Journal of Solar Energy Engineering Copyright © 2008 by ASME AUGUST 2008, Vol. 130 / 031005-1
Downloaded 20 Nov 2008 to 145.94.187.10. Redistribution subject to ASME license or copyright; see http://www.asme.org/terms/Terms_Use.cfm
These data have been used often to study reliability of WTs. 2.2 Data Analysis. Reports on O&M contain information
Still, there are many different aspects to consider other than fail- about the type of maintenance performed, affected component共s兲,
ure rates. For instance, downtime caused by failures 关6,7兴, effect date of occurrence, and downtime period. All information is
of icing 关8兴, and wind speed effects 关9兴 on reliability. Other re- stored in a database; thus, all the operational experience can be
searchers have used these data to analyze reliability of WTs and evaluated by filtering and combining data using individually de-
their components; nevertheless, there is very little literature in fined criteria.
reliability of components throughout their years of operation Maintenance is classified by the different types of repair, with
关7,10–13兴. the objective of focusing on unforeseen events and damages. Each
Few publications attempted to compare the data provided in all failure event is recorded per year of operation, differentiating oc-
these databases 关6,7,11,13兴. However, they all face the same chal- currences at each of the three periods of the operational life de-
lenge of comparing different topologies, placed in different sites, fined by the bathtub curve: “infant mortality” or “early” failures,
and with information collected in different ways. The results are “constant” or “random failures,” and “wear-out” failures. The first
usually failure rates in general, and when provided per compo- year of operation used for this paper begins after commissioning,
nent. They look at their reliability without comparing different usually within three months.
types of technologies used 关13兴. In other cases, they present fail- Evaluating operational experience to gain knowledge on how
ure rates of the whole WT, per year of operation 关6,9,11,13兴. Some reliable a machine or a facility works typically leads to figures
of these studies provide life curve analysis of WTs 关11兴. such as mean time between failures 共MTBF兲 and failure rates.
In general, literature is consistent in their conclusions about the According to the definition of these figures, the reports on O&M
lack of availability of data and the diversity of methods for data are systematically evaluated by dividing more recent WTs from
collection. Additionally, similar remarks on development of tech- older and smaller ones or by separating pitch-controlled WTs from
nology have come up in literature, such as the effect of introduc- stall regulated, etc.
ing new models in the market increasing mean failure rates in Manufacturers improved their machines either by enlarging ex-
these databases 关6,13兴. In particular, references such as Ref. 关12兴 isting types by some percentage of rotor diameter or by changing
show reliability analysis of generators and converters, but mostly technology and introducing a new model. Within the study, WTs
oriented to direct-drive use, and without analyzing the reliability of one manufacturer with more or less the same technology, just
throughout operational age. slightly differing in diameter and rated power, are put together in
This paper presents a further step in the reliability analysis of WT groups and evaluated accordingly. The number of WTs within
WTs. Sixty-three thousand maintenance reports collected through these groups differs from each other, making it difficult to process
the German program “250 MW wind” have been studied, focus- the data and to interpret results.
ing on the maintenance information provided on a yearly basis. In the following sections, a comparative analysis of the main-
Specifically, failure rates per year of operation and per WT are tenance reports is shown, focusing on failures and incidents of the
presented, emphasizing trends of technology of different compo- WTs as complete systems and on failure of major components. An
nents. incident is defined as a malfunction of the WT system, i.e., stand-
still, reduced power output, noise, etc., which required an un-
planned maintenance activity. Also, it should be stated that with
2 Approach one maintenance activity, several failures may be corrected. On
the other hand, failures represent any malfunction of a component
The study evaluates operational information from the German that was repaired. A repair may have been performed with an
250 MW Wind test program. This program includes a Scientific unplanned maintenance activity or during a regular preventive
Measurement and Evaluation Program 共WMEP兲, which is com- maintenance activity.
prised of data on operational experience of WTs for a period of up The term “failure rate” is used throughout this paper as the
to 15 years. “annual number of failures per WT.” “Incident rate” is used as the
2.1 Database German “250 MW Wind” Program. Since “annual number of incidents per WT.” Additionally, the minimum
1989, the German government has promoted the 250 MW Wind and maximum values and confidence bounds of the data used are
program in order to obtain statistically verifiable data on wind provided in the figures only for the cases in which it is considered
energy use in Germany. More than 1500 turbines with approxi- to add value for a better interpretation.
mately 350 MW rated power installed were incorporated in this
measure 关3兴. 3 Analysis
The 250 MW Wind program has benefited from the obligation
3.1 General Development of Reliability. Usually, WTs are
of each participant to take part in the Scientific Program WMEP
designed to operate for a period of 20 years. However, no final
over a period of at least ten years. Thus, the WMEP, carried out by
statement can be made yet concerning the actual life expectancy
ISET, collects continuously data from each individual turbine. The
of modern WTs, as until now, little operational experience of such
acquisition of data is made by means of a logbook for each tur-
a period is available. Nevertheless, changes in reliability with in-
bine, containing manual documentation of the operators. The op-
creasing operational age can provide indications of the expected
erators report using customized forms and send the reports di-
lifetime and the amount of maintenance required. Reliability can
rectly to ISET. These reports are collected in logbooks containing
be expressed as failure rate. The principle of its development is
the following information:
well known in other technical areas. Early failures often mark the
• standard project data, e.g., technical data, location informa- beginning of operation. This phase is generally followed by a
tion, grid connection, etc. longer period of random failures, with a statistically constant rate,
• disruptions, malfunctions, repair and maintenance measures, until it starts increasing with operation age 共wear-out failures兲 due
affected components, and downtimes. to wear and damage accumulation 关14,15兴. The total life period
• monthly figures of energy production and consumption by and the individual phases are naturally distinct for different tech-
regular readings of calibrated electricity meters nical systems. For WTs, hardly any experience is available in this
• O&M costs respect.
Figure 1 shows the annual number of component failures per
Up until the end of 2006, operators sent in around 63,000 re- WT depending on their operational age, with the corresponding
ports concerning maintenance or repair, approximately 89,000 confidence bound for each year data. These confidence bounds
quarterly reports on monthly energy yield, and around 14,000 an- represent a range between which 95% of the failures lie 关15,16兴.
nual reports concerning the operating costs of their plants. These data correspond to all events reported for nearly 1500 WTs,
Downloaded 20 Nov 2008 to 145.94.187.10. Redistribution subject to ASME license or copyright; see http://www.asme.org/terms/Terms_Use.cfm
Fig. 3 Number of incidents per WT per operational year; WTs
Fig. 1 Component failure rate per WT per year of operation are categorized by rated power
during the entire 250 MW Wind test program, and without dis-
finally, a third generation of WTs with a rated power of 1 MW and
criminating based on size or technology. Operators were required
above. As expected, there are significant data collected for older
to report for ten years. However, some operators kept providing
WTs 共Categories 1 and 2兲, and not so much for the megawatt scale
the reports on a volunteered basis after the tenth year. This is why
WTs.
data are presented for 15 years. Unfortunately, the confidence Figure 3 shows the amount of incidents per WT that required an
bound of those past years are very wide, with which conclusions unplanned maintenance activity, depending not only on their op-
cannot be made. Nevertheless, these data are considered of great erational age but also on their rated power. As stated above, one
value since reliability information for periods of 15 years is rarely incident can involve one or more component failures. Figure 3
found in the WT industry. also shows that WTs usually interrupt operation unexpectedly at
The results show two different scenarios: One in which tech- least once and up to five times a year, while conventional power
nology seems mature and shows random failures, and the other plants usually do not stop unexpectedly.
one in which high early failures occur mostly in the first year of It has to be stated that the columns represent different samples
operation. This is mainly because the types of WTs involved in the of turbines. The first years of operation are achieved by all tur-
program differ not only in the size but also in the maturity of the bines in the program, while going right in the graph, the samples
system itself. In some cases, the WTs enrolled correspond to new get smaller. These numbers can be seen in Table 1. After the tenth
models entering the market. These WTs suffered many failures year, the number of turbines reduces significantly due to the end
during the first years of operation 共early failures兲. Later, in Sec. of the program. As mentioned earlier, some owners and operators
3.2, few special cases will be analyzed. continued providing maintenance reports on a volunteer basis.
Figure 2 shows the annual rate of exchange of main compo- Thus, the right columns are assumed to be less trustworthy.
nents per WT. During the ten years of the program, a total of 947 Incident occurrences or unplanned maintenance visits of older
parts were replaced involving 538 WTs. These 947 parts account turbines below 1 MW were especially high during the first year of
for almost 1400 failures reported. The figure shows that blades operation and reduced to a somewhat lower level for the following
and generators are more often exchanged than other components. years of operation. In contrast, the group of megawatt WTs shows
This is an expected result, especially for blades for which repair significantly higher incident rates, which seem to decline slightly
methods are not easily performed on-site. by increasing age and to increase again after the sixth year. How-
In order to better understand the reliability of the different tech- ever, as seen from Table 1, the samples of eight and nine year old
nologies, three categories of rated power are created. The first one megawatt turbines are very small. The reliability of megawatt tur-
with WTs less than 500 kW of rated power, which includes a bines with advanced operational age will become clear only with
broad range of topologies, manufacturers, and sizes; then the sec- time.
ond category with WTs rated between 500 kW and 1000 kW; and For each technical system, it can be expected that failure rates
increase sometime after a longer period of lower rates driven by
random failures. This behavior is expected for WTs too. Even
though there are not enough data collected for the lifetime of
WTs, it seems that at least for WTs under 1 MW, the wear-out
failures do not start before the 11th year of operation 共Fig. 3兲.
However, it is not yet confirmed that the slight increase in the
failure rate of smaller turbines is a hint on wear-out failures.
Downloaded 20 Nov 2008 to 145.94.187.10. Redistribution subject to ASME license or copyright; see http://www.asme.org/terms/Terms_Use.cfm
Fig. 4 Example 1 of component failure rates of a megawatt WT
per year of operation Fig. 6 Component failure rates per WT per operational year,
depending on the use of stall or pitch control
3.2 Special Wind Turbine Models. The significantly higher In the end, besides high failure rates of components, no general
incident rates of the megawatt WT demand a closer look at the explanation for high incident rates of turbines of the megawatt
component failures causing all these incidents. While most of the was found.
WT types show similar development and similar numbers of dam-
aged components per year, some types show significant differ- 3.3 Differences Between Stall and Pitch. Pitch control is
ences. It was found that for some models, high component failure used to increase efficiency and to reduce stress for mechanical
rates dramatically decreased with time, while others showed a parts of the drive train. However, adding a system like pitch con-
high failure rate of subcomponents randomly developing over trol also means adding possibilities for failures.
time. This is mainly due to the immature stage of their develop- Figure 6 shows a comparison of component failure rates of
ment at the time of data collection. Nevertheless, it is interesting stall-controlled WTs to that of pitch controlled. It indicates that
to see how these turbines behaved. pitch-controlled WTs tend to have significantly more component
One example of the megawatt class is depicted in Fig. 4. It failures than stall-controlled ones.
shows a high frequency of damages of different subcomponents Specifically, reliability of certain components of stall- and
and a very significant improvement as well. It is a type of standard pitch-controlled turbines can deviate from each other quite signifi-
topology using stall control, fixed rotor speed, gearbox, and in- cantly. Especially, the rotor system 共without blades兲 of pitch-
duction generator. The development shows quite clearly poor re- controlled WTs naturally tends to increase failure rates. On the
liability due to early failures. In this special case, the high failure other hand, gearboxes, hydraulic systems, and mechanical brakes
rates were mainly driven by problems with the rotor, electrical, of stall-controlled WTs tend to increase failure rates as well, but at
and control systems. After six years, the problems, at least with a much lower level. Figures 7–9 show data for hydraulic systems,
the control system, seem to be solved, but the overall failure rates rotors, and mechanical brakes, respectively, for both stall-and
remain comparably high. Nevertheless, Fig. 4 represents a small pitch-controlled turbines.
group of three individual turbines belonging to the same type. Stall-controlled WTs normally use a hydraulic system for driv-
Another example of a megawatt turbine included in the pro- ing tip brakes. In some cases, the hydraulics are used for other
gram is depicted in Fig. 5. This one stands out due to its extremely purposes, such as yawing and mechanical braking. In some cases
high failure rates. However, it shows randomly shaped develop- of pitch-controlled WTs, hydraulic systems are used as pitch
ment of reliability. This turbine is also of a standard topology. drives, and also in some models with “active-stall” power control.
Different components drive the failure rate. As depicted, the In all cases regarding the reports in the 250 MW wind program,
failures do not occur at an early stage, but rather randomly, keep- the hydraulic system consists of pumps, tubes, and pipes, as well
ing overall failure rate at high level. Also, this WT is represented as valves and cylinders.
by three individual turbines only. One main difference between stall- and pitch-controlled WTs
regarding their reliability may be seen in the additional subcom-
Downloaded 20 Nov 2008 to 145.94.187.10. Redistribution subject to ASME license or copyright; see http://www.asme.org/terms/Terms_Use.cfm
Fig. 8 Rotor „without blades… failure rates per WT per year of
Fig. 10 Component failure rates per WT per operational year,
operation, depending on the use of stall or pitch control
comparing the use of synchronous and induction generators
ponents such as pitch drives and blade bearings. Here, failure rates
of the rotors of both technical concepts are compared without additional group.
counting failures of the blades, but only regarding hub, pitch Figure 10 shows clearly higher failure rates for WTs using syn-
drives, bolted joints, blade bearings, and some additional accesso- chronous generators. These exceed the failure rates of WTs using
ries. It is clear that the rotor failure rate for pitch-controlled WTs induction generators by about 0.15–0.3, corresponding to about
exceeds that for stall-controlled by about 0.2–0.25 failures per 40% of its value. The data for induction generators show an early
year and turbine, which corresponds to about 85% of its value. failure stage especially for the first year, decreasing during the
The additional subcomponents for pitch control seem to in- first and third year. Then, the data show a constant or “random”
crease the failure rate for these WTs. On the other hand, it was failure stage until the end of the ten year period. On the other
found that mechanical brakes are more often repaired in stall- hand, for the synchronous generators, there is an increase in faulty
controlled WTs. This advantage for pitch control may be caused events after the first year. This behavior is maybe due to the fact
by the possibility to first reduce forces and torques in the rotor by that the direct-drive concept was being introduced into the market.
pitching and only in a second step activate the mechanical brake. For the past years, the data show a tendency to decrease, indicat-
Figures 6–9 depict, on one hand, the differences between stall- ing the evolution of the concept as perhaps initial phase problems
and pitch-controlled turbines, and on the other hand, the develop- were solved. However, looking at the data, 31% average of the
ment of failure rates during the years of operation. While Fig. 6 annual failure rates correspond to direct-drive WTs, and as men-
shows that failure rates are particularly high in the first year of tioned above, they only represent a 23% of the sample size.
operation, this cannot be stated for subcomponents such as me- Figure 11 shows the same data of Fig. 10, except that Fig. 11
chanical brakes and rotors 共without blades兲 of pitch-controlled presents an additional differentiation for the synchronous genera-
WTs 共Figs. 8 and 9兲. Also, no hint can be found for an increase in tors. This group is divided between the use of a direct drive and
annual faults with increasing age. the use of a gearbox. Failure rates of WTs using induction gen-
erators are still the lowest among all. As it can be seen, the WTs
3.4 Generators and Full Power Converters. Most of the using gearbox and synchronous generators show a random failure
WTs involved in the 250 MW Wind test program use an induction for the ten year period. The data for direct drive confirm in a way
generator instead of synchronous generator in their topology. the hypothesis expressed above. The unclear behavior of the WTs
The sample of WTs in the WMEP database is smaller for syn- using synchronous generators depicted in Fig. 10 is similar to the
chronous generators than for induction generators, 27% versus
73%, respectively. Of the WTs using synchronous generators,
23% use direct-drive train. Furthermore, out of the WTs using
induction generators, only 0.1% corresponds to a double fed in-
duction generators 共DFIGs兲, and so it is not considered as an
Downloaded 20 Nov 2008 to 145.94.187.10. Redistribution subject to ASME license or copyright; see http://www.asme.org/terms/Terms_Use.cfm
Fig. 12 Generator failure rates per WT per operational year,
comparing induction and synchronous generators with a dis-
tinction of direct-drive systems
4 Results
Throughout the years, there have been different attempts to in-
novate on certain components, such as flexible hub, downwind
turbine, two-bladed rotors, direct-drive train, aerodynamic brakes,
pitch mechanisms, etc. Some of these have shown high failure
rates or “hard” failures, for instance, a flexible hub WT, or even
Fig. 13 Power electronics failure rates per WT per operational two-bladed machines. It is also true that some of these concepts
year, comparing induction and synchronous generators with a were not tested enough or were not tested by different manufac-
distinction of direct-drive systems turers, lacking the opportunity to mature the technology. This can
Downloaded 20 Nov 2008 to 145.94.187.10. Redistribution subject to ASME license or copyright; see http://www.asme.org/terms/Terms_Use.cfm
be seen from the evaluation of different models of mega-watt higher failure rates, which might be due to the necessity to dissi-
machines. However, it is shown that WTs of all power classes pate all the energy of the drive train by the disk brake on the high
suffer from several unforeseen downtimes due to failures of one speed shaft. Since modern megawatt turbines usually apply aero-
or few subcomponents. dynamic brakes, this kind of failures might get diminished. Fur-
Other than innovating in components or technology, what can thermore, the reliability of components is affected by the introduc-
be seen in this extensive database is that topologies of WTs are in tion of a new concept or technology. Not always the new
many cases a combination of standard components. For instance, component should be the focus of the reliability analysis. While
WTs can use a pitch, stall, or active-stall control, with synchro- the new component may seem to be highly reliable, it may affect
nous or induction generators, or they could use direct-drive train the behavior or reliability of other components due to changes in
or the gearbox, aerodynamic brakes, etc. There is still a lack of operational conditions. For instance, in the analysis of WTs with
understanding on what the best configuration is. Nevertheless, direct drive, the actual failures of the generator follow a “constant
some conclusions can be made by looking at failures in the or random” rate, while the total failure rate of these turbines
WMEP database from the main component point of view. These shows a different pattern. This pattern is similar to the failure rates
reports show significantly higher total failure rates for pitch- of electrical components, which are expected to be affected by the
controlled WT than for stall-controlled ones. However, for pitch- operation of the generator.
controlled WTs, failure rates in the hydraulic systems and me- Even with reduced failure rates, the reliability of modern WT
chanical brakes are lower than for stall-controlled WTs. On the still seems quite high compared to the more matured technologies.
other hand, rotor failure rates 共without the blades兲 are much Especially, for offshore application, this will cause low availabili-
higher. In the case of generator types, WTs with synchronous ties due to the difficult access. Thus, for future wind energy use, it
generators show higher failure rates than those using induction will be of great advantage not only to reduce failure rates of these
generators. Looking at component failures, electrical components components but also to develop a new maintenance strategy such
also showed higher failure rates in WTs with synchronous genera- as using condition monitoring of critical components. In that way,
tors. This is mainly due to the use of a full electronic converter. the number of failures and unplanned repairs gets reduced, main-
Accordingly, synchronous generators show higher failure rates tenance activities get planned, total downtimes will be reduced,
than induction generators. The use of direct drive shows higher and maintenance can be done during periods of low wind.
failure rates compared with WTs using gearboxes. However, the It is evident that there exists a lack of reliable operational data.
synchronous generators of these direct-drive machines show a Ten to fifteen years of failure events collected represent now one
constant failure rate after the first operational year. This brings of the few if not the only source 共in terms of year data兲 of infor-
into consideration that other components are responsible for these mation. The wind energy community should go on gathering in-
high failure rates, such as the case of power electronics. The latter formation, which is needed for improving reliability, and present
follow a similar failure behavior throughout the ten years of the it to the public.
WMEP program.
In general, these maintenance reports show that half of the WTs
failures are due to the electric components and to the control
system. These failures represent in most cases low downtime
compared with failures in other components such as generator or Acknowledgment
gearbox 关3,10兴.
The “250 MW Wind” program, providing a unique occasion for
Another aspect that influences reliability in this study is the fact
gathering with a long-term perspective operational data of a large
that WTs have escalated in size, keeping the basic concepts. Fail-
number of different turbines, was financed by the German Minis-
ure rates have also escalated with them as shown at the beginning
try for the Environment, Nature Conservation and Nuclear Safety.
of this analysis. On the other hand, WTs with low failure rates are
For additional information on the 250 MW Wind program, see
mostly low rated power machines. They do not show a specific
http://www.iset.uni-kassel.de and http://reisi.iset.uni-kassel.de.
type of topology but usually they have a simple configuration.
This work is part of the project PhD@Sea, which is substan-
Their highest failure rates are due to the control system and to
tially funded under the BSIK program of the Dutch Goverment
electrical components, which are the most common failures 关10兴.
and supported by the consortium We@sea, http://www.w.-at-
Entering in more detail, results show that early failures, espe-
sea.org.
cially when introducing a new model of WTs, are high but they
decrease with years of operation.
To conclude, it is important to mention that even though there
are not enough data collected for the lifetime of WTs, failure rates
in general decrease with time. In addition, based on these data, it References
can be expected that the WTs under 1 MW to the stage of wear- 关1兴 Gasch, R., and Twele, J., 2002, Wind Power Plants, Solarpraxis and James &
out failures do not begin before the 11th year of operation. James 共Science Publishers兲 Ltd., London, Chaps. 1–3.
关2兴 Hansen, M. O. L., 2002, Aerodynamics of Wind Turbines, James & James
共Science Publishers兲 Ltd., London.
关3兴 2006, “Wind Energy Report Germany 2006,” ISET, Kassel.
关4兴 1995–2004, “Eggersglüß: Windenergie X Praxisergebnisse, Land-
wirtschaftskammer Schleswig-Holstein,” Germany.
关5兴 1999–2001, “WindStats Newsletter,” 12共4兲–14共3兲, Denmark.
5 Conclusions 关6兴 Ribrant, J. 2006, “Reliability Performance and Maintenance—A Survey of
Failures in Wind Power Systems,” MS thesis, KTH School of Electrical En-
Reliability of WTs has improved with time and has achieved an gineering, Stockholm.
availability of 98% 关10兴. However, WTs fail at least once a year or 关7兴 Van Bussel, G. J. W., and Zaaijer, M. B., 2003, “Estimation of Turbine Reli-
even more often for larger turbines. As future plans look for off- ability Figures Within the DOWEC Project,” TU Delft, Report No. 10048.
关8兴 Durstewitz, M., 2005, “A Statistical Evaluation of Icing Failures in Germany’s
shore use of wind energy, reliability of WT components has to
’250 MW Wind’ Program,” ISET, Kassel.
improve. Otherwise, a significantly reduced availability is to be 关9兴 Tavner, P. J., Edwards, C., Brinkman, A., and Spinato, F., 2006, “Influence of
expected 关17兴 partly by the increase in downtimes due to failures Wind Speed on Wind Turbine Reliability,” Int. J. Energy Res., 30共1兲, pp.
combined with low site accessibility. 55–72.
关10兴 Hahn, B., Durstewitz, M., and Rohrig, K., 2007, “Reliability of Wind Tur-
However, gathering and analyzing operational data give reliable bines,” Wind Energy: Proceedings of the Euromech Colloquium, S. 329–332,
hints on potential for improving component reliability. It is shown Springer-Verlag, Berlin.
that mechanical brakes of stall-controlled turbines suffer from 关11兴 Tavner, P. J., Xiang, J., and Spinato, F., 2005, “Improving the Reliability of
Downloaded 20 Nov 2008 to 145.94.187.10. Redistribution subject to ASME license or copyright; see http://www.asme.org/terms/Terms_Use.cfm
Wind Turbine Generation and Its Impact on Overall Distribution Network 关14兴 Rao, S. S., 1992, Reliability-Based Design, McGraw-Hill, New York.
Reliability,” 18th International Conference on Electrical Distribution, CIRED, 关15兴 2008, NIST/SEMATECH e-Handbook of Statistical Methods, http://
Turin. www.itl.nist.gov/div898/handbook/.
关12兴 Tavner, P. J., Van Bussel, G. J. W., and Spinato, F., 2006, “Machine and 关16兴 Broemm, W. J., Ellner, P. M., and Woodworth, W. J., 2000, “AMSAA Reli-
Converter Reliabilities in Wind Turbines,” Third IET International Conference ability Growth Guide,” Army Materiel Systems Analysis Activity Aberdeen
on Power Electronics, Machines and Drives, pp. 127–130. Proving Ground, AMSAA-TR-652.
关13兴 Tavner, P. J., Xiang, 2005, “Wind Turbine Reliability, How Does It Compare 关17兴 Van Bussel, G. J.W., 2002, “Offshore Wind Energy, the Reliability Dilemma,”
With Other Embedded Generation Sources,” IEE RTDN Conference, London. Proceedings of the International Conference, Berlin, Germany, Jul. 2–6.
Downloaded 20 Nov 2008 to 145.94.187.10. Redistribution subject to ASME license or copyright; see http://www.asme.org/terms/Terms_Use.cfm