Professional Documents
Culture Documents
INSTALLATION MANUAL
Installation manual
English
VRVIII-C System air conditioner
Installationsanleitung
Deutsch
VRVIII-C System Klimaanlage
Manuel d’installation
Français
Conditionneur d’air VRVIII-C System
Рóêоводство по монтажó
Ðóññêèé
Кондиционер системы VRVIII-C
[System] Bruksanvisning
Norsk
RTSYQ10PY1 VRVIII-C System Klimaanlegg
RTSYQ14PY1
RTSYQ16PY1 Bruksanvisning
Svenska
RTSYQ20PY1 VRVIII-C System luftkonditionerare
[Independent units]
RTSQ8PY1 Polski
RTSQ10PY1
RTSQ12PY1
RTSQ14PY1
RTSQ16PY1
BTSQ20PY1
DAIKIN INDUSTRIES, LTD.
RXYQ5PY1(E), RXYQ8PY1(E), RXYQ10PY1(E), RXYQ12PY1(E), RXYQ14PY1(E), RXYQ16PY1(E), RXYQ18PY1(E), REYQ8PY1, REYQ10PY1, REYQ12PY1, REYQ14PY1, REYQ16PY1,
RXYQ20PY1(E), RXYQ22PY1(E), RXYQ24PY1(E), RXYQ26PY1(E), RXYQ28PY1(E), REYQ18PY1, REYQ20PY1, REYQ22PY1, REYQ24PY1, REYQ26PY1, REYQ28PY1, REYQ30PY1, REYQ32PY1,
RXYQ30PY1(E), RXYQ32PY1(E), RXYQ34PY1(E), RXYQ36PY1(E), RXYQ38PY1(E), REYQ34PY1, REYQ36PY1, REYQ38PY1, REYQ40PY1, REYQ42PY1, REYQ44PY1, REYQ46PY1, REYQ48PY1,
RXYQ40PY1(E), RXYQ42PY1(E), RXYQ44PY1(E), RXYQ46PY1(E), RXYQ48PY1(E), REYQ8PY1B, REYQ10PY1B, REYQ12PY1B, REYQ14PY1B, REYQ16PY1B,
RXYQ50PY1(E), RXYQ52PY1(E), RXYQ54PY1(E), REMQ8PY1, REMQ10PY1, REMQ12PY1, REMQ14PY1, REMQ16PY1,
3P216950-1D.fm Page 1 Tuesday, March 31, 2009 1:44 PM
EN60335-2-40,
DAIKIN.TCF.024D11/02-2009
0510260101
Shinri Sada
Manager Quality Control Department Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
1st of Mar. 2009 Kita-Ku, Osaka, 530-8323 Japan
3P216950-1D
00_CV_3P201178-10P.fm Page 2 Wednesday, September 2, 2009 11:09 AM
1 2
RTSQ8~12 RTSQ14 ·16 BTSQ20 (unit: mm)
3 3
≥10
≥300
≥300
1 ≥10 9 ≥10 ≥10 9
1
2 2
2 50~100 ≥20 50~100
≥500
≥500
8 8
6 6
4 4
≥10
≥100
≥100
figure 1 ≥50 9 ≥50 ≥10 9
≥500
≥500
1 8 8
6 6
2
5
2
≥1500
≥1000
3 5 5
≥1000
2 7
≥300
≥300
6
≥1500
≥1500 ≥200 ≥200 ≥200 ≥400 ≥200
4
(unit: mm) 6 6
figure 3 figure 2
5 3
3 4 4 3
3 4 3
4
4
6 2 5
1 2 1
figure 4 figure 5
460
A 5
300
B
≥765
00
765
729
631
≥1 00
3
≥1
765
727
00 0 0
≥1 ≥1
00 00
≥1 2 ≥1 2
1 1
figure 6 figure 7
4
1 4
6
7
3
2
1 2 6 9
3
4 5 3
4
5 5
8 8
3 5
1 2
1 2
3 4 3 4
10
5 8
13
13 13
4 13
3 8
7
7 3 5 6
4 9 7
2 13
10 11
6 13
11
2 2 9 14 9
14
1 1 12 12
1 2
1 2
4 5 4 5
3 3 13 11 11
14
11 8
11
8 14 9 11 8
14 7
14 3 11 7 11
14 8
6 11 14 11 11 6
4
7
10
13 9 5 11
14 10 12 3
9 13
12 12 13 10
9 10 9
10
figure 14 figure 15
1 A
2 1 B
2
3 8 7
4 7 1
1
5 1 8
7 2 3
4 4
266
6 5 6
17-1 17-2 17-3
figure 16 figure 17
1 5 5 6
3 4
A 1 2 3
5 2
3 4 4
figure 18 1
ED ED ED ED ED
2
7 8
1
B 2
figure 19 figure 20
1 2
2 3 4 5 6 4
1 3 10
15 15 A1P A1P A1P A1P A1P
10 12 17 16 TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT TO MULTI UNIT TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT TO MULTI UNIT TO MULTI UNIT
11 13 F1 F2 F1 F2 Q1 Q2 Q1 Q2 F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q1 Q2
18
7
14
5 9 9 7 9
9 9 7
4
6 7 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2
8
8 8
10
figure 21 figure 22
00_CV_3P201178-10P.fm Page 4 Wednesday, September 2, 2009 11:09 AM
3 3
(A1P)
(A1P)
1 2
5
6 4 4
6
F1 F2 F1 F2 F1 F2
5
4 2
3 1
F1 F2 F1 F2
1 2
5 7
7 L1 L2 L3 N
6 11
11
L1 L2 L3 N
1 1 4
3 3 12
8 2 2 8
4 4
4 9
9
ED ED
9 10
10
figure 26
1 17 6 2
1
6
9
9 16
4
7 7 8
5 2
10 6
8 8 3
3 3 10
4 4
5
15 9
19 15
13 11 18 12 13 14 7
11 12 14
figure 27 figure 28
1 4
10 5
11 12 1
9 13 15 1
1 8 3
6 1
7 14
3 16
2
17
4
20
5
: 21 : 23 19 2
: 22 : 24 18
2 6
3 7
1 7
7 1 6 8 9 10 12
5 8 3 5
1 6 2
4
2 13 11
1
14
3 2
5 16
3
9 10 : 17 : 19
4 4 15
: 18 : 20
RTSYQ10PY1 RTSYQ20PY1
TWO-STAGE COMPRESSION
RTSYQ14PY1
VRV System air conditioner
Installation manual
RTSYQ16PY1
1 English
01_EN_3P201178-10P.fm Page 2 Wednesday, September 2, 2009 11:10 AM
English 2
01_EN_3P201178-10P.fm Page 3 Wednesday, September 2, 2009 11:10 AM
• The indoor units that combined with RTSYQ-P system for air con-
ditioning are Daikin VRV series indoor units that compatible with Gas side accessory pipe
Name
R410A. To learn which indoor units are compatible with R410A, (1) (2) (3) (4)
refer to the product catalogs. To combine with other refrigerant 8 type 1 pc. 2 pcs.
indoor unit will cause malfunction.
Quantity
10 type 2 pcs.
1 pc. 1 pc.
12 type 2 pcs.
2-2 Technical and Electrical specifications
14 · 16 type 3 pcs. 2 pcs.
Refer to the Engineering Data Book for the complete list of specifica-
tions.
Shape
2-3 Main components
For main components and function of the main components, refer to φ25.4 φ22.2
the Engineering Data Book.
Equalizer side
2-4 Combination Liquid side accessory pipe accessory pipe
Name
• The following table shows a list of system names, system config- (1) (2) (3) (1) (2)
uration models, and the capacity of each connectable indoor unit.
8 type 2 pcs. 1 pc.
<Single outdoor unit system>
Quantity
10 type 2 pcs.
1 pc. 1 pc.
Composition unit Total capacity 12 type 1 pc. 2 pcs.
System name
Outdoor unit Function unit of indoor units 14 · 16 type 2 pcs.
3 English
01_EN_3P201178-10P.fm Page 4 Wednesday, September 2, 2009 11:10 AM
<Front side> <Suction side> from coming off and rust from occurring when bringing the unit
using a forklift.
h1
h2 Service h1
1500
500 + space
+
2 2
or more or more (4) After the outdoor unit is installed, remove the transportation
500
English 4
01_EN_3P201178-10P.fm Page 5 Wednesday, September 2, 2009 11:10 AM
(Refer to figure 5) Thickness :Select a thickness for the refrigerant piping which
1. Fork insertion place (outdoor unit only) complies with national and local laws.
2. Fork For R410A, the design pressure is 4.0 MPa (40-
3. Opening (large) bar).
4. Transportation bracket (yellow) The minimum thickness of piping according to
5. Hook of transportation bracket Japan’s High-Pressure Gas Safety Law (as of
January 2003) is shown below.
Temper grade (O type, 1/2H type) in the table indi-
5. PLACING THE UNIT cate the material types specified in JIS H 3300.
(unit : mm)
• Make sure the unit is installed level on a sufficiently strong base to
prevent vibration and noise. (Refer to figure 6 and 7) Temper grade O type
• The base should support the unit with the extent larger than outer diameter φ6.4 φ9.5 φ12.7 φ15.9
hatched area in figure 6 and 7. smallest thickness 0.80 0.80 0.80 0.99
If protective rubber is to be attached, attach it to the whole face of
(unit : mm)
the base.
• The height of the base should be at least 150mm from the floor. Temper grade 1/2H type
• Secure the unit to its base using foundation bolts. (Use four com- outer diameter φ19.1 φ22.2 φ25.4 φ28.6 φ31.8 φ34.9 φ38.1 φ41.3
mercially available M12-type foundation bolts, nuts, and washers.) smallest thickness 0.80 0.80 0.88 0.99 1.10 1.21 1.32 1.43
• The foundation bolts should be inserted 20 mm.
• For piping work, follow the maximum tolerated length, difference
20
(Refer to figure 6) in height, and length after a branch indicated in the “6-5 Example
1. Basic shape of outdoor unit and position of of connection”.
foundation bolt • Outdoor unit multi connection piping kit and refrigerant branching
2. Center of product kit (sold separately) are needed for connection of piping between
3. Product depth outdoor units (in case of multi system) and piping branches.
4. Basic size Use only separately sold items selected specifically according to
5. Four, 15 × 22.5 eclipse hole (foundation bolt hole) the outdoor unit multi connection piping kit, the refrigerant branch-
Model A B ing kit selection in the “6-5 Example of connection”.
RHSQ8 · 10 · 12 Type 930 792
6-2 Protection against contamination
RHSQ14 · 16 Type 1240 1102 when installing pipes
(Refer to figure 7) Protect the piping to prevent moisture, dirt, dust, etc. from
1. Basic shape of function unit and position of foundation entering the piping.
bolt Place Installation period Protection method
More than a month Pinch the pipe
Note Outdoor
Less than a month
• When installing on a roof, make sure the roof floor is strong
Regardless of the Pinch or tape the pipe
enough and be sure to water-proof all work. Indoor
period
• Make sure the area around the machine drains properly by setting
up drainage grooves around the foundation. Note
Drain water is sometimes discharged from the outdoor unit when Exercise special caution to prevent dirt or dust when passing pip-
it is running. ing through holes in walls and when passing pipe edges to the
exterior.
5 English
01_EN_3P201178-10P.fm Page 6 Wednesday, September 2, 2009 11:10 AM
English 6
01_EN_3P201178-10P.fm Page 7 Wednesday, September 2, 2009 11:10 AM
9. Piping on liquid side (procured locally) (2) Install the piping between the outdoor units horizontally or
10. Piping on gas side (procured locally) with a rising gradient toward outdoor unit A from outdoor unit
11. Blazing B in order to prevent oil remaining in the piping.
12. To outdoor unit
13. To indoor unit Pattern 1
(*1) RTSQ14P and RTSQ16P units only (procured locally for others)
Front connection Outdoor unit Function unit
(*2) RTSQ12P unit only (procured locally for other)
(*3) RTSYQ14P to RTSYQ20P systems only (procured locally for Level
Unit Unit
A B
others) To indoor unit
Piping between
(*4) <For RTSYQ14P and RTSYQ16P systems>
units
Refer to figure 16 and the following table, and cut the gas side
accessory pipe (3). Outdoor unit Function unit
Bottom connection
<RTSYQ20P system> Unit Unit
A B
Refer to the installation manual of the outdoor unit connection To indoor unit
piping kit and cut the gas side accessory pipe (3). Piping between
units
(Refer to figure 16)
1. Gas side accessory pipe (3) (Indoor side) Pattern 2
2. Cut to 130 mm.
3. Gas side accessory pipe (3) (Outdoor side) Front connection Outdoor unit Function unit
4. Cut to 73 mm. Unit Unit
5. Function unit Rising A B
gradient To indoor unit
6. Outdoor unit
7. Connecting piping on gas side (procured locally) Rise
8. To indoor units Outdoor unit Function unit
Bottom connection
Required dimensions for gas side Unit Unit
A B
System name accessory pipe (3)
To indoor unit
Outdoor side Indoor side Rise
RTSYQ14 · 16P
73mm 130mm Change to pattern 1 or pattern 2
type
Prohibited pattern
Note
• The dimensions shown in above table are required when installing Outdoor unit Function unit
Front connection
the piping (procured locally) on the gas side of the outdoor unit in Unit Unit
the position shown in figure 16. Downward A B To indoor unit
Refer to the table above and make necessary size adjustment if inclination
the working conditions of the on-site piping on the gas side differ. Downward inclination
Oil remains in piping
4. Piping Connections between Outdoor Units (for Multi Outdoor
Outdoor unit Function unit
Unit System Only) Bottom connection
• Observe the restrictions specified below to connect the outdoor Unit Unit
A B
units.
• The outdoor unit multi connection piping kit (sold separately) is
required for the connection of the piping between the outdoor Downward inclination
units. For the installation of the outdoor unit multi connection pip- Oil remains in piping
ing kit, refer to the installation manual provided with the kit. Unless
the kit is installed properly, the outdoor units may malfunction or (3) To avoid the risk of oil detention in the stopping unit, always
fail to operate. connect the shutoff valve and the piping between outdoor
(1) About outdoor unit multi connection piping kit units as shown A or B in the figure below.
• Install the joint horizontally so that the attached warning
label faces strait up, and the tilt is within ±15°.
(Refer to figure 17-1)
Do not install vertically. (Refer to figure 17-2) A
• Maintain a straight portion of 500 mm or more until the split
of the joint without wrapping any onsite piping around this B A
area.
Over 500 mm of straight area can be maintained by con- B
necting at least 120 mm of onsite pipe (straight) to the joint. Front connection Bottom connection
(Refer to figure 17-3)
(Refer to figure 17)
1. Warning label
2. Horizontal surface
3. ±15° or less
4. Ground
5. A-arrow view
6. B-arrow view
7. Onsite pipe (120mm length or more)
8. Straight part of 500mm or more
7 English
01_EN_3P201178-10P.fm Page 8 Wednesday, September 2, 2009 11:10 AM
Unit Unit
B B
Unit Unit
A A
Rising height :
200 mm or more
1. Connect straightly 2. Put rising
If less than 2m
If 2 m or more
English 8
9
Example of connection Branch with REFNET joint Branch with REFNET joint and header Branch with REFNET header
(Connection of 8 indoor units)
(*1) “ ” Indicate the Outdoor unit multi Function unit Outdoor Function unit Outdoor Function unit
Outdoor unit unit unit
connection piping kit.
H4
(*2) In case of multi outdoor system,
H4
H4
re-read “outdoor unit” to “Outdoor unit
multi connection piping kit” as seen REFNET joint
from the indoor unit. Single a
a (A, B) a
outdoor b REFNET joint b REFNET header
j
system (A~G) b
A B
H1
H1
6-5 Example of connection
H1
c d e f g h c
REFNET
header k
A B C D E F G
H2
i j k m n p q 7 8 c d e f g h i j
H2
d e f g h i
1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 3 4 5 6 7
8 8
H2
Outdoor unit Function unit Outdoor unit Function unit Outdoor unit Function unit
H3
H3
H3
H4
H4
H4
REFNET joint
r a r a (A, B) r a
Multi b b
b REFNET joint j REFNET header
outdoor
s (A~G) s s
system A B
H1
c d e f g h c
H1
H1
REFNET
header k
A B C D E F G
i j k m n p q 7 8
H2
H2
d e f g h i c d e f g h i j
1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 3 4 5 6 7
8 8
H2
Actual pipe Pipe length between outdoor unit (*2) and indoor unit ≤ 165m
length Example 8 : a + b + c + d + e + f + g +h +q ≤ 165m Example 6 : a + b + c + i ≤ 165m, 8 : a + b + j + ≤ 165m Example 8 : a + b + j ≤ 165m
Between outdoor unit (*2)
Equivalent Equvalent pipe length between outdoor unit (*2) and indoor unit ≤ 190m (Note 1)
Maximum and indoor unit
length (Assume eqivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, that of function unit to be 6m for calculation purposes)
allowable
length Total extention length Total piping length from outdoor unit (*2) to all indoor unit ≤ 500m
Between outdoor unit and function unit Actual and Actual pipe length from outdoor unit to function unit, that from first outdoor unit multi connection piping kit to outdoor unit ≤ 10m Function unit
Between outdoor unit and outdoor unit Equivalent Equivalent pipe length from outdoor unit to function unit, that from first outdoor unit multi connection piping kit to outdoor unit ≤ 13m Outdoor unit
multi connection piping kit pipe length a ≤ 10m
(Equivalent length ≤ 13m)
Allowable Between outdoor and indoor units Difference in height Difference in height between outdoor unit and indoor unit (H1) ≤ 50m (Max 40m if the outdoor unit is below)
r ≤ 10m
height Between indoor and indoor units Difference in height Difference in height between indoor units (H2) ≤ 15m (Equivalent length ≤ 13m)
difference Between outdoor and outdoor units s r a
Difference in height Difference in height between outdoor units (H3) ≤ 5m s ≤ 10m
Between outdoor unit and function unit Difference in height Difference in height between outodoor unit and function unit (H4) ≤ 1m (Equivalent length ≤ 13m)
Actual pipe Actual pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit ≤ 40m (Note 2)
Allowable length after the branch
length Example 8 : c + d + e + f + g + h + q ≤ 40m Example 6 : c + i ≤ 40m, 8 : j + ≤ 40m Example 8 : j ≤ 40m
English
English
Outdoor unit multi connection piping kit and How to select the REFNET joint How to select the REFNET header
Refrigerant branch kit selection When using REFNET joint at the first branch counted from the outdoor unit side, Choose from the following table in accordance with the total capacity index of all
choose from the following table in accordance with the outdoor system capacity the indoor units connected below the REFNET header.
type. (Example : REFNET joint A) 250 type indoor unit can not be connected below the REFNET header.
• Refrigerant branch kits can only be used with R410A.
• When multi outdoor system are installed, be sure to use the Outdoor system capacity type Refrigerant branch kit name Indoor unit total capacity index Refrigerant branch kit name
special separately sold Outdoor unit multi connection piping 10HP type KHRP26A33T x < 200 KHRP26M22H or KHRP26A33H
kit. (BHFP30A56). 14~20HP type KHRP26A72T 200 ≤ x < 290 KHRP26M33H
(For how to select the proper kit, follow the table at right.) 290 ≤ x < 640 KHRP26M72H
Choose the REFNET joints other than the first branch from the following table in 640 ≤ x KHRP26M73H + KHRP26M73HP
accordance with the total capacity index of all the indoor units connected below
the REFNET joint. How to select the outdoor unit multi connection piping kit
Indoor unit total capacity index Refrigerant branch kit name (This is required when the system is multi outdoor unit system.)
x < 200 KHRP26A22T Choose from the following table in accordance with the number of outdoor units.
200 ≤ x < 290 KHRP26A33T Number of outdoor unit Connecting piping kit name
290 ≤ x < 640 KHRP26A72T 2 units BHFP30AP56
Example for indoor units Example REFNET joint B : Indoor units 7 + 8 Example REFNET header :
connected downstream Example REFNET joint C : Indoor units 3 + 4 + 5 + 6 + 7 + 8
Example REFNET header : Indoor units 1 + 2 + 3 + 4 + 5 + 6 Indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
Pipe size selection Piping between outdoor unit (*2) and refrigerant branch kit (part A) Piping between refrigerant branch kits
Choose from the following table in accordance with the outdoor unit system capacity type. Choose from the following table in accordance with the total capacity type of all the
(unit : mm) indoor units connected downstream.
01_EN_3P201178-10P.fm Page 10 Wednesday, September 2, 2009 11:10 AM
The thickness of the pipes in the table shows Do not let the connection piping exceed the main refrigerant piping size (Part A).
the requirements of Japanease High Pressure Outdoor system Piping size (O. D.) If the piping size selected from the following table exceeds the piping size of part A,
Gas Controll low. (As of Jan. 2003) capacity type Gas pipe Liquid pipe decide the piping size in either of the following methods.
The thickness and material shall be selected in 10HP type φ22.2 φ9.5 (1) Reduce the size of the connection piping to the piping size of part A.
accordance with local code. 14,16HP type φ12.7 (2) Replace the piping of part A with piping that is a size larger (see the table in
φ28.6
20HP type φ15.9 Note 1) so that it will be the same as the size of the connection piping.
<In case of single outdoor unit system> (unit : mm)
Outdoor unit Piping size (O. D.)
Indoor capacity index
Piping between outdoor unit multi connection piping kit and outdoor unit (part B) Gas pipe Liquid pipe
Function unit Choose from the following table in accordance with the capacity type of x < 150 φ15.9
the outdoor unit connected. (unit : mm) 150 ≤ x < 200 φ19.1 φ9.5
Outdoor unit Piping size (O. D.) 200 ≤ x < 290 φ22.2
capacity type Gas pipe Liquid pipe 290 ≤ x < 420 φ12.7
Piping between outdoor unit and φ28.6
RTSP8 type φ22.2 φ9.5 420 ≤ x < 640 φ15.9
refrigerant branch kit (part A)
RTSP12 type φ28.6 φ12.7
Piping between refrigerant branch kit, and indoor unit
<In case of multi outdoor unit system> Match to the size of the connection piping on the indoor unit. (unit : mm)
Outdoor unit Piping size (O. D.)
Indoor unit capacity type
Gas pipe Liquid pipe
Function unit
20 · 25 · 32 · 40 · 50 type φ12.7 φ6.4
63 · 80 · 100 · 125 type φ15.9
200 type φ19.1 φ9.5
250 type φ22.2
Piping between Equalizer pipe (part D) (multi outdoor unit system only) (unit : mm)
outdoor unit (*2) and Piping size (O. D.) φ19.1
refrigerant branch
kit (part A)
Temper grade and wall thickness for pipes
Piping between outdoor unit and (Temper grade, O type and 1/2H type indicate the material type specified in JIS H 3300.)
outdoor unit multi connection Copper tube O. D. φ6.4 φ9.5 φ12.7 φ15.9 φ19.1 φ22.2 φ25.4 φ28.6 φ31.8 φ34.9 φ38.1 φ41.3
piping kit (part B)
Temper grade O type 1/2H type
Equalizer pipe (part C) Wall thickness
(Min. requirement) 0.80 0.80 0.80 0.99 0.80 0.80 0.88 0.99 1.10 1.21 1.32 1.43
10
11
How to calculate the
additional refrigerant Total length(m) Total length(m) FOR THE SYSTEM
to be charged R= of liquid piping 0.37 of liquid piping 0.26 SYSTEM NAME THE AMOUNT OF REFRIGERANT
size at φ22.2 size at φ19.1
RTSYQ10PY1 —
Additional refrigerant to Total length(m) Total length(m)
be charged : R(kg) of liquid piping 0.18 of liquid piping 0.12 RTSYQ14PY1 1.3kg
size at φ15.9 size at φ12.7
R should be rounded
off in units of 0.1 kg. RTSYQ16PY1 2.3kg
Total length(m) Total length(m)
of liquid piping 0.059 of liquid piping 0.022
size at φ9.5 size at φ6.4 RTSYQ20PY1 —
Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below.
System : RTSYQ20PY1
a : φ15.9 × 10m e : φ6.4 × 10m i : φ6.4 × 10m r : φ12.7 × 5m
Independent outdoor unit : RTSQ8PY1, RTSQ12PY1
b : φ15.9 × 30m f : φ6.4 × 20m j : φ9.5 × 20m s : φ9.5 × 10m
Function unit : BTSQ20PY1
c : φ12.7 × 20m g : φ6.4 × 20m k : φ9.5 × 10m
d : φ6.4 × 10m h : φ6.4 × 10m : φ9.5 × 10m
Required Conditions Example Drawings (In case of “Branch with REFNET joint”)
1. It is necessary to increase the pipe size between the first branch kit 8 c + d + e + f + g + h + q ≤ 90 m Increase the pipe size as follows
and the final branch kit. (Reducers must be procured on site) increase the pipe size of c, d, e, f, g, h φ 9.5 → φ12.7 φ15.9 → φ19.1 φ22.2 → φ25.4* φ34.9 → φ38.1*
However, the pipes that are same pipe size with main pipe must not φ12.7 → φ15.9 φ19.1 → φ22.2 φ28.6 → φ31.8*
be increased.
2. For calculation of Total extension length, the actual length of a+b+c×2+d×2+e×2+f×2+g×2 Outdoor unit Function unit REFNET joint
above pipes must be doubled. (except main pipe and the + h × 2 + i + j + k + + m + n + p + q ≤ 500 m (A~G)
pipes that are not increased) a
3. Indoor unit to the nearest branch kit ≤ 40 m i, j....... p, q ≤ 40 m b c d e f g h
A B C D E F G q
4. The difference between The farthest indoor unit 8 i j k m n p
[Outdoor unit to the farthest indoor unit] and [Outdoor unit The nearest indoor unit 1 1 2 3 4 5 6 7
Indoor units ( 1 - 8 ) 8
to the nearest indoor unit] ≤ 40 m ( a + b + c + d + e + f + g + h + q ) - ( a + b + i ) ≤ 40 m
*If available on the site, use this size. Otherwise it can not be increased.
English
01_EN_3P201178-10P.fm Page 12 Wednesday, September 2, 2009 11:10 AM
English 12
01_EN_3P201178-10P.fm Page 13 Wednesday, September 2, 2009 11:10 AM
7-3 Leading wire Procedure • All transmission wiring should use sheathed vinyl cord
• The power wiring and ground wiring are passed out from the 0.75-1.25 mm2 or cable (duplex).
power wiring hole on the sides, the front (knock hole) or the bot- • Transmission wiring should be done within the following limita-
tom frame (knock hole) . tions.
• The transmission wiring is passed out from the wiring hole (knock If they are exceeded, transmission problems may occur.
hole) on the front of the unit or from a piping hole. Between outdoor unit and indoor unit
Between outdoor unit and outdoor unit of other systems
(Refer to figure 21)
Max. wiring length :1,000 m
1. Outdoor unit
Max. total wiring length :2,000 m
2. Function unit
Max. no. of branches :16
3. Electric wiring diagram (Rear side of EL.COMPO.BOX
[Note]
lid)
No branch is allowed after branch (See figure 23)
4. Power wring and ground wiring
Max. no. of outdoor units of other system
5. Conduit
that can be connected
6. Piping outlet
: 10
7. Transmission wiring
Between outdoor unit and function unit
8. To Indoor unit and function unit
Between outdoor unit and outdoor unit of same system
9. Wiring inlet (front)
Max.wiring length :30 m
10. Through cover
11. Cut off the hatching parts. (Refer to figure 23)
12. Power wiring and ground wiring 1. Branch
13. Inside conduit 2. Branch after branch
14. To outdoor unit • The transmission wiring inside the EL.COMPO.BOX should be
15. Knock hole secured using the clamp (1) as shown in figure 24.
16. For transmission wring
17. For power wiring and ground wiring (Refer to figure 24)
18. Burr 1. Outdoor unit
2. Function unit
Note 3. Inside EL.COMPO.BOX
• Open the knock holes with a hammer or the like. 4. Fix two portions in the EL.COMPO.BOX with the
• After knocking out the holes, we recommend you remove any included clamp (1).
burrs and paint them using the repair paint to prevent rusting. 5. Fix a single portion in the EL.COMPO.BOX with the
(Refer to figure 21) included clamp (1).
• When passing wiring through the knock holes, remove burrs 6. Never connect power wiring.
around the knock holes and protect the wiring with conduit or pro-
tective tape. • Outside the units, the transmission wiring must be finished simul-
• If small animals might enter the unit, block off any gaps (hatching taneously with the local refrigerant piping, and wound with tape
parts in figure 21) with material (field supply). (field supply) as shown in figure 25.
(Refer to figure 25)
7-4 Transmission Wiring Connection Procedure 1. Gas pipe
• Referring to figure 22 connect the transmission wiring between 2. Liquid pipe
outdoor unit and function unit, outdoor unit and outdoor unit of 3. Transmission wiring
same system (Only in case multi outdoor unit system), outdoor 4. Insulation material
unit and indoor unit, outdoor unit and outdoor unit of other system. 5. Finishing tape
(Refer to figure 22) • Wiring to other systems should be connected to terminals F1 and
1. For single outdoor unit system F2 (TO OUT/D UNIT) on the PC-board of the unit. Connecting the
2. For multi outdoor unit system wires to the Q1, Q2 (TO MULTI UNIT) terminals results in mal-
3. Outdoor unit function.
4. Function unit
5. Master outdoor unit A (*)
7-5 Power Wiring Connection Procedure
6. Slave outdoor unit B (*) • Be sure to connect the power supply wiring to the power supply
7. To outdoor unit in other refrigerant system terminal block and hold it in place using the included clamp (1) as
8. Indoor unit shown in the figure 26.
9. Use 2-core cable (with no polarity). • The ground wiring should be bound to the power wiring using the
10. Never connect power wiring. included clamp (1) to prevent outside force from being applied to
(*) In the case of the multi outdoor unit system, the outdoor the terminal.
unit connecting the transmission wiring to the indoor unit (Refer to figure 26)
(outdoor unit A in figure 22) is the master and the other 1. Power supply (3N ~ 50 Hz, 380 - 415 V)
outdoor unit is the slave. Operate the control PCB (A1P) 2. Earth leakage circuit breaker
of the master for commissioning at the time of installation 3. Fuse
or local settings at the time of servicing. 4. Ground wiring
5. Outdoor unit
Note
• Do not connect the power wiring to terminals for the transmission 6. Function unit
wiring. Doing so would destroy the entire system. 7. Power supply terminal block
• When connecting wires to the terminal block on the PC-board, too 8. Ground terminal
much heat or tightening could damage the PC-board. Attach with 9. Clamp (1) (accessories)
care. 10. Power wiring and ground wiring (to power supply)
See the table below for the tightening torque of the transmission 11. Attach the insulating sleeve.
wiring terminals. 12. Lay and connect from the upper side
13 English
01_EN_3P201178-10P.fm Page 14 Wednesday, September 2, 2009 11:10 AM
English 14
01_EN_3P201178-10P.fm Page 15 Wednesday, September 2, 2009 11:10 AM
<The system for air tight test and vacuum drying> (2) If the pressure does not reach –100.7 kPa even after depressur-
• Referring to figure 29, connect an nitrogen tank, refrigerant tank, izing for at least two hours, repeat the vacuum breakdown - vac-
and a vacuum pump to the outdoor unit and function unit. uum drying process.
The refrigerant tank and the charge hose connection to refrigerant (3) After then, maintain the vacuum for an hour and make sure the
charge port or the valve A in figure 29 are needed in “9. ADDI- pressure does not rise by monitoring with a vacuum gauge.
TIONAL REFRIGERANT CHARGE AND CHECK OPERATION”.
(Refer to figure 29)
8-2 Pipe insulation
1. Gauge manifold • Insulation of pipes should be done after performing “8-1 Air tight
2. Nitrogen test and vacuum drying”.
3. Measuring device • Always insulate the liquid pipe, gas pipe and equalizer pipe (the
4. R410A tank (with siphon) piping between the outdoor units in the case of the multi outdoor
5. Vacuum pump unit system) and these pipe connections. Failing to insulate the
6. Charge hose pipes may cause leaking or burns.
7. Refrigerant charge port And be sure to use the insulation which can withstand such tem-
8. Liquid pipe shutoff valve peratures of 120°C or more for the gas piping because the high
9. Gas pipe shutoff valve pressure gas follows in these pipings.
10. Equaliger pipe shutoff valve • Thermal insulate the liquid pipe and gas pipe of the function unit
11. Outdoor unit A up to the point immediately before the piping support in the func-
12. Outdoor unit B (for multi outdoor unit system) tion unit. (Refer to figure 30)
13. Function unit • If there is a possibility that condensation on the shutoff valve
14. Liquid pipe service port might drip down into the indoor unit through gaps in the insulation
15. Gas pipe service port and piping because the function unit is located higher than the
16. Valve A indoor unit, etc., this must be prevented by caulking the connec-
17. Valve C tions, etc. (Refer to figure 30)
18. Valve B (Refer to figure 30)
19. The equalizer piping requires an airtight test and vacuum 1. Piping support
drying only for the multi outdoor unit system. 2. Gas pipe (to outdoor unit)
20. To indoor unit 3. Liquid pipe (to outdoor unit)
21. Local piping 4. Thermal insulator end (4 points)
22. Airflow 5. Perform caulking processing.
23. Shutoff valve 6. Liquid pipe (to indoor unit)
24. Service port 7. Gas pipe (to indoor unit)
<Air tight test> • Reinforce the insulation on the refrigerant piping according to the
Pressurize the liquid pipe, gas pipe and the equalizer pipe (for the installation environment. Condensation might form on the surface
multi outdoor unit system only) from the each shutoff valve ser- of the insulation. Refer to the below.
vice ports of outdoor unit and the service ports of function unit to Ambient temperature : 30°C, humidity : 75% to 80% RH : min.
4.0 MPa (40 bar) (do not pressurize more than 4.0 MPa (40 bar)). thickness : 15mm.
If the pressure does not drop within 24 hours, the system passes If the ambient temperature exceeds 30°C and the humidity
the test. 80% RH, then the min. thickness is 20mm.
If there is a pressure drop, check for leaks, make repairs and per- See the Engineering data book for detail.
form the airtight test again. • The piping lead-out hole lid should be attached after opening a
<Vacuum drying> knock hole.
Evacuate the liquid pipe, gas pipe and the equalizer pipe (for the If small animals and the like might enter the unit through the pip-
multi outdoor unit system only) from the each shutoff valve service ing lead-out hole, close the hole with blocking material (procured
ports of outdoor unit and the service ports of function unit by using on site) after completion of “9. ADDITIONAL REFRIGERANT
a vacuum pump for more than 2 hours and bring the system to CHARGE AND CHECK OPERATION”. (Refer to figure 31)
–100.7 kPa or less. After keeping the system under that condition (Refer to figure 31)
for more than 1 hour, check if the vacuum gauge rises or not. If it 1. Piping lead-out hole lid
rises, the system may either contain moisture inside or have leaks. 2. Open a knock hole at “ ”.
Note 3. Block “ ”.
[Airtight test and vacuum drying while in Evaculation mode setting]
When all the electrical work on the system including the indoor unit is Note
finished and it is safe to supply power to the system, turn ON the • After knocking out the holes, we recommend you remove burrs in
entire system and set the Evaculation mode setting (service mode) the knock holes (See figure 31) and paint the edges and areas
through the PCB (A1P) of the outdoor unit. All the connection piping around the edges using the repair paint.
and indoor unit excluding the equalizer piping can be airtight tested
and vacuum dried through the liquid pipe service port of the function
8-3 Checking of device and installation conditions
unit. Furthermore, refrigerant charging through the liquid piping is Be sure to check the followings.
possible while the system is not in operation. Refrigerant charging is For those doing electrical work
not possible while the system is in operation. 1. Make sure there is no faulty transmission wiring or loosing of a nut.
For the details of the Evaculation mode setting, refer to the [Service See “7-4 Transmission Wiring Connection Procedure”.
precautions] label (below) on the EL.COMPO.BOX lid of the outdoor 2. Make sure there is no faulty power wiring or loosing of a nut.
unit. See “7-5 Power Wiring Connection Procedure”.
If moisture might enter the piping, follow belows.
3. Has the insulation of the main power circuit deteriorated?
(I.e., if doing work during the rainy season, if the actual work
Measure the insulation and check the insulation is above regular
takes long enough that condensation may form on the inside of
value in accordance with relevant local and national regulations.
the pipes, if rain might enter the pipes during work, etc.)
(1) After performing the vacuum drying for two hours, pressurize to
Prohibition
0.05 MPa (i.e., vacuum breakdown) with nitrogen gas, then
depressurize down to –100.7 kPa for an hour using the vacuum Do not use a insulation resistance tester to light electric circuits (e.g.,
pump (vacuum drying). transmission wire terminals between outdoor and indoor units).
15 English
01_EN_3P201178-10P.fm Page 16 Wednesday, September 2, 2009 11:10 AM
For those doing pipe work • See [Shutoff valve operation procedure] in chapter 9-1 for details
1. Make sure piping size is correct. on how to handle shutoff valves.
See “6-1 Selection of piping material and Refrigerant branch- • After adding the refrigerant, make sure to close the lid of the
ing kit”. refrigerant charging port.
2. Make sure insulation work is done. The tightening torque for the lid is 11.5 to 13.9 Nm.
• Make sure to perform the check operation after installation. Oth-
See “8-2 Pipe insulation”.
erwise, the malfunction code “U3” will be displayed and normal
3. Make sure there is no faulty refrigerant piping. operation cannot be performed.
See “6. REFRIGERANT PIPING”. And the failure of “Check of miswiring” may also cause abnormal
operation. Performance may drop due to the failure of “Judgment
of piping length”.
9. ADDITIONAL REFRIGERANT • Check operation must be performed for each refrigerant piping
CHARGE AND CHECK OPERATION system.
The outdoor unit is charged with refrigerant when shipped from the Checking is impossible if plural systems are being done at once.
• The individual problems of indoor units can not be checked.
factory, but depending on the size and length of the piping when
About these problems check by test run after the check operation
installed, it may require additional charging.
For charging the additional refrigerant, follow the procedure in this is completed. (See chapter 10)
• The check operation cannot be performed in recovery or other
chapter.
service modes.
And then carry out the check operation.
English 16
01_EN_3P201178-10P.fm Page 17 Wednesday, September 2, 2009 11:10 AM
Tightening torque
The sizes of the shutoff valves on each model and the tightening
torque for each size are listed in the table below.
<Size of Shutoff Valve>
8HP type 10HP type 12HP type 14HP type 16HP type
φ9.5
<Tightening torque>
Shutoff Tightening torque N·m (Turn clockwise to close)
valve size Shaft (valve body) Cap (valve lid) Service port
17 English
01_EN_3P201178-10P.fm Page 18 Wednesday, September 2, 2009 11:10 AM
Note
Press the “MODE button” (BS1) if you get confused while operating.
This returns to Setting Mode 1 (H1P : OFF, default).
English 18
01_EN_3P201178-10P.fm Page 19 Wednesday, September 2, 2009 11:10 AM
During charging in heating mode, a person must manually close In case of cooling mode
valve A and stop operation. (7) Push the TEST button (BS4) once within 5 minutes after proce-
Beforehand, check the remaining refrigerant that is needed to dure (6) (*4) and close the all front panels (*5).
charge based on the “additional charging amount” in step 2 and After that, open the valve A immediately (See figure 34) (*6) and
the charged amount in step 3. watch the remote controller display of indoor unit.
• The refrigerant will be charged about 30kg in one hour at outdoor (8) If the remote controller display shows “PE” code (*7), ready to
temp. 30°C DB (about 12kg at outdoor temp. 0°C DB). close the valve A.
(The charging speed of refrigerant may increase depending on And go to procedure (9).
the quantity of remaining refrigerant in the tank or outdoor tem- If the remote controller display shows other code, close the valve
perature.) A immediately and refer to [Remote controller cooling mode mal-
• During Automatic refrigerant charging operation, you can stop the function code]
operation forcedly by pushing MODE button (BS1).
• The marks of LED mean as follows. Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.
h : OFF i : ON j : Blinking ∗ : OFF, ON or Brinking
(9) When the compressor stop working (the fan may continue rota-
tion.), close the valve A immediately (*8).
(1) Open the shutoff valves of the liquid pipe and gas pipe, and shut- And check the LED displays are as below and the remote control-
off valve of equalizer pipe (in the case of the multi outdoor unit ler display shows “P9” code.
system). (The valve A to C must be closed. See figure 34.) H1P H2P H3P H4P H5P H6P H7P
(2) • Close the EL. COMPO. BOX lid and all front panel except on i j j i i i i
the EL. COMPO. BOX side. (*1) And turn the power to the out-
door unit, function unit and all connected indoor units. (*2) After checking, push the MODE button (BS1) once and the charg-
• After H2P stop blinking (about 12 minutes after turning on the ing is complete.
power), check H2P is OFF. In case of heating mode
If H2P is ON, check the malfunction code in the remote control- (7) Push the TEST button (BS4) once within 5 minutes after proce-
ler of indoor unit and correct the malfunction in accordance with dure (6) (*4) and close the all front panels.
[Remote controller display malfunction code] in chapter 9-3. After that, open the valve A immediately (See figure 34) (*6) and
check the charged amount by meauring device.
Note
During operation, if the remote controller display shows “P2” or
All operation is done through outdoor unit (in case of multi out-
“P8” code, close the valve A immediately and refer to [Remote
door unit system, master unit)
controller heating mode malfunction code].
Distinguish the master and slave of the multi outdoor unit sys-
tem through the state of the H8P (MULTI) LED indicators. Beware the fan running when open the front panel.
i (ON) .............................................................. Master The fan may continue rotation after the system stop the operation.
(8) When the required amount of refrigerant is charged, close the
j (Blinking) or h (OFF) .................................... Slave
valve A (See figure 34) (*8) and push the RETURN button (BS3)
once. And then go to procedure (9).
Furthermore, the master and slave can be distinguished by
(9) Push the MODE button (BS1) once, and the charging is complete.
checking whether the transmission wire to the indoor unit is
connected or not. Notes (*1)~(*9)
(*1) Lead the refrigerant charge hose etc from the pipe intake.
Transmission wire is connected......................... Master
All front panels must be closed at the procedure (7).
Transmission wire is not connected................... Slave (*2) • If you perform the refrigerant charging operation within the
refrigerant system that have the power off unit, the operation
(3) Check the LED. And push the MODE button (BS1) once if the LED cannot finish properly.
displays is not as below. Check the number of outdoor and indoor units that is powered.
H1P H2P H3P H4P H5P H6P H7P For checking, see [How to check how many units are con-
h h i h h h h nected] in chapter 9-1.
• To energize the crankcase heater, make sure to turn on for
(4) Push the TEST button (BS4) once. (The LED displays will change 6 hours before starting operation.
as below.) (*3) It takes about 2~10 minutes for getting stability of refrigerant
H1P H2P H3P H4P H5P H6P H7P state.
i i i i i i i If the additional refrigerant is little and operation is started before
getting stability, the system can not judge the charging amount
(5) Hold the TEST button (BS4) down for 5 seconds or more. precisely and it cause over charge.
(The LED displays will change as below and fan of outdoor unit (*4) If the TEST button (BS4) is not pushed within 5 minutes, “P2”
will start rotation.) code will displayed in the remote controller. In this case, refer
H1P H2P H3P H4P H5P H6P H7P [Remote controller cooling (or heating) mode malfunction code].
h j h h h ∗ ∗ (*5) If the front panel is opened during the operation, the system can-
not operate properly.
(6) When the compressor start working and the LED displays change (*6) If you leave the system without connecting the refrigerant tank or
any state in below (*3), go to “In case of cooling mode” or “In case opening the valve A for 30 minutes or more, the system stop
of heating mode” in accordance with the LED displays. operation and “P2” code are displayed in remote controller.
H1P H2P H3P H4P H5P H6P H7P In this case, refer [Remote controller cooling (or heating) mode
Go to “In case of malfunction code].
j j j h i h i (*7) Depending on the situation of operation such as the charging
cooling mode”
amount is little, the “PE” code may not be displayed and the “P9”
Go to “In case of
j j h h i h i code may be displayed.
heating mode”
(*8) Always close the valve A and take the tank off.
The refrigerant charge port of this unit have electric expansion
valve and the valve are closed when charging is finished. How-
ever, the valve will opened when ather operation (Check opera-
tion, nomal operation, etc.). If you leave the tank connected, the
refrigerant will charged and it cause over charge.
19 English
01_EN_3P201178-10P.fm Page 20 Wednesday, September 2, 2009 11:10 AM
[Remote controller cooling mode malfunction code] (2) Make the onsite settings as needed using the push button (BS1-
Code The work contents BS5) on the outdoor unit PC-board (A1P) with the power on. (See
“10. ONSITE SETTINGS”)
PE Charging is almost finished. Ready to close the valve A.
(3) Perform the check operation following the Check Operation
The refrigerant tank is empty. Close the valve A and Method of the [Service Precautions] label (lower) on the EL.
replace empty tank to the new tank. After changing the COMPO. BOX lid (see figure 32). The system operation for about
PA
tank, open the valve A again. 45~60 minutes and automatically stops the check operation.
PH
Beware the fan running. The outdoor unit does If the malfunction code is not displayed in the remote controller
not stop operation. after the system stop, check operation is completed. Normal oper-
Close the valve A immediately, and restart the operation ation will be possible after 5 minutes. If the malfunction code is
P8
from procedure (3). displayed in the remote controller, correct the malfunction follow-
Operation is interrupted. Close the ing [Remote controller displays malfunction code] and perform the
valve A immedeately and check check operation again.
the below items. [Remote controller displays malfunction code]
• Check if the shutoff valves of Malfunc-
liquid pipe and gas pipe, and Installation error Remedial action
tion code
shutoff valve of equalizer
pipe (in the case of the out- E3, E4 The shutoff valve of the
P2 door unit multi system) is F3, F6 outdoor unit is left Open the shutoff valve.
opened. UF closed.
• Check the refrigerant tank is After correcting the
The phases of the Exchange two of the three
connected and the valve A abnormality, restart
U1 power to the outdoor phases (L1, L2, L3) to make a
was opend. the operation from
unit is reversed. proper connection.
• Check if the air inlet and out- procedure (3).
No power is supplied to Make sure the power source
let of the indoor unit are not U1
an outdoor, BS or wire is properly connected to
closed by an obstruction. U4
indoor unit (including the outdoor, BS or indoor unit
Operation is stoped abnormally. LC
phase interruption). and revise if necessary.
Close the valve A immediately.
There is conflict on the
Confirm the malfunction code and Check if the refrigerant piping
∗ connection of transmis-
correct the abnormality following UF line and the transmission wiring
sion wiring in the sys-
the [Remote controller displays are consistent with each other.
tem.
malfunction code] in chapter 9-2.
Recalculate the additional
Charging is finished. Close the valve A and take the
P9 amount refrigerant from the pip-
refrigerant tank off. E3
Refrigerant over- ing length and correct the refrig-
F6
[Remote controller heating mode malfunction code] charge. erant charge level by recovering
UF
any excessive refrigerant with a
Code The work contents
refrigerant recovery machine.
Close the valve A immediately and push the TEST button
• Check if the additional refrigerant
P8 (BS4) once. And restart from procedure (7) of “In case of charge has been finished correctly.
heating mode”. E4
Insufficient refrigerant. • Recalculate the additional amount
F3 refrigerant from the piping length and
Operation is interrupted. Close the valve A immedeately
add the adequate amount.
and check the below items.
• Check if the shutoff valves of liquid pipe and gas Field wiring is con-
pipe, and shutoff valve of equalizer pipe (in the case nected to “TO MULTI
P2 of the outdoor unit multi system) is opened. UNIT (Q1,Q2)” termi-
U7, U4 Remove the line from the “TO
• Check the refrigerant tank is connected and the nal on the outdoor unit
UF, UH MULTI UNIT (Q1, Q2)” terminal.
valve A was opend. PC-board (A1P) when
• Check if the air inlet and outlet of the indoor unit are the system is one out-
not closed by an obstruction. door system.
Note
9-3 Procedure of check operation If any malfunction codes other than the above are displayed, check
• Check operation perform the following work. Do the check opera- the service manual for how to respond.
tion following below.
Otherwise, malfunction code “U3” will be displayed in the remote
controller and nomal operation can not be carried out. 10. ONSITE SETTINGS
Check of shutoff valve opening
Use the push button switches (BS1 through BS5) on the outdoor unit
Check of miswiring
PC-board (A1P) to make the necessary onsite settings.
Judgment of piping length
See the “Service Precautions” label (upper) on the EL. CONPO. BOX
Check of refrigerant overcharge (*)
lid for details on the positions and operating method of the push but-
* Over charging is judged only when the automatic charging oper-
ton switches and on the onsite setting. (see figure 32)
ation in cooling mode is not performed.
Make sure to record the setting on the accessory “REQUEST FOR
Note THE INDICATION” label.
• Check operation can not carried out at outdoor temp. less than –5°C.
Perform the check operation at day or time that outdoor temp. is –5°C Warning Electric Shock Warning
or more. Use an insulated rod to operate the push buttons via the inspection
• For interrupting the check operation, push RETURN button (BS3). door of EL. COMPO. BOX lid.
[Check Operation Procedure] There is a risk of electric shock if you touch any live parts, since
(1) Close the EL. COMPO. BOX lid and all front panels except as the this operation must be performed with the power on.
side of the EL. COMPO. BOX and turn on the power to the out-
door unit, function unit and all connected indoor units. (Be sure to
turn the power on at least 6 hours before operation in order to
have power running to the crank case heater.)
English 20
01_EN_3P201178-10P.fm Page 21 Wednesday, September 2, 2009 11:10 AM
11-3 Checks After Test Run 2. Calculate the smallest room volume (m3 )
Incase like the following, calculate the volume of (A), (B) as a sin-
Perform the following checks after the test run is complete.
gle room or as the smallest room.
• Record the contents of field setting.
→ Record them on the accessory “REQUEST FOR THE INDI- A. Where there are no smaller room divisions
CATION” label.
And attach the label on the back side of the front panel.
• Record the installation date.
→ Record the installation date on the accessory “REQUEST
FOR THE INDICATION” label in accordance with the
IEC60335-2-40.
And attach the label on the back side of the front panel.
Note B. Where there is a room division but there is an opening
After the test run, when handing the unit over to the customer, make between the rooms sufficiently large to permit a free flow
sure the EL.COMPO.BOX lid, the inspection door, and the unit casing of air back and forth.
are all attached.
21 English
01_EN_3P201178-10P.fm Page 22 Wednesday, September 2, 2009 11:10 AM
3. Calculating the refrigerant density using the results of the calcu- NOTES
lations in steps 1 and 2 above.
English 22
00_CV_3P201178-10P.fm Page 5 Wednesday, September 2, 2009 11:09 AM