You are on page 1of 4

©2022 GE Grid Solution proprietary and confidential information. All Rights Reserved.

This document is the property of GE GRID Solution


and may not be reproduced, transmitted, stored, or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solution.

04
03
02
01
DRAWING NO.
TITLE

Main Circuit
Device list and Cable list
Outline and Arrangement
Cover & Drawing contents
Fan Control Cubicle

Chile SIC SING Project


25 MVAr / 500KV Single Shunt Reactor

SIC SING
3
3
3
3
Rev

Cover sheet
B141 TZ143
Fan Control Cubicle
©2022 GE Grid Solution proprietary and confidential information. All Rights Reserved. This document is the property of GE GRID Solution
and may not be reproduced, transmitted, stored, or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solution.

200

50
40
550

500
590

Label

Front

Bottom of cubicle
1-M8*20
50

9-M4*15
1000 600
300

250
355

40

410
SIC SING

120 140

45*80
1KK

1J
KM1

60*80
45*80
45*80
520

QF1

2J
Q1-Q2

Cover sheet
B141 TZ143

45*80
Fan Control Cubicle
AC Power 380/220V 50Hz
1J 2J
L1 L2 L3 N
1 L1 1KK:2
1 Common
TO NEXT UNIT
2
2
1 3 5
3 L2
QF1 4 3 KM1:13 Stop Fans

AC380V 4 KM1:14 Start Fans


5 L3
5 QF1:11
2 4 6
6 AC Power error
6 QF1:14
7 N
7 KM1:53
8 Fans in
Auto Manual 8 KM1:54 operation
9
10 9 Q1:21
1D1

To Control Room(availiable for SCADA)


Fans error

1D2 10 Q2:21
Terminal box
11 1FM
WTI 12 1D3 11-20
Stop Fans
13 14
13
14 2D1

3P AC 380V Supply

3P AC 380V Output
Start Fan

15 2D2

To Terminal box
2FM
16 2D3
and may not be reproduced, transmitted, stored, or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solution.

To Fan 1#

To Fan 2#
17-20
©2022 GE Grid Solution proprietary and confidential information. All Rights Reserved. This document is the property of GE GRID Solution

A1

A2
1 3 5
Fans in operation
KM1
2 4 6

QF114
2J:5 11
2J:6 Power supply error
1 3 5 1 3 5
KM154
2J:7 53
2J:8 Fans in operation
Q1 Q2
Q1
2J:9 2J:10 Fans error
21 22

21
Q2 22

2 4 6 2 4 6
1D1

2D1
1D2

1D3

2D2

2D3

Diagram for Switch 1KK

1FM 2FM Working Auto Stop Manual


Status
Pos.
0.55KW 2.5A 0.55KW 2.5A Contct No.
1-2

3-4

5-6

7-8 SIC SING Fan Control Cubicle

B141 TZ143

Cover sheet
DEVICE LIST
ITEM DEVICE No.REV. DESCRIPTION TYPE Q'TY MANUFACTORER SHEET No.
1 QF1 CIRCUIT-BREAKER IC65N 3P 25A+OF 1 SCHNEIDER 3
2 Q1-Q2 CIRCUIT-BREAKER 3RV6011-1DA15(2.2-3.2A) 2 SCHNEIDER 3
3 KM1 CONTACTOR LC1-D18M7C +LAD-N20 1 SCHNEIDER 3
4 1KK SHIFT SWITCH LW39-16B-6KC202/2 1 APT 3
5 1J TERMINALS UK10N 8 PHOENIX 3
6 2J TERMINALS UK5N 32 PHOENIX 3

CABLE LIST

No. CABLE No. CABLE TYPE FROM TO


and may not be reproduced, transmitted, stored, or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solution.

1 No.1 4×4(power supply) Fan 1# Fan Control Cubicle (1J 10,11,12)


©2022 GE Grid Solution proprietary and confidential information. All Rights Reserved. This document is the property of GE GRID Solution

2 No.2 4×4 (power supply) Fan 2# Fan Control Cubicle (1J 14,15,16)

3 No.3 8×2.5 (Signal) Terminal Box of Shunt reactor Fan Control Cubicle (2J 1,2,3,4)

4 No.4 8×2.5 (Signal) Control room(SCADA) Fan Control Cubicle (2J 5-10)

5 No.5 4×4 (power supply) Fan Control Cubicle Fan Control Cubicle(next unit)

6 No.6 4×4 (power supply) Control room Fan Control Cubicle(first unit of each bank)

SIC SING Fan Control Cubicle

B141 TZ143

Cover sheet

You might also like