t399I Settle time start [39D]
2nd pump
Speed
[310]
Feedback Flow
f
time
Master pump
Speed
Max speed
t3431 Upper band
Min speed
134Ll Lower band i
--l- I
I
I
I
I
time
Stop delay [39A] lsettte time stop t39FI
2nd pump
-i
Speed
time
(NG_s0-PC-zO_I)
8.1 EMC standards NOTE: With option Safe Stop, a "Safe Torque Off (STO)"
The AC drive complies with the following standards: stop according EN{EC 62061:2005 SIL 2 & EN-ISO
13849-t2OO6, can be achieved.
EN(IEC)6 1 800-3 :Z}}4Adjustable speed electronic power See chapter 13.10 page L79
drive systems, part 3, EMC product standards:
WARNING!
6020+1, specifies that every machine
EN
must be provided with a category O stop. lf
the application prevents this from being
implemented, this must be explicitly stated.
Furthermore, every machine must be provided with an
Emergency Stop function. This emergency stop must
ensure that the voltage at the machine contaGts, which
could be dangerous, is removed as quickly as possible,
without resulting in any other dangel. ln such an
Emergency Stop situatiotr, o category O or 1. stop may be
used. The choice will be decided on the basis of the
possible risks to the machine.
This chapter describes how to use the control panel. The AC Area A: Shows the actual menu number (3 or 4
drive can be delivered with a control panel or a blank panel. digits).
9.1 General
Area C:
AC drive is set for Local operation.
Shows the heading of the active menu.
The control panel displays the status of the AC drive and is
used to set all the parameters. It is also possible to control Area D: Shows the status of the AC drive (3 digits).
the motor directly from the control panel. The control panel The following status indications are possible:
can be built-in or located externally via serial
Acc Acceleration
communication. The AC drive can be ordered without the
Dec Deceleration
control panel. Instead of the control panel there will be a
12t Active I2t protection
blank panel.
Run Motor runs
Thp Tlipped
NOTE: The AC drive can run without the control panel stp Motor is stopped
being connected. However the settings must be such \rL Operating at Voltage limit
that all control signals are set for external use. SL Operating at Speed limit
CL Operating at Current limit
TL Operating at Torque limit
9.2 The control panel OT Operating at Temperature Limit
LV Operating at Low Voltage
sbv Operating from Standby power supply
SST Operating Safe Stop, is flashing when
<-- LC Display
activated
LCL : Operating with low cooling liquid level
+- LEDs Area E: Shows active parameter set and if it is a motor
parameter.
+- Control Keys
Area F: Shows the setting or selection in the active menu.
This area is empry at the 1 st level and Znd level
<- Toggle Key menu. This area also shows warnings and alarm
messages. In some situations this area could
indicate "+++" or " - - -" please see further
\
;^.
Function Keys information in chapter 9 .2.2 page 54
9.2.1The display
The display is back lit and consists of 2 rows, each with 22O Motor Data
space for 16 characters. The display is divided into six areas. STPET
The different areas in the display are described below:
Fig. 62 Example 2nd leuel m€nu
A B C
22L Motor VoIt
stpEIMl i 400
DE
Fig. 60 The display
The symbols on the control panel have the following gives a sta rt with
functions: RUN R:
ftA
right rotation
NOTE: Do not keep the Toggle key pressed for more than
five seconds without pressing either thc +, - or Esc key,
as this may activate the LoclRem function of this key
instead. See menu l2L7l.
level 'l'obo'l
ENTER key: i
confirm a changed _ ____/ ...,...,.,,1
setting
ENTER
step to a higher
,,,:,'ll'-:,:,:i::: ::;:l menu level
,.:l,:,ffi:.:..i:.::'
:
i
:
:
:: :
:
::: :j :
:
:
I
j: i: i
: : : I : I ;: :: : I :
:
:: : :: :; : I :; :; :;
I
:
:
:: :: ESCAPE key: ignore a changed
l.l:..,ii:.:Cmg.1..:ii;:1iil. setting, without
conf irm ing
step to a previous
menu within the same
PREVIOUS key: level
go to more significant
digit in edit mode
+ key:
increase a value 100 Preferred View
change a selection Displayed at power-up. It displays the actual process value as
default. Programmable for many other read-outs.
operation mode.
262L Baudrate
Stp 38400
Alternative 1,
til7hen you press the + or - keys to change a value, the cursor
is flashing to the left in the display and the value is increased
or decreased when you press the appropriate key. If you keep
the + or - keys pressed, the value will increase or decrease
continuously. \7hen you keep the key pressed the change
speed will increase. The Toggle k.y is used to change the
sign of the entered value. The sign of the value will also
change when zero is passed. Press Enter to confirm the value.
Use the ESC, Prev, Next or the Toggle keys to proceed and
to go to other menus. 2OO MAIN SETUP Press Next for menu
StPE t20ol.
key pressed
StpEII
,.'liis;.:'..'
Example:
(See Emotron Fielbus manual for detalied information)
'We
would like to conrrol the AC drive over a bus sysrem
using the first two bytes of the Basic Control Message by
arso
il: r.T,H x,::^'J JL :J,?XlJ )!,!l,T ;# ;.Hil'
process value.This is done by setting menu
12662) FB Sign al 2 rc 42905 and menu 126631FB Sign al 3
rc 42906.
typedef struct
{
int m:L7; // mantissa, -L024..L023
int e: 4; // exponent -8..1
unsigned j-nt fz L; // format, 1->special emoint format
) eint16;
/ /________
unsigned short int float to elnt16(float value)
{
eintl 6 etmp;
int dec-0;
while (f loor (val-ue ) !: value && dec<16)
{
dec**; value*-1 0;
)
if (va1ue>:0 && vafue<:32767 Cc dec::0)
* (short int *) &etmp: (short int) value;
else if (val-ue>:-l-000 cc val-ue<0 && dec::0)
i
etmP. e:0,'
etmP. f:1;
etmp.m: (short int) value;
l
else
{
etmP. m:0;
etmP. f:1;
etmp.e:-dec;
if (value>:0)
etmp.m:1; // Set sign
else
etmp.m=-1-; // Set sign
value:fabs 1va1ue);
while (val-ue>1000 )
{
etmp.e++; // increase exponent
val-ue:vaIue/ 10;
]
value*:0.5; // round
etmp.m:etmp.m*val-ue; / / make signed
)
return (* (unsigned short int *) &etmp) ;
)
/ / ________
float eint16_to_f1oat (unsigned short int vafue)
{
float f;
eint16 evalue;
evalue:* (eint16 *) &va1ue;
if (evafue. f)
{
if (evalue.e):0)
f: ( int ) evalue .m*powl0 (evalue.e);
else
f: ( int ) evalue .m/powl0 (abs (eval-ue.e));
)
else
f -va l-ue ;
return f;
Language l21,Ll
Select the language used on the LC Display. Once the
language is set, this selection will not be affected by the Load
Default command.
zLL Langruage
StpE English
Defa u lt: English
Communication i nformation
The start/stop si$nal comes from the digital The command comes from the inputs of
Remote 0
inputs of the terminal strip (terminals L-22), the terminal strip (terminals L-22).
Remote 0
For settings, see menu group [330] and
The command comes from the command
t5201. Keyboard 1,
keys of the Control Panel.
Keyboard 7 Start and stop is set on the Control Panel.
The command comes from the serial
The starVstop is set via the serial Com 2
communication (RS 485, Fieldbus).
communication (RS 485, Fieldbus.) See
Com 2 The command comes from the inputs of
Fieldbus or R5232/485 option manual for Remote +
deta ils. 3 the termina! strip (terminals L-22) or the
Keyb
keyboard.
Option 3 The start/stop is set via an option.
The command comes from the serial
Com +
4 communication (RS485, Fieldbus) or the
Com munication info rmation Keyb
keyboa rd.
Communication informatio n
Remote L Local Run/Stop control via remote . Via the serial interface options.
Keyboa rd 2 Local Run/Stop control via keyboard . The parameter sets.
Fig. 72 Rotation
Defa u lt: R+L NOTE: Edge controlled inputs can comply with the
Speed direction is limited to ri$ht
Machine Directive (see the Chapter 8. page 51) if the
7 rotation. The input and key RunL are inputs are directly used to start and stop the machine.
R
disa bled.
L 2
Speed direction is limited to left rotation. L7,.2.3 Mains supply voltage t2LBl
The input and key RunR are disabled.
NOTE 4: Motor Data in the different sets M1 to M4 can Motor Power t223)
be revert to default setting in menu [243], Default)Set. Set the nominal motor power. If paralell motors, set the
value as sum of motors power.
WARNING!
Enter the correct motor data to prevent 223 Motor Power
dangerous situations and assule correct c StpEIMl : (PN9M) k
control.
Defa u !t: PNOMVSD
2L Motor Vo1ts NOTE: The Motor Power value wlll always be stored as a
c StpEMl: 400 3 diglt value in W up to 999 W and in kW for all higher
powels.
400 V for FDU48
Defa u lt: 500 V for FDU52 Communication information
690 V for FDU69
Range: 100-700 v Modbus lnstance no/DeviceNet no: 43043
Resolution 1V Profibus slot/index L68/2O2
Long,
Fieldbus format
NorE: The Motor volts value will always be stored as a 3 1=1 W
digit value with a resolution of 1V. Modbus format Elnt
Long,
Fieldbus format
1=0.1 V
Modbus format El nt
Defa u lt: 4
Communication info rmation 2-744
Range:
Modbus format El nt
NOTE: The default settlngs are for a standard 4-pole
motor according to the nominal power of the AC drlve.
None 0 Limited l2t overload curve. l2l9l Rotation is set to L the RunR k.y is inactive and vice
versa. The ID run can be aborted by giving a Stop command
Self T
Normat l2t overload curve. Means that the via the control panel or Enable input. The parameter will
motor stands lower current at low speed. automatically return to OFF when the test is completed.
Expanded l2t overload curve. Means that the The message "Test Run OKI" is displayed. Before the AC
Forced 2 motor stands almost the whole current also drive can be operated normally again, press the STOP/
at lower speed. RESET k.y on the control panel.
During the Short ID run the motor shaft does not rotate.
Communication information The AC drive measures the rotor and stator resistance.
\ilfhen the motor has no cooling fan, None is selected and off 0 Not active
the current level is limited to 55o/o of rated moror currenr. Parameters are measured with injected DC
Short L
\With a motor with a shaft mounted fan, Self is selected and current. No rotation of the shaft will occur.
the current for overload is limited to 87o/o from 20o/o of
synchronous speed. At lower speed, the overload current Communication information
allowed will be smaller.
tVhen the motor has an external cooling fan, Forced Modbus lnstance nolDeviceNet no: 43049
is
selected and the overload current allowed starts at 90o/o from Profibus slot/index !68/2O8
rated motor current at zero speed, up to nominal motor
Fieldbus format U lnt
current at 7Ao/o of synchronous speed.
Modbus format U lnt
Fig. 73 shows the characteristics with respect for Nominal
Current and Speed in relation to the motor ventilation type
selected. NOTE: To run the AG drive it is not mandatory for the lD
RUN to be executed, but without it the performance will
not be optimal.
Xlnom for l2t
1.00
NOTE: lf the lD Run is aborted or not completed the
0.90
o.87 messa$e "lnterrupted!" will be displayed. The previous
data do not need to be changed in this case. Check that
the motor data are correst.
0.55
FiS. 73 12 t curues
Switching frequency 6 kHz, random fre- Modbus lnstance no/DeviceNet no: 43052
H 3
quency (+750 Hz)
Profibus sloVindex 168/2rL
Switching frequency and PWM mode Fieldbus format Long, t=7. pu lse
Adva nced 4
setup via l22E)
Modbus format Elnt
Unit: rpm
Communication information
,
:
\"'' :
.\ \
\\ \\
\,,,,)L,.... \\
*}.rry*
\r,
\\:\ \
\\ \-
Fig. 74 12 r function
Fig. 74 shows how the function integrates the square of the Menu 1234) PTC contains functions to enable or disable the
motor current according to the Mot I2t Curr 12321and the PTC input. Here you can select and activate PTC and/or
Mot I2t Tim e [233]. PT100.
tilfhen the selection Thip is set in men u 1231] the AC drive
trips if this limit is exceeded. 4 Thermal Prot
'When the selection Limit is set in men u
1231] the AC drive stpE! off
reduces the torque if the integrated value is 95a/o or closer to
Defa ult: off
the limit, so that the limit cannot be exceeded.
PTC and PT1O0 motor protection are
off 0
disabled.
NOTE: lf it is not possible to reduce the current, the AC
drive will trip after exceeding 11oo/o of the limit. Enables the PTC protection of the motor
PTC T
via the insulated option board.
Communication informatio n
Modbus lnstance nolDeviceNet no: 43065
Profibus sloVindex L68/224 Modbus lnstance no/DeviceNet no: 43066
Fieldbus format U lnt Profibus sloVindex L68/225
Modbus format U lnt Fieldbus format U lnt
Modbus format U lnt
NOTE: This menu is only valid for PT 1OO.
Communication i nformatio n
Defa u lt: A>B B t Only the selected parameter set will revert
C 2 to its default settings.
A>B 0 Copy set A to set B
A>D 2 Copy set A to set D All four parameter sets will revert to the
ABCD 4
default settings.
B>A 3 Copy set B to set A
All settings, except l21.I), 122!1-l22Dl,
B>C 4 Copy set B to set C Factory 5 t26Ll and [9231, will revert to the default
B>D 5 Copy set B to set D settings.
C>B 7 Copy set C to set B M2 7 Only the selected motor set will revert to its
D>B 10 Copy set D to set B All four motor sets will revert to default
ML234 10
settings.
D>C lT Copy set D to set C
Communication information
Communication info rmation
NOTE: Trip log hour counter and other VIEW ONLY menus
NOTE: The actual value of menu [310J will not be copied are not regarded as settings and will be unaffested.
into the other set.
A>B means that the content of parameter set A is copied NOTE: lf "Factory" is selected, the message "Sure?" is
displayed. Press the + key to display "Yes" and then
into parameter set B.
Enter to confirm.
0
StpEI No copy
Defa lt: No Copy
45 Load from CP
u
I StpEI No Copy
No Copy o Nothing will be copied
Defa lt: No Copy
copy ! Copy all settings
u
M1M2M3
M4
15 Data from motor t, 2,3 and 4 are loaded.
Communication information
NOTE: Loading from the control panel will not affect the
value in menu [31O].
If the maximum number of trips has been reached, the trip off 0 off
message hour counter is marked with an '?\". 1-3600 1-3600 1-3600 s
NOTE: An auto reset is delayed by the remaining ramp Motor Lost t2561
time. Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Overvolt G 1254)
Delay time starts counting when the fault is gone When the 256 Motor Lost
time delay has elapsed, the alarm will be reset if the function
is active.
stpE! off
Defa u lt: off
254 Overvolt G off o off
stpE! off 1-3600 1-3600 1-36O0 s
Communication information
Communication information
Modbus lnstance no/DeviceNet no: 43083
Modbus lnstance nolDeviceNet no: 43076
Profibus sloVindex 1:68/242
Profibus sloVindex L68/235
Fieldbus format Long, 1=1 s
Fieldbus format Long, 1-1 s
Modbus format El nt
Modbus format El nt
Modbus Instance no/DeviceNet no: 43086 Modbus lnstance nolDeviceNet no: 43088
Profibus slot/index L68/245
Profibus sloVindex 768/247
Field bus format Long, 1-1 s
Field bus format Long, 1-1 s
Modbus format Elnt
Modbus format El nt
Modbus format El nt
Delay time starts counting when the fault is gone. \7hen the off 0 off
time delay has elapsed, the alarm will be reset if the function 1-3600 1-3600 1-3600 s
is active.
Communication information
Modbus lnstance no/DeviceNet no: 43080 Modbus lnstance no/DeviceNet no: 43089
Profibus sloVindex L68/239 Profibus slot/index 168/248
Fieldbus format Long, 1:1 s Fieldbus format Long, 1=1 s
Modbus format El nt Modbus format El nt
Modbus lnstance nolDeviceNet no: 43091 Modbus lnstance nolDeviceNet no: 43093
Profibus sloVindex L68/250 Profibus sloVindex 768/252
Fieldbus format Long, 1=1 s Fieldbus format Long, 1=1 s
Modbus format El nt Modbus format Elnt
Min Alarm Trip Type [251] Max Alarm Trip Type t25Nl
Select the preferred way to react to a min alarm trip. Select the preferred way to react to a max alarm trip.
Modbus lnstance nolDeviceNet no: 43092 Modbus lnstance nolDeviceNet no: 43094
Profibus slot/index 768/25r Profibus sloVindex 1:68/253
Fieldbus format U lnt
Fieldbus format U lnt
Modbus format U lnt
Modbus format Ulnt
Modbus lnstance nolDeviceNet no: 43082 Modbus lnstance nolDeviceNet no: 43096
Profibus slot/index 168/24r Profibus slot/index 1:69/O
Modbus lnstance no/DeviceNet no: 43095 Modbus lnstance nolDeviceNet no: 43097
Profibus slot/index 168/254 Profibus sloVindex L68/239
Fieldbus format Long, 1=1 s Fieldbus format Long, 1=1 s
Modbus lnstance nolDeviceNet no: 43098 Modbus lnstance no/DeviceNet no: 43100
Profibus sloVindex L68/240 Profibus sloflindex 169/4
Fieldbus format U lnt Fieldbus format U lnt
Modbus format Ulnt Modbus format Ulnt
Communication information
Communication information
Modbus lnstance nolDeviceNet no: 43070
Modbus lnstance nolDeviceNet no: 43099 Profibus sloVindex 768/22e
Profibus sloVindex L69/3 Fieldbus format Long, 1=1s
Fieldbus format Long, 1-1 s
Modbus format El nt
Modbus format Elnt
Address [2631]
NOTE: Toggling the setting in this menu will perform a
soft reset (re-boot) of the Fieldbus module. Enter the unit address of the AC drive.
263L Address
RS232/485 1262) stpE! 62
Enter to set up the parameters for RS2321485
Press
(Modbus/RTU) communicatiotr. Defa u lt: 62
Range: Profibus 0- L26, DeviceNet 0-63
262 RS232/485 Node address valid for Profibus and DeviceNet
stp
Process Data Mode 12632)
Enter the mode of process data (cyclic data). For further
Baud rate 1262L) information, see the Fieldbus option manual.
Set the baud rate for the communication.
StPE
264L ComFIt Mode
Defa u lt: RW stpE! off
RW o
Defa u lt: off
Read 7
off 0 No communication supervision.
Valid for process data. Select R (read only) for logging
process without writing process data. Select RW in normal RS232 / 485 selected:
cases to control inverter. The AC drive will trip if there is no
communication for time set in parameter
126421.
Additional Process Values 126341 Fieldbus selected:
Trip L
Define the number of additional process values senr in cyclic The AC drive will trip if:
messages. 1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter 126421.
2634 AddPrVa1ues 2. lf a serious network error has occurred.
stpE! 0 RS232 / 485 selected:
The AC drive will give a warning if there is
Defa u lt: o
no communication for time set in
Range: o-8 parameter [26421.
Fieldbus selected:
Warning 2
The AC drive will give a warning if:
1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter !p6a21.
2. lf a serious network error has occurred.
Long, 1=0,1 s
Selection: On/Otf
Fieldbus format
lP Address [2651]
stpE! 0
Defa u lt: 0
51 IP Address Ra nge: 0-65535
0. 0. 0. 0
Commun ication information
Default I 0.0.0.0
Table 23
NOTE: The actual value in menu [3tO] ls not copied, or
SeleEted process Unit for reference and loaded from the control panel memory when Gopy Set
source Resolution 12421, Copy to CP 12441or Load from CP 12451 is
actual value
performed.
Speed rpm 4 digits
Torque o/
/o 3 digits
NorE: lf the MotPot func-'tion is used, the reference value
OC
PTlOO 3 digits ramp times are according to the Acc MotPot t333] and
Freq uency Hz 3 digits Dec MotPot t334] settings. Actua! speed ramp will be
limited according to Acc Time t33q and Dec Time [332J.
L1,.3.1 Set/View Reference Value NOTE: Write access to this parameter is only allowed
t310I when menu "Ref Gontrol I2L41is set to Keyboard. When
Reference control is used, see sestlon "1o.s Reference
View reference value signal" on page 6O
As default the menu [3 t O1 is in view operation. The value of
the active reference signal is displayed. The value is displayed
according to selected process source, l3zt] o. the process L1'3.2 Process Settings t320I
unit selected in menu 'sflith
1322]. these functions, rhe AC drive can be ser up to fit the
application. The menus [110], [120], [310], [3e 4-068)
Set reference value and lzttl use the process unit selected in l3zll and l3zz1
If the function Reference Control L2l4] is ser ro for the application, e.g. rpm, bar or m3lh. This makes it
"Keyboard", the reference value can be set in menu Set/View
possible to easily ser up the AC drive for the required process
Referen.. [310] or as a moror potentiometer with the + and requirements, as well as for copying the range of a feedback
- keys (default) on the control panel. Selection is made with sensor to set up the Process Value Minimum and Maximum
parameter Keyboard Reference Mode in menu 136gl. The in order to establish accurare acrual process information.
ramp times used when setting rhe reference value with
MotPot, function selected in 136g] are according ro menus
Acc MotPo r 1333) and Dec MotPo t 13341. Process Source l321-l
The ramp times used for the reference value when Normal Select the signal source for the process value that controls
function is selected in men u 13691, are according ro Acc the motor. The Process Source can be set to act as a function
Time l33ll and Dec Time l3lZ). of the process signal on AnIn F(AnIrr), a function of the
Menu [3 t O1 displays on-line the actual reference value motor speed F(Speed), , function of the shaft torque
according to the Mode Settings in Thbl e 23. F(Torque) or as a function of a process value from serial
communication F(Bus). The right function ro select
depends on the characteristics and behaviour of the process.
310 Set./VLew ref If the selection Speed, Torque or Frequency is ser, the AC
Stp 0 drive will use speed, torque or frequency as reference value.
Defa u lt: 0 rpm
Example
Process Source t321-l and Process Unit An axial fan is speed-conrrolled and there is no feedback
Dependent on:
[3221 signal available. The process needs to be controlled within
Speed mode 0 - max speed [343] fixed process values in "m3/hr" and a process read-out of the
air flow is needed. The characteristic of this fan is rhat the air
Torque mode 0 - max torque [351J
flow is linearly related to the actual speed. So by selecting
Min according to men u 13241- max accord- F(Speed) as the Process Source, the process can easily be
Other modes
ing to menu [325] controlled.
The selection F(xx) indicates rhat a process unit and scaling
is needed, set in men vs 1322)-32A1. This makes it possible
to e.g. use pressure sensors ro measure flow etc. If F(AnIn) is
l. O,rly when Drive mode l2l3) is set to Speed or Y lHz. rpm 8 Revolutions per minute
NOTE: The motor control method depends on the Modbus lnstance nolDeviceNet no: 43303
selection of drive mode [213], regardless of selected
process source, [321]. Profibus slot/index L69/2O7
Communication information
h 52 n
101
No. for serial No. for serial
Character Gharacter I 53 LO2
comm. comm.
o
I 54 103
Space 0 m 58
2
) 55 IO4
0-9 1- 10 n 59
k 56 3
105
A T7 n 60
57
B L2 o 61
C 13 o 62 Example:
D T4 o 63 Create a user unit named kPa.
E 15 p 64 1 . \7hen in the menu 1323] press Next ro move the cursor
F 76 q 6s to the right mosr position.
G t7 r 66 2. Press the + k.y until the characrer k is displayed.
H 18 S 67
3. Press Next.
19 t 68
4. Then press the + k.y until P is displayed and confirm
J 20 u 69 with Nexr.
K 27 u 70
5. Repeat until you have entered kPa.
L 22 V 7T
M 23 w 72
323 User Unit
N 24 X 73
SIPET
o 25 v 74
P 26 z 75 Default: I tt,to characters shown
o
a 27 a 76
Communicatio n information
R 28 a 77
S 29 o 78
43304
T 30 ! 79 43305
U 31 80 Modbus lnstance nolDeviceNet no:
43306
43307
U 32 # 81 43308
V 33 $ 82 43309
W 34 o/
/o 83 L69/2O8
X 35 & 84 L69/zoe
Y 36 Profibus slot/index L6e/2LO
85
L69/277
Z 37 ( 86 L69/272
A 38 ) 87 L69/2L3
A 39 * 88 Fieldbus format U lnt
o 40 + 89 Modbus format Ulnt
a 4T 90
a 42 \When sending a unit name you send one character at a time
91
b 43 starting at the right mosr position.
92
c 44 / 93
d 45 94
e 46 95
e 47 96
Ulnt
lnt
Modbus format
Defa u lt: 0
Modbus format El nt
Ratio=Quadratic
Process Max t3251
This menu is not visible when speed, torque or frequency is
STPET
10 1OO
Defa u lt: Max process Max [32b]
Process Min [324]
Min -L Min
Fig. 76
Max -2 Max
0.000-
10000
0-10000 0.000-10000 L1'3.3 Staft/Stop settings t33OI
Submenu with all the functions for accelerarion,
deceleration, starting, stopping, etc.
Commun ication inforrnation
Set-up:
Communication information
Process Min 13241 = 10
Process Max 13251 = 100
Modbus lnstance no/DeviceNet no: 43LOL
Ratio ?Zq = linear
F(Value), ProcMin 13271 = 150 Profibus slot/index r6e/5
F(Vhlue), ProcMax l3Zt1 = 1500
Fieldbus format Long, 1=0.01 s
\with this set-up, the process data is scaled and linked to
Modbus format El nt
known values which results in an accurare control.
(06-F12)
Communication information
Communication information
Com mun ication i nformation
Modbus lnstance nolDeviceNet no: 43LO4
Modbus lnstance no/DeviceNet no: 43L42
Profibus sloVindex L6e/8
Profibus slot/index L69/6
Fieldbus format Long, 1=0.01
Fieldbus format Long, 1-0.01 s
Modbus format El nt
Modbus format Elnt
Communication information
Acceleration Ramp Type t3371
Modbus lnstance nolDeviceNet no: 43105 Sets the rype of all the acceleration ramps in a paramerer ser.
Profibus slot/index See Fig. 80. Depending on the acceleration and deceleration
76e/e
requiremenrs for the application, the shape of both the
Fieldbus format Long, 1=0.01 ramps can be selected. For applications where speed changes
Modbus format Elnt need to be started and stopped smoothly, such as a conveyor
belt with materials that can drop following a quick speed
change, the ramp shape can be adapted to a s-shape and
prevent speed change shocks. For applications that are nor
critical in this, the speed change can be fully linear over the
Nom
complete range.
t2251
Max speed
[343]
337 Acc Rmp
[331]
StpEI Linear
Defa u lt: Linea r
rpm
The motor flux increases gradually. The
Fast 0 motor shaft starts rotating immediately
once the Run command is given.
Communication information
The motor decelerates to 0 rpm according Brake not engaged - Brake Warning and
Decel 0
to the set deceleration time.
continued operation (keep torque)
Coast L The motor freewheels naturally to 0 rpm. The brake acknowledge signal is compared to the actual
brake output signal at srop. If acknowledge is still active, i.e.
Communication in formation brake not engaged, while brake ourpur is low for the Brake
Engage time lSlgl then a Brake warning is generated and
Modbus lnstance nolDeviceNet no: the torque is kept, i.e. prolonging normal brake engage
43TTT
mode, until brake closes or an emergency action is needed
Profibus slot/index 76e/L5 by the operator, such as setting down the load.
Fieldbus format Ulnt
Modbus format U lnt
Modbus format El nt
Hr I.Hffit
!l l-,1
rir
rir
Start I
t.l
I
l
I
Mechanical
Open
Brake
Closed
Brake Relay On
Output
off
ron mu e place wltnln
these time intervals
Ra nge: O.0O-3.0O s
Communication information
Communication information
Modbus lnstance nolDeviceNet no: 431,L6
The "Brake Fault trip time" for "Brake not released" this purpose.
function is specified in this menu. The release torque initiates the torque reference from the
speed controller during the Brake Release Time l33C). The
release torque defines a minimum level of release (holding)
33H Brk Fau1t torque. The set release rorque is internally overruled if the
StpEl 1.00s actual required holding rorque measured at the previous
Defa u lt: 1.00s closing of brake is higher.
The release torque is ser with sign in order ro define the
Range 0.00 - 5.00s holding rorque direction.
Modbus format El nt
Communicatio n information
Note: The Brake Fault trlp time should be set to longer Modbus lnstance no/DeviceNet no: 43118
time than the Brake release time[33C].
Profibus sloVindex L69/22
The "Brake not engaged" warning is using the setting of Fieldbus format Long, I=LH%
parameter "Brake Engaged time [33E1". Modbus format Elnt
Following Figure shows principle of brake operation for
fault during run (left) and during srop (right).
Note! Function is deactivated if set to Ao/o.
Bra ke Bra ke
release time release time Brake wait Brake engage
33C 33C time time
ItsJ 33F 33E
Start t!
tl
Running tt
* L.- I
fo
-1 I r
Speed>o : @
I
- Brakerelay t-
ll tt
Brake acknowtedg" I [-rw'
r tt r
It
lt tt
BrakeTrip- ',,f I F l, I I
-
<33H 33H <33H I
Brake warning
Brake Fault trip time
During run During stop
* Memorized load torque level, if function activated with parameter [331] Release Torque.
** Time for operator to set down the load.
NOTE: Menu [386] has higher priorlty than menu 13421. Modbus format UInt
Range: 0-4xMotorSyncSpeed
Skip Speed 2 Low t3461
Communication information The same function as menu 1344) for the Znd skip range.
Skip Speed LO
Skip Speed 2 High 1347)
The same function as menu 13451 for the Znd skip range.
347 SkipSpd 2 Hi
stpfi 0
Speed Reference
NG 06-F17 Defa u lt: 0 rpm
Modbus format lnt output current of the AC drive followin$ the relation:
LOOo/o Tmot corresponds to 1fi)% lmot.
The maximum possible setting for parameter 351 is
limited by Inom/lmot x L2Oo/o, but not higher than 4OOo/r.
Jog
NOTE: The power loss in the motor will increase by the
Freq square of the torque when operating above 7,OO'/r.4AO%
torque will result in 16OO% power loss, which will
increase the motor temperature very quickly.
stpE! off motor saturation. This can cause a "Power Fault" trip.
The effeet of lxR Compensation is stronger with higher
powel motors.
Defa u lt: off
off 0 Function disabled
NOTE: The motor may be overheated at low speed.
Automatic 7 Automatic com pensation Therefore it is important that the Motor l2t Current t2321
User Defined 2 User defined value in percent. is set correctly.
Communication information
Flux Opti mization t354I
Flux Optimization reduces the energy consumption and the
Modbus lnstance no/DeviceNet no: 43742
motor noise, at low or no load conditions.
Profibus sloVindex L6e/46
Flux Optimization auromatically decreases the Y|H.z rario,
Fieldbus format Ulnt depending on the actual load of the moror when the process
Modbus format U lnt is in a steady situarion. Fig. 88 shows the area within which
the Flux Optimization is active.
Communication information
Fig. SS Flux Optimizing
Modbus lnstance nolDeviceNet no: 43L43
Profibus sloVindex L69/47
NorE: Flux optimlzation works best at stable sltuations
Fieldbus format Long in slow changing ptocesses.
Tlimit = Plimi tlo/o) / (Actual Speed / Sync Speed) the paramerer Digln I lSZl ] for the selection of the motor
potentiometer function.
NOTE: The maximum possible setting for parameter 355 Non Volatile. After a stop, trip or power
is limited by lnom/lmor x L2Oo/o, but not hi$her than down of the AC drive, the reference value
4OOo/o. at the moment of the stoP will be
Non volatile L
memorized. After a new start command
the output speed will resume to this saved
Communication information value.
Motpot
UP
Speed mode 0 - max speed t3431 The reference value is edited as a normal
parameter (the new reference value is
Torque mode 0 - max torque [351] Normal 0 activated when Enter is pressed after the
Min according to men u [324) - max according value has been changed). The Acc Time
Other modes
to menu [325] t3311 and Dec Time t3321 are used.
The reference value is edited using the
Communication in formation motor potentiometer function (the new
MotPot 7 reference value is activated directly when
the key * or - is pressed). The Acc MotPot
Modbus lnstance no/DeviceNet no: 43L32-43138
t3331 and Dec MotPot t3341 are used.
Profibus sloVindex L69/36-L69/42
Fieldbus format Long Com municatio n information
Modbus format El nt
Modbus lnstance no/DeviceNet no: 43139
The same settings are valid for the menus: Profibus sloVindex 769/43
1363) Preset Ref 2, with default 250 rpm Fieldbus format Ulnt
1364) Preset Ref 3, with default 500 rpm Modbus format U lnt
1355) Preset Ref 4, with default 750 rpm
13661 Preset Ref 5, with default 1000 rpm
1367) Preset Ref 5, with default 1250 rpm NOTE: When Key Ref Mode is set to MotPot, the
[368] Preset Ref 7, with default 1500 rpm reference value ramp times are according to the Acc
MotPot [333] and Dec MotPot t3341 settings. Actual
The selection of the presets is as in Thbl e 24.
speed ramp will be limited according to Acc Time t3g1]
and Dec Time [332].
Table 24
0 0 0 Analogue reference
0 T L Preset Ref 3
7 0 T Preset Ref 5
L T 0 Preset Ref 6
7 L T Preset Ref 7
386 PID4{inSpd
stpE off
Defa ult: off [341] Min Speed
Ra nge: off, 0.01 -3600 s
Fig. 9l PID Stop/skep with normal PID
Com munication information
Exampl e 2 PID control = inverted (tank leve!
Modbus lnstance nolDeviceNet no: 4337L control)
Profibus sloVindex 17o/20 l3Ztl = F (AnIn)
l3zz1 = rrr
Fieldbus format Long, 1-0.01 s
[3t01 = 7 m
Modbus format E! nt 13421 - 2 s (inactive since [1S01 is activated and have higher
prioriry)
[34 t ]= Inverted
NOTE: Menu t3861 has hlgher priority than menu 13421. t3861 = 30 s
13871 -- 1 m
PID Activation Margi n [387] The AC drive will stop/sleep when the speed (PID output) is
below or equal to Min Speed for 30 seconds. The AC drive
The PID activation (wake-up) margin is related to the
will activate/wake up when the "Process value" goes above
process reference and sets the limit when the AC drive
the PID Activation Margin which is related to the process
should wake-up/start again.
reference, i.e. goes above (7 +l) m. See Fig . 92.
Communication information
Modbus format El nt
NOTE: lt is important that the systenr has reached a Modbus lnstance nolDeviceNet no: 43374
stable situation before the Steady State Test is initiated.
Profibus sloVindex L7O/23
Fieldbus format Long, 1=0.01 s
88 PrD Stdy Tst Modbus format nt
stpfiI off El
Defa u lt: off Example: The PID Steady Test srarrs when the process value
lltt] is within the margin and Steady State Test \Wait Delay
Range: off, 0.01-3600 s has expired. The PID ourpur will decrease speed with a srep
value which corresponds to the margin as long as the Process
Communication information value l7tt] stays within steady stare margin. \il7hen Min
Speed l34l] is reached the steady state test was successful
Modbus lnstance nolDeviceNet no: 43373 and stop/sleep is commanded if PID sleep function
Profibus slot/index tf S6land l3S7) is activated. If the Process value lZttl goes
L7O/22
outside the set steady srare margins then the test
Fieldbus format Long, 1=0.01 s
failed and normal PID operation will continue, see Fig. 93
Modbus format El nt
t38el
[31O] Process Ref
t38el
1772) Speed
Defa u lt: 7
Com munication information
1-3 Number of drives it l/O Board is not used.
Modbus lnstance no/DeviceNet no: 43163
Number of drives if 'Alternating MASTER' is
1-6 used, see Select Drive t3931 . (l/O Board IS Profibus sloflindex 1:69/67
used.)
Fieldbus format Ulnt
Number of drives if 'Fixed MASTER' is used,
see Select Drive t3931. Modbus format Ulnt
7-7
(l/O Board is used.)
The Runtime of the master drive Modbus lnstance no/DeviceNet no: 43165
determines when a master drive has to be
changed. The change will only take place
Profibus sloVindex L69/6e
after a: Fieldbus format Ulnt, 1=1 h
Stop 0
- Power Up
- Stop Modbus format Ulnt, 1=1 h
- Standby condition
- Trip condition.
Drives on Change t3961
The master drive will be changed if the
timer setting in Change Timer t3951 has If a master drive is changed according to the timer function
elapsed. fhe change will take place (Change Condition=Timer/Borh 13941), it is possible to
immediately. So during operation the leave additional pumps running during the change
additional pumps will be stopped operation.'$7'ith this function the change operation will be
Timer T temporarily, the 'new' master will be as smooth as possible. The maximum number to be
selected accordingto the Run Time and the programmed in this menu depends on the number of a
additional pumps will be started again. dditional drives.
It is possible to leave 2 pumps running
during the change operation. This can be Example:
set with Drives on Change [396J. If the number of drives is set to 6, the maximum value will
The master drive will be changed if the be 4. This function is only active if Select Drive 1393]=All.
timer setting in Change Timer t3g5l has
elapsed. The 'new' master will be selected
396 Drives on Ch
Both 2
according to the elapsed Run Time. The
change will only take place after a: stpE! 0
- Power Up
- Stop Defa u lt: 0
- Standby condition.
- Trip condition. Range: 0 to (the number of drives - 2)
Speed
Example:
Max Speed = 1500 rpm Max
Min Speed = 300 rpm
Upper Band - l0o/o
Start delay will be activated:
Range = Max Speed to Min Speed = 1 500-300 = 1200 rpm
l0o/o of I 200 rpm = 120 rpm
Start level = 1500-120 - 1380 rpm <-r
Stop Delay [39A]
(NG_5GPC-r 3_r)
Speed
l--_;l Flow/Pressure
Start De1ay
Start Delay t3991
(NG_5o-rc-12_1) stpE! 0s
Fig. 94 Upper band Defa u lt: Os
Range: 0-999 s
Lower Band t3981
If the speed of the master drive comes into the lower band Communication information
an additional drive will be stopped after a delay time. This
delay time is set in the parameter Stop Delay t39A]. Modbus lnstance nolDeviceNet no: 43169
Defa u lt: o%
\
O to Upper Band level. O% 1=rax speed) means
Range:
that the Limit function is switched off.
Flow/Pressure
Stop Delay t39AI
Communication information (NG_5O-PC-15_2)
Speed
Max
Flow/Pressure
Start Delay t3991
(NG_so-PC-14_2)
Additional pump
Defa u lt: 0s
Tra ns
Range: 0-999 s
{
Com munication info rmation Min
FloVPressure
Modbus lnstance no/DeviceNet no: 43773 Actual start
command of next
Profibus slot/index L69/77 pumP (RELAY) (Nc_so-pc-16_1)
Flow/Pressure
Transition Speed Start t39El Transition speed
decreases overshoot
The transition speed start is used to minimize a flow/
\
pressure overshoot when adding another PumP. \7tren an
additional pump needs to be switched on, the master PumP
will slow down to the set transition speed start value, before
the additional pump is started. The setting depends on the
dynamics of both the master drive and the additional drives. Time
The transition speed is best set by trial and error. Fig. 99 Effect of rransition speed
ln general:
. If rhe additional pump has 'slow' start/stop dynamics, Settle Time Stop t39Fl
then a higher transition speed should be used. The settle stop allows the process to settle afrer a pump is
. If the additional pump has 'fast' start/stop dynamics, switched off before the pump control continues. If an
then a lower transition speed should be used. additional pump is stopped D.O.L. (Direct On Line) or Y/
A, the flow or pressure can still fluctuate due to the'rough'
start/stop method. This could cause unnecessary starting
398 Transs Start and stopping of additional pumps.
stpfi 60t
During the Settle stop:
Defa u lt: 60% o PID controller is off
Ra nge: 0-1OO% of total min speed to max speed . the speed is kept at a fixed level afrer stopping a pump
Modbus format El nt
Trans
Actual
Transition Speed Stop t39cl Min
The transition speed stop is used to minimize a flow/
pressure overshoot when shutting down an additional pump. Switch off procedure starts
The setting depends on the dynamics of both the master
Fig. 100 Thansition speed stop
drive and the additional drives.
E Pump error
Modbus lnstance nolDeviceNet no: 43321,
Profibus slot/index L69/225
Num ber backup/reserve [39P]
Sets the number of pumps used for backup/reserve which in Fieldbus format U lnt
normal conditions can not be selected. This function can be Modbus format U lnt
used for increasing redundancy in the pumP system by hav-
ing pumps in reserve that can be activated when some
pumps indicate fault or are shut off for maintenance. Alarm Trip t4L2l
Selects which alarm must cause a trip to the AC drive.
39P No of Backup
stpE! 0 4L2 A1arm trip
Defa u lt: 0
stpE! off
Ra nge: 0-3 Defa u lt: off
Se lectio n: Same as in menu [411]
Com munication info rmation
Communication information
Modbus lnstance no/DeviceNet no: 43L77
Basi
Alarm Start Delay 14L41 Min Alarm
This parameter is used i[ for example, you wanr to override
an alarm during the start-up procedure.
Load curve
Sets the delay time after a run command, after which the
alarm may be given.
Speed
. If Ramp AIarm=On. The srarr delay begins after a RUN
command. Fig. 101
. If Ramp Alarm=Off. The stam delay begins after the
acceleration ramp. 415 Load Type
StpEI Basic
4L4 Start De1ay
stpflI 2s Defa u lt: Basic
Modbus lnstance no/DeviceNet no: 43326 Modbus lnstance nolDeviceNet no: 43327
Modbus lnstance no/DeviceNet no: 43330 Modbus lnstance nolDeviceNet no: 43331
Modbus lnstance nolDeviceNet no: 43328 Modbus lnstance nolDeviceNet no: 43329
Min Pre Alarm Response delay l4L82l Min Alarm Response delay 14L92)
Sets the delaytime benveen the first occurrence of min pre Sets the delaytime berween the first occurrence of min
alarm condition and after when the alarm is given. alarm condition and after when the alarm is given.
Modbus lnstance no/DeviceNet no: 43332 Modbus lnstance nolDeviceNet no: 43333
Profibus sloVindex 169/236 Profibus slot/index 769/237
Fieldbus format Long, 1-0.1 s Fieldbus format Long, 1-0.1 s
Modbus format Elnt Modbus format Elnt
Communication information
DC link voltage
Fig. 102
(06-F6Onew)
LI".5.1 Analogue lnputs [51O] Anlnl = ( l0-4) I (20-4) * (1 500-0) * 0 - 562.5 rpm
Submenu with all settings for the analogue inputs. AnIn2 -- (5-41 I (20-4) * (3OO-0) + 0 = 18.75 rPm
The actual process reference will be:
Anlnl Function t51-1I +562.5 + 18.75 = 581 rpm
Sets the function for Analogue input l. Scale and range are
Analogue lnput Selection via Digital lnputs:
defined by AnIn I Advanced settings [513]. \Mhen rwo different external Reference signals are used, €.8.
4-20mA signal from control centre and a 0- l0 V locally
511 Anlnl Fc mounted potentiometer, it is possible to switch between
StpE Process Ref these two different analogue input signals via a Digital Input
set to 'Anln Select".
Defa u lt: Process Ref
AnIn I is 4-20 mA
off o lnput is not active AnIn2 is 0-10 V
Max Speed T The input acts as an upper speed limit. Digln3 is controlling the Anln selection; HIGH is 4-20 mA,
Max Torque 2 The input acts as an upper torque limit. LO\f is 0-10 V
The input value equals the actual process [5t t] Anlnl Fc = Process Ref;
value (feedback) and is compared to the set AnInl as reference signal input
Process Va I 3 reference signal (set point) by the PID
controller, or can be used to display and l5tZl AnInl Setup - 4-20mA;
view the actual process value. set Anln I for a current reference signal
Reference value is set for control in [513A] Anln 1 Enable = Digln;
Process Re{ 4 process units, see Process Source [321] setAnln 1 to be active when Digln3 is HIGH
and Process Unit 13221.
l5t+1Anln2 Fc = Process Ref;
set AnIn2 as reference signal input
Commun ication information
t5l5l Anln2 Setup = 0-l0V;
set AnI n2 for a voltage reference signal
Modbus lnstance nolDeviceNet no: 4320]t
Profibus sloVindex L6e/ 105 [516,{] AnIn2 Enabl - lDigln;
setAnln2 to be active when Digln3 is LO\V
Fieldbus format U lnt
1523) Digln3=Anln;
Modbus format U lnt
set Dlgln3 as input fot selection of AI reference
Signal on Anlnl = 8 V
Adding analogue inputs Signal on Anl n2 = 4Y
If more then one analogue input is set to the same function, [5t t] AnInl Function = Process Re[,
the values of the inputs can be added together. In the l5tZl Anlnl Setup = 0-10 V
fo[owing examples we assume that Process Sour ce 1321] is 15134) Anlnl Function Min = Min (0 rpm)
set to Speed. 15136) Anlnl Function Max = Max (1500 rPm)
Example 1: Add signals with different weight (fine tuning). [5138] AnIn 1 Operation = Add+
l5tll Anln2 Function - Process Ref,
Signal on Anlnl = 10 mA
t5151 AnIn2 Setup = 0-10 V
Signal on Anl n2 - 5 mA
\rcq Anln2 Function Min - Min (0 rpm)
[5t t] AnInl Function = Process Ref. [5 t ee1 AnIn2 Function Max - Max ( 1 500 rpm)
Anlnl Setup 15L21 NorE: Always check the needed set up when the setting
The analogue input setup is used to configure the analogue of s1 is changed; selection will not adapt automatically.
input in accordance with the signal used that will be
'$7ith
connected to the analogue input. this selection the Com munication information
input can be determined as current (4-20 mA) or voltage
(0- 10 V) controlled input. Other selections are available for
Modbus lnstance nolDeviceNet no: 43202
using a threshold (live zero), a bipolar input function, or a
user deftned input range. \7ith a bipolar input reference Profibus sloVindex L69/1:06
signal, it is possible to control the motor in rwo directions. Fieldbus format U lnt
See Fig. 104.
Modbus format U lnt
Communication information
5133 Anrnl BipoJ-
Modbus lnstance nolDeviceNet no: 43203 StpEIlo. oov /20. oomA
Profibus slot/index 1.:69/ LO7
Defa u lt: 1O.OO V/2O.OO mA
Fieldbus format Long
Range: 0.0-20.0 mA, 0.00-10.00 V
Modbus format Elnt
Emotron AB OL-4428-01r3
Functional Description
Anlnl Function Min [5134] Anlnl Function Max [5136]
'$7'ith
\7ith AnIn 1 Function Min the physical minimum value is Anln 1 Function Max the physical maximum value is
dependent of the selected function of Anlnl [;11]. dependent of the selected function of Anlnl [t11]. See
Table 25.
Communication information
Table 25 shows corresponding values for the min and max
selections depending on the function of the analogue input
Modbus lnstance nol
[5tt1. 43207
DeviceNet no:
Communication information NOTE: With Anln Min, Anln Max, Anln Function Min and
Anln Function Max settings, loss of feedback signals
Modbus lnstance nolDeviceNet no 43541, (e.8. voltage drop due to long sensor wiring) can be
L7O/ 1e0
compensated to ensule an acculate process control.
Profibus slot/index
Long,
Speed t=7- rpm
Fieldbus format Torq ue L=Lo/o
Process val 1-0.001-
Modbus format El nt
Profibus slot/index
Digln 2 Anlnl is only active if the digitat input is high
769/L72
Fieldbus format Ulnt
Communication information
Modbus format Ulnt
Modbus lnstance nolDeviceNet no Anln 7 4321:0
Anlnl- Filter [5139] Profibus sloVindex Anln 1, 169/ LI4
If the input signal is unstable (e.g. fluctuation reference
Fieldbus format Ulnt
value), rhe filter can be used to stabilize the signal. A change
of the input signal will reach 630/o on AnIn I within the sei Modbus format U lnt
AnInl Filter time. After 5 times theset rime, Anlnl will
have reached l00o/o of the input change. See Fig. 108.
Anln2 Function t514I
Parameter for setting the function of Analogue Input 2.
5139 AnInI-ffi
stPEI o- ls Same function as AnIn 1 Func t5 t t 1.
Emotron AB OL-4428-01r3
Funstional Description
Anln2 Setup [515] Anln3 Setup t5181
Parameter for setting the function of Analogue Input 2' Same functions as Anlnl Setup l5tZ1.
Communication information
Modbus lnstance no/DeviceNet no: 43222
Communication information
Com munication in formation
43223-43230
43213-43220 Modbus lnstance nolDeviceNet no: 43543
Modbus lnstance no/DeviceNet no 43542
43553
43552 L69/L27 -r6s/r34
L69/7L7 -L24 Profibus slot/index L7O/ L92
Profibus slot/index 17o/ L91, L7O/2O2
77O/2O1,
51A AnInA Fc
517 AnIn3 Fc stpE! off
stpE! off
Defa u lt: off
Default: lOff
Se lection: Same as in menu [511]
Selection: Same as in menu [511]
Emotron AB 07-4428-0113
Functional DescriPtion
Anln4 Set-up [518] Lf,.5.2 Digital Inputs [S2O]
Same functions as Anlnl Setup l5tZ1. Submenu with all the settings for the digital inputs.
518 AnIn4 Setrrp NorE: Additional inputs will become avaitable when the
StpEI 4-2 l/O option boards are connected.
Feedback input PumP 4for PumP/Fan Parameter Set Set Ctrl 1 Set Ctrl 2
Pump4
18 control and informs about the status of the 0 0
Feedb A
a uxiliary connected PumP/fan.
B 1, o
Feedback inPut PumPS for PumP/Fan
Pump5 o
19 control and informs about the status of the C 1,
Feedb
auxiliary connected Pump/fa n. D t L
Feedback input PumP 6 for PumP/Fan
Pump6
20 control and informs about the status of the
Feedb NOTE: To activate the palameter set selection' menu
auxilia ry connected Pum P/fan.
241, must be set to Digln.
Timer 1 Delay t6431 will be activated on the
Timer L 2L
rising edge of this signal.
22
Timer 2 Delay t6531 will be activated on the Digital lnput 215221to Digital lnput 8
Timer 2
rising edge of this si$nal.
t528I
Activates other parameter set. See Table I
Set Ctrl 1 23 Same function as lSZ1l. Default function for Digln
Digln
26 for selection Possibilities.
B is Reset. For Digln 3 to 7 the default function is Off.
Activates other parameter set. See Table
Set Ctrl 2 24
26 for selection Possibilities.
522 Digln
Mot PreMag 25
Pre-magnetises the motor. Used for faster
motor start.
stpE! Ru
Communication information
The scale of the voltage controlled output Profibus slot/index 169/ L57
that controls the full range for the output
User V 6 Fieldbus format Long, 1=0.01
signal. Can be defined by the advanced
AnOut Min and AnOut Max menus. Modbus format El nt
Sets the output for a bipolar voltage
User Bipol V 7
output, where the scale controls the AnOutl Max [5332]
range for the output signal. Scale can be This parameter is automatically displayed if User mA or
defined in advanced menu AnOut Bipol.
User V is selected in menu AnOutl Setup 1532]. The menu
will automatically adapt to current or voltage setting a
Com munication information ccording to the selected setup. Only visible if l;lZ] = User
mAA/..
Modbus lnstance nolDeviceNet no 43252
Communicatio n i nformation
AC drive AC drive
Master Slave Modbus Instance no/DeviceNet no 43254
Profibus slot/index r6e/ 158
Fieldbus format Long, 1=0.01
Fig. 109
Example
Thble 27 shows corresponding values for the min and max Set the Anout function for Motorfrequency to 0Hz, ser
selections depending on the function of the analogue ourpur AnOut functionMin 15334) ro "l.Jser-defined" and AnOutl
15311. VaMin15335) - 0.0. This results in an anlogue ourput signd
from 014 mA to 20mA::\Hz to Fmot.
This principle is valid for all Min to Max settings.
Emotron AB OL-4428-01r3
Functional Description
AnOutl Function Value [5335] AnOutl Function Value Max [53371
a user-defined
\With AnOutl Function VaMax you define a user-defined
With AnOutl Function VaMin you define
value for the signal. Only visible when user-defined is value for the signal. Only visible when user-defined is
User defined 2 Define user value in menu [5337] Modbus lnstance no/DeviceNet no: 4326L
Emotron AB AI-4428-01r3
Functional Descri Ption
Communication information
The frequency is limited by the
At Max spd 7
Maximum Speed.
Modbus lnstance nolDeviceNet no: 43262
No Trip 8 No Trip condition active.
Profibus slot/index 169/1:66
Trip I A Trip condition is active.
Fieldbus format U lnt
AutoRst Trip 10 Autoreset trip condition active.
Modbus format Int
U
Limit lt A Limit condition is active.
stPEI Rea
!LY 25 Logic output Y inverted.
LZ 26 Logic output Z.
Defa u lt: Ready
lV 27 Logic output Z inverted.
Output is not active and constanily
off o CA1 28 Analogue comparator 1 output.
low.
!A1 29 Analogue comp 1 inverted output.
Output is made constanily high, i.e.
On 7 for checking circuits and trouble CA2 30 Analogue comparator 2 output.
shooti ng.
tA2 31 Analogue comp 2 inverted output.
Running. The AC drive output is active
Run 2 CD1 32 Digital comparator 1 output.
- produces current for the motor.
Stop !D1 33 Digital comp 1 inverted output.
3 The AC drive output is not active.
Emotron AB OI-4428-01r3
Fu nctional Description
37 Timerl output Com Error 80 Serial communication lost
T1Q
Acc 64 Acceleration along the acc. ramP Modbus lnstance no/DeviceNet no 43271,
Dec 65 Deceleration along the dec. ramP Profibus slot/index 169/ !75
Emotron AB OL-4428-01r3
Functional Descri Ption
Digital Out 215421 Retay 2 [552]
NorE: The definitions described here are valid for the NOTE: The definitions descrlbed here are valid for the
active output condition. active output condition.
Sets the function for the digital output 2. Sets the function for the relay output 2.
Communication information
Retay L t5511
Sets the function for the relay ourpur l. same function as Modbus lnstance nolDeviceNet no: 43275
digital ourput | 5q1l can be selected. Profibus slot/index L69/L79
Fieldbus format U lnt
51 Re1ay 1 Modbus format
stpE! rrip U lnt
Defa lt:
u Trip Board Relay [554] to ts5Cl
Selection: Same as in menu [541] These additional relays are only visible if an I/O option
board is fitted in slot 1,2, or 3. The ourputs are named Bl
Com mun ication information Relay l-3, 82 Relay t-3 and 83 Rel ay l-3. B stands for
board and l-3 is the number of the board which is related to
Modbus lnstance no/DeviceNet no: 43273 the position of the I/o option board on the option
mounting plate.
Profibus slot/index 769/r77
Fieldbus format U lnt NorE: vlsible only if optional board is detected or if any
Modbus format input/output is astivated.
U lnt
Emotron AB OI-4428-01r3
Functiona I Description
Communication information LL.5.6 Virtual Connections t560I
Functions to enable eight internal connections of
Modbus lnstance no/DeviceNet no 435rr-43519 comparator, timer and digital signals, without occupying
Profibus slot/index !7O/ 160 -L7O/ 168 physical digital in/outputs. Virtual connections are used to
*ir.l.rs connection of a digital outPut function to a digital
Fieldbus format U lnt
input function. Available signals and control functions can
Modbus format U lnt be used to create your own specific functions.
43277 -43278,
Modbus lnstance nolDeviceNet no: 43521,-43529
Same function as virtual connection I 5e1] and The analogue hysteresis rype comparator uses the rwo
1562).
available levels to create a hysteresis for the comparator
Communication information for virtual connections 2-8 berween setting and resetting the output. This function gives
Destination. a clear difference in switching levels, which lets the process
'With
adapt until a certain action is started. such a hysteresis,
43283, 43285,43297 , even an unstable analogue signal can be monitored without
Modbus lnstance nolDeviceNet no 43289, 4329].., 43293, getting a nervous comparator output signal. Another feature
43295 is the possibiliry to ger a fixed indication that a certain level
L69/ L87,189, Lgt, has been passed. The comparator can latch by setting Level
Profibus sloVindex
193, 195, 1.97,199 LO to a higher value than Level HI.
Fieldbus format U lnt The analogue window comparator uses the two available
Modbus format U lnt levels to define the window in which the analogue value
should be within for setting the comparator output.
The input analogue value of the comparator can also be
Communication information for virtual connections 2-8
selected as bipolar, i.e. treated as signed value or
Source.
unipolar, i.e. treated as absolute value.
43284, 43286,43298, Refer to Fig. ll4, page 146 where these functions are
Modbus lnstance nolDeviceNet no 43290, 43292,43294, illustrated.
43296
Digital comparators [615]
L69/ 188, 190, t92, There arc 4 digital comparators that compare any available
Profibus sloVindex
194,196, 1gg, 200
digital signal.
Fieldbus format U lnt
The output signals of these comparators can be logically tied
Modbus format U lnt together to yield a logical output signal.
All the output signals can be programmed to the digital or
relay outputs or used as a source for the virtual connections
t5601.
below the lower limit, the output signal CAl is set low and Output Volt 6 V
!A1 high.
Frequency 7 Hz
DC Voltage 8 V
Analogue value:
Menu [6111] Heatsink Tmp I OC
Signal:CA1
OC
ljustable Level Hl. PT100_1 10
Menu l6Lt2)
PT100_2 1! OC
OC
PT100_3 T2
Energy 13 kwh
Mains Time 15 h
For \Tindow comparator type [61 14] , when the value is
benveen the lower and upper levels, the output signal value
Anlnl 16 o/o
CAl is set high and !A1 low, see Fig I 13. \When the value is Anln2 L7 %
outside the band of lower and upper levels, the output CAI
Anln3 18 o/o
Emotron AB OL-4428-01r3
Fu nctional Description
Analogue Comparator 7-, Example
This example describes, both for hysteresis and window ryPe
Level High t61L2l comparator, the normal use of the constant level high and
Sets the analogue comParator high level, with range 1ow.
according ro the selected value in men,, [6111].
Menu Funstion Setting
ffiLeve1 Hr
343 Max Speed 1500
stpEl 300
61LL CA1 Value Speed
Default: lsoO rpm
6TT2 CA1 Level Hl 300 rpm
Range: See min/max in table below.
6113 CA1 Level LO 2OA rpm
DC voltage, V 0 1.250 L
oC o 100 L
Heatsink temp,
oC -100 300 T
PT 100 _r_2_3,
tpq4l Hv$erSis
Energy, kwh 0 1000000 o
Modbus format El nt
Emotron AB 0!-4428-0113
Fu nctiona I Descri Ption
No. Description Hysteresls Wlndow Analogue Comparator L,
The reference signal passes the
Level Low [6113]
Level LO value from below (positive Sets the analogue compararor low level, with unit and range
7
edge), the comparator CA1 does not according ro the selected value in menu [6 ] 1 I ] . .
change, output stays low.
Emotron AB OL-4428-01r3
Fu nctiona I Description
Analogue Comparator 7-, Polarity [6115]
Type t61141 = Window
selects how the selected value in ] should be handled
[6 ] 1 l
CA1
prior to the the analogue comParator , i.e. as absolute value t61151 Unipolar
'
or handled with sign. See Fig. ll4 t61121'Hl > o
lorrsJ Lo >o
An.Value
[6111]
CA1
115 CA1 Po1ar 't61151 Bipolar An.Value
t611Zl Ht > 0
STPET Unipolar forrg] Lo > o t61111
t61131,8jtr|}
CA1
Defa u lt: Unipolar
t61151 Bipolat
^--^ t
An.Value
Emotron AB OL-4428-01r3
Fu nctional DescriPtion
Analogue Comparator 2, Analogue Comparato r 2, Type 16L241
Level High t6L22l Function is identical to analogue compararor t,
Function is identical to analogue compararor 1,
Typ. l6tr4l.
level high 16rr2l.
6L24 CA2 Type
6L22 cA STPET Hysteresis
stPEI 20t, Defa u lt: Hysteresis
20% Hysteresis 0 Hysteresis type compa rator
Range: Enter a value for the high level. Window T Window type comparator
Modbus lnstance nolDeviceNet no: 43405 Modbus lnstance no/DeviceNet no: 43482
Profibus slot/index L7O/54 Profibus slot/index L7O/L3!
Long Long,
L=t W, 0.1 A, 0.1 V, L=t W, 0.1 A, 0.1 V,
Fieldbus format 0.LH2,0.1"C, 1 kwh, Fieldbus format O.LHz, O.1oC, 1 kwh,
tH, L%, 1 rpm or 0.001 tH, L%, 1 rpm or 0.001
via process value via process value
Modbus format Elnt Modbus format Elnt
Modbus lnstance nolDeviceNet no: 43406 Modbus lnstance nolDeviceNet no: 43487
Profibus slot/index 17o/55 Profibus slot/index L7O/L36
Long,
Long,
L=L W, 0.1 A, 0.1 V,
Fieldbus format L=L W, 0.1 A, 0.LV,
O.1"Hz, O.1oC, 1 kwh, Fieldbus format O.tHz, O.1oC, 1 kwh,
tH,7%, 1 rpm or 0.001
LH,7%. 1 rpm or 0.001
via process value
via process value
Modbus format Elnt Modbus format Elnt
Emotron AB OL-4428-01r3
Fu nctional Description 147
CA3 Setup t61-31 Analogue Comparator 3,
Analogue comparators 3, parameter group' Level Low t61331
Function is identical to analogue comparator 1,
Ra nge: Enter a value for the high level. Window L Window type comParator
Modbus lnstance no/DeviceNet no: 43472 Modbus lnstance no/DeviceNet no: 43483
Profibus sloVindex L7O/L2r Profibus sloVindex L7O/1.32
Long Long,
t=L W, 0.1 A, 0.1V, L=7, W, 0.1 A, 0.1 V,
Fieldbus format 0.1 Hz, 0.1oC, 1 kwh, Fieldbus format 0.1 Hz, 0.1oC, 1 kwh,
LH, Lo/q 1 rpm or 0.001 LH, 1o/o, 1 rpm or O.001
via process value via process value
Emotron AB OI-4428-01r3
Fu nctiona I Descri Ption
Analogue comparator 3, polar t6i-35] Analogue Comparator 4, Level High
Function is identical to analogue compararor 1,
Polar [61 I 5]. 16L42l
Function is identical to analogue compararor 1 level high
l6t tzl.
6135 cA3 Pollti
StpE Unipolar 6L42 CA4 Level HI
Defa u lt: Un ipola r stpE! 100rpm
Unipolar 0 Absolute value of [6111] used Defa u lt: 10Orpm
Bipolar 7 Signed value of [6111] used Range: Enter a value for the high level.
Modbus lnstance no/DeviceNet no: 43488 Modbus lnstance nolDeviceNet no: 43475
Profibus slot/index L7O/L37 Profibus slot/index L7O/L24
Long, Long
t=t W, 0.1A, 0.1 V, t=t W, 0.1 A, 0.1 V,
Fieldbus format O.LHz,0.1"C, 1 kwh, Fieldbus format 0.1 Hz, 0.1"C, 1 kwh,
LH, to/o, 1 rpm or 0.001 LH, to/u 1 rpm or O.OO1
via process value via process value
Modbus format El nt Modbus format Elnt
Emotron AB 07-4428-0113
Functiona I Description L49
Analogue Comparato r 4, TYPe 16144l Digital comparator SetuP t6l-51
Function is identical to analogue comParator 1, level Typ. Digital comparators, Parameter grouP.
16rr4l
Digital Comparator 1, [615U
6L44 CA4 TY'Pe Selection of the input signal for digital comParator 1 (CD1).
stpEl windo The output signal CD I is set high if the selected input
signal is active. See Fig. 1 16.
Defa u lt Window
The output signal can be Programmed to the digital or relay
Hysteresis 0 Hysteresis tyPe comParator
outputs or used as a source for the virtual connections t560].
Window ! Window type comparator
Communication information
Digital signal: Signal: CD1
Modbus format El nt
Modbus lnstance no/DeviceNet no: 43408
6L54 CD 4 7 0 0 7
StpEI Read
1,
1, 1, T ! 0
Defa ult: Ready
Selection: Same selections as for Digout 1 t5411. The output signal can be programmed to the digital or relay
outputs or used as a Virtual Connection Source [5601.
Communication information
620 LOGIC Y
Modbus lnstance nolDeviceNet no: 43478 Stp CA1 & !A2&CD1
Profibus slot/index L7O/727
Fieldbus format U lnt Communication information
Modbus format U lnt
Modbus lnstance nolDeviceNet no: 31035
Profibus slot/index L27/ 779
Fieldbus format Long
Modbus format Text
The comparator !A2 is set for load < 20o/o. Defa u lt: CA1
The 3 comparators are all AND-ed, given the "broken belt !A1 L
detection". cA2 2
tT2 13
NOTE:Set menu l624lto "." to finish the expression
when onty two comparators ale lequlred for Logic Y. CA3 L4
!A3 15
CA4 16
!A4 L7
CD3 18
!D3 19
CD4 20
!D4 2T
Communication i nformation
Emotron AB OI-4428-01r3
Functional Description
L1.6.3 Logic OutPutZ t63OI ZComp 2 t6331
Selects the second comParator for the logic Z function.
630 LOGIC Z
stpfi CA1 & !A2&CD1 633 Z Comp 2
stpE! tA2
The expression must be Programmed by means of the Defa u lt: tA2
menus 16311 to 1635). Selection: Same as menu [621-]
Alternate 2
T1Q
Communication i nformation
timer might differ for a set change compared to normal timer after it is acrivated. Timer I can be acrivared by a high
triglglering of a timer. signal on a Digln that is set to Timer I or via a virtual
destination [560.l.
643 TimerlDe1iy
Timerl Trig
stpEl 0:00:00
Defa ult: 0:00:00 (hr:min:sec)
T1Q Range: 0:00:OO-9:59:59
Communication informatio n
Fig. It8
43433 hours
Modbus lnstance no/DeviceNet no: 43434 minutes
Timer 1,Trigl641]
43435 seconds
!7O/82, L7O/83,
64L Timerl- fr$ Profibus slot/index
17o/84
stPEI orf Fieldbus format Ulnt
Defa u lt: off Modbus format Ulnt
Selection: Same selections as Digital Output 1 menu t5411
Communication information
Emotron AB OI-4428-01r3
Functional Description
Timer 1,T1, 16441 Timer l Value t64el
\Mhen timer mode is set to Alternate and Timer 1 is enabled, Timer I Value shows actual value of the timer.
this timer witl automatically keep on switching according to
the independently programmable up and down times' The 649 Timerl Va].ue
Timer I in Alternate mode can be enabled by a digital input stpE! 0:00:00
or via a virtual connection. See Fig. 118. Timer 1 Tl sets the
up time in the alternate mode. Defa u lt: 0:00:00, hr:min:sec
Range: 0:00:00-9:59:59
644 Timer 1T1
SIPET 0:00:00 Commun ication information
L7O/85, L70/86,
Profibus slot/index L7O/87
LL.6.5 Timer2[65OI
Fieldbus format Ulnt
Refer to the descriptions For Tirnerl.
Modbus format U lnt
Range:
Communication information
Communication information
Modbus lnstance nolDeviceNet no: 43451,
NOTE: Timer 1T1 t6441 and Timer 2T1, t6541 are only
vlsible when Timer Mode is set to Alternate.
Emotron AB OL-4428-01r3
Fu nctiona I Descri Ption
Timer 2 Mode tOS2l Timer 2T2 t6551
653 Timer2Ddfay
I
554 Timffi
stpE! 0:00:00
Defa u lt: O:OO:00, hr:min:sec
Range: 0:00:00-9:59:59
Communication information
43456 hours
Modbus lnstance nolDeviceNet no: 43457 minutes
43458 seconds
Emotron AB OL-4428-01r3
Functional Description
L7..7 View Operati on/Status Torque t7131
Displays the actual shaft torque.
[7oo]
Menu with parameters for viewing aI[ actual operational 7L3 Torque
data, such as sPeed, torque, Power, etc'
Stp 0t 0.0
L7..7.!. Operation t71OI Unit: %, Nm
o/o,
Resolution: 7- 0.1 N m
L21,/ L47
IT-E ocess Val Profibus sloVindex L21,/L48
stp Long, 1-0.1 Nm
Fieldbus format Long, L=7- o/o
Un* lm::Si,Xi,'E ;:'""sourcer321l Modbus format El nt
Speed: lrPm,4digits
Resolution
Other units: 3 digits
Shaft power l7L4)
Commun ication in formation Displays the actual shaft Power.
Modbus format El nt
Unit I rpm
Resolution: 1 rpm, 4 digits
Electrical Power t7151
Communication information Displays the actual electrical outPut power.
Emotron AB OL-4428-01r3
Fu nctiona I Descri Ption
Communication information
Frequency [718]
Displays the actual output frequency.
Modbus lnstance nolDeviceNet no: 31006
Profibus slot/index L2L/ 150
718 Frequency
Fieldbus format Long, 1=1W
Stp Hz
Modbus format Elnt
Unit: Hz
Resolution: O.7 Hz
Current ITLG)
Displays the actual outpur currenr.
Communication information
Resolution: 0.1 v
Output Voltage l7L7l
Displays the actual output voltage.
Communication informatio n
Unit: "C
Resolution: 0.1" c
Emotron AB OI-4428-01r3
Functional Description
PT 100- 1,-2-3 Te m P t71 Bl LL.7.2 Status l720l
Displays the actual PT 1 00 temPerature.
I VSD Status l72Ll
ffioo L,2,3
oC
Indicates the overall status of the AC drive.
Stp
Unit: | "C
72L VSD Status
1"C
stp L/222/333/ 44
Resolution:
-Key (keyboard)
Source of Runl -Rem (remote)
333 Stop/Reset com- -Com (Serial comm.)
mand
-Opt (option)
Warning 17221
Display the actual or last warning condition. A warning
occurs if the AC drive is close to a trip condition but still in
operation. During a warning condition the red trip LED
will start to blink as long as the warning is active.
122 l{arnings
Stp warn. msg
Emotron AB O7'4428-O1r3
Fu nctiona I Descri Ption
Fieldbus Digital lnput Status t7231
integer Warning message Indicates the srarus of the digital inpurs. See Fig . 120.
value
1 Digln I
0 No Error 2 Digln 2
1, Motor l2t 3 Digln 3
4 Digln 4
2 PTC
5 Digln 5
3 Motor lost 6 Digln 6
4 Locked rotor 7 Digln 7
8 Digln 8
5 Ext trip
The positions one to eight (read from left to right) indicate
6 Mon MaxAlarm the status of the associated input:
7 Mon MinAlarm
1 High
8 Comm error
0 Low
9 PTlOO
The example in Fig. 120 indicates that Digln 1,
L7 Pump Digln 3 and Digln 6 are active at this momenr.
L2 Ext Mot Temp
726 AnIn 3 4
724 DigOutstatus Stp -100t 65t
Stp RE 100 Do 10
Fig. 123 Analogue input stdtas
Fig l2 I Digital outPut status example
Communication information
Communication information
Modbus lnstance nolDeviceNet no: 3to2L,3rO22
Modbus lnstance nolDeviceNet no: 31018
Profibus slot/index 727/165, L21,/166
Profibus sloVindex 721,/L62
Fieldbus format Long, t=t%
Fieldbus format Ulnt, bit O=DigOutl,
bit 1=Dig0ut2 Modbus format El nt
bit 8=Relayl
Modbus format bit 9=Relay2
bit 10=Relay3 Analogue Output Status 17271
Indicates the status of the analogue outputs. Fig. 120. E.g. if
4-20 mA output is used, the valu e 20o/o equals rc 4 mA.
Analogue lnput Status 17251
Indicates the status of the analogue inputs I and 2.
727 AnOut 1 2
Stp -100t 65t
725 AnIn 1
Stp -100t 65t Fig. 124 Analogue output stdtus
Modbus format El nt
The first row indicates the Analogue outputs.
I Anout 1
The ftrst row indicates the analogue inputs.
2 AnOut 2
1 AnIn 1
Reading downwards from the first row to the second row the
2 Anln 2 status of the belonging outpur is shown in o/o:
Reading downwards from the first row to the second row the
o/o: - 1O0o/oAnOut I has a negative 1 00o/o outPut value
status of the belonging input is shown in
65o/oAnOut2 has a 55o/o outPut value
- 100o/o AnIn t has a negative 1 00o/o input value
The example in Fig. l2O indicates that both the Analogue
65o/a Anln2 has a 650/o inPut value outputs are active.
So the example in Fig. 122 indicates that both the Analogue
inputs are active. NOTE: The shown percentages are absolute values
based on the full range/scale of the in- our output; so
NOTE: The shown percentages are absolute values related to either O-10 V or O-2O mA.
based on the full range/scale of the in- our output; so
related to either O-10 V or O-20 mA.
No o
Yes I
Communication i nformation
Emotron AB OL-4428-01r3
Functional Description
Mains time 1732) Reset Energy [7331]
Resets the enerry counter. The stored information will be
Displays the total time that the Ac drive has been connected will start.
erased and a new registration period
to the mains supply. This timer cannot be reset.
Defa u lt: No
Unit: I n, mm:ss (hours: minutes: seconds)
Selection: No, Yes
Range: 00: 00: 00- 262L43: 59: 59
Modbus format Ulnt, L=Lh/m/s NOTE: After reset the setting automaticatly goes back to
,,Nort.
Energy t7331
Displays the total energy consumption since the last energy
reset 173311 took Place'
733 Energy
Stp kllh
Unit: I Wn (shows Wh, kwh, MWh or GWh)
Ra nge: 0.0-999999GWh
Communication information
Modbus format El nt
Emotron AB OL-4428-01r3
Functional Description
11.8 View Trip Log ISOOI Trip message [811]-t81Nl
Main menu with paramerers for viewing all the logged trip The information from the status menus are copied to the
data. In total the AC drive saves the last 1 0 trips i" it . trip trip message log when a trip occurs.
memory. The trip memory refreshes on the FIFo principie
(First In, First out). Every trip in the memory is logg.d
t, Trip menu Copied from Description
the time of the Run Time tTlt] counter. At every trip, th.
actual values of several parameter are srored and available for 811 7lL Process Value
troubleshooting.
8L2 7!2 Speed
813 772 Torque
11.8.1 Trip Message log tg1.0l
8r4 7!4 Shaft Power
Display the cause of the trip and what time that it occurred.
\[hen a trip occurs the status menus are copied to the trip 815 7L5 Electrical Power
message log. There are nine trip message logs
\ilZhen the tenth
tgl0l-tg90l. 816 776 Cu rrent
trip occurs the oldest trip *itt disappear.
8L7 7L7 Output voltage
818
8x0 Trip message 71.8 Frequency
For fieldbus integer value of trip message, see message table 81c 726 Analogue input status 3-4
for warnings, l7ZZ1. 81H 727 Analogue output status 1-2
81r 728 l/O status option boa rd L
NOTE: Bits o-5 used for trip message value. Bits 6-1s
for internal use. 81,l 729 l/O status option boa rd 2
81K 72A l/O status option board 3
Communication information
811 731t Run Time
Depends on parameter,
Modbus format see respective parame-
ter.
Emotron AB OL-4428-01r3
Functional Description
Example: L1.8.3 Reset TriP Log [8AO]
Fig. 121 shows the third trip memory menu [830]: Over Resets the content of the 10 trip memories'
temperature trip occurred after 1396 hours and 1 3 minutes
in Run time. EAO Reset TriP
Stp No
830 Over temP
Stp 1396h:13 Defa u lt: No
No 0
A11 nine alarm lists contain the same ryPe of data' For
example DeviceNet parameter 31 l0l in alarm list 1
.o.rrrirs the same data information as 31 1 51 in alarm list 2'
It is possible ro read all parameters in alarm lists 2-9 l>y
,..rl.,rlating the DeviceNet instance number into a Profibus
slot/index number. This is done in the following way:
slot rlo : abs((dev instance no-l)1255)
index rro = (dev instance no-1) modulo 255
dev instance no = slot nox255+index no+1
'We
Example: want to read out the process value out from
alarm list 9. In alarm list I process value has the DeviceNet
instance numb er 31102. In alarm list 9 it has DeviceNet
instance no 31502 (see table 2 above). The corresponding
slot/index no is then:
slot rro = abs((3$A2-l)1255)-123
index no (modulo)= the remainder of the division above =
Emotron AB OL-4428-01r3
Fu nctional DescriPtion
11.9 System Data tgOOI Table 2B Information for Modbus and profibus ruumber,
Main menu for viewing all the AC drive sysrem data. sofiutare uersion
Bit Description
LL.9.1 VSD Data tg2OI 7-O mtnor
13-8 major
VSD Type 19271
release
Shows the AC drive rype according ro the type number. OO: V, release version
The options are indicated on the L5-1,4 01: P, pre-release version
rype plate of the AC drive. 1O: B, Beta version
7t: a, Alpha version
NOTE: lf the control board is not configured, then type
type shown is FDU4O-XXX.
Table 29 Information for Modbus and profibus numben
option uersion
Communication information
Software 19221
Shows the software version number of the AC drive.
922 Software
Stp V 4.30
Fig. 126 Example of sofiware uersion
Emotron AB OL-4428-O1r3
Functional Description L67
Unit name t9231
Option to enter a name of the unit for service use or
cusromer identity. The function enables the user to define a
name with max 12 characters. Use the Prev and Next key to
move the cursor ro the required position. Then use the +
and - keys to scroll in the character list. confirm the charac-
ter by moving the cursor to the next position by pressing the
Next k"y. See section User-defined [Jnit 1323].
Example
Create user name I.JSER 15.
3. Press Next.
3 Unit Name
Stp
Default I Itlo characters shown
Emotron AB OL-4428-01r3
Fu nctiona I Descri Ption
L2. Troubleshooting, Diagnoses and Maintenance
' The Ti'ip relay or ourput is active (if selected). Trip/Otf /Warn
LC Level Normal/Soft LCL
o The "TRP" srarus indication is displayed (area D of the Via Digln
display). Desat ### * On Normal
Apart from the TRIP indicarors there are rwo more DClink error On Normal
indicators ro show that the inverrer is in an "abnormal" Power Fault
situation. PF #### x
On Normal
The \Tarning relay or ourput is active (if selected). Safe stop Warning SST
Emotron AB 07-4428-0113
Troubleshooting, Diagnoses and Maintenance
L2.2 Trip conditiolls, causes and L2.2.1 Tech nically qual ified personnel
Installation, commissioning, demounting, making measure-
remedial action menrs, erc., of or at the AC drive may only be carried out by
The table later on in this section must be seen as a basic aid personnel technically qualified for the task.
to find the cause of a sysrem failure and to how to solve any
problems that arise. An Ac drive is mostly just a small part
of a complete Ac drive sysrem. sometimes it is
Lz.2.20pening the AC drive
difficul, io determine the cause of the failure, although the
AC drive gives a certain trip message it is not always easy to WARNING!
find th. tight cause of the failure. Good knowledg. of the Always switch the mains voltage off if lt is
complete drive system is therefore necessary to open the AC drive and walt at
least 7 mlnutes to allow the capacitors to
necessary. Contact your supplier if you have any questions'
discharge.
The AC drive is designed in such a way that it tries to avoid
trips by limiting torque, overvolt etc.
WARNING!
Failures occurring during commissioning or shortly after ln case of malfunctioning always check the
commissioning are most likely to be caused by incorrect DC-link voltage, or wait one hour after the
settings or even bad connections. mains voltage has been switched off, before
dismantling the AC drlve for repair.
Failures or problems occurring after a reasonable period of
failure-free operation can be caused by changes in the system
or in its environment (e.g. wear). The connections for the control signals and the switches are
isolated from the mains voltage. Always take adequate
Failures that occur regularly for no obvious reasons are
precautions before opening the AC drive.
generally caused by Electro Magnetic Interference. Be sure
ihm the installation fulfils the demands for installation
stipulated in the EMC directives. See chapter 8' page 51' L2.2.3 Precautions to take with a
Sometimes the so-called "Tlial and error" method is a connected motor
quicker way to determine the cause of the failure. This can
If work must be carried out on a connected motor or on the
b. dor,e at any level, from changing settings and functions to
driven machine, the mains voltage must always first be
disconnecting single control cables or replacing entire drives. 'Wait at least 7 minutes
disconnected from the AC drive.
The Tlip Log can be useful for determining whether certain before continuirg.
trips occur at certain moments. The Tlip Log also records
the time of the trip in relation to the run time counter.
L2.2.4Autoreset TriP
WARNING!
If the maximum number of Thips during Autoreset has been
lf it is necessary to open the AC drive or any reached, the trip message hour counter is marked with an
..Art.
part of the system (motor cable housing'
conduits, electlical panels, cabinets, etc') to
inspect or take measure-ments as suggested in this
lnstructlon manual, it is absolutely necessary to read
830 O\TERVOLT G
and follow the safety instructions in the manual. Trp A 345:45:L2
Fig. 127 Autoreset triP
Emotron AB OI-4428-01r3
L70 Troubleshootin& Diagnoses and Maintenance
Table 3l Ti'ip condition, their possible causes and remedial action
Max alarm level (overload) has been - Check the load condition of the machine
Mon MaxAlarm - Check the monitor setting in section L!.6, page
reached.
!41,.
Min alarm level (underload) has been - Check the load condition of the machine
Mon MinAlarm - Check the monitor setting in section !!.6, page
reached.
!47.
Emotron AB 07-4428-0113
Troubleshooting Diagnoses and Maintenance
Tdble 31 Trip condition, their possible cduses and remedial action
Remedy Slze* *
Trip condition Possible Cause
No master pump can be selected due to Check cables and wiring for Pump feedback
error in feedback si$nalling. signals
Pump check settings with regard to the pump feedback
NOTE: Only used ln PumP Control. digital inputs
Motor current exceeds the peak AC drive Check the acceleration time settings and
cu rrent: make them longer if necessary.
- Too short acceleration time. Check the motor load.
- Too high motor load Check on bad motor cable connections
Over curr F - Excessive load change Check on bad earth cable connection
- Soft short-circuit between phases or Check on water or moisture in the motor housing
phase to earth and cable connections.
- Poor or loose motor cable connections Lower the level of lxR Compensation [352]
- Too high lxR ComPensation level
Over volt Too high DC Link voltage: check the deceleration time settings and make
D(eceleration) - Too short deceleration time with them longer if necessary.
respect to moto r/machine inertia. Check the dimensions of the brake resistor and
Over volt - Too small brake resistor malfunctioning the functionality of the Brake chopper (if used)
G(eneration) Brake chopper
OPTION lf an Option sPecific triP occurs Check the description of the specific option
Emotron AB OL-4428-01r3
L72 Troubleshooting, Diagnoses and Maintenance
Tdble 31 Trip condition, their possible causes and remedial acilon
Desat BCC *
Power Fault
One ofthe 10 PF (power Fault) trips below Check the PF errors and try to determine the
has occured, but could not be determined. cause. The trip history can be helpful.
PF Fan Err * Error in fan module check for clogged air inlet filters in panel door and
blocking material in fan module. E&Up
PF HCB Err* Error in controlled rectifier module (HCB) Check mains supply voltage D&Up
Error in current balancing: Check motor.
PF Curr Err * - benveen differenr modules. Check fuses and line connections
- ber'ween rwo phases within one module. Check the individual moror currenr leads with an G& Up
clamp on amp merer.
Error in voltage balancing, overvoltage
PF Overyolt * detected in one of the power modules Check motor.
Check fuses and line connections. G& Up
(PEBB)
PF DC Err * DC-link error and mains supply fault Check mains supply voltage
Check fuses and line connections. D&Up
*
= 2...6 Module number if parallel power units (size 300-1500 A)
** If no size is mentioned in this column, the information
= is valid for all sizes.
Emotron AB OL-4428-01r3
Troubleshooting Diagnoses and Maintenance 1.73
L2.3 Maintenance
The AC drive is designed not to require any servicing or
maintenance. There are however some things which must be
checked regularly.
If AC drives are built into cabinets, also check and clean the
dust filters of the cabinets regularly.
Check external wiring, connections and control signals.
Tighten terminal screws if necessary. For more information
on maintenance, please contact your EMOTRON service
Partner.
Emotron AB OL-4428-01r3
L74 Troubteshooting, Diagnoses and Maintenance
13. Options
The standard options available are described here briefly. L3.2 Handheld
Some of the options have their own instruction or
installation manual. For more information please contact Gontrol Panel 2.O
your supplier. See also Emotron VF)UFDU 2.0 Product
catalogue for more info.
Paft number Description
panel
@@@ memory to copy all data (such as parameter set data and
motor data) from one AC drive to the HCP and then load
@ortootor@)ot
13.3 EmoSoftcom
EmoSoftCom is an optional software that runs on a personal
computer. It can also be used to load parameter settings
from the AC drive to the PC for backup and printing.
Fig 128 Control panel in mounting cassette
Recording can be made in oscilloscope mode. Please contact
Emotron sales for further information.
All AC drivesizes can be fitted with an optional built-in Rmin [ohm] if supply Rmin [ohm] lf supply
Type
brake chopper. The brake resistor must be mounted outside 380-415 VAc 440-480 VAc
the AC drive. The choice of the resistor depends on the
application switch-on duration and dury-cycle. This option FDU48-OO3 43 50
can not be after mounted. -o04 43 50
-006 43 50
WARNING!
The table gives the mlnlmum values of the -008 43 50
brake resistors. Do not use resistors lower -010 43 50
than this value. The AC drive can trip or even
be damaged due to high braking currents. -013 43 50
-018 43 50
The following formula can be used to define the power of -o26 26 30
the connected brake resistor:
-031 26 30
(Brake level Vod2 -037 T7 20
Pr.rirto, xED
R-i, -046 T7 20
'Where: -061 10 T2
-o74 10 L2
P...ir,o, required power of brake
resistor -090 3.8 4.4
Brake level VncDC brake voltage level (see Thble 32) -109 3.8 4.4
Rmin minimum allowable brake resistor -746 3.8 4.4
(see Thble 33,Table 34 and Thble 35 -L75 3.8 4.4
ED effective braking period. Defined as:
-2LO 2.7 3.1
ED = tbt
-250 2.7 3.1
120 [s]
-300 2x3.8 2x4.4
tb, Active braking time at nominal braking -375 2x3.8 2x4.4
power during a 2 minute operation
cycle.
-430 2x2.7 2 x3.t
Maximum value of ED - 1, meaning continuous braking.
-500 2x2.7 2x3.!
-600 3x2.7 3x3.1
Table 32
-650 3x2.7 3x3.1
Supply voltage (Vnc) -750 3x2.7 3x3.1
Brake level (Voc)
(set in menu [218J
-860 4x2.7 4x3.7
220-240 380
-1000 4x2.7 4x3.L
380-415 660
-!200 6x2.7 6x3.1
440-480 780
-1500 6x2.7 6x3.1
500- 525 860
550-600 1000
660-690 1150
01-3876-04 R5232/485
01-3876-05 Profibus DP
o1-3876-06 DeviceNet
For communication with the AC drive there are several Fig. 129 Connection of standby suppb opilon on size B,C and
option boards for communication. There are different E-F
options for Fieldbus communication and one serial commu-
nication option with RS232 or RS485 interface which has
x1
galvanic isolation. Name Function Specification
terminal
External, AC drive
13.9 Standby supply board T Ext. supply 1
main power inde-
24VDc !LO%
pendent, supply
option voltage for control
Double iso-
2 Ext. supply 2 lated
and communica-
Part number Description tion circuits
External, AC drive
A- OV
main power depend-
24 V Dc !!Oo/o
ent, supply voltage for
Double isolated
B+ +24Y control and communi-
cation circuits
and 2.
3. Power conductor stage (checking status and feedback of
driver circuits and IGBT's).
o Give a STOP signal to the AC drive, according to the set
Run/Stop Control in menu 12151.
To enable the AC drive to operate and run the motor, the
following signals should be active:
o Give a new Run command, according to the set Run/
Stop Control in menu [215].
. "lnhibit" input, terminals 1 (DC+) and 2 (DC-) on the
Safe Stop option board should be made active by con-
NOTE: The method of generating a STOP command ls
necting 24YDC to secure the supply voltage for the
dependent on the selections made in Start Signal Level/
driver circuits of the power conductors via safery relay
Edge t21AI and the use of a separate Stop input via
Kl . See also Fig. 133. digital input.
o High signal on the digital input, e.g. terminal 10 in Fig.
133, which is set to "Enable". For setting the digital
input please refer to section 1 1.5.2, page 131 .
These two signals need to be combined and used to enable WARNING!
the output o[ the AC drive and make it possible to activate a The safe stop function can never be used for
Safe Stop condition. electrical maintenance. Fot elec'trical
maintenance the AC drive should always be
dlsconnected from the supply voltage.
NOTE: The "Safe Stop" condition according to EN-IEC
62061:2OO5 SIL 2 & EN-ISO 13849-t2OO6, can only be
realized by de-actlvatlng both the "lnhibit" and "Enable"
inputs.
x1
Name Function Specificatlon
pin
NO contact
3
relay K2 Feed back; confi rmation 48V Do/
P contact of activated inhibit 30 vAo/2 A
4
relay l\2
4 Voc
W
Digour
Fig. 133
FDU48-026 31 LL 26 7.5 27
FDU48-031 37 15 5I 11 25
C
FDU48-037 44 18.5 37 15 29.6
FDU48-046 55 22 46 18.5 37
FDU48-061 73 30 61 22 49
D
FDUAB.O74 89 37 74 30 59
FDU48-090 108 45 90 37 72
..'900,
400 750 355 600
FDU48-860 LO32 450 860 400 688
)
500 1000 450 800
FDU48-L2OO 1,440 630 L200 500 960
K
1800 ,, 8O0 1500 630 1200
FDU48-026 31 15 26 10 21
FDU48{31 37 20 31 15 25
C
FDU48-037 44 25 37 20 29.6
FDU48-046 30 46 25 37
FDU4B-061. 73 40 61 30 49
D
FDU48.O74 8g 50 74 40 59
FDU48-090 108 60 90 50 72
FDU:52-003, ,1,1 ,
2.5 1'1 '2.fr,
FDU52-026 31 15 26 LL 27
FDU52s3t . 18.5 :
31 15 25
C
FDU52-O37 44 22 37 18.s 29.6
rDU52-046 30 46 22 37
FDU52-061_ 73 37 61 30 49
D
89 45 v4 37 59
FDU69-090 108 55 90 45 72
FDU69-109
,: :,
i 131 75 109 55 87
F69
FDU69-L46 175 90 ]'46 75 7r7
110 L75 90 r40
FDU69-2TO 252 L32 270 110 168
J69
FDU69-650 780 650 650 550 520
FDU69-750 900 ,
750 750 600 600,,
FDU69-090 90 90 75
General
Digital:
Output voltage: High: >2o vDc @50 mA, >23 VDC open
Low: <1VDC @5O mA
Shortcircu it cu rrent(oo): 100 mA max (together with +24 VDC)
Relays
lP20 tP54
Model
Max temp. Derating: possible Max temp. Derating: possible
Models
Frame Dim.HxWxD[mm] Dim.HxWxD[mm] weight IP2o weight IP54
size tP20 IP54 tksl tksl
Bi 350(416)x2O3 x 2OO L2,.5
026 to 046 C 440(572)xL7Bx292 24
D.. 545(590) x 22O x 295 32
90 to 109 E 950x285x314 56
146 to,t7s E. 950 x,285 x 314 60
zLO to 250 F 950 x 345 x3L4 74
u tO36,x,,50O X 390 225;Qx60Ox6o0 L40 350
430 to 5OO H 1036x500x450 2250 x 600 x 600 L70 380
1036x730x450 225Ox 900 x 600 506
860 to 1-OOO J 1036x1L00x450 2250 x 1200 x 600 340 697
( 1036x1560x450 2250 x 1BO0,x 6OO 496 987
Models
Frame Dim.HxWxD[mm] Dim.HxWxD[mm] Weight lP2O Welght lP54
size tP20 tP54 tkel tksl
90:.tO..175 ,, F6g: 1090x345x314 77
27O to 375 H69 1,L76 x 500 x 450 2250 x 600 x 6O0 L76 399
[69 ]
Contamination, No electrically conductive dust allowed. Cooling air must be clean and free from corro-
according to IEC 6072I-3-3 sive materials. Chemical gases, class 3C2. Solid particles, class 3S2.
Table 4S Storage
L4.T.LAccording I EC ratings NOTE: The dimensions of the power terminals used in the
[Jse mains fuses of the rype gllgG conforming to IEC 269 models 3OO to 15OO can differ depending on customer
or installation cut-outs with similar characteristics. Check specification.
the equipment first before installing the glands.
Max. Fuse = IrrXimum fuse value that still protects the AC
drive and upholds warranty.
,i ,,..
, ,:
t t
'
M32 (L2-2O)/
:FDU**-008 6.9 0.5*to M32 opening
FDU* *-010,, 8,7 M25+reducer : : .: aa:
:.1 :
, FDU48: (3x)35-240
648 frame
FDU69: (6x)35-15O
FDU**1200
FDU4'8: (6x)35,-2.4Q frante
FDU**,1500 1500 :
6 AJT6
FDU48-006 6 AJT6
.10 AJTlO
15,6, .
'24 AJT2O
FDU4B_026 22 25 tuT25
.FDU'4&031 ,26 , 30
'I r'.1 : : : '
FDU48-037 31 35 AJT35
FDU48'046 45 ,
AJT45,
FDU48-061 52 60 AJT60
, 80' AJT8O.
110 AJTlX.O
L75 AJT175 :
250 Al1250
FDU48-250 216 250 AJT250
520,
FDU48-650 562 600 AJT600
648 ,:
, A4BQ70O
864 1000
FDU48-L2OO 1037 L200 A4BQ !2OO
A4BQ15oO
FDU48-004
FDU4g-006
FDU48-013 ,
FDU48-018
FDU48'0,19
FDU4S.O6I AWG 12-AWG 4 L,,6/1.2 AVVG 12-AWG 4 t.6/L.2 AWG 12-AWG 4 L.6IL?
FDU4S-A74 AWG IO.AWG O 2|B/3,O AWG IO.AWG O 2.8/3,O AWG IO-AWG O 2.8/3.O
'
'::
FDU48-300 2xAWG 4/O- 2xAWG3/O- Copper (Cu)
24/78 24/L8 frame TRon
,v \,,
FDU48-375 2 x 300 kcmil 2 x 4OO kcmil
l
aa a :
FDU48-600
3xAWG 4/O- 2xAWG3/O-
FDU48-650
3 x 300 kcmil
24/rB 2 x 4OO kcmil
24/78 f rame
FDU48-750
1 +10 v +:tO VDC Supply voltage +1O VDC, max 1O rnA output
:tl
biRolar: -10 r +10 VDC,or *20 -
Terminal X2
31.,, ]N/C 1 ,
B3
aa'
N/O is closed when the relay is active
:a
4t N/C 2
Relay 2 Output
potential free change over
Run, active when the relay output
0.1 - 2 A/Umax 250 VAC or 42 VDC
AC drive is started
43 N/O 2
Terminal X3
250 Autoreset
251, No of Trips o
DEFAULT CUSTOM 252 Overtemp off
1-OO Preferred View 253 Overvolt D off
110 1st Line Process Val 254 Overvolt G off
t20 2nd Line Current 255 Overvolt off
200 Main Setup 256 Motor Lost off
2LO Operation 257 Locked Rotor off
2tL Language English 258 Power Fault off
2L2 Select Motor M1 259 Undervoltage off
273 Drive Mode V/Hz 254 Motor lzt off
2L4 Ref Control Remote 258 Motor l2t TI Trip
5L97 An n3 ValMax o
5198 An n3 Oper Add+
519A An n3 Enabl On
51A An n4 Fc off
51B An n4 Setup 4-2OmA
51C An n4 Advan
880
881 Process Value
882 Speed
818 Torque
886 Current
887 Output voltage
888 Frequency
888 PT100_1,2,3
88C AC drive Status
881 lO Status 81
88J lO Status 82
88K lO Status 83
890
891 Process Value
892 Speed
893 Torque
898 PT100_1,2,3
E
ECp ...........a ,......o.... .....175 J
Edge control ...... .......39,68
Electrical specification Jog Frequency 105
..187
EMC ............ ............ ......16
Currenr conrrol Q-20mA) ..28
Double-ended connection ...... ...27
RFI mains filter .......16
Single-ended connection ...... .....27
Twisted cables ... ......28
Emergency srop ..5 1
F
Factory settings ...... .......,............78
Fail safe ...... ..44
Emotron AB 07-4428-0113
205
L
LCD display .--...53
Level control 39, 68
Load default ....-..78
Load monitor .... .....4A, 1 18
Local/Remote ....67
Lock code ....67
Long motor cables ... 18
Low Voltage Directive ...... ...--7
Lower Band ............ ...........114
Lower Band Limit .. 1 15
Emotron AB OL-4428-01r3
(7zq "rc2
(727) ...... ..162
(728-72A) ...... ...... 163
(7to) .. 163
(7tr) ... .-... 163
(7311).................. ...... 163
(7121 ...... .. 164
(733) ...... ...... ...... ..164
(7331) ...... ...... 164
(Boo) .. t65
(810) .. 165
(811-81N) ...... t65
(820) .. 166
(830) .. 166
(8A0) . t66
(eool .. t67
(ezo1 -. 167
(9221 ...... ..167
33F .......... 101
616 .... t47
Minimum Frequency ....97
Monitor function
Alarm Select ... 122
Delay time ..... 1 19
Max Alarm ..... I 18
Overload ..40, I 18
delay
Response ...l2O, 122
Start delay I 19
Motorcables ...... 16
Motor cos phi (power factor) ...... .....70
Motor dara ..69
Motor frequenry .....70
Motor I2t Currenr . l7l
Motor identification run .....71
Motor Lost .. 8l
Motor lost ...... .124
Motor Potentiometer ...... 107, l3l
Motor potentiomerer ... I 3 1
Motor ventilation ....71
Motors ...... ....5
Motors inparallel ....21
MotPot ................ ..........96
Multi-motor application ......65
N
Nominal motor frequency . 103
Number of drives ...... .. ll2
o
Operation . ...64
Options ... ..28, 175
Brake chopper 17 6
External Control Panel (ECP) 175
I/O Board ....., 177
Output coils ...... ... 178
Protection class IP23 and
rP54 ...175
Serial communicarion,
fieldbus 178
OR operator 151
Emotron AB 07-4428-0113
207
output coils ....178 Running motor
Output Voltage .....159
Overload. ...40,118 S
Overload alarm ..40 Select Drive ll2
Settle Time 1 16
P Setup menu ..56
Parameter sets ......
Menu structure .-.....56
Load default values -.-.-..78 Shaft power 158
Load parameter sets from Signal ground ...195
Panel
Control --.79 Sirrgle-ended connection .-...-27
Parameter Set Selection ......35 Sofrware .....167
Select a Parameter set . ...77 Sound characteristic ....-..72
PID control ..-....45 Speed .........158
PID Controller l0g Spinstart........ .....98
Closed loop PID control ... 109 Standards ... ....6
Trip .......54
R Trip causes and remidial action 170
Reference
Trip Message log ....165
Frequency .123 Trips, warnings and limits --169
RUN .....54 W
Run command . ..54 \Wiring
Run Left command . ""' 131
Run Right command ... 131
Emotron AB OL-4428-01r3
o
cr)
I
sl
o
rl
a
rl
o
N
cr)
rl
o I
00
N
$
Emotron AB, Miirsaregatan 12, SE-250 24 Helsin$bor$, Sweden $
sl
Tel: +46 42LG 99 00, Fax: +46 42LG 99 49 o
m
E-mail: info@emotron.se
wulflw.emotron.com o
o
E
LrJ