The default settings for the parameters are programmed at the factory. The parameter settings for
the engine monitoring system can be viewed on Caterpillar Electronic Technician (ET). For
information that is related to the engine monitoring system, refer to Troubleshooting, "Engine
Monitoring System".
Table 4
Trip Points for the Monitoring System
Level of Delay
Trip Point and Enabling Derate
Event Code Severity Time in
Conditions (%)
Seconds
(1) N/A
108 °C (226 °F)
(3) N/A
115 °C (239 °F)
70 °C (158 °F)
In order to enable this event,
the engine must be running
E199 Low Coolant for ten minutes and the
(1) 120 N/A
Temperature coolant temperature must
exceed
75° C (167° F) before the
temperature returns to the
trip point.
E278 High
Exhaust (2)
(2) N/A
Differential 50° C (122° F)
Temperature
(1) N/A
100 °C (212 °F)
E361 High Engine
Map Dependent
Coolant (2) 10
101 °C (214 °F) Values
Temperature
(3)
E1044 High Intake (1)
Manifold Pressure 8 25
(3)
(2)