June 16, 2016

Almelo, The Netherlands

Presentation
CONTINUOUS POWER IN YOUR CONTROL

 Our company
 The power of our products
 Global service partner to rely on
Unequalled Installed Base

AMERICAS EMEA APAC


287 Units 1064 Units 550 Units
540 MVA 1319 MVA 842 MVA

 1901 Units delivering 2,700.985 kVA of Continuous Power


Unrivalled Global Presence

EMEA

APAC
AMERICAS
Complete Global Coverage

14 Hitec Sales and Support Centres and global Hitec partners


Complete Customer Support

 Strategically located regional service and support centres


 Regional 24 x 7 x 365 helpdesks
 Full trained and certified engineers
 Strategic spares and stock management
 Local preventive & corrective maintenance
 Operational reports
 Service level agreements
 Customer training & documentation
 Service consultancy
Powerful Service Platform

 Intuitive user interface


 Status ‘at a glance’
 Advanced remote connectivity
 Extensive monitoring
 Condition-based maintenance
 Automated ‘health’ notification
 Detailed operational reports
 Authorisation levels
x

 In response to market demand HITEC has


developed the PowerPRO series of Dynamic
UPS Systems
The First and the Best in Rotary UPS

First battery rotary First DRUPS Induction coupling free 2250 kVA Dual Celebrating 50 years Launch
UPS (300 kVA) rotating inner rotor Output UPS of DRUPS

1956 1969 1991 2001 2006 2015

1963 1974 1998 2006 2013 2014


500 kVA DRUPS 2500 kVA UPS and Ride
Through system
First 3000 kVA First 3600 kVA Re-branding of HITEC
DRUPS MV DRUPS

“HITEC has been driving technology innovation and providing robust and reliable Dynamic UPS systems throughout the world for 60 years”
The New Standard for Continuous Power

 Economic
 Innovative
 Powerful
 Efficient
 Reliable
 Compact
 Intuitive
 Connected
 Sustainable
 Straightforward
The New Standard for Continuous Power

 50 Hz:
1600 kVA - 2200 kVA

 60 Hz:
1800 kVA - 2700 kVA
Power performance

 Available ratings:
 Emergency standby power (ESP)
 Prime-rated power (PRP)
 Continuous output power (COP)
 Data centre continuous (DCC)

 Available optimisations:
 Fuel Optimized
 TA-Luft
 EPA Tier 1
 EPA Tier 2 (NEA)
Lowest Operating Cost

 Highest Operating Efficiency


Optimised design delivers up to 97.5%
total system efficiency while delivering full power conditioning to the load
 Maximum Uptime
Auto-lubrication, smart monitoring, and a highly accessible design results in
extended service intervals and reduced service time
 Low Service Requirement
Fewer operational interruptions. Only one shut-down per annum and an
overhaul every 10 years
Most Efficient continuous power solution available

 Reduces operational costs


 Minimizing environmental impact
 Reduced Carbon Footprint
 A+++ System Efficiency
 Up to 97,5%
Unrivalled Space Savings

 Smallest Footprint
Compact design offers >40% space saving over
Static UPS and between 5% to 10% over other DRUPS manufacturers
 Battery-free
Releases internal ‘white space’ within the facility for business expansion
and revenue generation
 Compact Design
Reducing the building cost and the Gross Floor Area (GFA) lowers rental
and increases opportunities for revenue generation
Smallest Footprint

Footprint 16,9 m²
 2000 kVA

Footprint 14,2 m²
 2000 kVA

 2000 kVA Others Footprint 14,6 m²


Space Saving v’s DRUPS

 X 2000 kVA
Footprint: 16.9 m²
Mass: 25,000 kg

2000 kVA
Footprint: 14.2 m² 5% - 10%
+ Mass: 26,000 kg Space Saving
17%
2000 kVA
Nearest DRUPS Footprint: 14.6 m²
Competitor Mass: 27,000 kg
+ 4%
Space Saving v’s Static UPS
+ 2000 kVA
17%
 X Footprint: 14.2 m²
Mass: 26,000 kg

> 40% Space Saving

+ 2000 kVA
17% Footprint: 24 m²
Mass: 35,000 kg

+ 4%
Increased Power Security

 Highest Reliability
Improved design based upon unrivalled experience
and recognition of the latest customer requirements
 Supports all load types
Continuous support for the cooling equipment simplifies the mechanical
system and increases the reliability of the facility
 Advanced Communication
Intuitive communication, advanced monitoring and real-time reporting
Proven Technology
Free Wheel Clutch
Synchronous generator

Diesel Engine
Kinetic Energy Module

Base frame with anti vibration dampers


Operational Innovation
High efficiency cooling Noise attenuating covers
Low emission engine

Health indicator

Integrated air filtration

Status indication

Plug and play control cabling


Maximum Uptime

Automatic bearing lubrication


Accessible measuring points
Service access

Sliding covers

Ducted cooling
“One Control Panel” Unit Control + Control Box

Unit Speed-Up
Intuitive Operation and Control

 Improved Control Panel


 Full color 5.7” HMI
 Latest PLC design
 New HITEC Digital Controller
 Plug and play
 Prefabricated cabling
Unit ON/OFF
Control Panel NB Auto/Bypass
Touch screen HMI
SB Utility/Auto

 Straightforward design
 Easy to understand Alarm
 Multi language
Attention
 Reliable
Running
 Safe Engine Isolation Switch
Key Switch: local/remote control
Emergency Stop
Control Panel 2000
mm

Dimensions and weight


 Width: 2200 mm
 Depth: 625 mm
 Height: 2000 mm
 Footprint: 1,32 m²
 Weight: 750 kg
Ethernet Programmable Automation Controller (ePAC)

 Use of High-tech ePAC with Ethernet built right into its core
 Based on latest technology and standards
 High precision
 Cyber secure built-in
 High speed backplane bus
 Time stamping less than 50 millisecond
New Digital Controller 2 (DiCon 2)

 Based on latest technology and standards


 Ethernet-TCP/IP connected
 Increased logging time
 Time stamping less than 10 millisecond New service monitoring tool (Dicon Scoop Program)

 Latest high precision net-analyser on board


(measures utility harmonic’s, THD, unbalance)
 Improved start battery monitoring (voltage &
current values available)
 1 Utility mode
System Operation  2 KEM flywheel mode + engine start
 3 Engine / KEM flywheel mode
 4 Cool down/shut mode
 1 Utility Mode

3900/4200
KEM inner rotor

∆ Speed : 2400 RPM

1500/1800
KEM outer rotor/
Utility failure: generator shaft
 Q1 open
 Start engine
 Take energy from inner rotor
Lower Energy or Fuel consumption

Flexible Energy Storage Optimisation (ESO) mode


 Depending on load levels the ESO speed is calculated
(PLC) and set into the Variable Speed Drive (VSD)
 Ongoing check via speed measurement on the inner rotor

Diesel Start Delay (DSD) functionality


 Upto 2 seconds Diesel Start Delay possible.
 Directly influences ESO levels and KVA rating of the unit.
PowerPRO Technological Progression
AC/DC Exciter
DRUPS

Generator Inner Rotor Engine

Outer Rotor Freewheel Clutch

(QPS) Pony DC
Motor Exciter

Flywheel
Inner Rotor Generator Engine
Technological Innovation
KEM design allows for continuous KEM design reduces the module Dual-shaft Generator design allows for
lubrication of the outer and inner bearings operating temperature continuous lubrication of the bearings

Outer Rotor

Pony Motor Clutch

Inner Rotor Generator Engine

Diesel Start Delay


DC Exciter (DSD mode) gives up to
Energy Storage Optimisation 2 seconds delay and
Large diameter inner rotor Dual-shaft Generator is
(ESO mode) reduces losses and gives reduces fuel usage
reduces module length and equipped with high efficiency
load-dependent energy storage decreases rotational speed cooling to reduce losses
Kinetic Energy Module “World Class design”

 Brushless design
 Reduced weight
 Compact design
 Efficiency optimized
 Increased uptime
 Low Maintenance
Kinetic Energy Module “construction”
Housing Outer rotor Inner rotor

Exciter machine: Make the


regulated DC to transfer
the kinetic energy to the
Pony motor AC machine: generator shaft. 99% of
to speed up the inner rotor time: OFF (means cold)
and herewith ongoing
storing kinetic energy Generator shaft
connection

Grease catch tray:


suitable for 10 years grease
Kinetic Energy Module “speed and capability”

50 Hz 60 Hz
Speed inner rotor 3.900 rpm 4.200 rpm

Speed outer rotor 1.500 rpm 1.800 rpm

∆ Speed 2.400 rpm 2.400 rpm

Power capability 2.200 kVA 2.700 kVA


Kinetic Energy Module “Automatic bearing lubrication”

 Lubrication of KEM and generator bearings


 Daily lubrication of all 6 bearings
 2 grease reservoirs of each 2 Liters
 Refill grease reservoir 1x per year
 Grease level and flow detection
 Control & feedback to monitoring system

“Standard on PowerPRO2700 range”


Kinetic Energy Module “Automatic bearing lubrication”

 Continuous and controlled lubrication while running (No STOP)


 Refill of grease reservoirs 1x per year while running (No STOP)
 Recommended overhaul time once every 10 years
 Calculated bearing lifetime of 10 years

“Low service requirements = Low TCO”


Kinetic Energy Module “figures”

Dimensions and weight:


 Length: 1.797 mm
 Width: 1.436 mm 1340 mm

 Hight: 1.340 mm
 Footprint: 2,58 m²
 Total: 5.800 kg

Characteristics
 Insulation Class: F
 RAL Color: 7024 (anthracite) 1436 mm
Advanced Data Collection
Secured Data Storage on site

Data collection

Data processing

Site owner Site operator


Advanced Communication Option
Secured data storage

Data collection
Customer X
Data processing

Customer Y

Customer Z Secured login


( Outstanding Service / Customer specific)
Features

Kinetic energy Freewheel


Air inlet Generator Diesel engine Base frame
module clutch

Vibration monitoring NA Standard Standard NA NA Standard

Condition monitoring NA Standard Standard NA NA NA

Temperature monitoring Standard Standard Standard Standard Standard NA


Automatic bearing lubrication NA Standard Standard Standard Standard NA

Oil suppletion facility NA NA NA NA Optional NA


Powerful Service Platform

 Remote monitoring and control


 Real time information and data
 Powerful alarm management for faster response
 Continuous diagnostics monitoring for improved predictive maintenance
 Easy to operate and less training required
“Machinery health monitoring is essential to evaluate
machine conditions and perform predictive maintenance”
Why High Performance HMI

 Better graphics for operations effectiveness (Less=More)


 Provides information instead of displayed numbers
 Limited use of colours, only in case of alarm (action).
 Properly formatted trends or important parameters
 Values related to normal, abnormal or alarm conditions
 Logical and consistent navigational methods
 Validation and security measures

“As an operator I can take action before alarms occur!”


Title A

 x

Clear system overview


including unit and
circuit breaker status
Title A

 x

Fast and detailed


trouble shooting
Detailed information
available in 3 simple clicks
Easy selection of
multiple criteria (Pens)

Accurate Data
in time path
available.
Overview of events, priority,
timeline and status
Measurable Impact

 Information instead of data


 Active support instead of re-active
 Operator and Hitec helpdesk have same information
 Automated reports for your convenience
 Reduction of field service interventions
 Reduction of unplanned maintenance
 Detailed maintenance advise
The Solution Providers
We are 24/7 Field Service,
24/7 Helpdesk support , and maintenance
available for global inspections, training
advise can be provided due to our
field service, efficient and service
advanced remote monitoring platform.
maintenance and consultancy.
quick repairs.
Your uptime is our
Mission.
 Our global parts network is available to meet your needs.
 Repair and restore with original quality parts.
 Overhaul shops in The Netherlands, Taiwan and United States.
 Fast and accurate delivery of original parts and lubricants
 Single resource for all your aftermarket needs

“Providing the parts you need – When and Where you need them”
Dedicated to Safety and Quality

 Certified ISO 9001:2008 guidelines


 Certified VCA** 2008/5.1
 Comply to EMC directive 2004/108EC
 In accordance with EN6204-2
 Continuous quality improvement
• Plan, Do, Check, Act
Customer Requirements Benefits
Maximum reliability The evolution of Hitec’s dynamic energy storage technology

Automatic lubrication and monitoring systems that reduce


Lower servicing requirements and increased uptime
downtime to one interval per year
Optimised component design that delivers
Lower energy consumption and reduced operational costs
market leading efficiency
Reduce plant room space and
Highest available power density per square metre
increase revenue generating opportunities

A user friendly and improved working environment Integrated noise reduction and air filtration

Embedded smart functionality,


Remote support and condition based management
enhanced user connectivity and reporting

Quality assured, reliable and simplified installation Plug and play control cabling and connections

Minimize environmental impact Lower carbon footprint and no toxic batteries


Thank you