INDIVIDUAL TEST REPORT PER CONTROL PANEL BT ANS TYPE

Ref. Control panel: 583_22

Ref. Art. 8.3.1 Equipment inspection, including wiring control and, if necessary, an electrical functioning trial

x Test of mechanical buttons, blocks and bolts, ect…

x Visual test of protection grade

x Visual test of air and superficial distances

x Random test of good connection of bolts

x Test of existing and compliant of identification plate

x Conformity test of the device using the wiring circuits diagrams

x Correct functioning test, including the auxiliary circuits

Ref. Art. 8.3.2 Insulation – dielectrical trials

x Test of insulation resistance (Art. 8.3.4), alternatively to the one listed here below.

Test of insulation between active parts connected each other’s and the frame of the device, following the parameters listed

here below:

f=50 Hz and t=1 min

Nominal insulation voltage Ui [V] Test voltage [V]

Ui <= 60 1000

60 < Ui <= 300 2000

x 300 < Ui <= 690 2500

690 < Ui <= 800 3000

800 < Ui <= 1000 3500

1000 < Ui <= 1500 3500

Ref. Art. 8.3.3 Test of protection devices and the electrical continuity of the protection circuits

x Test of protection devices to prevent direct contacts

x Visual test of protection circuits

x Random trials on the PE contact on the good connection of bolts

Ref. Art. 8.3.4 Test of insulation resistance

x Test of the insulation resistance (Ref. Art. 8.3.2), alternatively to the one listed here below

x Test of insulation resistance between circuits and the masses, following the parameters listed here below:

U applied [V] = U exercise [V] = R [kOhm] =

(F – PE) R <= 1000 [Ohm/V]

Legend of the employed symbols: x Present Not present