GAS KITS AND ACCESSORIES

Litho U.S.A.

E2008 Lennox Industries Inc.


Dallas, Texas, USA
506063−01
03/08
IGNITION CONTROL
REPLACEMENT KIT
INSTALLATION INSTRUCTION FOR IGNITION CONTROL REPLACEMENT KIT (40W53)
USED WITH G24E−2T/4T/6T/7T, G24M−2T/4T/6T, G24MCE−2T/4T/5T/6T, G29M−1T/2T, GH30
AND GH90
RETAIN THESE INSTRUCTIONS Table of Contents
FOR FUTURE REFERENCE
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . 1
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
WARNING Installation Illustrations  G24E, G24M, G24MCE
and G29M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
This conversion kit is to be installed by a licensed Installation  G24E  2T/4T/6T/T7 . . . . . . . . . . . . . 3
professional installer (or equivalent) or a service Installation  G24M  2T/4T/6T . . . . . . . . . . . . . . . . 4
agency according to the manufacturer’s Installation  G24MCE  2T/4T/5T/6T . . . . . . . . . . 6
instructions and all requirements of the current Installation  G29M  1T/2T . . . . . . . . . . . . . . . . . . . 7
United States National Fuel Gas Code Installation  GH30 and GH90 . . . . . . . . . . . . . . . . . . 9
(ANSI−Z223.1/NFPA 54), or the current National DSI Control Board Operation . . . . . . . . . . . . . . . . . . . 11
Standard of Canada CSA−B149 Natural Gas and Blower Speed/Timing Adjustment . . . . . . . . . . . . . . . . 11
Propane Installation Codes. If the information in Start−Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
these instructions is not followed exactly, a fire or Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
explosion may result, causing property damage, Application
personal injury or loss of life. The qualified agency
performing this work assumes responsibility for See table 1 for the application of this ignition control
this conversion. replacement kit.
Table 1. Ignition Control Kit Application
Furnace Models
Shipping and Packing List Kit−Provided Control
Existing Control
using the Existing
Being Replaced Control

Package 1 of 1 contains the following: RAM


G24M−2T/4T
(3MC5)
G24E−2T/4T/6T
2  Mounting plates 33J6201
RAM
2  Control boards United (3MC6) G24MCE−2T/4T/5T
Technologies 82J7401
1  Terminal strip Electronic Controls
(UTEC) G24E−7T
1  Wiring harness (12−pin to 15−pin) (101707−01 and EGC−3A (23L5101) G24MCE−6T
101700−01) 40W53 G29M−1T
1  Wiring harness (12−pin to 9−pin)
G24MCE−6T
1  Wiring harness (12−pin to 12−pin) EGC−3ACE G29M−2T
(49L9401) GH30 − T
1  Bag assembly that includes the following: GH90 − T

(1) Ignition cable


(8) #8 − 18 x 1/2 hex−head self−tapping screws
CAUTION
(4) #6 − 32 x 7/8 hex−head thread forming screws Physical contact with metal edges and corners
while applying excessive force or rapid motion can
(2) #8 − 18 x 3/4 hex−head thread forming screws result in personal injury. Be aware of, and use
(10) Unused hole stickers caution when working near these areas during
(6) Wires installation or while servicing this equipment.
(1) Diagnostic label
(1) Conversion label
WARNING
(10) Wiring diagrams Before installing or servicing unit, be sure ALL
power to unit is OFF. More than one disconnect
Check equipment for shipping damage. If you find any switch may be present. Electrical shock can cause
damage, immediately contact the last carrier. personal injury or death.

03/08 506063−01
Page 1
*2P0308* *P506063-01*
Installation Illustrations  G24E, G24M, G24MCE and G29M
Use the following instructions along with the specific unit model instructions in the next section when installing the new
control boards.

SNAP
MOUNTED

SCREW #8 − 18 X 1/2 (8)

Figure 1. Mounting Plates Installation Figure 3. 101700−01 Control Board Installation

TB5 24V TERMINAL STRIP

SCREW #8 − 18 X 3/4 (2)

SCREW #6 − 32 X 7/8 (4)

Figure 2. 101707−01 Control Board Installation Figure 4. TB5 24V Terminal Strip Installation

W2 W1 G R C OC Y1 Y2

W2 W1 G R C OC Y1 Y2

Figure 5. TB5 24V Terminal Strip

Page 2
Installation  G24E  2T/4T/6T/7T 3. Secure the 101707−01 control board to the mounting
plate with the four self−tapping sheet metal screws (#6
1. Set the thermostat to the lowest setting. Shut off gas − 32 x 7/8) provided as illustrated in figure 2.
supply and disconnect electrical power from the unit. 4. Snap−mount the 101700−01 control board on the
mounting plate positioned as illustrated in figure 3.
2. Remove access door and turn gas valve knob to OFF.
5. Secure the 24V terminal strip to the blower access
Removal of 3MC5 or 3MC6 Control Board and panel as illustrated in figure 4, with the two hex−head
Related Wiring sheet metal screws (#8 − 18 x 3/4) provided.
1. Disconnect the ignition cable from the spark electrode NOTE − Use a #32 − 0.116 drill bit to make the two pilot
and control board and discard. holes required to mount the 24V terminal strip with the
fasteners provided.
2. Mark and disconnect all wires from control board.
6. If replacing the:
3. Disconnect the main wire harness at the control board a. 33J6201 or 82J7401 RAM controls, use the 12−pin
socket. to 15−pin conversion harness provided.
4. Remove and discard control board. b. 23L5101 or 49L9401 Heatcraft controls, use the
12−pin to 9−pin conversion harness provided.
5. Remove the wire from the pressure switch terminal 7. When using the 15−pin or 9−pin conversion harness,
that connects to the limit switch. Trace the wire back connect the 12−pin plug into the white 12−pin P1 socket
to the limit switch and cut the wire at the limit switch on the 101700−01 control board.
terminal. Tape the terminal with electrical tape.
8. Reconnect existing wires as follows:
6. Remove the flame sense wire connected to the flame a. Reconnect the blue wire from the circuit breaker to
sensor terminal. the blue wire with the male quick−connect terminal
a. Trace the wire from the flame sensor terminal to of the 12−pin plug pin 1.
the 15−pin plug connector pin 12. b. Reconnect yellow wire from 24V side of
b. Clip the flame sense wire flush with the plug transformer T1 to C on the 24V terminal strip.
connector. c. Reconnect black wire from 240V terminal on
transformer T1 to L1 terminal on 101707−01
Removal of EGC−3A (23L5101) or EGC−3ACE control board
(49L9401) Control Board and Related Wiring
d. Reconnect the white wire from the 240V neutral
1. Disconnect and discard the ignition cable from the terminal on transformer T1 and common blower
spark electrode and control board. terminal to L2 terminal on 101707−01 control
2. Mark and disconnect all wires from the EGC control board.
board. e. Reconnect the black wire from door switch to L1
terminal on 101707−01 control board.
3. If the unit has an EGC−3ACE conversion sticker, f. Perform the applicable procedure:
disconnect and remove the 15−pin to 9−pin conversion
D G24E−2T/4T/6T: Reconnect the red, brown,
harness from the control board and the main unit
harness. white, and yellow (R,G,W,Y) thermostat wires
from the A4 interface control.
4. Disconnect the main wire harness from the control D G24E−7T: Connect the red, brown, white,
board socket. yellow and blue (R,G,W,Y,C) thermostat wires
5. Remove and discard the EGC control board. from TB1 terminal strip to TB5 24V terminal
strip.
6. Remove the wire from the pressure switch terminal g. Connect the provided green/yellow wire with a ring
that connects to the limit switch. Trace the wire back terminal on one end and a male quick−connect
to the limit switch and cut the wire at the limit switch
terminal on the other end to the metal standoff
terminal. Tape the terminal with electrical tape.
marked MOUNT SCREW REQUIRED on the
7. Remove the flame sense wire connected to the flame 101707−01 control board.
sensor terminal and discard the wire.. h. Reconnect the piggyback terminated green/
yellow wire from ground bar and gas valve ground
Installation of 40W53 Ignition Control Replacement to the male quick−connect terminal of green/yellow
Kit wire that was connected in paragraph g above.
Use the following illustration and procedures to install the 9. Connect ignition cable provided to 101707−01 control
40W53 Ignition Control Replacement kit in G24E units: board and spark electrode 1/4" quick connect
terminals.
1. Cover any unused blower access panel holes with the
small blank stickers provided in the kit. IMPORTANT
2. Secure both control mounting plates to the blower
access panel as illustrated in figure 1, using the eight Do not include ignition lead in any group or bundled
self−tapping screws (#8 − 18 x 1/2) provided. wires. Route ignition lead separately.

Page 3
Steps 10 and 11 are for G24E−2T,−3T,4T or 6T furnaces a. 537044−01 over existing sticker which is located
that were converted to use an EGC−3ACE control board. on the inside surface of the G24E−2T/4T/6T
access panel.
NOTE − If the main wire harness in the unit is a 9−pin
b. 537050−01 over existing sticker which is located
connector control then skip to step 12.
on the inside surface of the G24E−7T access
10. Connect the white wire from pin 1 of the 15−pin panel.
interface wire harness to L2 terminal of the 101707−01 21. Apply the 580041−01 diagnostic sticker provided on
control board. blower access panel over the existing sticker.
11. Connect the black wire from pin 2 of the 15−pin socket 22. Apply the 580040−01 conversion sticker provided next
interface wire harness to D1 terminal of the 101707−01 to the existing rating plate located on the inside
control board and skip to step 14. vestibule area of the cabinet.
If the EGC−3ACE was the original control board, or the Installation  G24M  2T/4T/6T
main unit wire harness has a 9−pin plug then continue with
step 12: 1. Set the thermostat to the lowest setting. Shut off gas
supply and disconnect electrical power from the unit.
12. Reconnect the inducer motor CMB BL WR wire to D1
on the 101707−01 control board. 2. Remove access door and turn gas valve knob to OFF.
13. Reconnect the inducer motor L2 wire to L2 on the Removal of 3MC5 or 3MC6 Control Board and
101707−01control board. Related Wiring
1. Disconnect and discard the ignition cable from the
14. Reconnect the provided flame sense white wire with
spark electrode and control board.
3/16 x 0.020 bare quick−connect to the FS terminal on
the 101700−01 control board. 2. Mark and disconnect all wires from control board.
15. Connect the blower heating speed tap to HEAT 3. Disconnect the main wire harness from the control
terminal, cooling speed tap to COOL, and the low board socket.
speed tap to one of the UNUSED terminals on the 4. Remove and discard control board.
101707−01 control board. 5. Remove the wire from the pressure switch terminal
16. Connect the 12−pin to 12−pin white wiring harness to that connects to the limit switch. Trace the wire back
the black 12−pin P2 socket on the 101700−01 control to the limit switch and cut the wire at the limit switch
board and the white 12−pin socket on the 101707−01 terminal. Tape the terminal with electrical tape.
board. 6. Remove the flame sense wire connected to the flame
sensor terminal.
NOTE − The wiring harness is polarized so it will only a. Trace the wire from the flame sensor terminal to
connect one way. Match the male pins in the harness to the the 15−pin plug connector pin 12.
female pins in the white 12−pin socket on the 101707−01 b. Clip the flame sense wire flush with the plug
control board. Match the female pins in the harness to the connector.
male pins in the black socket on the 101700−01 control
Removal of EGC−3A (23L5101) or EGC−3ACE
board. (49L9401) Control Board and Related Wiring
17. Connect the black wire with the insulated 3/16 1. Disconnect the ignition cable from the spark electrode
connectors provided in the assembly bag to the FS and control board and discard.
terminal on the 101700−01 control board and to the FS
terminal on the 101707−01 control board. 2. Mark and disconnect all wires from the control board.
3. If the unit has an EGC−3ACE conversion sticker,
18. Connect the long purple wire attached to pin 8 on the
disconnect and remove the 15−pin to 9−pin conversion
12−pin conversion plug to the empty terminal on the
harness from the control board and the main unit
pressure switch.
harness.
19. On the 12−pin harness plug connection to 101700−01, 4. Disconnect the main wire harness at the control board
connect the following wires to the TB5 24V terminal socket.
strip:
5. Remove and discard the EGC control board.
a. Yellow wire from pin 2 to C.
6. Remove the wire from the pressure switch terminal
b. Green wire from pin 7 to G. that connects to the limit switch. Trace the wire back
c. Red wire from pin 9 to R. to the limit switch and cut the wire at the limit switch
d. White wire from pin 10 to W1. terminal. Tape the terminal with electrical tape.
e. Blue wire from pin 11 to Y1. 7. Remove the flame sense wire connected to the flame
20. Apply wiring diagram sticker: sensor terminal and discard the wire.

Page 4
Installation of 40W53 Ignition Control Replacement 9. Connect ignition cable provided to control board and
Kit spark electrode 1/4" quick connect terminals.
Use the following illustration and procedures to install the
40W53 Ignition Control Replacement kit in G24M units: IMPORTANT
1. Cover any unused blower access panel holes with the
Do not include ignition lead in any group or bundled
small blank stickers provided in the kit.
wires. Route ignition lead separately.
2. Secure both control mounting plates to the blower
access panel as illustrated in figure 1, using the eight Steps 10 and 11 are for G24M−2T/4T furnaces that were
hex−head self−tapping screws (#8 − 18 x 1/2) provided. converted to use an EGC−3ACE control board.
3. Secure 101707−01 control board to mounting plate
NOTE − If the main wire harness in the unit is a 9−pin
with the four hex−head thread forming screws (#6 − 32
connector control then skip to the step 12.
x 7/8) provided as illustrated in figure 2.
4. Snap−mount 101700−01 control board to the mounting 10. Connect the white wire from pin 1 of the 15−pin socket
plate as illustrated in figure 3. interface wire harness to L2 terminal of the 101707−01
control board.
5. Screw the 24V terminal strip to the blower access
panel as illustrated in figure 4, with the two hex−head 11. Connect the black wire from pin 2 of the 15−pin socket
sheet metal screws (#8 − 18 x 3/4) provided. interface wire harness to D1 terminal of the 101707−01
control board and skip to step 14.
NOTE − Use a #32 − 0.116 drill bit to make the two pilot
holes required to mount the 24V terminal strip with the If the EGC−3ACE was the original control board, or the
fasteners provided. main unit wire harness is a 9−pin plug then continue with
step 12:
6. If replacing the:
a. 33J6201 or 82J7401 RAM controls, use the 12−pin 12. Reconnect the inducer motor CMB BL WR wire to D1
to 15−pin conversion harness provided. on the 101707−01 control board.
b. 23L5101 or 49L9401 Heatcraft controls, use the 13. Reconnect the inducer motor L2 wire to L2 on the
12−pin to 9−pin conversion harness provided. 101707−01 control board.
7. When using the 15−pin or 9−pin conversion harness, 14. Reconnect the provided flame sense white wire with
connect the 12−pin plug into the white 12−pin socket P1 3/16 x 0.020 bare quick−connect terminal to the FS
on the small 101700−01 control board. terminal on the 101700−01 control board.
8. Reconnect existing wires as follows: 15. Connect the blower heating speed tap to HEAT
a. Reconnect the blue wire from the circuit breaker to terminal, cooling speed tap to COOL, and the low
the blue wire with the male quick−connect terminal speed tap to one of the UNUSED terminals on the
of the 12−pin plug terminal 1. 101707−01 control board.
b. Reconnect yellow wire from 24V side of 16. Connect the 12−pin to 12−pin white wiring harness
transformer to C on the 24V terminal strip. provided to the black 12−pin socket P2 on the
c. Reconnect black wire from 240V terminal on 101700−01 control board, and the white 12−pin socket
transformer to L1 terminal on 101707−01 control on the 101707−01 control board.
board.
NOTE − The wiring harness is polarized so it will only
d. Reconnect the white wire from neutral 240V
power supply connection to L2 terminal on connect one way. Match the male pins in the harness to the
101707−01 control board. female pins in the white 12−pin socket on the 101707−01
e. Reconnect black wire from door switch to L1 control board. Match the female pins in the harness to the
terminal on 101707−01 control board. male pins in the black socket on the 101700−01 control
f. Reconnect R, G, W, and Y thermostat wires to the board.
corresponding screw terminal on the TB5 24V 17. Connect the black wire with the insulated 3/16
terminal strip. connectors provided in the assembly bag to the FS
g. Connect the provided green/yellow wire ring terminal on the 101700−01 control board and to the FS
terminal to the mounting screw of 101707−01 terminal on the 101707−01 control board.
control board marked with MOUNT SCREW 18. Connect the long purple wire attached to pin 8 on the
REQUIRED and connect the male quick−connect 12−pin conversion plug to the empty terminal on the
terminal to ground terminal of the gas valve. pressure switch.

Page 5
19. On the 12−pin harness plug connection to 101700−01, 6. Remove the wire on the pressure switch terminal that
connect the following wires to the TB5 24V terminal connects to the limit switch. Trace the wire back to the
strip: limit switch and cut the wire at the limit switch terminal
a. Yellow wire from pin 2 to C. and tape the terminal with electrical tape.
b. Green wire from pin 7 to G. 7. Remove the flame sense wire connected to the flame
c. Red wire from pin 9 to R. sensor terminal and discard the wire.
d. White wire from pin 10 to W1. Installation of 40W53 Ignition Control Replacement
e. Blue wire from pin 11 to Y1. Kit
20. Apply wiring diagram sticker: Use the following illustration and procedures to install the
a. 537043−01 over existing sticker which is located 40W53 Ignition Control Replacement kit in G24MCE units:
on the inside surface of the G24M−2T/4T access 1. Cover any unused blower access panel holes with the
panel. small blank stickers provided in the kit.
b. 537051−01 over existing sticker which is located 2. Secure both control mounting plates to the blower
on the inside surface of the G24M−6T access access panel as illustrated in figure 1, using the eight
panel. hex−head self−tapping screws (#8 − 18 x 1/2) provided.
21. Apply the 580041−01 diagnostic sticker provided on 3. Secure 101707−01 control board to mounting plate as
blower access panel over the existing sticker. illustrated in figure 2, with the four hex−head
22. Apply the 580040−01 conversion sticker provided next self−tapping sheet metal screws (#6 − 32 x 7/8)
to the existing rating plate located on the inside provided.
vestibule area of the cabinet. 4. Snap−mount 101700−01 control board to the mounting
plate as illustrated in figure 3.
Installation  G24MCE  2T/4T/5T/6T
5. Screw the 24V terminal strip to the blower access
1. Set the thermostat to the lowest setting. Shut off gas panel as illustrated in figure 4, with the two hex−head
supply and disconnect electrical power from the unit. sheet metal screws (#8 − 18 x 3/4) provided.
2. Remove access door and turn gas valve knob to OFF. NOTE − Use a #32 − 0.116 drill bit to make the two pilot
Removal of 3MC5 or 3MC6 Control Board and holes required to mount the 24V terminal strip with the
Related Wiring fasteners provided.
1. Disconnect and discard the ignition cable from the 6. If replacing the:
spark electrode and control board. a. 33J6201 or 82J7401 RAM controls, use the 12−pin
to 15−pin conversion harness provided.
2. Mark and disconnect all wires from the control board.
b. 23L5101 or 49L9401 Heatcraft controls, use the
3. Disconnect the main wire harness from the control 12−pin to 9−pin conversion harness provided.
board.
7. When using the 15−pin or 9−pin conversion harness,
4. Remove and discard the control board. connect the 12−pin plug into the white 12−pin socket
5. Remove the wire from the pressure switch terminal P−1 on the 101700−01 control board.
that connects to the limit switch. Trace the wire back 8. Reconnect existing wires as follows:
to the limit switch and cut the wire at the limit switch a. Reconnect the blue wire from the circuit breaker to
terminal. Tape the terminal with electrical tape. the blue wire with the male quick connect terminal
6. Remove the flame sense wire connected to the flame of the 12−pin plug terminal 1.
sensor terminal. b. Reconnect yellow wire from 24V side of
a. Trace the wire from the flame sensor terminal to transformer T1 to C on the 24V terminal strip.
the 15−pin plug connector pin 12. c. Reconnect black wire from 240V terminal on
b. Clip the flame sense wire flush with the plug transformer T1 to L1 terminal on 101707−01
connector. control board
Removal of EGC−3A (23L5101) or EGC−3ACE d. Reconnect the white wire from the 240V neutral
(49L9401) Control Board and Related Wiring terminal on transformer T1 and common blower
1. Disconnect the ignition cable from the spark electrode terminal to L2 terminal on 101707−01 control
and control board and discard. board.
e. Reconnect black wire from door switch to L1
2. Mark and disconnect all wires from the control board.
terminal on 101707−01 control board.
3. If the unit has an EGC−3ACE Conversion Sticker, f. Reconnect the red, brown, white, yellow and blue
disconnect and remove the 15−pin to 9−pin conversion thermostat wires (R, G, W, Y, C) to the TB5 24V
harness from the control board and the main unit terminal strip from the TB1 terminal strip.
harness. g. Connect the provided green/yellow wire with a ring
4. If the unit has a 23L5101 or 49L9401 control board, terminal on one end and a male quick−connect
disconnect the main wire harness from the EGC terminal on the other end to the metal standoff
control board socket. marked MOUNT SCREW REQUIRED on the
5. Remove and discard the EGC control board. 101707−01 control board.

Page 6
h. Reconnect piggyback terminated green/yellow c. Red wire from pin 9 to R.
wire from ground bar and gas valve ground to the d. White wire from pin 10 to W1.
male quick−connect terminal of green/yellow wire e. Blue wire from pin 11 to Y1.
connected in (g) above. 20. Apply wiring diagram sticker:
9. Connect ignition cable provided to 101707−01 control a. 537045−01 over existing sticker which is located
board and spark electrode 1/4" quick connect on the inside surface of the G24MCE−2T/4T/5T
terminals. access panel.
b. 537049−01 over existing sticker which is located
IMPORTANT on the inside surface of the G24MCE−6T access
panel.
Do not include ignition lead in any group or bundled
21. Apply 580041−01 diagnostic sticker provided on the
wires. Route ignition lead separately.
blower access panel over the existing sticker.
Steps 10 and 11 are for G24MCE  2T/4T/5T furnaces 22. Apply 580040−01 conversion sticker provided next to
that were converted to use an EGC−3ACE control board. the existing rating plate located on the inside vestibule
NOTE − If the main wire harness in the unit is a 9−pin area of the cabinet.
connector control then skip to the step 12. Installation  G29M  1T/2T
10. Connect the white wire from pin 1 of the 15−pin socket
1. Set the thermostat to the lowest setting. Shut off gas
interface wire harness to L2 terminal of the 101707−01 supply and disconnect electrical power from the unit.
control board.
2. Remove access door and turn gas valve knob to OFF.
11. Connect the black wire from pin 2 of the 15−pin socket
interface wire harness to D1 terminal of the 101707−01 Removal of EGC−3A (23L5101) or EGC−3ACE
control board and skip to step 14 (49L9401) Control Board and Related Wiring
If the EGC−3ACE was the original control board, or the 1. Disconnect and discard the ignition cable from the
main unit wire harness is a 9−pin plug then continue with spark electrode and control board.
step 12: 2. Mark and disconnect all wires from the control board.
12. Reconnect the inducer motor CMB BL WR wire to D1 3. Disconnect the main wire harness at the control board
on the 101707−01 control board. socket.
13. Reconnect the inducer motor L2 wire to L2 on the 4. Remove and discard the control board.
101707−01 control board. 5. Remove the wire on the pressure switch terminal that
14. Reconnect the provided flame sense white wire with connects to the limit switch. Trace the wire back to the
limit switch and cut the wire at the limit switch terminal
3/16 x 0.020 bare quick−connect terminal to the FS
terminal on the 101700−01 control board. and tape the terminal with electrical tape.
6. Disconnect and discard the flame sense wire
15. Connect the blower heating speed tap to HEAT
connected to the flame sensor terminal.
terminal, cooling speed tap to COOL, and the low
speed tap to one of the UNUSED terminals on the Installation of 40W53 Ignition Control Replacement
101707−01 control board. Kit
16. Connect the 12−pin to12−pin white wiring harness to Use the following illustration and procedures to install the
the black 12−pin socket P2 on the 101700−01 board 40W53 Ignition Control Replacement kit in G29M units:
and the white 12−pin socket on the 101707−01 control 1. Cover any unused blower access panel holes with the
board. small blank stickers provided in the kit.
NOTE − The wiring harness is polarized so it will only 2. Secure both control mounting plates to the blower
connect one way. Match the male pins in the harness to the access panel as illustrated in figure 1, using the eight
female pins in the white 12−pin socket on the 101707−01 hex−head self−tapping screws (#8 − 18 x 1/2) provided.
control board. Match the female pins in the harness to the 3. Secure 101707−01 control board to mounting plate as
male pins in the black socket on the 101700−01 control illustrated in figure 2, with the four hex−head sheet
board. metal screws (#6 − 32 x 7/8) provided.
17. Connect the black wire with the insulated 3/16 4. Snap−mount 101700−01 control board to the mounting
connectors provided in the assembly bag to the FS plate as illustrated in figure 3.
terminal on the 101700−01 board and to the FS 5. Screw the 24V terminal strip to the blower access
terminal on the 101707−01 control board. panel as illustrated in figure 4, with the two sheet metal
18. Connect the long purple wire attached to pin 8 on the screws (#8 − 18 x 3/4) provided.
12−pin conversion plug to the empty terminal on the NOTE − Use a #32 − 0.116 drill bit to make the two pilot
pressure switch. holes required to mount the 24V terminal strip with the
19. On the 12−pin harness plug connection to 101700−01, fasteners provided.
connect the following wires to the TB5 24V terminal 6. Install the 12−pin to 9−pin conversion harness
strip: provided.
a. Yellow wire from pin 2 to C. 7. Connect the 12−pin plug into the white 12−pin socket
b. Green wire from pin 7 to G. P1 on the 101700−01 control board.
Page 7
8. Reconnect existing wires as follows: 13. Connect the blower heating speed tap to HEAT
a. Reconnect the blue wire from the circuit breaker to terminal, cooling speed tap to COOL terminal, and the
the blue wire with the male quick−connect terminal low speed tap to one of the UNUSED terminals on the
of the 12−pin plug terminal 1. 101707−01 control board.
b. Reconnect yellow wire from 24V side of 14. Connect the 12−pin to 12−pin white wiring harness to
transformer T1 to C on the 24V terminal strip. the black 12−pin socket P2 on the 101700−01 control
c. Reconnect black wire from 240V terminal on board and the white 12−pin socket on the 101707−01
transformer T1 to L1 terminal on 101707−01 control board.
control board NOTE − The wiring harness is polarized so it will only
d. Reconnect the white wire from the 240V neutral connect one way. Match the male pins in the harness to the
terminal on transformer T1 and common blower female pins in the white 12−pin socket on the 101707−01
terminal to L2 terminal on 101707−01 control control board. Match the female pins in the harness to the
board. male pins in the black socket on the 101700−01 control
e. Reconnect black wire from door switch to L1 board.
terminal on 101707−01 control board. 15. Connect the black wire with the insulated 3/16
f. Reconnect thermostat wires (R,G,W1,Y and W2 if connectors provided in the assembly bag to the FS
used) from room thermostat S1 to the TB5 24V terminal on the 101700−01 control board and to the FS
terminal strip. terminal on the 101707−01 control board.
g. Connect the provided green/yellow wire with a ring 16. Connect the long purple wire attached to pin 8 on the
terminal on one end and a male quick−connect 12−pin conversion plug to the empty terminal on the
terminal on the other end to the metal standoff pressure switch.
marked MOUNT SCREW REQUIRED on 17. On the 12−pin harness plug connection to 101700−01,
101707−01 control board. connect the following wires to the TB5 24V terminal
h. Reconnect green/yellow ground wire to the male strip:
quick−connect terminal of green/yellow wire that a. Yellow wire from pin 2 to C.
was connected in paragraph g above. b. Green wire from pin 7 to G.
9. Connect ignition cable provided to the 101707−01 c. Red wire from pin 9 to R.
control board and spark electrode 1/4" quick connect d. White wire from pin 10 to W1.
terminals. e. Blue wire from pin 11 to Y1.
18. Apply wiring diagram sticker:
IMPORTANT a. 537042−01 over existing sticker which is located
Do not include ignition lead in any group or bundled on the inside surface of the G29M−1T access
wires. Route ignition lead separately. panel.
b. 537041−01 over existing sticker which is located
10. Reconnect the inducer motor CMB BL WR wire to D1 on the inside surface of the G29M−2T access
on the 101707−01 control board. panel.
11. Reconnect the inducer motor L2 white wire to L2 on 19. Apply provided diagnostic sticker 580041−01 on
the 101707−01 control board. blower access panel over the existing sticker.
12. Reconnect the provided flame sense white wire with 20. Apply conversion sticker 580040−01 provided beside
3/16 x 0.020 bare quick−connect to the FS terminal on existing rating plate located on the inside vestibule
the 101700−01 control board. area of the cabinet.

Page 8
Installation  GH30 and GH90 2. Secure 101707−01 control board to mounting plate as
illustrated in figure figure 7, with the four hex−head
1. Set the thermostat to the lowest setting. Shut off gas self−tapping screws (#6 − 32 x 7/8) provided.
supply and disconnect electrical power from the unit.
2. Turn gas valve knob to OFF and remove control box
cover.
Removal of EGC−3A (23L5101) or EGC−3ACE
(49L9401) Control and Wiring
1. Disconnect and discard the ignition cable from the
spark electrode and control board.
2. Mark and disconnect all wires from the EGC control
board.
3. Disconnect the the main wire harness at the control SCREW
board plug. #6−32 X 7/8 (8)

4. Remove and discard the EGC control board.


5. Remove the wire from the pressure switch terminal
that connects to the limit switch. Trace the wire back
to the limit switch and cut the wire at the limit switch
terminal. Tape the terminal with electrical tape.
6. Remove the flame sense wire from the flame sensor
terminal and discard the wire.
Installation of 40W53 Ignition Control Replacement
Kit
Use the following illustration and procedures to install the Figure 7. 101707−01 Control Board Installation
40W53 Ignition Control Replacement kit in GH30 and (GH30 and GH90)
GH90 units:
3. Snap mount the 101700−01 control board into the
1. Secure both control mounting plates to the blower control box as illustrated in figure 8,
access panel as illustrated in figure 6, using the eight
hex−head self−tapping screws (#8 − 18 x 1/2) provided.

PRESSURE
SWITCH

TWO−STAGE
CONTROL BOARD

SNAP MOUNT

SCREW
#8−18 X 1/2 (8)

Figure 6. Mounting Plates Installation Figure 8. 101700−01 Control Board Installation


(GH30 and GH90) (GH30 and GH90)

Page 9
4. Screw the 24V terminal strip to the control box as f. Connect the provided green/yellow wire with a ring
illustrated in figure 9, with the two #8−18 x 3/4 sheet terminal on one end, and a male quick−connect
metal screws provided. Locate the terminal strip at the terminal on the other end to the metal standoff
top of the box, right of the pressure switch. marked MOUNT SCREW REQUIRED on the
101707−01 control board.
g. Reconnect the green/yellow ground wire to the
male quick−connect terminal of the green/yellow
wire connected in the previous step.
24 V TERMINAL
STRIP
8. Connect the ignition cable provided to 101707−01
PRESSURE control board and ignitor.
SWITCH

IMPORTANT
Do not include ignition lead in any group or bundled
SCREW wires. Route ignition lead separately.
#8−18 X 3/4 (2)
9. Reconnect the inducer motor CMB BL WR wire to D1
on the 101707−01 control board.
10. Reconnect the white L2 wire from the two−stage 9 pin
pin 2 to L2 on the 101707−01 control board.
11. Reconnect the provided flame sense white wire with
3/16 x 0.020 bare quick−connect to the FS terminal on
the 101700−01 control board.
12. Connect the blower heating speed tap to HEAT
terminal, cooling speed tap to COOL, and the low
speed tap to one of the UNUSED terminals on the
Figure 9. 24V Terminal Strip Installation 101707−01 control board.
(GH30 and GH90)
13. Connect the 12−pin−to−12−pin white wiring harness to
NOTE − Use a #32 − 0.116 drill bit to make the two pilot the black 12−pin socket P2 on the 101700−01 control
holes required to mount the 24V terminal strip with the board and the white 12−pin socket on the 101707−01
fasteners provided. board.
5. Install the 12−pin to 9−pin conversion harness NOTE − The wiring harness is polarized so it will only
provided.
connect one way. Match the male pins in the harness to the
6. Connect the 12−pin plug into the white 12−pin socket female pins in the white 12−pin socket on the 101707−01
P1 on the 101700−01 control board. control board. Match the female pins in the harness to the
7. Reconnect existing wires as follows: male pins in the back socket on the 101700−01 control
a. Reconnect the blue wire from the circuit breaker to board.
the blue wire with the male quick connect terminal 14. Connect the black wire with the insulated 3/16
of the 12−pin plug terminal 1. connectors provided in the assembly bag to the FS
b. Reconnect the yellow wire from the 24V side of terminal on the 101700−01 control board and to the FS
transformer T1 to the C on the 24V terminal strip. terminal on the 101707−01 control board.
c. Reconnect the black wire from the 240V terminal
15. Connect the long purple wire attached to pin 8 on the
on transformer T1 and the black wire from the door
12−pin conversion plug to the empty terminal on the
interlock switch to the L1 terminals on 101707−01 pressure switch.
control board
d. Reconnect the four white neutral wire terminals to 16. On the 12−pin harness plug connection to 101700−01,
L2 on the 101707−01 control board from the: connect the following wires to the TB5 24V terminal
strip:
D Transformer T1 240V
D B3 blower a. Yellow wire from pin 2 to C.
D Power supply b. Green wire from pin 7 to G.
D Two−stage A86 control board’s 9−pin connector,
pin 2. c. Red wire from pin 9 to R.
e. Reconnect the thermostat wires (R,G,W1,Y and
d. White wire from pin 10 to W1.
W2 if used) from S1 thermostat to the TB5 24V
terminal strip. e. Blue wire from pin 11 to Y1.

Page 10
17. Apply the 537040−01 wiring diagram sticker provided
over the existing sticker located on the inside of unit
120
access panel.
130
18. Apply the 580041−01 diagnostic sticker provided on 150
the control box cover over the existing sticker.

SPEED−UP
19. Apply the 580040−01 conversion sticker provided next
to the existing rating plate located on blower access
door. P2

DSI Control Board Operation


Figure 10. 101707−01 Control Board Fan OFF
Time Setting
The DSI control boards 101707−01 (see figure 11),
101700−01 (see figure 12) control the indoor and Start−Up
combustion air blowers along with:
1. Burner ignition control IMPORTANT
2. Diagnostic LED (see table 2 for flash codes, or the Before lighting, smell all around the appliance area
diagnostic code sticker provided in the kit) for gas. Be sure to smell next to the floor because
See table 3 for complete details on control operations and some types of gas are heavier than air and will settle
table 4 for fault code conditions. on the floor.

Table 2. 101707−01 Control Board


Green LED Status Indicator
CAUTION
LED (GREEN) STATUS Use only your hand to move the gas control knob.
Never use tools. If the knob will not move by hand,
STEADY ON Control OK in standby, call for heat, cool,
or fan modes. do not try to repair it, call a licensed professional
installer (or equivalent) or a service agency. Force or
STEADY OFF Internal control fault or no power. attempted repair may result in a fire or explosion.
1 FLASH Lockout due to failed ignition or flame
dropouts. Placing Furnace into Operation
2 FLASHES Pressure switch is open with inducer on. 1. Make sure thermostat is set below room temperature
and power is turned off to unit.
3 FLASHES Pressure switch is closed with inducer off.
2. This appliance is equipped with an ignition device
4 FLASHES Limit switch is open.
which automatically lights the burner. DO NOT try to
5 FLASHES Flame detected with gas valve closed. light the burner by hand.
6 FLASHES Compressor output delayed from short 3. Place the gas valve control in the OFF position. Do not
cycle/staging timer. force.
7 FLASHES Fault detected in 1104−3 operation. 4. Wait 15 minutes to clear out any gas. If you then smell
gas, immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
Blower Speed/Timing Adjustment instructions.
5. Place the gas valve control knob in the ON position.
6. Turn on all electrical power to unit.
IMPORTANT 7. Set thermostat above room temperature.
Turn electrical power off before making any 8. Check gas line supply pressure with unit operating.
adjustments. The minimum pressure as shown on the rating
nameplate must be available. Then check and adjust
manifold pressure to the value indicated on the unit
The fan ON time of 30 seconds is not adjustable. Fan OFF name plate.
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by moving the jumper 9. Set heat anticipator to 0.65 for Honeywell gas valve
and 0.50 for White Rogers gas valve.
on the 101707−01 control board as illustrated in figure 10.
The unit is shipped with a factory fan OFF setting of 150 10. Run unit through a minimum of three complete cycles
seconds. Valid options for fan OFF is 120, 130 and 150 to check for normal operation.
seconds. Fan OFF time will affect comfort and is 11. Set thermostat to desired settings.
adjustable to satisfy individual applications. 12. Replace access panel.

Page 11
1/4 In QUICK−CONNECT TERMINAL
DESCRIPTIONS
L2 LINE VOLTAGE RETURN (COMMON)
D1 01 COMBUSTION BLOWER (LINE
GREEN STATUS VOLTAGE)
LED LINE VOLTAGE HOT INPUT
L1
UNUSED PART TERMINALS FOR UNUSED
MOTOR SPEEDS
COOL BLOWER COOL SPEED (LINE
VOLTAGE)
HEAT BLOWER HEAT SPEED (LINE
VOLTAGE)
SPARK HIGH VOLTAGE SPARK OUTPUT
LOCATED ON TOP OF TRANSFORMER
T1
P1 12−PIN PLUG − FEMALE PLUG/
MALE TERMINALS
PIN 1 VAC HOT FROM TRANSFORMER
PIN 2 24VAC RETURN TO TRANSFORMER
PIN 3 GAS VALVE OF 1104−3 OUTPUT LIMIT
SWITCH
FLAME SENSOR (FS)
PIN 4 LIMIT SWITCH
PIN 5 PRESSURE SWITCH/GAS ENABLE TO
1104−3
PIN 6 PRESSURE SWITCH INPUT
PIN 7 MANUAL FAN INPUT FROM
THERMOSTAT (GREEN)
PIN 8 PRESSURE SWITCH CUT
PIN 9 24VAC TO THERMOSTAT (RED)
PIN 10 HEAT DEMAND INPUT FROM
THERMOSTAT (WHITE)
P1 CONNECTION PIN 11 COOL DEMAND INPUT FROM
THERMOSTAT (YELLOW)
PIN 12 COMPRESSOR CONTACTOR OUT (NOT
USED)
FAN OFF DELAY SELECT
ECON
HEAT FAN OFF DELAY
120 SEC
135 SEC
150 SEC
COOL FAN OFF DELAY
0 SEC

FAN ON DELAY
HEAT FAN ON DELAY
3/16 In QUICK−CONNECT TERMINAL DESCRIPTIONS
MOUNT SCREW REQUIRED 30 SEC FROM GAS VALVE OPEN
FS FLAME SENSOR
COOL FAN ON DELAY
ECON THERMOSTAT CALL FOR CONTINUOUS FAN
7 SEC

Figure 11. 101707−01 Control Board

Page 12
P1 12−PIN SOCKET− FEMALE CONTACTS P2 12−PIN SOCKET− MALE PIN CONTACTS
PIN 1 SYSTEM PASS−THROUGH (CONTINUOUS 24VAC FROM PIN 1 SYSTEM PASS−THROUGH (CONTINUOUS 24VAC FROM
TRANSFORMER) 24VAC COMMON (CHASSIS GROUND)
PIN 2
PIN 2 24VAC COMMON (CHASSIS GROUND)
PIN 3 GAS VALVE OUTPUT
PIN 3 GAS VALVE OUTPUT
PIN 4 SYSTEM PASS−THROUGH (LIMIT SWITCH OUTPUT)
PIN 4 SYSTEM PASS−THROUGH (LIMIT SWITCH OUTPUT)
PIN 5 PRESSURE SWITCH ENABLE INPUT FORM 1068−406
PIN 5 LIMIT SWITCH INPUT (COMMON WITH PIN 9)
PIN 6 PRESSURE SWITCH INPUT
PIN 6 PRESSURE SWITCH INPUT
PIN 7 SYSTEM PASS−THROUGH (THERMOSTAT FAN INPUT)
PIN 7 SYSTEM PASS−THROUGH (THERMOSTAT FAN INPUT)
PIN 8 SYSTEM PASS−THROUGH (PRESSURE SWITCH OUTPUT)
PIN 8 SYSTEM PASS−THROUGH (PRESSURE SWITCH OUTPUT)
PIN 9 SYSTEM PASS−THROUGH (THERMOSTAT R")
PIN 9 SYSTEM PASS−THROUGH (THERMOSTAT R")
PIN 10 THERMOSTAT CALL FOR HEAT INPUT (W)
PIN 10 THERMOSTAT CALL FOR HEAT INPUT (W)
PIN 11 SYSTEM PASS−THROUGH (THERMOSTAT CALL FOR
PIN 11 SYSTEM PASS−THROUGH (THERMOSTAT CALL FOR COMPRESSOR INPUT.
COMPRESSOR INPUT.
PIN 12 SYSTEM PASS−THROUGH (COMPRESSOR CONTACTOR
PIN 12 SYSTEM PASS−THROUGH (COMPRESSOR CONTACTOR
OUTPUT)

0.187" X 0.020" MALE QUICK−CONNECT TERMINALS (TWO PLACES)


FS FLAME SENSE INPUT

Figure 12. 101700−01 Control Board

Page 13
Table 3. Control Operation
INPUT
Mode B − ON W − OFF G − ON G − OFF Y − ON Y − OFF
STANDBY Call for heat mode. Normal In steady fan mode Normal Goes to steady Normal
cool.
CALL FOR HEAT Normal Goes into standby. Indoor blower Indoor blower en-
energized on heat ergized on cool
PRE−PURGE speed. Ignition speed. Ignition
IGNITION Gas valve de− cycles continues. cycle continues.
energized. Blower
HEAT WARM−UP energized on heat Heat mode Indoor blower
speed. Goes to overrides G. energized on cool
post−purge mode. Blower shuts off. speed. Goes to
steady heat mode.
STEADY HEAT Indoor blower Indoor blower
already energized energized on heat
POST PURGE Call for heat mode. Normal on heat speed. speed, heat cycle
Blower remains on continues.
HEAT OFF through re−ignition
DELAY unless blower off
STEADY FAN delay expires. Normal Goes to standby
mode.
STEADY COOL Runs normal heat G ignored, cooling Normal Normal Goes to cool off
mode except has priority. delay.
blower is on cool
COOL OFF speed. Goes to steady Normal
DELAY cool.
LOCKOUT Remains in lockout Reset lockout if W Run heat speed Runs cool speed
for one hour. off more than three fan. fan (if W is off).
seconds.

Table 4. Fault Code Conditions


INPUT
Mode LIMIT SWITCH OPEN PRESSURE PRESSURE FLAME NOT FRAME
SWITCH OPEN SWITCH CLOSED PRESENT PRESENT
STANDBY Energize inducer LED flashes four Normal Ignored while W is Normal Energizes inducer
and heat speed times while limit is off. . and heat speed
blower open. When limit blower, LED
CALL FOR HEAT switch re−closes, Goes to pre−purge Inducer off until flashes five times.
Normal mode. pressure switch.
inducer runs Goes to lockout.
through post−purge open. Flashes
and begins heat three times.
PRE−PURGE Energize heat blower off delay. If Flashes two times Normal
speed blower. call for heat is until pressure
present when post switch. closes,
IGNITION De−energize gas purge completed, pre−purge time Goes to inter− Goes to heat on
valve, energize restart call for heat. begins when purge delay.
heat speed blower. pressure switch.
HEAT WARM−UP Gas valve shut off, Normal
closes. heat speed blower
STEADY HEAT De−energize gas on goes to
valve. re−purge.
POST−PURGE Inducer and heat Ignored while W is Ignored while W is Normal Energizes inducer
speed blower off. off. and heat speed
HEAT OFF remain on. blower, LED
DELAY flashes five times.
STEADY FAN
STEADY COOL Runs cool speed
blower until off
COOL OFF delay over, then Energizes inducer
DELAY switch to heat blower remains on
speed blower and cool speed. LED
inducer energized. flashes five times.
LOCKOUT Inducer and heat
speed is on. LED
flashes five times.

Page 14
Wiring Diagrams

Figure 13. G24E−2T, 4T, and 6T Typical Unit Wiring Diagram

Page 15
Figure 14. G24E−7T Typical Unit Wiring Diagram

Page 16
Figure 15. G24M−2T and 4T Typical Unit Wiring Diagram

Page 17
Figure 16. G24M−6T Typical Unit Wiring Diagram

Page 18
Figure 17. G24MCE−2T, 4T and 5T Typical Unit Wiring Diagram

Page 19
Figure 18. G24MCE−6T Typical Unit Wiring Diagram

Page 20
Figure 19. G29M−1T Typical Unit Wiring Diagram

Page 21
Figure 20. G29M−2T Typical Unit Wiring Diagram

Page 22
Figure 21. G29M−2T (Two−Stage) Typical Unit Wiring Diagram

Page 23
Figure 22. GH30 and GH90 Typical Unit Wiring Diagram

Page 24