You are on page 1of 1

A B C D E F G H

E1096345 09-19 RELEASED


1 1
2 TB2
MODEL 2000 53 52 61 505 506 507 508 509
CONTROL PANEL ETHERNET SWITCH
SHUTDOWN SHUTDOWN WARNING WARNING
* RSC FR FR FR FR WR WR WR WR PORT 8
START/RUN (14) (11) (11) (12) (24) (21) (21) (22) (14) (11) (11) (12) (24) (21) (21) (22)
* GENERATOR LOADED 554 555 556 557 558 559 560 561 562 563 564 565

RJ45
* SPARE 1 WARNING

CAT 5E CABLE (100M MAX)


* SPARE 1 SHUTDOWN

P275387 (OR EQUAL)


3 ENGINE RUNNING GENERATOR READY
* SPARE 2 WARNING RR RR RR RR
TO BE LOADED
LR LR
(14) (11) (11) (12) (24) (21) (21) (22) (14) (11) (11) (12)
* SPARE 3 WARNING 566 567 568 569 570 571 572 573 574
*SPARE 2 SHUTDOWN

-A
CUSTOMER ETHERNET
NETWORK
CUSTOMER SUPPLIED CONTACTS MUST HAVE A CONTACTS FOR CUSTOMER USE RATED 10A@30VDC OR 250VAC
ONE AMPERE RATING AT 24VDC AND THE TOTAL
CONTACT PLUS WIRE RESISTANCE MUST NOT
EXCEED THREE OHMS AT 40°C
4

E1096345
NOTES
SEE ENGINATOR ORDER DATA SHEET FOR ADDITIONAL CUSTOMER CONNECTIONS.
* COMPONENT NOT SUPPLIED BY WAUKESHA
SEE PD007B FOR COMPONENT ABBREVIATIONS
MODELS DIMENSIONS ARE IN INCHES [MM] ROR - 04-12-2019
2000 DESCRIPTION
5
CUSTOMER CONNECTIONS
THIRD ANGLE PROJECTION
REFERENCE DOCS.
DRW. VB 09-30-19 FILE C.C. PART NO.
PC2217P
CHK. AZ 09-30-19 252 PC2217X
A B C APP. TLS 09-30-19 COPYRIGHT 2019, SCALE SHEET 1 OF 1