Any quotations in this document are taken directly from the CSA – B149.

1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

NOTE: The B149.1-2005 covers both Natural Gas and Propane


Installations. Where a clause is specific to one fuel the wording
will specify “For Natural Gas applications” or “For Propane
applications”.

1. Scope 1. Scope

1.2 This Code does not apply to 1.2 This Code does not apply to Revised – The volume was reduced to 150 g from 250 g.
Cylinders of 225 g are being used in restaurants for portable
(l) butane fuel cylinders of 150 g capacity or less; and (l) butane fuel cylinders of 250 g capacity or less; and cooking. Incidents have occurred and no one appears to have
jurisdiction for these cylinders.

1.4 This Code and any Standard referenced in it do not make New Clause This was an amendment to clarify that the Code is intended to
or imply any assurance or guarantee with respect to life address safety performance. It is not intended to guarantee a
expectancy, durability, or operating performance of equipment product’s life expectancy, durability, or operating performance.
and materials referenced in the Code.

1.6 In this Code, unless approved otherwise by the 3.1.2 Where the word “shall” is used in this Code, it indicates a Revised.
authority having jurisdiction, “shall” indicates a mandatory requirement unless approved otherwise by the authority
requirement; “should” indicates a recommendation or that having jurisdiction.
which is advised but not mandatory; “may” indicates an
advisory or optional statement. Notes to the text do not
include mandatory or alternative requirements. The
purpose of a note is to separate from the text explanatory
or informative material that is not properly a part of this
Code. Notes to figures and tables, however, are
considered part of the figure or table and are written as
mandatory requirements. Legends to figures are also
written as mandatory requirements.
2. Reference publications 2.3 Reference publications

*3 Definitions 2.1 Definitions

1 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

Heater –
Non-recirculating direct gas-fired industrial air heater – a New definition. This definition was required for the new Section 7.21 covering
heater in which all the products of combustion generated by the Non-recirculating direct gas-fired industrial air heater (DFIAH)
gas-burning device are released into the airstream being and to maintain continuity with the applicable CSA Standard
heated and whose purpose is to offset building heat loss by 3.7 and is considered a subset under heater.
heating only outside air.

Fitting - an item in a piping or tubing system that is used as a Fitting - an item in a piping or tubing system that is used as a Revised by deleting the word nipple.
means of connection, such as an elbow, return bend, tee, means of connection, such as an elbow, return bend, tee, A nipple should not be included in the definition of fitting since
union, bushing, coupling, or cross, but does not include such union, bushing, coupling, cross, or nipple, but does not include a nipple is a type of pipe.
functioning items as a valve or pressure regulator. such functioning items as a valve or pressure regulator.

Maximum operating pressure – the maximum pressure to


which any component or portion of fuel system can be Maximum Allowable Operating Pressure – the maximum Rationale: The term “Maximum allowable operating pressure”
subjected (Accepted Revisions 2001) pressure to which any component or portion of the fuel is not used in the Code other than in the “Definitions”. The
system can be subjected. term “Test pressure” is mentioned in Table 5.22.2.

Overpressure Protection Device – a device that under


abnormal conditions will act to reduce, restrict, or shut off the New definitions. These definitions were required for the revisions in Clause 5
supply of gas flowing into a system to prevent gas pressure in covering Pressure Controls and to maintain continuity with CSA
that system from exceeding the rated pressure of the system Standard 6.22 for Line Pressure Regulator.
components.
Monitoring regulator – an overpressure protection
device that functions as a second gas pressure
regulator in series with the primary gas pressure
regulator.
Overpressure relief device – an overpressure
protection device that functions by discharging gas
from the downstream system.
Overpressure shut-off device – an overpressure
protection device that functions by completely shutting
off the flow of gas into the downstream systems.

2 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

Regulator –
These definitions were required for the revisions in Clause 5
Line Pressure regulator – a gas pressure regulator intended New definitions. covering Pressure Controls and to maintain continuity with CSA
for installation in a gas distribution system between the utility Standard 6.22 for Line Presser Regulator.
service regulator or first-stage regulator (propane) and gas
utilization equipment. A definition for Line Pressure regulator was included to
describe its function
Lock-up (positive shut-off regulator – a regulator that is
capable of maintaining a reduced outlet pressure when the fuel A definition for a lock-up regulator was added to be consistent
flow condition is static. with the B149.3 Code.

4. General 3. General

4.2.11
4.3 Responsibilities of the installer 3.3 Responsibilities of the Installer
4.3.7 It shall be the responsibility of the installer of a piping or 3.3.7 It shall be the responsibility of the installer Revised by creating a new Clause for part (b) to clarify the
tubing system to perform pressure tests in accordance with (a) of a piping or tubing system to perform pressure tests in responsibilities for different installers that are inevitably
Clause 6.22.2 and to ensure that the piping or tubing system is accordance with Clause 5.22.2 and to ensure that the piping or involved in completing a gas installation <see below>.
gas-tight at the completion of the tests. tubing is gas tight at the completion of the tests; and The installer of the piping or tubing is not necessarily the same
one who installs any of the gas appliances.

4.3.8 It shall be the responsibility of the installer of an appliance 3.3.7 It shall be the responsibility of the installer This new Clause was added to increase the awareness that it
to perform tests in accordance with Clause 6.22.3 and to (a) <see above> is the responsibility of the appliance installer to ensure the
ensure that the system is gas-tight at the completion of the (b) of the appliance to perform tests in accordance with connection, valve train and system components are gas-tight.
tests. Clause 5.22.3 and to ensure that the system is gas tight at the
completion of the tests.

4.17 Appliance ductwork connections

*4.17.2 Return air ducts in an enclosure shall be in accordance


with the provisions set out for duct systems in The National To clarify that the installation requirements for return air ducts
Building Code of Canada. New Clause systems are in the Building Code.

3 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

4.22 High-altitude installations 3.22 High Altitude Installations


4.22.1 For high-altitude installations, appliances shall be 3.22.1 New appliances with inputs up to and including Revised – To clarify that all appliances new or used shall be
certified in compliance with CSA CGA 2.17 and shall be 400,000 (120 kW) and certified for high altitude operation shall adjusted for high altitude locations in accordance with CSA
adjusted to the high-altitude rating shown on the nameplate be adjusted to the high altitude rating shown on the nameplate CGA-2.17 and the manufacturers instructions.
when installed at elevations between 2000 ft and 4500 ft (600 when installed at elevations between 2000 ft and 4500 ft (600
m and 1350 m) above sea level. m and 1350 m) above sea level. The requirements of Clause 4.22.1 should not be restricted to
new appliances.
5.2 Pressure regulators

5.2.1 General

5.2.1.3 A pressure regulator shall not be bypassed. 4.2.6 A system regulator (propane) or line (natural gas) shall
not be bypassed. Rationale: no regulator should be bypassed

5.2.1.4 When a line pressure regulator is required and the


inlet supply pressure to the regulator exceeds 0.5 psig (3.5 New Clause Rationale: To correct differences in terms between B149 and
kPa), it shall be of the positive shut-off type. the standard for line pressure regulators CSA 6.22.

5.2.1.5 A line pressure regulator shall have: Rationale: (2003 Accepted Revisions): Moved from 4.2.7.
(a) a manual shut-off valve installed upstream of the regulator; The term “or line pressure regulator (natural gas)” was
and New Clause added to this section by letter ballot 01-02 at the June 2001
(b) either a line relief device or an overpressure protection B149 meeting to correct differences between B149 and the
device. standard for line pressure regulators which permits
The regulator vent and relief device vent shall terminate overpressure protection devices (overpressure shutoff
outdoors. device, overpressure relief device or monitoring regulator)
not just internal relief. The different regulators for propane
and natural gas have been revised to only line pressure
regulators because the scope of CSA 6.22 Line Pressure
Regulators is being revised so that the standard applies to
both propane and natural gas.
5.2.2 Additional requirements for pressure regulators for 4.1 Pressure Inside Buildings
propane applications

4 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

5.2.2.4 When used on a system operating at 2 psig (14 kPa) or 4.1.4 When used on a 2 psig (14 kPa) system, a pressure Clause revised to be specific to propane and to reflect
less, a line pressure regulator equipped with a regulator equipped with a leak limiting system orificed for 1 changes in CSA 6.22. The requirements for vent-lined
leak limiting system orificed for 1 ft3/h (0.0283 m3/h) shall be ft3/h (0.0283 m3/h) shall be exempt from the requirement of regulators to be installed in a ventilated space only was
exempt from the requirement of Clause 5.2.1.5(b). Clause 4.1.7(b). added for extra safety.
A regulator with vent limiting means shall be installed in a
ventilated space only.

5.2.3 Additional requirements for pressure regulators for


natural gas applications

When used on a system operating at 2 psig (14 kPa) or less, a 4.1.4 When used on a 2 psig (14 kPa) system, a pressure Clause revised to be specific for natural gas . The
line pressure regulator equipped with regulator equipped with a leak limiting system orificed for 1 requirement for vent limiting regulator to be installed in a
a leak limiting system orificed for 2.5 ft3/h (0.0706 m3/h) shall ft3/h (0.0283 m3/h) shall be exempt from the requirement of ventilated space was added for extra safety.
be exempt from the requirement of Clause 4.1.7(b).
Clause 5.2.1.5(b). A regulator with vent limiting means shall
be installed in a ventilated space only.

5.3 Relief devices:


Except as specified in Clauses 5.2.2.4 and 5.2.3, when a line 4.3 Line Relief Devices Rationale: The term “or line pressure regulator (natural
pressure regulator is not equipped with an gas)” was added to this section by letter ballot 01-02 at the
internal relief device, it shall have immediately downstream an Except as specified in Clause 4.1.4, when a system June 2001 B149 meeting to correct differences between
overpressure protection device or a line regulator is not equipped with an internal relief device, it B149 and the standard for line pressure regulators CSA
relief device as required in Clause 5.2.1.5(b), with a discharge shall have immediately downstream relief device as required in 6.22. This section has been modified so that it is
setting of either Clause 4.1.7(b), with a discharge setting of not less than conformance with the standard for line pressure
(a) not less than 2 times and not more than 3 times the delivery either: regulators which permits overpressure protection devices
pressure on systems operating up to 5 psig (35 kPa); or (a) 2 times and not more than 3 times the delivery pressure on (overpressure shutoff device, overpressure relief device or
(b) not less than 1.5 times and not more than 2 times the systems operating up to 5 psig (35 kPa); or monitoring regulator) not just internal relief. The different
delivery pressure on systems operating at more than 5 psig (b) 1.5 times and not more than 2 times the delivery pressure regulators for propane and natural gas have been revised
(35 kPa). on systems operating at more than 5 psig (35 kPa). to only line pressure regulators because the scope of CSA
The relieving pressure setting of the line relief device shall be 6.22 Line Pressure Regulators is being revised so that the
not higher than that of the lowest-rated The relieving pressure setting of the line relief device shall be standard applies to both propane and natural gas.
component or accessory located downstream. not higher than that of the lowest rated component or
accessory located downstream.

5 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

5.6 Appliance and pilot pressure regulators

5.6.1 Appliance and pilot pressure regulators in propane


applications
5.6.1.3
When an appliance pressure regulator without internal relief 4.5.2 For Propane: When an appliance pressure regulator Rationale: Moved from 4.5.2. The requirement for a
having an inlet pressure not in excess of without internal relief having a diaphragm not in excess of 6 in diaphragm 6 in. or less is design restrictive. A regulator having
2 psig (14 kPa) is installed on an appliance, it shall be vented (150 m) in diameter and an inlet pressure not in excess of 2 a diaphragm 6 in. or larger and certified to operate with the
to the outdoors unless it is constructed psig (14 kPa) is installed on an appliance, it shall be vented to appropriate vent limiter should be permitted. The limiting
or equipped with a device to limit the escape of gas from the the outdoors unless it is constructed or equipped with a device orifice rate has been revised to 2.5 ft3/h so that the Btu content
vent opening in the event of diaphragm to limit the escape of gas from the vent opening in the event of of the released gas is the same for natural gas and propane.
failure, and the opening in the device shall restrict the escape of diaphragm failure, and the opening in the device shall restrict The requirement to prevent the install of vent limiter equipped
gas to not more than 1 ft3 (0.0283 m3) the escape of gas to not more than 1 ft3 (0.0283 m3) per hour regulators in a confined space was added for extra safety. Line
per hour of a gas having a specific gravity of 1.53. A regulator of a gas having a specific gravity of 1.53. A regulator with a pressure regulators for natural gas certified to CSA 6.22 are
with a vent limiting means shall not be vent limiting means shall only be installed in a ventilated tested with vent limiters rated at 2.5 ft3/h.
installed in a confined space. location.

5.6.2 Appliance and pilot pressure regulators in natural gas 4.5.2 For Natural Gas When an appliance pressure Rationale: Moved from 4.5.2. The requirement for a
applications regulator without internal relief having a diaphragm not in diaphragm 6 in. or less is design restrictive. A regulator having
When an appliance pressure regulator without internal relief excess of 6 in (150 mm) in diameter and an inlet pressure not a diaphragm 6 in. or larger and certified to operate with the
having an inlet pressure not in excess of 2 psig (14 kPa) is in excess of 2 psig (14 kPa) is installed on an appliance, it appropriate vent limiter should be permitted. The limiting
installed on an appliance, it shall be vented to the outdoors may be constructed or equipped with a device to limit the orifice rate has been revised to 2.5 ft3/h so that the Btu content
unless it is constructed or equipped with a device to limit the escape of gas from the vent opening in the event of of the released gas is the same for natural gas and propane.
escape of gas from the vent opening in the event of diaphragm diaphragm failure and the opening in the device shall restrict The requirement to prevent the install of vent limiter equipped
failure, and the opening in the device shall restrict the escape of the escape of gas to not more than 1 ft3 (0.0283 m3) per hour regulators in a confined space was added for extra safety. Line
gas to not more than 2.5 ft3 (0.0706 m3) per hour of a gas of a gas having a specific gravity of 0.6. pressure regulators for natural gas certified to CSA 6.22 are
having a specific gravity of 0.6. A regulator with vent limiting tested with vent limiters rated at 2.5 ft3/h.
means shall be installed in a ventilated space only.

6. Piping and tubing systems, hose, and fittings 5. Piping and tubing systems, hose, and fittings

6.2.1 Piping shall comply with ASTM A 53 / A 53M or A 106. 5.2.1 Piping shall comply with ASTM A 53 or A 106. Revised -

6.2.5 Flared nuts shall be forged. New Clause Rationale: Flared machined nuts do crack. The intent of the

6 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

proposal is to ensure that flared nuts are not of machined type.


6.2.8 Tubing shall be one of the following: 5.2.7 Tubing shall be of seamless copper or steel. Revised – To clarify that tubing also includes corrugated
stainless steel tubing.
a) Corrugated stainless steel tubing (CSST);
b) Seamless copper; or
Seamless steel.

6.2.20 Corrugated stainless steel tubing (CSST) and associated New Clause To clarify that CSST and fittings used for natural gas and
fittings shall comply with ANSI/IAS LC1/CSA 6.26 or CSA CGA propane fuel systems shall certified to applicable CSA
Certification Laboratory Requirement LAB-009. Standard or the CGA Lab Requirement.

6.7.4 Piping or tubing in solid flooring, such as concrete, shall 5.7.4 Piping or tubing in solid flooring, such as concrete, Rationale: The existing requirements of Clause 5.7.4 are
be laid in channels and suitably covered to permit shall be laid in channels and suitably covered to permit design-restrictive with respect to the use Corrugated Stainless
access to the piping or tubing. Alternatively, the piping or tubing access to the piping or tubing. Alternatively, the piping or Steel Tubing (CSST) and Flexible Copper Tubing (FCT) in new
shall be encased in ducts so that there is tubing shall be encased in ducts so that there is a free air high/low buildings with concrete floor slab applications. The
free air space around the pipe or tube. Such a duct shall be space (of not less than 0.5 in (13 mm)) around the pipe or existing requirements would require a thicker concrete slab if
ventilated. (Accepted Revisions, 2001) tube. Such a duct shall be ventilated. tubing were installed in ducts that would normally be required.
The intent of this clause was to provide a path or egress for
any leaks and protect the tubing from damage. Canadian Gas
Research Institute performed a number of tests pulling various
diameters of tubing through duct smaller than presently
required by Clause 5.7.4. The results of the testing indicated
that even pulling large diameter tubing through a smaller duct
with 90 degree bends did not generate a force sufficient to
damage CSST or FCT. Also the Subcommittee was in the
opinion that any space sufficient for pulling tubing through also
provides sufficient space for any egress of gas. The use of a
smaller clearance is not without precedence. This practice has
been employed in the US. NFPA 54 does not require any
clearance, but only protection against corrosion.
6.11.3 A gas convenience outlet shall comply with ANSI Z22.99 New Clause To clarify that gas convenience outlets shall comply with CSA
/ CSA 6.24. Standard 6.24.

7 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

6.16.12 Corrugated stainless steel tubing (CSST) and fittings New Clause To clarify to installers that the installation of CSST shall comply
shall be protected against physical damage in accordance with with the manufacturer’s certified installation instructions and
the manufacturer’s certified installation instructions and with this with the requirements in the CSA-B149.1 Code.
Code.

6.17.2 In every care or detention occupancy, commercial, The new requirement is to ensure that piping and tubing
industrial, and assembly building, piping or tubing where the New Clause systems with pressures in excess of 14 in w.c. (3.5 kPa) are
pressure is in excess of 14 in w.c. (3.5 kPa) shall be identified identified to advise the user and personnel performing work or
at the following locations: maintenance on the system of the supply pressure. This
(a) shut-off valves, and information is necessary for selecting appliances, equipment
(b) wall, ceiling, and floor penetrations. and components or replacement parts that are suitable for the
pressure supplied.

6.17.4 Every piping or tubing system that enters a building 5.17.3 Every piping or tubing that enters a building that has Rationale: Note: Commas are inserted after the words
that has two or more gas meters shall be two or more gas meters shall be clearly identified with the “building” and “meters”. the intent is to clarify the wording. The
permanently identified with the room number, apartment number of the room, apartment number or the area of the word “clearly” is vague and thus it is proposed to replace it with
number, or the area of the building it serves. (Accepted building it serves. “permanently”.
Revisions, 2001)

6.20 Hose and hose fittings

6.20.1 Except as permitted in Clause 7.22.3, a hose 5.20.1 A hose connected to a vented appliance shall be Revision – To clarify that hose may be used for connecting
connected to a vented appliance shall be prohibited. prohibited. infrared radiant tube heaters to gas piping where breakage is a
concern due to expansion and contraction.

6.20.3 When a hose is used 5.20.3 When a hose is used


(c) for connecting a construction heater, it shall be neither (c) for connecting a construction heater, it shall be neither Revision - In order to allow more hose when connecting a
less that 15 ft (4.6 m) nor more than 75 ft (24 m) in total less that 15 ft (4.6 m) nor more than 50 ft (16 m) in total construction heater to a natural gas or propane supply for
length; length; greater flexibility on larger construction sites.

6.20.6 When tanks or pieces of equipment are interconnected, Rationale: A major fire resulted from the rupture of a liquid
provision shall be made to compensate for vibration and New Clause propane hose interconnecting a vaporizer and three tanks.
differential settling of the tanks, equipment, and interconnecting The hose has been cut by a grass cutting tool. The hose met

8 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

piping. Where a flexible hose is used for this purpose, it shall be the CAN/CGA-8.1 Standard but was not made with metallic
a flexible metallic hose complying with ULC C536or a hose reinforcement. For years, the industry used the metallic
connector with stainless steel reinforcement complying with reinforcement hose for application with liquid propane.
CSA CAN/CGA-8.1. Because of competitive market combined with the efforts to cut
installation cost, some supplies promote the type I hose as a
replacement for the type II hose for liquid propane. The
proposed change will maintain the good practices of the
industry. (2003 Accepted Revisions)
6.21 Connectors
6.21.5 When the connector described in Clause 6.21.4 is used 5.21.5 When a metal connector is used with a commercial Revised – To clarify that the connector shall comply with
with a commercial cooking appliance installed on wheels or cooking appliance installed on wheels or rollers, a CSA Standard 6.16 and installation shall maintain the
rollers, a noncombustible retraining device shall be provided to noncombustible retraining device shall be provided to protect clearances as specified in Clause 7.31.4. The Clause as
protect the connector, and the installation shall be in the connector, and the installation shall be in accordance with previously written was ambiguous with respect to which
accordance with Clause 7.31.4. Clause 6.30.4. connector was being referred to. This revision clears up
that ambiguity.
Table 6.3 Table 5.22.2
Pressure test requirements Pressure test requirements
(See Clause 6.22.1 and 6.22.2) (See Clauses 5.22.1 and 5.22.2) Revised – { See (a) , (b) and (c) }

* Propane maximum operating pressure is defined as <No change to text within the Table> Added information to define operating pressures for propane to
(a) 250 psi (1750 kPa) for piping and tubing operating clarify the test pressure required for propane piping systems
at container pressure; Notes: that are exposed to container pressures or that can contain
(b) 350 psi (2400 kPa) when connected to the outlet of (1) These test pressures and test durations are minimum liquid propane.
a pump compressor requirements. Circumstances can require test
(c) 375 psi (2570 kPa) minimum or the setting of the pressures and test durations in excess of those shown
hydrostatic relief valve in piping that can contain in the Table.
liquid propane, that can be isolated by valves, and (2) All wrapped and/or factory-coated piping systems of all
that require hydrostatic relief valves as specified in sizes and lengths shall be tested at a minimum
Clause 4.4.1 of this Standard or Clause 4.6.1 of CSA pressure of 100 psig (700 kPa) in accordance with the
B149.2. time duration in the table

Notes: (1) and (2) no changes

7. Installation of specific types of appliances 6. Installation of specific types of appliances

9 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

Rationale: Currently, a flexible aluminum duct is being used as


7.4 Commercial Type Clothes Dryers New Clause. a transition duct between dryer and rigid moisture duct. It has
been noted that when the machine is moved for servicing or
7.4.3 A certified flexible foil noncombustible-type duct may be cleaning purposes, the flexible aluminum transition ducts has a
used as a transition connection between the tendency to separate. Using an approved flexible foil flexible
dryer exhaust and a rigid moisture duct. transition duct will allow for an air tight transition connection,
easier installation and movement of appliance for servicing and
cleaning in and around the appliance without the possibility of
separation causing exhaust and lint leakage into the laundry
room. (2003 Accepted Revisions)

7.13 Central Furnaces New Clause. New requirement to ensure installers pay careful attention to
the arrangement of the installation ductwork to prevent
7.13.6 Furnace return-air ducting installed in an enclosure in contaminated air from entering the return-air system and
which any spillage-susceptible appliances are creating a health hazard.
located (including the furnace) shall be sealed to the furnace Rationale: The investigation into a CO fatality revealed that a
casing, and joints in the ducting shall be contributing factor in the accident was inadequate sealing of
sealed to prevent infiltration of air from the enclosure into the the return air ducting for a furnace. If the portion of the return
return-air ducting. air ducting in the enclosure was sealed to prevent the
infiltration of air from the enclosure into the heating duct
system, this problem may have been prevented. A clause
should be added to ensure proper sealing of furnace return air
ducts. A similar requirement is already in the code for multi-
story vent systems (refer to 8.21.4).

7.18 Construction heaters and torches

7.18.1 A construction heater shall be located to minimize the 6.18.1 A construction heater shall Revised – Mechanical damage was generalized to damage
danger of damage and upset. (a) be located so as to minimize the danger of mechanical since any damage to the appliance would be a concern.
damage and upset

7.18.2 A construction heater shall be installed on a solid, level, 6.18.1 A construction heater shall New – There is now available a construction heater that is
noncombustible base or, where so designed, suspended in (b) be installed on a solid, level, noncombustible base. approved for use as a suspended heater. The new requirement
accordance with the manufacturer’s certified installation is to ensure construction heaters are installed in accordance

10 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

instructions. with the manufacturer’s certified installation instructions (i.e.


Infra-red heaters certified for use as construction heaters.

7.21 Non-recirculating direct gas-fired industrial air heaters In 1998 the Joint ANSI/CGA Heavy Duty Heater Subcommittee
(DFIAH) New Section voted to provide code coverage for the Non-Recirculating
Direct Gas-Fired Industrial Air Heaters (DFIAH) for installation
in Canada.

7.21.1 A non-recirculating DFIAH shall be installed only in


industrial buildings, except as specified in Clause 7.21.10 to New Clause The following comments will provide rationale that may pertain
7.21.12. to one or more of the new Clauses.

1/ The new harmonized American National Standard Z83.4 /


CSA Standard 3.7 covers DFIAH whose purpose is to offset
building heat loss only in industrial and commercial
applications.

7.21.2 A non-recirculating DFIAH shall not supply air to an New Clause 2/ The DFIAH are not permitted to heat or ventilate areas
area where sleeping accommodation is provided. containing sleeping quarters and this is consistent with the past
application of direct-fired heaters.

7.21.3 A non-recirculating DFIAH shall be certified to be in


compliance with ANZI Z83.4/CSA 3.7. A non-recirculating New Clause 3/ A non-recirculating DFIAH is used extensively to provide
DFIAH may be used as a door heater, make-up air heater, or a fresh air ventilation and/or to purge or dilute contaminants from
space heater, or for a combination of these functions. When a an occupied space.
non-recirculating DFIAH is used as a door heater or a make-up
air heater, the requirements of Clause 7.21 shall supersede the
requirements of Clause 7.19 for door heaters and Clause 7.20
for make-up heaters.

7.21.4 A non-recirculating DFIAH shall be installed with a 4/ The CSA Standard 3.7 contains test requirements for
clearance from combustible materials not less than that marked New Clause clearance to combustible materials and the DFIAH shall be
on the rating plate. See also Clause 4.14.2. installed in accordance with the manufacturer’s installation

11 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

instructions and marking on the rating plate.

7.21.5 All supply air to a non-recirculating DFIAH shall be 5/ The DFIAH by the Scope of the CSA Standard 3.7 and by
ducted directly from outdoors. New Clause the definition these heaters must have all the air handled by the
heater ducted directly from outdoors.

7.21.6 Inlet ducting, when used, shall be purged with at least 6/ There are installations that have inlet and outlet ducting to
four air changes prior to an ignition attempt. New Clause locate the DFIAH in a more desired location within a building.
The CSA Standard 3.7 requires heater housing to be purged
four air changes before the ignition system is activated. This
action serves to purge the heater and discharge ducting to
remove any flammable vapours that may be present prior to
an ignition attempt.

7.21.7 If outside air dampers or closing louvers are used, they 7/ The heater operation requires all of its air from outside, any
shall be interlocked so that the main burners do not operate New Clause device which serve to close off that air supply are required to
until the air dampers are fully open. provide a signal once they are in a full open position.

7.21.8 The design of the installation shall include adequate 8/ These heaters may be utilized to heat building and to offset
provisions to permit a non-recirculating DFIAH to operate at its New Clause heat loss, as such, their installation must be designed to
rated capacity, taking into account the structure’s designed include the air load which infiltrates and exfiltrates the building
exfiltration rate, by providing properly designed relief openings envelope as a result of local climatic conditions. Therefore, the
or an interlocked powered exhaust system, or a combination of installations of these heaters are site specific and shall be
these methods. designed by a professional engineer.

Where the installation is dependent upon exfiltration through 9/ When interlock devices are required to operate a non-
the building envelope or through relief openings, the structure’s circulating DFIAH, a means is necessary to permit testing of
designed exfiltration rate and the size of the relief openings the appliance without activating the interlocking source.
shall be determined by a professional engineer.

Relief openings shall be louvres or counterbalanced gravity


dampers. Motorized dampers or closable louvres may be used,
provided that they are interlocked so that the main burners do
not operate until the air dampers are fully open.

12 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

7.21.9 A non-recirculating DFIAH shall be located not less than To clarify that a minimum of 20 ft is required between the
20 ft (6 m) horizontally from a vertical plane in which New Clause exposed flame in the DFIAH and any combustible
combustible gas, vapour, or dust is present. concentration of gas, vapour, or dust.

7.21.10 A DFIAH, when installed for the purpose of ventilating To clarify that the DFIAH is interlocked with the fire alarm for
or pressurizing an elevator shaft or stairwell, shall be New Clause the purpose of providing ventilation or pressurization to prevent
(a) activated only by a fire alarm system under normal prolonged exposure to products of combustion.
operation; and
(b) equipped with a normally open momentary manual switch
that will permit testing of the DFIAH without activating the fire
alarm system. This switch shall be installed on or located
directly adjacent to the DFIAH and shall be identified as to its
function.

7.21.11 When a DFIAH is installed for the ventilation of a A DFIAH used solely for this purpose shall be activated by a
storage garage and the DFIAH is solely activated by a carbon New Clause carbon monoxide (CO) sensor and must be capable of being
monoxide senor, the DFIAH shall be installed with a normally tested without activating the CO alarm.
open momentary manual switch to permit testing of the DFIAH.
This switch shall be located either on or directly adjacent to the
DFIAH and shall be identified as to its function.

7.21.12 When a DFIAH is either installed in or ducted to a To limit the exchange of air between a food preparation area
kitchen, it shall be installed in accordance with the following New Clause and any area occupied by the public in a building where the
procedures: kitchen is served by a DFIAH. The designer will ensure proper
operation and performance of the DFIAH to prevent an excess
(a) Where the food preparation area and the area frequented by air pressure imbalance on the HVAC system serving the public
the public is interconnected by means area.

(i) of either normally closed doors or a permanent


opening(s) and the total free area of the opening(s)
does not exceed 16 ft2 (1.5 m2), the DFIAH shall be
interlocked with a mechanical exhaust system and the
proven airflow capacity of the interlocked exhaust

13 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

system shall not be less than 90% of the make-up air


supply; or

(ii) other than those indicated in item (i), the DFIAH


shall be interlocked with a mechanical exhaust system
100% or more than 105% of the make-up air supply.

(b) All other requirements contained in Clause 7.21, where


applicable, shall apply.

7.22. Infrared heaters 6.21. Infrared heaters

7.22.1 Where an infrared heater is of the unvented type, it shall 6.21.1 Where an infra-red heater is of the unvented type, it This Clause was revised in order to clarify the intent of the
(a) be protected against physical damage; shall requirements contained in Item (e).
(b) comply with Clause 4.9.2; (a) be protected against physical damage;
(c) not be installed in a residential or care or detention (b) comply with Clause 3.9.2;
occupancy building; (c) not be installed in a residential or care or detention
(d) when certified for use as a construction heater, comply with occupancy building;
Clause 7.18 and be exempted from item (e) to (g); (d) when certified for use as a construction heater, comply with
Clause 6.18 and be exempted from item (e) , (f), and (g) of this
(e) be provided with mechanical ventilation Clause;
(e) be provided with mechanical ventilation so located that the
(i) that is so located that the products of combustion products of combustion from each heater are effectively
from each heater are effectively removed outdoors; removed outdoors, have a ventilation volume of at least 300
(ii) that has a ventilation volume of at least 300 cfm cfm for each 100 000 Btuh (30 kW) input or fraction thereof;
(142 dm3 /s) for each 100 000 Btuh (30 kW) input or and the mechanical ventilation is sufficient to maintain the
fraction thereof; and level of carbon dioxide at less than 5000 ppm measured 6 ft (2
(iii) is sufficient to maintain the level of carbon dioxide m) above the work area;
at less than 5000 ppm measured 6 ft (2 m) above the
work area;
(f) have the ventilation system so interlocked that any reduction (f) have the ventilation system so interlocked that any
of the volume of airflow required by Item (e) for a heater or reduction of the volume of air flow required by Item (e) for a
group of heaters will cause the shutdown of the heater or group heater or group of heaters will cause the shutdown of the
of heaters; heater or group of heaters;

14 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

(g) be provided with combustion and ventilation air compatible (g) be provided with combustion and ventilation air
with Item (e); compatible with Item (e);
(h) not be installed in an exit passageway or stairway within 8 ft (h) not be installed in an exit passageway or stairway within 8
(2.5 m) measured horizontally from an exit door; and ft (2.5 m) measured horizontally from an exit door; and
(i) be provided with clearance from combustible material as (i) be provided with clearance from combustible material as
certified and indicted on the appliance. certified and indicted on the appliance.

7.22.3 An infrared heater of the unvented type shall be installed 7.21.3 An infrared heater of the unvented type shall be This Clause was revised by adding the requirements for the
in accordance with the certified marking and the manufacturer’s installed in accordance with the certified marking and the use of a Type I hose to connect to the gas supply due to the
certified installation instructions. It shall be protected against manufacturer’s certified installation instructions. It shall be extreme expansion and contraction of the tube-type heaters.
physical damage. A tube-type infrared heater shall only be protected against physical damage. The metal connectors were failing as the result of stress
connected with a Type I hose connector that is caused by expansion / contraction that some heater
(a) certified as being in compliance with CSA CAN/CGA-8.1; manufactures state can be up to 1 inch per 10 ft of tube
and
(b) of a length of 36 ± 6 in (90 ± 15 cm).

7.32 Residential-type ranges

7.32.7 When the underside of the combustible material above a 7.32.7 When the underside of the combustible material above Revised by adding reference to Clause 7.32.4 to identify where
residential-type range is protected with insulating millboard at a residential-type range is protected with insulating millboard to find the minimum clearances from combustible materials.
least 0.25 in (6 mm) thick covered with sheet metal not less at least 0.25 in (6 mm) thick covered with sheet metal not less
than 28 MSG (0.3 mm), the clearance above the range as than 28 MSG (0.3 mm), the clearance above the range as
specified in Clause 7.32.4 may be reduced to 24 in (600 mm). specified may be reduced to 24 in (600 mm).

7.32.8 An exhaust hood, an exhaust appliance, or a New Clause This Clause was added to clarify hoods, exhaust appliances or
combination thereof installed above a range shall be installed in combination units (space saver microwaves) that contain
accordance with certified installation instructions for such an combustible materials or may be affected by moisture
exhaust hood or appliance. generated from cooking shall be installed in accordance with
the manufacturer’s certified instructions.

8. Venting systems and air supply for appliances 7. Venting systems and air supply for appliances

8.10.13 A false ceiling space, or a confined space used for Rationale: To allow concentric, balanced flue venting

15 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

return air, shall not contain a vent or vent connector New Clause systems and other vent/vent connectors with sealed joints
that does not have sealed joints or seams. or seams to be installed in false ceiling spaces (2003
Accepted Revisions)
8.12.11 The venting of a gas-fired appliance into a chimney 7.12.11 The venting of a gas-fired space-heating appliance Revision accepted 2000, deleted the words space-heating.
flue common to both halves of a semi-detached house is into a chimney flue common to both halves of a semi- To avoid spillage of flue gases into the adjacent unit and
prohibited. detached house is prohibited. to clarify that the risk is similar in connecting any
appliances other than space heating as well
8.30.2 An approved appliance not identified in Clause 8.30.1(d) 7.30.2 An approved appliance not identified in Clause Revised.
may be installed under a canopy, provided that the appliance is 7.30.1(d) may be installed under a canopy, provided that
interlocked so that operation is permitted only when exhaust (a) the appliance is interlocked so that operation is permitted Rationale: There is no apparent reason as to the need or
airflow is proven. only when exhaust air flow is proven; the function of the 4 minute delay. These 2 provisions are
(b) the appliance is interlocked through a 4-min time delay considered out of date, and no longer applicable.
manual reset device; and
(c) the manual reset device is readily accessible and its
function is identified.

9. Natural gas compressors and cylinders


8. Natural Gas Compressors
9.2 Requirements for cylinders

9.2.1 Refillable cylinders shall be manufactured, tested, 8.2.1 A cylinders shall be manufactured, tested, inspected, Revised.
inspected, and marked in accordance with the requirements of and legibly marked in accordance with Transport Canada The Clause was updated to specify that refillable cylinder
the Transportation of Dangerous Goods Regulation (TDG requirements. shall comply with the TDG regulations of Transport
regulations) of Transport Canada. Canada.

9.3 Cylinder filling and cylinders

9.3.2 Cylinders used indoors shall not be filled in excess of Revised: 8.3.2 Cylinders shall not be filled in excess of Rationale: It was agreed the reference temperature should
300 psig (2100 kPa) at 59ºF (15 ºC). 300 psig (2100 kPa). be specified. A member stated that the norm is 15 C.
Additionally, it was agreed to qualify cl. 9.3.2 because
cylinders used indoors should be filled only to 300 psig
regardless of where used.
9.3.3 A cylinder connected for filling shall be located outdoors, Revised: 8.3.3 A cylinder connected for filling shall be
unless indoor filling is approved by the authority having located outdoors, unless indoor filling is approved by the Accepted revisions from M14.1.3. June 2002 Meeting

16 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

jurisdiction, and shall be authority having jurisdiction, and shall be


(a) filled through (a) filled through Rationale: Editorial. It was agreed that the term
(i) an approved manifold; and (i) an approved manifold; and “permanent wall” should be replaced with the defined term
(ii) an approved connector equipped with a back check valve (ii) an approved connector equipped with a back check “building opening”.
at the point of cylinder connection; valve at the point of cylinder connection;
(b) located not less than 3 ft (1 m) from a building opening or (b) located not less than 3 ft (1 m) from a permanent wall or
air intake; and air intake; and
(c) located not less than 10 ft (3 m) from a mechanical air (c) located not less than 10 ft (3 m) from a mechanical air
intake. intake.

10. Vehicle refueling appliances (VRA) without storage (for 8. Vehicle refueling appliances (VRA) without storage (for
natural gas only) natural gas only)
10.1 Installation

10.1.1 A VRA refuelling system shall be certified in Revised: 9.1.1 A VRA refuelling system shall be Rationale: A VRA must meet the certification
compliance with the requirements of CSA 12.6. designed and installed to provide NGV at up to the requirements of CSA 12.6. All of the pressure parameters
temperature-compensated equivalent of 3000 psig (20 680 are defined in 12.6
kPa) at 70ºF (21ºC). The pressure shall not exceed 3600
psig (24 820 kPa) regardless of the temperature.
10.1.6 When a vehicle is fuelled indoors, a gas detector shall 9.1.6 Where indoor fuelling of a vehicle is acceptable to the Revised
(a) be installed within 6 in (150 mm) of the ceiling or highest authority having jurisdiction, a gas detector shall
point above the refueling area; (a) be installed within 6 in (150 mm) of the ceiling or highest The VRA’s have proven to be reliable for indoor refueling and it
(b) be set to activate at natural gas detection levels at and point above the refueling area; is no longer necessary to obtain prior approval from the AHJ.
above one-fifth of the lower limit of flammability of natural gas; (b) be set to activate at natural gas detection levels at and In addition, the previous wording in item (c) was rearranged to
(c) upon activation, produce an audible and visual alarm; above one-fifth of the lower limit of flammability of natural gas; clarify the installation requirements for the gas detector.
(d) be interlocked with a mechanical ventilation system (see (c) upon activation, produce an audible and visual alarm, be
Clause 10.1.7; and interlocked with a mechanical ventilation system (see Clause
(e) be interlocked to shut off the VRA. 9.1.7, and be interlocked to shut off the VRA(s).

10.1.7 The mechanical ventilations system referred to in 9.1.7 The mechanical ventilation system referred to in Revised
Clause 10.1.6(d) shall Clause 9.1.6.(c) shall
To clarify that the ventilation rate is 25 times the flow rate of the
a) vent the fuelling area to the outdoors at a flow rate of 25 (a) vent the fuelling area to the outdoors at a flow rate of 25 VRA and not the building.
times the flow rate of the VRA; and times the flow rate of any building used in connection with

17 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Clause in New Edition Clause in previous edition Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.1-2005, Mississauga: CSA B149.1-00, Mississauga: CSA

VRA(s); and
b) provide for minimum clearance from the discharge as (b) provide for minimum clearances from the discharge as
specified in Table 5.2 outlined in Table 4.5.10.

10.3 Piping, tubing, and hose

10.3.1 The following requirements shall apply to all gas piping 9.3.1 All gas piping required to install a VRA and its associated Revised
required to install a VRA and its associated equipment equipment shall be installed as follows: This Clause was modified to clarify that the installers shall
(a) They shall be installed in accordance with the (a) the gas supply line to the inlet of a VRA shall be installed in follow the manufacturer’s installation instructions, the CSA-
manufacturer’s certified instructions. accordance with the requirements of Clause 5 of this Code or B149.1 piping requirements and the CSA B108.
(b) The gas supply line to the inlet of a VRA shall be installed in the authority having jurisdiction;
accordance with the requirements of Clause 6 of this Code or (b) discharge piping from the outlet of a VRA not directly
the authority having jurisdiction. connected by the manufacturer shall be installed in
(c) Discharge piping, not directly connected by the accordance with the requirements of GCA Standard
manufacturer, from the outlet of a VRA shall be installed in CAN/CGA-B108 and pressure tested 1.5 times the working
accordance with the requirements of CSA B108. pressure for the duration of 15 min with no evidence of
leakage; and
(c) in accordance with the manufacturer’s certified
instructions.

Annex A (informative) Appendix A

Note: Note:

This informative annex has been written in normative This Appendix is not a mandatory part of this Code.
language to facilitate adoption where users of this Code or However, it has been written in mandatory terms to
regulatory authorities wish to adopt it formally as facilitate adoption where users of this Code or regulatory
additional requirements to this Code. authorities wish to formally adopt it as additional
requirements to this Code.

18 of 19
Any quotations in this document are taken directly from the CSA – B149.1-2005
NATURAL GAS and PROPANE INSTALLATION CODE
* Summary of Changes – not intended to be all inclusive

Annex H – Purging of piping and tubing systems Appendix H – Purging of piping and tubing systems
Note: This annex is a mandatory part of this Standard.
Re-numbering only

Annex I
General Information Tables for
New
1.1 Properties of Propane, Butane and Natural Gas
1.2 Combustion data
1.3 Orifice capacity
1.4 Conversion of volumes of one kind to another

19 of 19
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

Note: The CSA B149.2-00 Code covers the Propane Storage


and Handling.
1. Scope 1. Scope

1.2 This Code does not apply to 1.2 This code does not apply to Revised – The volume was reduced to 150 g from 250 g.
Cylinders of 225 g are being used in restaurants for portable
(h) butane fuel cylinders of 5.3 oz (150 g) capacity or less; (h) butane fuel cylinders of 250 g capacity or less; and cooking. Incidents have occurred and no one appears to have
and jurisdiction for these cylinders.

1.4 The valves given in yard/pound units are the standard. 3.1.1 This Code contains SI (metric) equivalents to yard/pound Revised. To clarify the intent and the units that are considered
This Code contains SI (metric) equivalents to yard/pound units units so that the Code can be used in SI (metric) units. SI to be the requirement.
so that the Code can be used in SI (metric) units. SI (metric) (metric) equivalents may be approximate. Yard/pound units
equivalents can be approximate. shall be regarded as the requirement.

1.5 In this Code, unless approved otherwise by the authority 3.1.2 Where the word “shall” is used in this Code, it indicates a This Clause was revised in order to reflect CSA’s policy and
having jurisdiction, “shall” indicates a mandatory requirement unless approved otherwise by the authority terms consistent with other CSA Codes.
requirement; “should” indicates a recommendation or that having jurisdiction.
which is advised but not mandatory; “may” indicates an
advisory or optional statement. Notes to the text do not include
mandatory or alternative requirements. The purpose of a note
is to separate from the text explanatory or informative material
that is not properly a part of this Code. Notes to figures and
tables, however, are considered part of the figure or table and
are written as mandatory requirements. Legends to figures are
also written as mandatory requirements.

*3 Definitions 2.1 Definitions

1 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

Cylinder – a container designed and manufactured in Cylinder – (with respect to NGV/propane storage) a container Revised – To clarify that propane containers shall be
accordance with a cylinder specification authorized for the designed and fabricated in accordance with the specifications designed and manufactured under the TDG Regulations of
containment and transportation of propane under the of Transport Canada (TC) or the U.S. Department of Transport Canada
Transportation of Dangerous Goods (TDG) Regulations of Transportation for the storage and transportation of propane.
Transport Canada.

Combustible — material that fails to conform to ULC CAN4- Combustible – material that fails to conform to ULC Standard
S114 requirements for noncombustibility. CAN4-S114.

Flue gas dilution air – see Air Supply New This was added to be consistent with the CSA-B149.1

Continuous pilot – a pilot that burns without turndown New See above
throughout the entire time the burner is in service, whether the
main burner is firing or not.
TC – Transport Canada New To clarify that TC means Transport Canada as it was
proposed to delete the abbreviations from the Code.

4. General 3. General

4.3 Responsibilities of the installer 3.3 Responsibilities of the Installer

4.3.5 It shall be the responsibility of the installer of a piping or 3.3.5 It shall be the responsibility of the installer Revised by creating a new Clause for part (b) to be consistent
tubing system to perform pressure tests in accordance with (a) of a piping or tubing system to perform pressure tests in with the B149.1 and to clarify the responsibilities for different
Clause 6.22.2 of CSA B149.1 and to ensure that the piping or accordance with Clause 5.22.2 of CSA Standard B149.1 and to installers <see below>. The installer of the piping or tubing is
tubing system is gas-tight at the completion of the tests. ensure that the piping or tubing is gas tight at the completion of not necessarily the same one who installs the gas appliances.
the tests; and

2 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

4.3.6 It shall be the responsibility of the installer of an appliance 3.3.5 It shall be the responsibility of the installer This new Clause was added to be consistent with the B149.1
to perform tests in accordance with Clause 6.22.3 of CSA (a) <see above> and to increase the awareness that it is the responsibility of the
Standard B149.1 and to ensure that the system is gas-tight at (b) of the appliance to perform tests in accordance with appliance installer to ensure the connection, valve train and
the completion of the tests. Clause 5.22.3 of the CSA Standard B149.1 and to ensure that system components are gas-tight.
the system is gas tight at the completion of the tests.

4.5 Suitability of use 3.5 Suitability of Use

4.5.4 Before reconnection to the supply piping or tubing, a used 3.5.4 A used appliance shall be inspected and determined by Editorial revision only – No change in the intent of this Clause.
appliance shall be inspected and determined by the install to the installer to be safe for continued used before reconnection
be safe for continued use. to supply piping or tubing.

5.3 Protection of containers and equipment 4.3 Protection of Containers and Equipment

5.3.2 When containers are installed in locations that do not 4.3.2 When a container is located in a vehicular traffic area, Revised to clarify the intent of the Clause by listing specific
afford protection from damage from motor vehicles on any protection from physical damage shall be provided in locations that would require protection from motor vehicles.
street, highway, avenue, alley, or parking lot, they shall be compliance with Clause 6.19.4.
protected by posts or guardrails in compliance with Clause
7.19.4 unless otherwise approved by the authority having
jurisdiction.

3 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

6. Cylinder systems 5. Cylinder Systems

6.1.8 A refillable cylinder with a capacity of 45 lb (20 kg) or less 5.18 A refillable cylinder with a capacity of 45 lb (20 kg) or less Revised only by adding the equivalent French wording for the
shall be equipped with an effective gas-tight seal such as a shall be equipped with an effective gas-tight seal such as a marking on the cap.
plug, cap, or other equally effective device. A protective cap for plug, cap, or other equally effective device. A protective cap for
the valve outlet shall be attached to the cylinder connection the valve outlet shall be attached to the cylinder connection To ensure manufacturers provide instruction in both English
device. The protective cap shall bear the following marking: device. The protective cap shall bear the following marking: and French.
“PLACE CAP ON CYLINDER VALVE OUTLET WHENEVER
THE CYLINDER IS NOT CONNECTED FOR USE” PLACE CAP ON CYLINDER VALVE OUTLET WHENEVER
*The equivalent French wording is “METTRE LE THE CYLINDER IS NOT CONNECTED FOR USE
BOUCHON SUR LA SORTIE DU ROBINET LORSQUE LA
BOUTEILLE N’EST PAS UTILISEE”.

6.2 Liquid level gauges on cylinders 5.2 Liquid level gauges on cylinders

6.2.1 A liquid level gauge that requires the bleeding of propane 5.2.1 A liquid level gauge such as a rotary, fixed-liquid-level,
to the atmosphere, such as a rotary, fixed-liquid-level, or slip- or slip-tube type that requires the bleeding of propane to the Editorial revision only – No change in the intent of this Clause.
tube type, shall be designed so that any bleed valve opening is atmosphere shall be designed so that any bleed valve opening
not larger that a No. 54 drill size (1.4 mm) unless it is provided is not larger that a No. 54 drill size (1.4 mm) unless it is
with a excess-flow valve. provided with an excess flow valve.

6.5 Storage and use of cylinders at locations other than 5.5 Storage and Use of Cylinders at Locations Other than
filling plants Filling Plants

4 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

6.5.1.9 5.5.1.9 Except as noted below, an outdoor cylinder storage


An outdoor cylinder storage area, special cylinder storage area, special cylinder storage room, or a cylinder storage
room, or a cylinder storage building described building described in Clause 6 shall be located in accordance
in Clause 6 shall be located in accordance with Table 6.3 with with Table 6.3 with respect to
respect to Revised by adding a new Note to address the installation of
(a) the nearest building or group of buildings; (a) the nearest building or group of buildings; cabinets or cages for exchange or sale of 20 lb (9 kg) propane
(b) the line of adjoining property that may be built upon; (b) the line of adjoining property that may be built upon; cylinders at retail sites.
(c) public thoroughfares or sidewalks; and (c) public thoroughfares or sidewalks; and
(d) the line of adjoining property occupied by schools, (d) the line of adjoining property occupied by schools,
churches, hospitals, athletic fields, or other points of public churches, hospitals, athletic fields, or other points of
gathering. public gathering.

Table 6.3 Table 5.5.1.9


Cylinder storage clearances Cylinder storage clearances
(See Clause 6.5.1.9) (see Clause 5.5.1.9)

Distance ft (m) to
Distance, ft (m) Quantity of propane stored Items Items
to Items (a) to Items (c) lbs (kg) (a) and (b) (c) and (d)
Quantity of propane and (b) of and (d) of
stored, lb (kg) Clause 6.5.1.9 Clause 6.5.1.9
Up to and including 500 (225) 0*† 10 (3)
Up to and including 500 (225) 0*† 10 (3)
500 (225) to 2500 (1135) 15 (4.5) 25 (7.5)
501 (225) to 2500 (1135)‡ 15 (4.5) 25 (7.5)
2501 (1135) to 5000 (2270) 25 (7.5) 25 (7.5)
2501 (1135) to 5000 (2270) 25 (7.5) 25 (7.5)
Over 5000 (2270) 25 (7.5) 50 (15)
Over 5000 (2270) 25 (7.5) 50 (15)

*3 ft (1 m) from any building opening.


†10 ft (3 m) from any mechanical air intake. * 3 ft (1 m) from any building opening.
‡ Cylinders that have a maximum capacity of 20 lb (9 kg) intended for † 10 ft (3 m) from any mechanical air intake.
exchange or sale shall be stored in no more than four adjacent cabinets that
may be located against a noncombustible building wall at one retail site. No
more than one cabinet may be located against a combustible wall. Each
cabinet shall contain no more than 500 lb (225 kg) of propane. Cabinets shall
be 3 ft (1 m) from any building opening and 10 ft (3 m) from any mechanical air
intake. Cabinets shall be 25 ft (7.5 m) from the line of adjoining property
occupied by schools, churches, hospitals, athletic fields, or other points of
public gathering.

5 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

6.5.6 Storage of non-refillable cylinders in retail outlets 5.5.6 Storage of Nonrefillable Cylinders within Retail
and their warehouses (mercantile occupancies) Outlets and Warehouses

6.5.6.1 The requirements of Clause 6.5.6 apply to non-refillable 5.5.6.1 The requirements of this Clause shall apply to cylinders Revision to correctly identify the types and capacities of the
cylinders (TC-39, TC-2P, and TC-2Q) with net capacities of manufactured to TC Specifications 39, 2P, and 2Q and known “single-trip” cylinders. No change in the intent of this Clause.
more than 0.36 lb (150 g) and less than 1.05 lb (475 g), as “single trip” or “nonrefillable” cylinders
commonly referred to as “single-trip” cylinders.

6.5.6.2 Cylinders located within the display area of a retail 5.5.6.2 Cylinders located within
outlet (mercantile occupancy) shall be display ed as follows: (a) a retail outlet may be displayed
(a) Cylinders shall be removed from cartons, or cartons shall (i) in one area only and limited to a total of 60
be display cut. cylinders or a maximum of 60 lbs (27 kg) of propane:
(b) Cylinders shall be securely stacked to a height of no more or
than 6 ft (2 m) from the base to the top of the display. Shelves (ii) in not more than two areas and limited to a total of
used to display cylinders shall be of a stable construction and 60 cylinders or a maximum of 60 lbs (27 kg) of
shall not exceed 8 ft (2.43 m) in overall height. propane for each display area, provided that the retail
(c) Display of cylinders shall be in compliance with the outlet is sprinklered and the propane display areas are
clearances, separations, quantities, and other requirements separated from each other by not less than 50 ft (15
listed in Table 6.4. m);
(b) a storage are for retail outlet shall be
(i) limited to a total weight of 300 lbs (135 kg) of
propane; or
(ii) subject to approval of the authority having
jurisdiction when the total weight of propane is in
excess of 300 lbs (135 kg) of propane; and
(c) other storage areas used to store cylinder in excess of 300
lbs (135 kg) shall comply with
(i) Clauses 5.5.1 and 5.5.2 for outdoor storage; and
(ii) Clauses 5.5.1 and 5.5.8 for indoor storage.

6 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

Table 6.4
Storage of non-refillable cylinders in mercantile occupancies
{See Clause 6.5.6.2 (c)}

For sprinklered* For areas without


Areas sprinklers

Separation from sources of ignition 25 ft (7.6 m) 25 ft (7.6 m)

Separation from marked fire exits 25 ft (7.6 m) 25 ft (7.6 m

Separation between display arrays 8 ft (2.5 m) 8 ft (2.5 m)


Cylinders

Separation of display arrays from 8 ft (2.5 m) 8 ft (2.5 m)


Class 1 and 2 flammable liquids,
Level 2 and 3 aerosols, oxidizers,
And highly combustible products made
From or using Styrofoam® for packing

Maximum net weight of cylinders 500 lb (227 kg) † 300 lb (135 kg) ‡
In each display

Maximum combined net weight of 1000 lb (454 kg)§ 300 lb (135 kg) ‡
Cylinders, Level 2 and 3 aerosols,
Oxidizers, and Class 1 (flammable
Liquids) and Class 2 (combustible
Liquids) in 20 x 20 ft ( 6x6 m) area

Total aggregate net weight cylinders 1000 lb (454 kg)† 300 lb (135 kg) ‡
In total display area

7 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

*Sprinklered in accordance with NFPA 13 for at least


Ordinary Hazard Occupancies.
† Quantity shall be reduced to 300 lb (135 kg) when
storage above cylinders prevents direct discharge from
sprinklers located overhead.
‡ Cylinders shall be protected on three sides by metal or
wire bulkheads.
§Quantities in excess of 1000 lb (454 kg) shall be relocated
to other 20 x 20 (6 x 6 m) areas separated by a minimum
distance of 25 ft (7.6 m).

8 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

6.5.6.3 Cylinders located in the backstock (warehouse) area of


a retail outlet (mercantile occupancy) shall be stored as follows: NEW

(a) Cylinders shall be in packaging approved by, and marked


in accordance with, the Transportation of Dangerous
Goods Regulations and securely stacked to a height of not
more that 6.56 ft (2 m).
(b) Storage of cylinders shall be in compliance with the
separation, clearances, quantities, and other requirements
listed in Table 6.5

Table 6.5
Storage of non-refillable cylinders in the backstock (warehouse)
area of mercantile occupancies
(See Clause 6.5.6.3 (b).)

For sprinklered* For areas without


Areas sprinklers

Separation from sources of ignition 25 ft (7.6 m) 25 ft (7.6 m)

Separation from marked fire exits 25 ft (7.6 m) 25 ft (7.6 m)

Separation of display arrays from 8 ft (2.5 m) 8 ft (2.5 m)


Class 1 flammable liquids, oxidizers
Level 2 and 3 aerosols, plastic
Packaging, and Styrofoam®

Maximum net weight of cylinders 1000 lb (227 kg) † 300 lb (135 kg)
in each storage area

Maximum net weight of cylinders 2000 lb (908 kg) ‡ 300 lb (135 kg)
Class 1 (flammable liquids) and
Class 2 (combustible liquids),
Level 2 and 3 aerosols, and oxidizers
in a 20 x 20 ft ( 6x6 m) area

Total aggregate net weight cylinders 4000 lb (1816 kg) 300 lb (135 kg)
in entire backstock area

Clearance between sprinkler heads as required by NFPA 308 for level 3


and arrays of cylinders aerosol products

9 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

* Sprinklered in accordance with NFPA 13 for at least Rationale: TC-39M cylinders used for the packaging of
Ordinary Hazard Occupancies. propane for use with portable and handheld appliances are,
† Quantity shall be reduced to 300 lb (135 kg) when because of their design, construction and safety features,
storage above cylinders prevents direct discharge from inherently safer as a container for flammable and combustible
sprinklers located overhead. products that are TC-2P and TC-2Q containers which are not
‡ Quantities in excess of 2000 lb (908 kg) shall be equipped with pressure relief valves. TC-2P and TC-2Q
relocated to other 20 x 20 (6 x 6 m) areas separated by a containers are commonly used for Level 2 and Level 3
minimum distance of 25 ft (7.6 m). aerosols. Capacities of Level 3 aerosols {greater than 13,000
Btu/lb (30 kJ/g)} can exceed the caloric capacity of the
standard 400 to 455 g TC-39 propane cylinders. The
accompanying information supports these proposed new
requirements for the handling and storage of propane cylinders
in retail premises (occupancies).
6.5 Storage and use of cylinders at locations other than 5.5 Storage and use of cylinders at locations other than
filling plants filling stations
6.5.7.3 A sign indicating “NO SMOKING” shall be permanently 5.5.7.3 A sign indicating “NO SMOKING” shall be permanently Revised only by adding the equivalent French wording for the
displayed in the cylinder storage area. The sign shall be in displayed in the cylinder storage area. The sign shall be in signage.
accordance with the requirements for signs in Clause 7.12.3. accordance with the requirements for signs in Clause 6.12.3.
* The equivalent French wording is “DEFENSE DE FUME”. To ensure owners provide instruction in both English and
French.
6.6 Transportation of cylinders 5.6 Transportation of cylinders

10 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

6.6.7 Every cylinder delivery vehicle shall be marked legibly 5.6.7 Every cylinder delivery vehicle shall be marked legibly Revised only by adding the equivalent French wording for the
and conspicuously on both sides and on the rear, in letters not and conspicuously on both sides and on the rear, in letters not signage.
less than 4 in (100 mm) high and of a colour that contrasts less than 4 in (100 mm) high and of a colour that contrasts
sharply with the background, with at least on of the following: sharply with the background, with at least on of the following: To ensure owners provide instruction in both English and
(a) the words “COMPRESSED LP GSA”*; (a) the words COMPRESSED LP GSA; French.
(b) the word “FLAMMABLE”†; (b) the word FLAMMABLE;
(c) the word “PROPANE”‡; or (c) the word PROPANE; or
(d) the name of the carrier if the name includes the word (d) the name of the carrier if the name includes the word
“PROPANE”‡. PROPANE.

*The equivalent French wording is “GAZ PL COMPRIME”.


†The equivalent French wording is “INFLAMMABLE”.
‡The equivalent French wording is “PROPANE”.

6.7 Installation of cylinders 5.7 Installation of cylinders


6.7.3 Notwithstanding the requirements in Clause 6.5 and 5.7.3 Except as permitted in Clause 5.5 and 5.7.2, a cylinder Editorial only – same intent
6.7.2, a cylinder containing a maximum of 5 lb (2.5 kg) of containing a maximum of 5 lb (2.5 kg) of propane, which is not
propane, which is not connected to any other cylinder, may be connected to any other cylinder, may be connected for use
connected for use indoors with the permission of the authority indoors with the permission of the authority having
having jurisdiction. jurisdiction.

7.4 Excess-flow and back check valves 6.4 Excess Flow and Back Check Valves
7.4.4 Instead of using an excess-flow valve, a tank opening 6.4.4 In place of an excess-flow valve, a tank opening may be Revised only – Same intent.
may be fitted with a quick-closing internal valve that, except fitted with a quick-closing internal valve that, except during
during operating periods, shall remain closed. The internal operating periods, shall remain closed. The internal mechanism
mechanism for the valve shall be provided with secondary for the valve shall be provided with secondary controls
controls consisting of a fusible link or plug with a melting point consisting of a fusible link or plug with a melting point of not
of not more that 210°F (105°C) that shall cause the internal more that 210°F (105°C) that shall cause the internal valve to
valve to close in case of fire. close in case of fire.

7.10 Location of consumer tanks 6.10 Location of Consumer Tanks

11 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

7.10.2 Clause references renumbered Table 7.4 6.10.2 This Clause references Table 6.10.2

Table 7.4 <New foot note> Table 6.10.2


Revision to Table only – Same intent.
Total aggregate water Total aggregate water
capacity, USWG (L) capacity, USWG (L) To clarify that all clearances for tanks over 10 000 USWG (38
000 L) are at the discretion of the authority having jurisdiction.

Over 10 000 (38 000) § § § § Over 10000 At the discretion of the authority having jurisdiction.
(38 000)
* same
† same
† same
§ At the discretion of the authority having jurisdiction.

7.11 Tank supports 6.11 Tank Supports


7.11.5 Notwithstanding the requirements in Clause 7.11.4, 6.11.5 Except as provides in Clause 6.11.4, horizontal tanks Revised only – Same intent.
horizontal tanks with a capacity greater than 200 USWG (7500 with a capacity greater than 200 USWG (7500 L) may be
L) may be mounted on a skid frame, provided that mounted on a skid frame, provided that

(a) the skid frame assembly is designed to accommodate (a) the skid frame assembly is designed to accommodate
anticipated loads; anticipated loads;
(b) the base is designed to accommodate static and dynamic (b) the base is designed to accommodate static and dynamic
loads imposed by the tank and skid frame; and loads imposed by the tank and skid frame; and
(c) steps are taken to allow for differential movement between (c) steps are taken to allow for differential movement between
any fixed piping and the skid frame assembly. any fixed piping and the skid frame assembly.

7.12 Filling plants and refill centres 6.12 Filling Plants and Refill Centres

12 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

7.12.11 Foot note added 6.12.11 Revised only by adding the equivalent French wording for the
signage.

7.12.12 Foot note added 6.12.12 Revised only by adding the equivalent French wording for the
signage.

7.14 Storage of containers at filling plants 6.14 Storage of Containers at Filling Plants
7.14.2 When stored outdoors, a container shall be inside the 6.14.2 A container when stored outdoors shall be inside the Revised item (d).
fenced area of a filling plant and shall fenced area of a filling plant and shall
(a) be stored 25 ft (7.5 m) or more from the property line; (a) be stored 25 ft (7.5 m) or more from the property line; The clearance from the cylinders in storage and the filling plant
(b) be kept clear of means of access to any storage tank, (b) be kept clear of means of access to any storage tank, storage tanks was increase to 25 ft (7.5 m) to provide adequate
container storage area, or building; container storage area, or building; space for fire suppression in the event if a fire at either location.
(c) be stored not less than 4 ft (1 m) from the fence when the (c) be stored not less than 4 ft (1 m) from the fence when the
fence has openings greater than 2 x 2 (50 x 50 mm), but may fence has openings greater than 2 x 2 (50 x 50 mm), but may
be stored alongside a fence when the fence has openings 2 x 2 be stored alongside a fence when the fence has openings 2 x 2
in (50 x 50 mm) or smaller; and in (50 x 50 mm) or smaller; and
(d) not be stored within 25 ft (7.5 m) of the filling plant storage (d) not be stored within 10 ft (3 m) of the filling plant storage
tank. tank.

7.19.4 Protection against vehicular Traffic (see Annex B) 6.19.4 Protection against vehicular Traffic (See Append B)

13 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

7.19.4.3 Posts or guardrails used for the protection of a tank *6.19.4.3 Posts or guardrails used for the protection of a tank
shall be located shall be located To provide a closer service access for vehicles to the point of
(a) not less than 3.5 ft (1 m) from all sides of the tank, (a) not less than 3.5 ft (1 m) from all sides of the tank, transfer and to minimize the length of transfer hose.
ventilated cabinet, or enclosure; and ventilated cabinet, or enclosure; and
Note: Vehicles are not normally considered a source of ignition
(b) to ensure that a minimum of 3.5 ft (1 m) will be maintained (b) to ensure that a minimum of 10 ft (3 m) will be maintained within the dispensing zone providing the engine and any
between the point of transfer or cylinder filling scale and between the point of transfer or cylinder filling scale and source of ignition is turned off before and during the refueling
any source of ignition, including vehicles. any source of ignition, including vehicles.

7.20 Dispensing devices 6.20 Dispensing Devices


7.20.2 A remote dispensing device shall be protected from 6.20.2 A remote dispensing device shall be protected from Revised.
damage with the use of posts damage with the use of posts
(a) as stipulated in Clause7.19.4.1, items (b), (c), and (d); and (a) as stipulated in Clause 6.19.4.1(b) to(d); and To provide a protected working space for a person who is filling
(b) located to provide a minimum of (b) located to provide a minimum of 1 ft (300 mm) of clear a cylinder at an island and to ensure a safe location for purging
(i) 1 ft (300 mm) of clear space between the posts and space between the posts and the dispenser. of a propane container from the dispensing zone.
the dispenser; and
(ii) 3.5 ft (1 m) of clear space between the posts and an
island dispenser that incorporates a cylinder filling
scale.

When purging equipment is provided, a vent pipe shall be


installed to discharge the vapours to an ignition-free location at
least 10 ft (3.5 m) from the dispenser.

Note: Vehicles are not normally considered a source of ignition


within the dispensing zone. Provided that the engine and any
source of ignition is turned off before and during the refueling.
The person who is filling or purging any propane container is
responsible for ensuring that there is no source of ignition
within 10 ft (3.5 m) measured horizontally.

14 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

7.20.6 Added foot notes 6.20.6 Revised only by adding the equivalent French wording for the
signage.
* The equivalent French wording is “DEFENSE DE FUMER
DANS UN RAYON DE 3 M – COUPER LE MOTEUR
PENDANT LE REMPLISSAGE”.

†The equivalent French wording is “DEFENSE DE FUMER–


COUPER LE MOTEUR”.

8.11 Tank truck and cargo liner lettering 7.11 Tank truck and cargo liner lettering

8.11.1 Added foot note Revised only by adding the equivalent French wording for the
signage
*The equivalent French wording is “GAZ PL COMPRIME”.
†The equivalent French wording is “INFLAMMABLE”.
‡The equivalent French wording is “PROPANE”.

9.3 Direct-Fired Vaporizers 8.3 Direct-Fired Vaporizers

9.3.3 A direct-fired vaporizer is considered a source of ignition 8.3.3 A direct-fired vaporizer shall be located at least 10 ft This revision clarifies this type of vaporizer is a source of
and shall be located at a distance in accordance with the (3 m) from any tank or from the fill points of any tank, and at ignition and the minimum clearance requirements are covered
requirements of Table 7.4 from any tank or from the fill points least 25 ft (7.5 m) from a building or property line. under Table 7.4.
of any tank, and at least 25 ft (7.5 m) from a building or
property line.

11.5 Installation of tanks 10.5 Installation of Tanks

15 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

11.5.9 A label made of durable material that is not adversely 10.5.9 A label made of durable material that is not adversely Revised only by adding the equivalent French wording for the
affected by water, employing an adhesive that is not water affected by water, employing an adhesive that is not water marking on the filling location label.
soluble, shall be affixed adjacent to the filling location. The soluble, shall be affixed adjacent to the filling location. The
label shall be worded as follows: “EQUIPPED WITH A STOP- label shall be worded as follows: To ensure manufacturers provide instruction in both English
FILL VALVE. USE OF FIXED LIQUID LEVEL GAUGE IS NOT and French.
REQUIRED”*.
* The equivalent French wording is “POURU D’UN EQUIPPED WITH A STOP-FILL VALVE. USE OF FIXED
ROBINET D’ARRET DE REMPLISSAGE; L’UTILISATION LIQUID LEVEL GAUGE IS NOT REQUIRED.
D’UNE JAUGE A TUBE FIXE N’EST PAS REQUISE”.

11.5.13 A tank 10.5.13 A tank


Editorial change in item (b)
(a) on a vehicle shall be so located as to minimize the (a) on a vehicle shall be so located as to minimize the
possibility of damage; possibility of damage; The reference Clause 10.5.3(a) was wrong the correct
(b) that is located at the rear of a truck and that is protected by reference is item (a) within the Clause.
(b) that is located at the rear of a truck and that is protected by a substantial bumper shall be deemed to conform with
a substantial bumper shall be deemed to conform with Item Clause 10.5.3(a); and
(a); and (c) that is mounted within 8 in (200 mm) of the engine or the
exhaust system shall be shielded against heat radiation by
(c) that is mounted within 8 in (200 mm) of the engine or the the use of a metal shield located not less than 1 in (25 mm)
exhaust system shall be shielded against heat radiation by from the tank. The metal heat shield shall not be attached
the use of a metal shield located not less than 1 in (25 mm) to the exhaust system.
from the tank. The metal heat shield shall not be attached
to the exhaust system.

Annex A (informative)

A.4.4 Vacuum purging New

16 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

The container shall be designed for the vacuum to which it will


be subjected.
To remove air and moisture from a container being prepared
for propane service using vacuum
purging, complete the following steps:
(a) Connect the suction side of an LP-gas compressor to the
container being purged. Open the
container valve and turn the compressor on.
(b) Ensure that any container opening is capped.
(c) Ensure that the outlet of the compressor is venting the air to
atmosphere.
(d) Using an appropriate manometer, stop the process when
the negative pressure reaches the value
stated in Table A.2, according to the altitude above sea level of
the location where the purging is
taking place.
(e) Shut the container valve off.
(f) Connect the vapour line from the storage tank to the
container. Open the valve and allow the flow
of propane until a pressure of approximately 15 psig (105 kPa)
is reached.
(g) Add methanol as required and shut off the valve. The
container is ready to be filled with propane.

17 of 18
Any quotations in this document are taken directly from the CSA – B149.2-2005
PROPANE STORAGE and HANDLING CODE

Clause in New Code Clause in previous code Recommendations, Interpretations and Rationale
Source: Canadian Standards Association (2005), CSA Source: Canadian Standards Association (2000), CSA
B149.2-05, Mississauga: CSA B149.2-00, Mississauga: CSA

Table A.2
Negative pressure required for vacuum purging
(See Clause A.4.4.)

Altitude above sea level, ft Gauge reading, in Hg


0 25.85
500 25.31
1000 24.78
1500 24.26
2000 23.75
2500 23.24
3000 22.74
3500 22.25
4000 21.77
4500 21.29
5000 20.82
5500 20.35
6000 19.90

18 of 18