Professional Documents
Culture Documents
PREPARED FOR
BILFINGER LTD
DESIGN SPECIFICATION
DONCASTER,UK
13 APRIL 2023
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
All information in this document and the document itself is subject to copyright © governed
by the law of the UK.
Revision History
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
CONTENTS
CONTENTS 3
SCOPE AND CONDITIONS 4
1 Definitions 4
2 Scope 5
3 Site Conditions and Requirements 6
ELECTRICAL SYSTEM 7
4 Overview 7
5 General Requirements 7
6 Incoming Connection 8
7 Export Connection (To be confirmed) 9
8 Power Distribution 9
9 Electrical Panel 10
10 Field Mounted Electrical Equipment 11
11 Uninterrupted and Backup Power Supplies 11
INSTRUMENTATION & CONTROL 13
12 Use of Instruments 13
13 Instrument Selection and Arrangement 14
14 Cables and Panel Wirings 16
15 Control, Networking and Interface Hardware 17
FUNCTIONAL REQUIREMENTS 18
16 Logic Controller 18
17 Human Machine Interface 18
18 Communications Interface 18
19 Safety Instrumented Systems 19
20 Explosive Atmospheres 19
21 Quality and Functional Testing 20
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
2 Scope
2. An Electrical System for each subsystems will be designed, manufactured
and integrated into their equipments by the Subcontractor that will then be
installed by the Installer at the Site such that:
2.1 Each Subsystem shall include part of the Plant such that there is
an asset shall belong to one Subsystem only. The following list of
each electrical package includes the subsystems which are in Sub
contractor’s scope:
a) Feed reception & Kiln feed;
b) HTP Kiln & Solid product handling;
c) Gas cleaning unit;
d) SACTO;
Other than the above mentioned electrical packages, will not be in
Sub Contractor’s scope of work.
2.2 Electrical System for the Balance of Plant shall be any Plant that
causes the interconnection and interoperability of the Subsystems.
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
ELECTRICAL SYSTEM
4 Overview
4. The Electrical System for the each package as mentioned in the clause 2.1
will include and meet the requirements of this clause:
4.1 General requirements of clause 5 will be applied to any component
or functionality of the electrical system.
4.2 The Electrical System for subsystems will include:
a) Each Electrical Panel to the requirements of clause 9;
b) Field mounted electrical equipment including motors and
control devices to the requirements of clause 10;
c) An uninterruptible power supply (UPS) to the requirements of
clause 11;
d) Instruments to the requirements of clause 12&13;
e) All interconnecting wiring and cabling to the requirements of
clause 14; and
f) Control, networking and interfaces to the requirements of
clause 15.
4.3 The Electrical system for each package as described in the clause
2.1 shall have the functional requirements for safe and smooth
operation including:
a) Logic controller in accordance with clause 16;
b) A Human Machine Interface (HMI) in accordance with clause
17;
c) A Communications interface with the installers equipment in
accordance with clause 18.
d) Safety Instrumented Systems in accordance with clause 19;
e) Provision for electrical equipment in hazardous areas in
accordance with clause 20;
4.4 All components of the electrical system will be subjected to quality
management and testing by the Subcontractor prior to delivery to
the Site in accordance with clause 21.
5 General Requirements
5. Unless specifically stated otherwise, any part of the electrical equipment
shall meet the requirements of this clause.
5.1 With reference to IEC 60364-5-54 and BS 7671, the subsystems
shall be of the TN-C-S type connecting to the Installers system. All
conductive parts of the subsystem equipment shall be
equipotential bonded back to the earthing connection provided by
the Installer.
5.2 Electrical equipment for subsystems shall operate on voltages as
follows:
a) for motors and three phase equipment, 415V AC at 50Hz;
b) for electrical equipment in burner applications, 230V AC at
50Hz;
c) for control circuits including PLC inputs and outputs in
electrical panels, 24V DC;
d) for instruments, control valves & SOVs requiring power,
24VDC; or
e) for instruments using loop power, 0-10V/4-20mA DC.
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
5.3 The electrical wiring system and components for the subsystems
shall be selected and manufactured in accordance or be able to be
installed in compliance with the following standards:
Low-voltage electrical installations (IEC 60364 series)
IEC 60364-1 Fundamental principles, assessment of general
characteristics
IEC 60364-4 Protection for safety
Part 41: Protection against electric shock
Part 42: Protection against thermal effects
Part 43: Protection against overcurrent
Part 44: Protection against voltage disturbances and
electromagnetic disturbances.
IEC 60364-5 Selection and erection of electrical equipment
Part 51: Common rules
Part 52: Wiring systems
Part 53: Isolation, switching and control
Part 54: Earthing arrangements
IEC 60364-6 Verification
IEC 60364-7 Requirements for special installations or locations
Part 714: External lighting
Part 715: Extra-low-voltage lighting installations
Explosive Atmospheres (IEC 60079 series)
IEC 60079-14 Electrical installations design, selection and erection
IEC 60079-17 Electrical installations inspection and maintenance
5.4 The electrical system shall include the protections against lightning
strike required to prevent any harm to personnel or Plant in
accordance with the following standards:
Protection against lightning (IEC 62305 series)
IEC 62305-1 General Principles
IEC 62305-2 Risk Management
IEC 62305-3 Physical damage to structures and life hazard
IEC 62305-4 Electrical and electronic systems within structures
5.5 Tagging for all Electrical Components, Panel, Cables, and
Instruments in the subsystems should be in accordance as
described in Asset Tagging & Naming Specification(T2927-0-40).
6 Incoming Connection
6. The incoming electrical supply connection or ‘Incomer’ from plant to the
every individual Electrical systems as listed in clause 2.1 has the
characteristics of this section.
a) a separate dedicated main incoming supply 415VAC will
have the characteristics described in sub clause 6.4
b) 230VAC Uninterrupted power supply as given by the sub
clause 6.5
c) Export connections to Infrastructure as given by clause 7.
6.1 The Incomer is a low voltage, alternating current, three phase
power supply. The Incomer has a capacity higher than the total
Plant electrical load.
6.2 The Incomer is connected through Infrastructure to the national
grid as owned and operated by the Authority named by the
Purchaser.
6.3 The Infrastructure will include any three phase earthing
transformers and necessary upstream and downstream protection
of the transformer such that the design fault level for the main
distribution board connected to the incomer is less than 10kA for 1
second.
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
6.4 The Plant will operate to design capacity and availability of main
incomer when supplied through the incomer with the following
characteristics:
a) Nominal phase to phase voltage is 415V AC;
b) Voltage is consistently within ± 3% of the rated voltage;
c) Nominal frequency is 50Hz;
d) Frequency is consistently within ±1% of the rated frequency;
e) Harmonic distortion does not exceed the requirements of
IEC 61000-3-2; and
f) Flicker within the requirements of IEC 61000-3-3.
6.5 Electrical system requires a 230VAC uninterrupted power supply
with the characteristics listed below.
a) Nominal phase to phase voltage is 230V AC;
b) The Performance requirements of Uninterrupted power
supply should be in accordance with IEC 62040
c) Voltage is consistently within ± 3% of the rated voltage;
d) Nominal frequency is 50Hz;
e) Frequency is consistently within ±1% of the rated frequency;
8. The incomer will terminate at a main distribution board which will distribute
power to the Plant and subsystems as described in this clause.
8.1 The main distribution board shall be the single point of power
connection where power is to be consumed in the Plant other than
at the Gas Generators(refer Clause 7). This distribution board shall
be located either in or in the vicinity of the control and operations
building.
8.2 Each subsystem shall have not more than one switchboard, an
electrical panel containing circuit breakers, motor starters, variable
Page 9 of 21 Anergy – Transforming Waste
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
9 Electrical Panel
9. The Electrical panel will be designed, manufactured & installed in
accordance with the following characteristics.
9.1 Electrical panels and their associated components shall be
manufactured in accordance with the following standards:
Low voltage switchgear and controlgear assemblies (IEC 61439 series)
IEC 61439-1 General Rules
IEC 61439-2 Power switchgear and controlgear assemblies
IEC 61439-3 Distribution boards intended to be operated by
ordinary persons
IEC 61439-6 Busbar trunking systems (busways)
Panels shall have a minimum segregation of Form 2A. Preferred
equipment nominated will be utilised where possible.
9.2 The electrical panel and the corresponding components mounted
on the panel's surface shall have an IP rating that complies with
clause 10.1.
9.3 Electrical panel specified in the clause 2.1 will have multiple power
connections from the Infrastructure:
d) a separate dedicated main incoming supply connection from
the Infrastructure as given by clause 6.
e) An Uninterrupted power supply from the Infrastructure as
given by the clause 11
f) Export connections to Infrastructure as given by clause 7.
9.4 A single isolation switch (or “main isolator”) shall be provided for
each Electrical panel to isolate the system from the incoming
power supply. The selection of isolators shall be as specified in
clause 8.3.
9.5 The Main isolator in each subsystem will completely disconnect
the circuit from the electrical supply in order to achieve absolute
isolation from the Main distribution board. The Main Isolator shall
be selected and installed shall comply with IEC-60947-3
standards.
9.6 This may include circuit breakers, motor starters, variable speed
drives, relays, Controllers and other components required to
distribute power appropriately to individual loads for that system.
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
9.7 Isolation for any other electrical equipment outside of the main
panel shall be through the main isolator only or as specifically
otherwise described in this document.
9.8 The electrical panels will have capacity for growth of approximately
20%, which includes isolator switches, additional gland spacing
and additional terminal spaces.
9.9 Thermostat and Hygrostat units shall be installed for use of
temperature control for electric surface heating systems inside the
electrical Panels in Non-Hazardous Areas.
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
11.3 Each Gas Generator shall be equipped with a battery system and
starter motor as required by the manufacturer inside of the
respective cubicle.
11.4 During ESD, the SACTO subsystem will continue to operate
effectively with backup power or alternatively if this is unavailable
then in such a manner to safely remove dirty syngas.
11.5 Lighting UPS shall be provided by rechargeable batteries located
within lights nominated as an emergency.
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
12. The Plant uses Instruments to support the Operation as described by this
clause.
12.1 The subsystems will be provided with instrumentation that sensors
a process variable for the purpose of:
a) Controlling the quality or quantity of part of the Process;
b) determining if the Process is within operational limits;
c) providing a safety function to prevent damage to people or
the Plant.
Any Instrument that does not perform a function above but is
required for analytical purposes does not form part of this
Specification. Such instruments if otherwise required to be
installed by the Agreement must be compatible with this
Specification.
12.2 Instruments, embedded within mechanical plant, shall be also
considered to be a part of that mechanical plant for the purpose of
this Specification. Instruments that form part of the burner system
for thermoprocessing equipment are considered to be part of that
mechanical plant.
12.3 Instruments that are also electrical equipment shall be
considered as both an instrument and electrical equipment for the
purposes of this Specification.
If additional accessories including support brackets, manifolds,
tubes, isolation valves or other fittings are required to attach the
sensing device to mechanical plant, structure or piping, this
forms part of the instrument and is also subject to this clause.
12.4 Instruments that provide function of clause 12.1(b) only can be
local indication only (for example gauges) if it is unlikely to
fluctuate, is ambiguous, or is more likely to provide a
troubleshooting role. Local indication on instruments that are
electrical equipment will generally be not provided.
12.5 Instruments that are electrical equipment shall have a minimum
rating in accordance with IEC 60529 (Degrees of protection
provided by enclosures) of:
a) IP54 if not in a wet area or likely to require washdown; or
b) IP65 otherwise.
This excludes any instrumentation required for burner systems
which apply EN 746-2 (Combustion and fuel handling systems).
12.6 Instruments, selected and arranged as given by clause 12 and 13,
shall be able to be removed from service and replaced and where
Instrument inputs can be suspended for short periods in order to
perform maintenance whilst the Process is in operation.
12.7 Connections by instruments to the Process and particularly piping
shall where practicable adhere to the requirements of the concern
piping.
12.8 Instruments where they are to be supported by structure and in
fact connection by instrument tubing to piping will be clustered
together as is possible.
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
i)
Transmitters will be loop powered and have a
4-20mA output. If a pressure transmitter is to be
placed in a hazardous area, the instrument will have
protection in order of preference either IECEx Ex'd'
or IEXEx Ex'i'. The instrument will be positioned
preferably on a nearby structure with tubing going
to measuring points on the HTP Kiln system.
b) For inserted devices including orifice plates, venturi nozzles
and nozzles used to create differential pressure:
i) These instruments will conform to the Standards
listed below. Straight pipe both before and after the
instrument will conform to the manufacturer's
instructions. Head loss from the instrument will be
appropriate to the line and duty.
ii) Measurement of fluid flow by pressure differential
devices (IEC 5167 series)
iii) IEC 5167-1 General principles and requirements
iv) IEC 5167-2 Orifice plates
v) IEC 5167-3 Nozzles and venturi nozzles
vi) IEC 5167-4 Venturi tubes
13.9 However in other cases particularly liquid duties, paddle type,
magnetic flow and other such measurement devices will be used if
appropriate. Straight pipe both before and after the instrument will
conform to manufacturers instructions. Head loss from the
instrument will be appropriate to the line and duty.
13.10 Transmitters will be loop powered and have a 4-20mA output. If a
pressure transmitter is to be placed in a hazardous area, the
instrument will have in order of preference either IECEx Ex’d’ or
IEXEx Ex’i’.
13.11 Control Valves and actuators will be selected appropriate to the
duty in the Process required including consideration for the
accuracy and precision. Valves will otherwise be in accordance
with their fluid code requirements as per following clauses:
a) Metallic Industrial Piping (EN 13480 series)
b) Pressure piping (ASME B31 Series)
c) Plastics piping systems for gaseous fuels-Polyethylene (EN
1555 series)
13.12 In order of preference and with consideration for requirements,
actuators can be solenoids, pneumatic quarter turn, pneumatic
linear, rotating motorised actuators or linear motorised actuators.
13.13 On/off type actuators will use control voltages as given by clause
5.2. Auxiliary power will be avoided if possible. Modulating
actuators will use a 4-20mA signal and whilst it is preferred the
actuator is loop powered, if the power consumption is excessive it
will be self-powered.
13.14 The use of pneumatic actuators particularly will be preferred to
avoid having any electrical components placed inside hazardous
areas. If this is unavoidable, the preference will be to have
protection in order of preference either IECEx Ex‘d’ or IEXEx Ex‘i’.
13.15 Level transmitters including ultrasonic, radar, optical, conductivity
or magnetic proximity can be used in various duties within the
subsystems other than level or position transmitters and switches
given in sub clause 13.6. Nucleonic devices will be avoided. In
each case, the installation will satisfy the manufacturer's
instructions.
13.16 Transmitters will be loop powered and have a 4-20mA output. If
the transmitter or switch is to be placed in a hazardous area, the
Page 15 of 21 Anergy – Transforming Waste
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
14. The following details the type of cables & handling of cables.
14.1 Cable Specifications
a) All cables shall comply with UK, BS standards along with the
following unless otherwise noted:
i) IEC 60502-1 (1kv power cables);cable specifications
ii) IEC 60228 (conductor size and rating);
iii) IEC 61158
iv) EN 50575 (fire rating);
v) EN 50288 (instrumentation and communications
cables);
vi) EN 60445 (colours for conductors).
b) All multicore cables shall be provided with an integral
insulated earth conductor. minimum core size shall be 2.5
mm².
XVB OR
LV Power 0.6/1.0kV, XLPE/ STA/SWA - 2.5mm2
Equivalent
(excl. VSD cables) V75 PVC
Hazardous areas
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
Data/ CAT6 - - - - -
Comm. (RJ45
terminated)
14.2 Cables & wiring for the electrical panel shall be provided in
accordance with the standard wiring sizes & specifications as
described below.
a) All control wiring shall be a minimum of seven strands of
copper with a cross section not less than 1.5 mm2.
b) Power Wiring for the loads like Motors, Packages, Utilities
shall be minimum of 2.5mm2. Selection of wiring size shall
be in calculation with load, voltage drop and accordance
with selection criteria of IEC and BS (British Standards)
c) All current transformer wiring shall be a minimum of seven
strands of copper with a cross section not less than 2.5
mm2.
d) Wiring used for the connection of signals to Programmable
Logic Controller (PLC) Input/Output (I/O) modules shall be
1.0 mm2
e) All wiring shall be terminated to components or terminal
strips, no joints shall be permitted in the wiring.
14.3 Any wiring shall be installed in accordance with the requirements of
the referred standards in clause 14. The Insulation shall be PVC
type, minimum V90, 0.6/1kV grade. Cable insulation colours shall
be as follows: (client to confirm)
415VAC 3 phase Brown,Black,Grey, Blue(neutral)
Earth Green/Yellow
230VAC Power Red-Line, Blue -neutral
230VAC Control Red-Line, Blue -neutral
24VDC Control Orange positive, Purple negative
Analog circuits Pink
Volt-free White
14.4 Standards and selection of cables shall be as described in this
Section Cables and Panel Wirings in this document.
15. Hardware for the control (logic controller), networking and interface shall
meet the following requirements:
15.1 Programmable Logic Controller(PLC) which will contain logic for the
purpose of accepting any supervisory commands and to safely
operate only electrical equipment within the scope of the
subsystem switchboard that the PLC is housed in.
15.2 PLCs having the characteristics as described in clause 16;
15.3 Human Machine Interface shall be installed on the front door of
electrical panel whereif necessary, which allows the operator to
control and monitor the corresponding subsystems as described
in the clause 17;
15.4 PLCs shall be capable of communicating to the plant network as
specified in the communication interface clause 18.
15.5 On each electrical panel, an alarm with a simulated sound and light
shall be provided to draw the Operator's attention. Basic controls
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
FUNCTIONAL REQUIREMENTS
16 Logic Controller
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
19. The subsystem control system will include safety instrumented systems,
that is systems that perform critical functions for safe operation, as given by
this clause.
19.1 Any safety instrumented system that is identified either in this
Specification or through the implementation of the Plant
subsystems unless otherwise noted will be in accordance with the
following Standards:
Safety instrumented systems for the process industry sector
(IEC 61511)
IEC 61511-1 Framework
IEC 61511-2 Guidelines for application of IEC 61511-1
IEC 61511-3 Determination of the required safety integrity
levels
19.2 Burner systems in the subsystems will comply with the following
standards.
Industrial Thermoprocessing Equipment (EN 746 series)
EN 746-1 Common safety requirements
EN 746-2 Combustion and fuel handling systems
EN 746-3 Generation and use of atmosphere gases
19.3 Emergency Stop on the subsystems Control panel will be
connected in the fail-safe loop and will be classified as a safety
instrumented system.
19.4 The emergency bypass valve between the Kiln Subsystem and the
SACTO subsystem will be classified as a safety instrumented
system.
19.5 Burner Flame Management has been designed, built in and in
compliance with IEC 61511 standards and applying the known
technical rules of safety and envisaging all the potential danger
situations.
20 Explosive Atmospheres
20. The syngas generated by the Process is flammable and feed and product
char are each both combustible. As such, risks arise from fire and explosion
which are mitigated by the Plant in accordance with this clause.
20.1 The Plant will be analysed for any hazardous areas (or areas with a
NT Comment; potentially explosive atmosphere) in accordance with the following
This needs to be Standards.
done as Area Explosive Atmospheres (IEC 60079 series)
Classifiction IEC 60079-10.1 Classification of areas - Explosive gas atmospheres
Drawings not IEC 60079-10.2 Classification of areas - Explosive dust atmospheres
received and 20.2 In areas designated hazardous, mechanical plant and electrical
datasheets do not equipment shall be selected with appropriate protection to mitigate
reference risks as put forwards by the following Standards:
requirements
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control
Electrical Design Basis, Design Specification T2927-0-44 Rev C
ed, Date: 2023-04-13 09:36:13+01:00, By: Devayani, Reviewed by: Nithyapriya Madhanagopal, Approved by: Leelakrishnan Mohanraj, Download on: 2023-04-27 12:29:07+0100, Download by: Bilfinger UK Document Control