Contractor Job Code 0-8494-20-0000

Contract No. 5360/B/2020

Project Doc. No. SD-000-13821-0001


Basrah Refinery Upgrading Project Document Class X

DATA SHEET FOR MV ELECTRIC


MOTORS

Rev. Date Description Prepared by Checked by Approved by


00 28-Apr-21 IFR N. Oka T. Tsurumachi K. Jingushi

M S
J-06D
-M a y - 2021
PRINT
ED 1/4
WHEN
LLED
NCONTRO
Project Doc. No.
DATA SHEET FOR MV ELECTRIC
Basrah Refinery MOTORS SD-000-13821-0001
Upgrading Project

REVISION HISTORY
Rev. Section Page Description

M S
J-06D
-M a y - 2021
PRINT
ED 2/4
WHEN
LLED
NCONTRO
Project Doc. No.
DATA SHEET FOR MV ELECTRIC
Basrah Refinery MOTORS SD-000-13821-0001
Upgrading Project

HOLD List
No. Section Page Description

M S
J-06D
-M a y - 2021
PRINT
ED 3/4
WHEN
LLED
NCONTRO
DATA SHEET FOR
MV ELECTRIC MOTORS
Project Doc. No.:
SD-000-13821-0001

ITEM NO.
Q'TY
DATA SHEET
P.O.NO.
FOR
REV. 00 01 02 03
MV ELECTRIC DATE
MOTORS PRP'D
APR'D
REQUIREMENTS AND CONDITIONS DRIVEN MACHINE DATA
1 Service Outdoor / Indoor 41 Type Pump / Comp. / Blower / Fan / Mixer/Others

2 Area Classification Zone 2 Group IIB 42 Centrif. / Recipro. / Rotary

3 Ambient Temperature 55°C Max. 43 Manufacturer


4 Design Temperature (humidity) 45°C Max. (95% at 45°C) 44 Counter Torque
5 Altitude Less than 1,000m 45 B.H.P. kW

6 Rated Voltage 6.6 V 3 ph 50 Hz 46 Moment of Inertia (WR2) kg-m


2

7 Cooling Method IC511 (IEC 60034-6) 47 Req’d End Play DE mm NDE mm


IP55
8 Degree of Protection (as minimum)
(IEC 60034-5) 48 Thrust UP kg Down kg
Type of Protection Ex db / Ex eb
9 for Hazardous Areas (Note 1)
(IEC 60079-14) 49 Coupling Method Direct / Belt / Gear

10 Temperature Class for hazardous area use T3 (IEC 60079-0) 50 Half Couplng Supplied by Manufacturer
At Motor Side
11 Duty Type S1 (IEC 60034-1) 51 Fitted by Manufacturer

12 Required Output * kW MOTOR MANUFACTURER'S DATA


13 Service Factor 61 Motor Manufacturer
14 Thermal Class / Temperature Rise F/B (IEC 60085) 62 Manufacturer Order No.

15 No. of Poles 63 Serial No.


16 Type of Mounting Horizontal / Vertical 64 Motor Dwg. No.
Direction of Rotation Construction for
17 (Viewed from coupling side)
CW / CCW Hazardous Areas
65 Standard
18 Starting Method DOL / VSD / SST Performance Dimensions

19 L/R current Is/In < 650%** 66 Type and/ or Frame Size


Main Terminal Box
20 Thread Size * NPT inch 67 Stator Winding Connection Star / Delta
Main Terminal Box 2
21 Cable Type & Size * mm 68 Insulation Class & Temp. Rise Insulation Class Temp. rise K

22 Position of main terminal box (drive end) Right / Left / Top 69 Rated Output / Current kW A
T.B. Thread
23 Size 70 Rated Speed rpm

24 Space Heater Required (220 V 1ph 50Hz) * 71 Power Factor F.L. % 3/4 Load % 1/2 Load %
Winding Temp
25 Required (2 x winding/2 x bearing) * 72 Efficiency F.L. % 3/4 Load % 1/2 Load %
Detectors

26 Noise 85 dBA 73 Locked Rotor Current %

27 Finish Colour RAL 5010 74 Locked Rotor Torque %


28 Stator Winding Connection Star 75 Pull-up / Breakdown Torque Pull-up % Breakdown %
29 C.T. for Diff. Relay Required (Equal or Above 2.5 MW) 76 Starting Time sec. at 80% Volt sec. at 100% Volt

30 C.T. Ratio 77 Permissible Locked Rotor Time sec.(Cold) sec.(Hot)

31 Thread Size of T.B. for C.T. * 78 Time Constant Heating min. Cooling min.

32 System Neutral Resistance earthed 79 Number of sequential start Hot Cold

2 2
33 Pull-up / Breakdown Torque * / 200 % 80 Motor Rotor Inertia (WR ) kg-m

81 Bearing Type and/or No. DE NDE

82 Lubrication System Grease / Oil / Self Lub. / Forced Lub.

83 End Play DE mm NDE mm

84 Weight Rotor kg Total kg

Vendor shall complete the Data Sheet. 85 Space Heater V ph HZ W

* The Data marked * will be advised after receipt of vendor’s 86 Lubrication Interval Time h

data filled in this format 87 Locked rotor power factor rated torque
** Including standards tolerances
88 Thrust UP N Down N

Note 1 : For VSD drive motor, if Ex eb motor have been 89 Axial Thrust N
selected, it should be type tested with converter as a 90 Coupling end-float mm
unit according to IEC 60079-14. However, if Ex db is
selected type test certificate will not be required as
long as the winding RTDs are provided as per
project specification.

D M S21
-
J06-Ma y - 2 0
ED 4/4