Client Name: ZLD technologies Pvt ltd Scheme: Reference Document No.: 29P-P_ID / Rev. No.00 Prepared Dated: 26.03.2024 Sr. Parameters Description No. General / Process 1 Tag No. as per annexure 2 Service as per annexure 3 Process Fluid Water Vapor @ max. 150°C 4 Quantity 4 Nos. 5 Model Vendor to provide 6 Make STD Functional 7 Type For Vapour application 8 Instrument Measurement Range as per annexure 9 Protection class IP65 10 Standard IEC 61298, IEC 60529, IEC 60068-2-6/7, 11 Max. Operating temperature 150.0 °C 12 Design Temperature Vendor to provide 13 Operating pressure as require 14 Accuracy ± 0.5% of Calibrated Span Transmitter Specification 15 Accuracy / Repeatability ± 0.05% of Calibrated Span 16 Stability ± 0.1% of URL for 2 years. 17 Response Time 100 m/ sec. 18 Type 2 Wire 19 Power Supply 24V DC (Loop Powered) 20 Output 4-20mA 21 Local Indicator Not applicable 22 Electrical Connection Plug type connector 23 Process Connection ½” NPTM Material of Construction 24 Case MOC SS304 25 Sensing Element Diaphragm 26 Diaphragm SS304 27 Socket Material SS304 28 Bezel Ring SS304 Accessories 29 Tag Plate MOC - SS Required Annexure Sr. Tag Service Range Quantity. No. 1 PT-101 at Calandria Cl-1 -1 to 1.5 Bar 1 2 VLS-101 at Vapour Separator VLS-1 -1 to 1.5 Bar 1 3 PT-102 at Calandria Cl-2 -1 to 1.5 Bar 1 4 FV-102 At Flash vessel FV-2 -1 to 1.5 Bar 1