Professional Documents
Culture Documents
GL in Kowski 1997
GL in Kowski 1997
Keywords
Modeling Generator Circuit Breakers, Transient This paper reports on many simulated conditions ana-
Response, Escalation Voltages, Circuit Breaker Reig- lyzed by using the Electromagnetic Transient Program
nition, Circuit Breaker Restrike, Vacuum Circuit (EMTP). Ten generators in the range of 50 through
Breakers, Load Shedding, Electromagnetic Transient 300 MVA have been considered.
Program
1 Introduction
Abstract
The stresses imposed on generator circuit breakers,
This paper focuses on multiple reignitions and volt- i.e. on circuit breakers installed between a generator
age escalation that may occur during load shedding and its associated step-up transformer, exceed by a
when vacuum circuit-breakers are used as generator considerable degree those imposed on general purpose
circuit-breakers. The probability of multiple reigni- medium voltage circuit breakers [3] [ll].One peculiar-
tions and voltage escalation is proportional to the arc ity of generator circuit breakers is that the switching of
angle and is very small. However, repeated reignitions load currents-irrespective of the load power factor-
and voltage escalation may be observed in vacuum gives rise to a transient recovery voltage corresponding
switching devices after opening operations due to their to the transient recovery voltage of a low power factor
ability to interrupt high frequency currents. The trans- circuit [5] [9].
former side capacitance and the magnitude of the load In the past, mainly air-blast and magnetic air cir-
shedding play a significant role in developing repeated cuit breakers have been used as generator circuit
reignitions and voltage escalation when vacuum circuit breakers. In the 1980's the first generator circuit
breakers are used as generator circuit breakers. Of par- breakers using SF6 gas as arc-extinguishing medium
ticular concern is the case when a protective capacitor were introduced into the market. Considerable ser-
is connected to the system side of the circuit breaker. vice experience is available for these types of circuit
Although this capacitor reduces the magnitude of the breakers which proves the suitability of these arc-
Dansient Recovery Voltage, it decreases the transient extinguishing principles for generator circuit breaker
frequencies and increases the reignition current that application.
flows through the vacuum circuit breaker after a volt- Recently, vacuum circuit breakers have also been
age breakdown. In all the cases under study, the reig- used as generator circuit breakers, especially for gen-
nition/escalation problems are more severe with the erators with ratings below 100 MW [7]. It is well
protective capacitor connected to the system for rela- known that during low power factor switching, e.g.
tive low load shedding at short arc angles. during the switching of stalled motors or during re-
actor switching, vacuum interrupters and the associ-
ated power system, under certain conditions, may in-
96 SM 402-8 PWRD A paper recommended and approved by the IEEE
Switchgear Committee of the IEEE Power Engineering Society for teract by interchanging energy in the form of multiple
-
presentation at the 1996 IEEWPES Summer Meeting, July 28 August reignitions that may lead to severe voltage escalation
1, 1996, in Denver, Colorado. Manuscript submitted December 12, [l] Therefore the question if and under what condi-
I995: macle availablefor printing ~ p n 1 2 31996.
, tions multiple reignitions and voltage escalation can
lected closer to the highest value of the range under ator circuit breaker model at different arc angles for
consideration. a distributed parameter isolated phase busbar model.
The generator voltage source is represented by a A 50 MVA generator, at full load current, high BV
sub-transient voltage behind a sub-transient induc- and high DI/DT circuit breaker characteristics with-
tance in series with a small resistance estimated ac- out protective capacitor have been considered. Mode
cording to an appropriate X/R ratio. This sub- terminations A or B refer to successful or unsuccessful
transient voltage is calculated by taking into account opening at the end of the reignition sequence, respec-
the first-pole-to-clear factor [3] [ll]. The power sys- tively. In mode termination A, the gap successfully re-
tem load has been set equal to the generator rated covers after a series of restrikes. In mode termination
current at unity power factor. Additionally, the gen- B, the gap fails to interrupt after the last reignition,
erator model includes a shunt capacitance in parallel terminating high frequency current clearings. In this
with a damping resistor. The damping resistor is dis- case, the final interruption is accomplished at the next
cussed in section 4. power frequency current zero [l].
The generator busbar model is a lumped circuit pa- Table 4 shows the responses under similar condi-
rameter model. It should be noted here that the gen- tions as those indicated for Table 3 but a lumped pa-
erator busbar have been assumed to be of the isolated rameter isolated phase busbar model ( T model) is used
phase bus type. Two identical T circuits at each cir- instead. Both bus models (distributed and lumped)
cuit breaker sides represent the lumped bus model. practically agree at the arc angle of 100 psec. Addi-
The lumped model was chosen instead of the dis- tionally, at lower arc angles the T bus model (Lumped
tributed model because the lumped model gave higher Parameters Cable Model) gives more severe responses
escalation voltages and higher number of reignitions with higher escalation voltages and higher number
in the preliminary simulations as it is seen by compar- of reignitions. Consequently, the T bus model was
ing tables 3 and 4. On the physical basis the lumped adopted as the worst case scenario.
parameter model is valid as long as the greatest fre- The transformer model consists of an inductance in
quency of interest has a period at least ten times larger series with a resistance estimated by an appropriate
than the travel time of the largest element in the model X/R ratio. The current through the transformer in-
[12]. The circuit parameters of the Isolated Phase Bus- ductance has been set to the generator rated current
bar (IPB) are calculated by a support program (Cable [3] [ll].Additionally, the transformer model includes
Constants) available in EMTP [SI. It is assumed that a shunt capacitance in pardlel with a damping resis-
busbars have a length of 20 m at each circuit breaker tor, in the low voltage side. This damping resistor
side for generator ratings less than 100 MVA. For gen- is discussed in section 4. Protective capacitors may
erator ratings between 100 and 300 MVA, a length of optionally be connected a t the low voltage terminal
50 m is assumed. of the transformer. Table 5 shows the inductances
Table 3 shows the responses of the vacuum gener- and shunt capacitances corresponding to each genera-
222
Table 6: ComDarison of Series and Parallel DamDine. Table 7: Summary of Critical Responses Calculated
Damping Escalation Voltage Reignitions Mode from E Tp. -
. , , I . (fisec.)
, (I<v) . (No.)
. . Load CP Esc.
t -% nF I<v BV DI/DT
Series -3.9460 4857.8 1 B
Parallel -6.5818 4986.0 27 B 100 100 26.0 H L
40 100 94.5 M L
20 100 66.2 M M
100-700 kHz) is increased if protective capacitors are 20 100 60.7 M M-L
connected to the system side of the vacuum genera- 20 300 53.5 M L
tor circuit breaker. The damping resistors, R, and 20 100 68.7 M M-L
Rt, associated with C, and Ct have been set to a 200 20 100 71.3 M M-L
value that limits the TRV to 1.5 times the steady state 228 20 100 84.5 M L
maximum recovery voltage [4]-[6].On the other hand, 20 100 60.4 M L
the same resistors have to provide lower damping fac-
tors for the high frequency reignition current which
is typically less damped than the TRV. One method the system side of the circuit breaker. For the 73
of solving this is to connect the generator and trans- MVA generator with 100 n F protective capacitor, for
former shunt capacitances (C,and Ct) in parallel with instance, there is no escalation/reignition problems
damping resistors (Rgpand Rt,), as shown in Figure 1. when 20 % of the rated load (15 MVA) is interrupted.
These parallel resistors provide the necessary damping However, escalation/reignition problems exist at 40 %
to limit the TRV and provide a lower damping at reig- load switching.
nition frequencies. If series resistors were chosen, the Definite rule of thumb for avoiding reignitions can
damping at high reignition frequencies would be too not be given because many factors are involved in the
high. escalation/reignition phenomenon. However, the mag-
Table 6 shows the responses of series and paral- nitude of the switched load and the capacitance on
lel damping resistors for a vacuum generator circuit the system side of the circuit breaker play a signif-
breaker model, with high BV and high DI/DT char- icant role. For the 143 MVA generator there is no
acteristics, and arc angle of 10 psec., for a generator voltage problem for 20 % load (29 MVA) switching,
of 50 MVA, at full load, without protective capacitor. even if a protective capacitor of 100 nF is connected
The high damping introduced by series resistances re- to the low voltage side of the step-up transformer.
duces multiple reignition currents through the circuit For higher protective capacitor values (300 nF) esca-
breaker. lation/reignition problems appear, as it is shown in
The discharge currents associated with the busbar Table No. 7.
capacitances and circuit breaker contact gap capaci- Figure 3 shows sample waveforms of the circuit
tance also influence the reignition behavior of the cir- breaker current (top trace) and voltage (bottom trace)
cuit breaker although their frequencies are very high. for the 200 MVA generator with protective capacitor
(100 nF) on the system side of the circuit breaker. The
5 Results of Simulations current is chopped to zero at approximately 4228 psec.
This paper presents the responses of the reignition The arc angle is in the range of 0 to 10 psec., the load
behavior of vacuum circuit-breakers when modelled in current is about 20 %, and the maximum escalation
EMTP for several generator ratings. On an average, voltage is only 1.15 kV.
108 cases per generator rating have been examined Figure 4 shows the escalation voltage as a function
with and without protective capacitors for different of the BV characteristics and DI/DT high frequency
loads, and different vacuum generator circuit breaker clearing capability of the vacuum circuit breaker
characteristics. Ten generators have been chosen in model for the 50 MVA generator with 100 nF pro-
the range from 50 to 300 MVA. tective capacitor when 100 % of the load is shed. The
Table No. 7 shows some of the critical vacuum gen- escalation voltage is highest for the BV characteristics
erator circuit breaker (VGCB) model responses (worst between 15 and 25 kV/ms (middle range).
cases). The escalation/reignition problem is most se- Figure 5 shows the escalation voltage as a function
vere when the load switched is in the range from 17 of the protective capacitor when 20 % of the rated load
to 52 MVA with a protective capacitor connected on is shed at an arc angle of 10 psec. for the 143 and 200
224
:::
30
ures G and 7 show the escalation voltage responses for
tlie 200 MVA generator and a vacuum ciicuit bIeal\er
iiiodel w i t h medium BV and low DI/DT cliaiacteiis-
tics Flgure 6 shows tlie escalatioil voltage as a func- W
0
tion of the aic angle when GO % of the iated load
loo0 dl/dl -1000 0 slopeof BV4 0
IS switched and a 100 nF piotective capacitoi IS col]-
iiected Figuie 7 shows tlie escalation voltage as a
function of the load current being switched at an arc
angle of 10 psec , and a protective capacltoi of 100 nF
is connected to the system side of the circuit bleakel Figure 4: Maximum Escalation Voltage for the 50
Figure 8 shows the escalation voltage as a fuiic- MVA Generator as a Function of the Vacuum Circuit
tion of the breakdown voltage strength ( A A paiame- Breaker Model Characteristics.
ter, also called k-factor El]) with low DI/DT clearing
80 1
capability for the 200 MVA generator The arc angle
is 10 psec., the load switched is 20 % of the rating,
and a 100 n F protective capacitor is connected to the
system side of the step-up transformer The escalation
voltages are more severe for medium range of k-factors
PI 121.
6 Conclusions
0 200 400 600
This paper assesses the possible overvoltages that Cp in nF
can develop across the vacuum generator circuit
Figure 5: Escalation Voltage vs. Protective Capacitor.
breaker during load shedding. The vacuum circuit
breaker is known for its excellent recovery rate after
current zero and for its ability to interrupt high fre-
quency reignition currents. Some combinations of vac-
uum circuit breaker characteristics (BV,DI/DT), load
current, and power plant equipment parameters may
lead to reignition/escalation problems. Experience in-
dicates that the reignitions are extremely rare events,
at worst they may occur 3.6 % of the time (arc angles
0-100 psec.) for 60 Hz, 3$ systems.
As a summary of this paper the -following conclu-
sions can be drawn: Arc angle in us
-1
References
Greenwood, A.N., and Glinkowski, M.T.,“ Volt-
2 age Escalation in Vacuum Switching Operations
”IEEE Ib-ansactions on Power Dehuery Volume
w“ 3, N0.4, 1111 1G98-17OG11987.
r“.t Gl~tiltowsk~, M T., Behavzor of Vacuum Siuztclizng
20 Deuzces for Short Gaps , Ph D Thesis, December
1989, Rensselaei Polyteclinic Institutc, Tioy, New
0
0 YOrk
k-factor in V/us
IEEE Standard C37.013-1993, IEEE Standard
Figure 8: Escalation Voltage vs. Breakdown Voltage for AC High- Voltage Generator Circuit Breakers
Strength. Rated on a Symmetrical Current Basis.
Thuries E., Pham, V.D., Vadaszi, J., and Bor-
gonovo, J., “ Generator Circuit-Breaker Transient
1. Under certain conditions the escalation of volt-
Recovery Voltage in Most Severe Short-Circuit
age across the vacuum generator circuit breaker is
Conditions,” Electra, No.113, pp. 43-50, 1987.
possible when it is used for load shedding. In the
worst case, high overvoltages may be generated Thuries E., Pham, V.D., Vadaszi, J., and Bor-
gonovo, J., ‘‘ Generator Circuit-Breaker Dansient
~