CERTIFICATE NO.

: 23/01/0

CUSTOMER : M/s. SAS Corporation


VERIFICATION DATE : 06/01/2023.
RECOMMENDED RE–VERIFICATION DATE: 05/01/2024.

CUSTOMER’S EQUIPMENT DATA


TOP LOADING ARM (HYDROTEST)
U.I. NO : TLA-001 TIME DURATION: 3 Hours
TYPE : C32RF TEST FLUID/SIZE: Water / 4”
MAKE : OPW TEST PRESSURE: 100 Psi

VERIFICATION EQUIPMENT
DIGITAL TEST GAUGE: MAKE: Ashcroft. SERIAL No.: 781636. RANGE: -1 ~ 30 Bar
TRACEABILITY: INSCAL - UAE. CAL DATE: 02-NOV-2023. CAL DUE DATE: 01-NOV-2024.

VERIFICATION PROCEDURE: W-09-40.


VERIFICATION CONDITIONS:
TEMPERATURE : 28 + 1 0C
RELATIVE HUMIDITY : 46 + 10% RH.

VERIFICATION RESULT STATUS [PASS]


MEASURING MODE UNIT UNDER MASTER GAUGE STATUS
START TIME: 10:30 TEST APPLIED READING IN Bar
END TIME: 13:30 PRESSURE
Pressure Simulation by Hydraulic Pump. 100 Psi
10:30 100 Psi
11:00 100 Psi
11:30 100 Psi
12:00 100 Psi
12:30 100 Psi
13:00 100 Psi
13:30 100 Psi No Leakage Found
NOTE: There was no leak or pressure drop detected during this test from their tubes, joints, seals, swivels and
loading valve. They are working satisfactory.

The normal working pressure range of the loading arm is up to 60 Psi and assembly passed for operation.

The verification result indicated refers to the measured values only, with no account being taken of the instrument’s
ability to maintain its verification

VERIFIED BY: SIGNATURE: ------------------------. CHECKED BY SIGNATURE: ----------------


F-07-03 Issue No. “2” Rev.”1” Dated: 10/11/2017.