You are on page 1of 6

Overvoltage Considerations in Applying

Distributed Resources on Power Systems


Phil Barker, IEEE Senior Member

DR itself.
Abstract— Distributed Resources (DR) can be a source of
overvoltage problems for the electric power system if care is II. GROUND FAULT OVERVOLTAGES
not exercised in the design and interface of the DR
equipment. Conversely, DR may be adversely impacted by Proper grounding and use of the correct interface
overvoltage conditions that originate on distribution feeders transformer for DR is important to avoid causing
during faults, switching events, or as a result of lightning. Use overvoltages on the power system during ground faults.
of the appropriate DR grounding, interface transformer This is important when interfacing DR to four-wire
winding, proper switching methods, anti-island protection multigrounded-neutral distribution circuits. This type of
settings, lightning surge protection, and equipment voltage
circuit grounding design represents the vast majority of
withstand ratings can help reduce the chance that either the
DR or the utility system will be adversely impacted by distribution circuits in the United States.
overvoltages. This paper reviews the overvoltage issues
associated with the application of DR on power systems and To understand how DR can generate an overvoltage during
recommends approaches for prevention of problems. a ground fault, consider Figure 1. In this example, we have
a four-wire multigrounded-neutral distribution circuit that
Index Terms—Distributed Generation, Distributed
has one conductor (phase-C) faulted to the neutral. Once
Generation Interconnection, Overvoltage Protection,
Generator Grounding, Transformer Configuration this occurs, a high fault current is generated until the
substation circuit breaker opens (typically after about five
cycles). Once the substation source is cleared, if the DR is
I. INTRODUCTION still feeding into the system, then the potential of the

T oday there is much interest in distributed resources neutral (earth) essentially becomes that of phase C of the
(DR) due to advancements in these technologies and DR. Any loads or equipment connected between an
the belief by many that DR is a viable alternative to unfaulted phase (A or B) and neutral will suddenly be
conventional transmission and distribution system subjected to voltages that are equivalent to the line-to-line
enhancements. However, it is important to recognize that voltage – that is about 1.73 times time higher than the
there are many power system interface issues that must be prefault condition! The distribution transformers serving
dealt with in the design, operation and protection of DR. A customers on these phases are connected line-to-neutral and
key area of concern is the potential for DR to create thus would subject customer equipment to such
overvoltages that are damaging to the power system and overvoltages.
A Transformer
customer loads. This paper focuses on the overvoltage B experiences
C overvoltage
issues of DR and provides some solutions to those issues. Neutral
A
Substation
Breaker
The main overvoltage related issues associated with DR Opens
include: C

Gen.
Avoiding severe ground fault overvoltages on four-
wire multigrounded neutral circuits
Phase C is Faulted -
Identifying the potential for and avoiding resonant Raising neutral to
potential of Phase C
overvoltages during islanding conditions
Preventing voltage regulation related overvoltages
due to high DR power injection Figure 1 – Overvoltage due to an ungrounded DR
Designing and specifying DR installations to be feeding into a power system
resistant to common surge and power frequency For a more detailed explanation of the ground fault
overvoltage conditions imposed by the operating overvoltage, consider the vector diagram of Figure 2. At the
environment. time of pre-fault conditions, the phase-to-neutral (earth)
voltage is in the normal range with all three voltages
The first three of these issues deal with preventing the DR balanced 120 degrees apart. Once the fault occurs, and after
from damaging the power system or customer load the substation breaker opens, the neutral (earth) essentially
connected to it. The last issue is for the protection of the

0-7803-7519-X/02/$17.00 © 2002 IEEE


109

Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on May 18,2023 at 11:01:11 UTC from IEEE Xplore. Restrictions apply.
rises to the same potential as phase C and line to neutral by utilities (and recommended by most interconnection
voltage on phases A and B become 1.73 times the pre-fault experts) as the proper way to interface a distributed
level. Since the nominal prefault voltage may be as high as generator to a four-wire multigrounded distribution circuit.
105% due to the ANSI voltage regulation allowance, the Effective grounding means that the generator is grounded
voltage could go as high as 182% of nominal during the sufficiently well that the voltage rise on the unfaulted
faulted condition. Utility equipment such as lightning phases during a ground fault is no greater than about 125%
arresters and loads can be damaged in just a few cycles by above the nominal voltage rating of the system. This is the
voltage this high and so this poses a serious risk to utility same standard that the utility system is designed for. ANSI
equipment and loads. C62.92 (see reference 1), defines an effectively grounded
system as one where the following criteria are achieved:
Va
Xo/X1 ≤ 3 and Ro/X1 ≤ 1

Where the DR equivalent source impedances feeding


into the power system are:
Earth
Vc Vb Xo = the zero sequence impedance of the
DR
Pre-fault Conditions
Va X1= positive sequence impedance
Ro= Zero sequence resistance

The DR machine characteristics, the grounding impedance


used (if any), and the type of interface transformer
Vb employed for the interconnection are the factors that
Vc
Earth determine these impedance ratios. Basically, if the above
During fault Conditions ratios are satisfied then this is equivalent to saying that the
zero sequence path (neutral and grounding return path) for
Figure 2 – Vector diagram showing neutral offset during
the generator has sufficiently low impedance relative to the
line-to-ground fault.
positive sequence that not much neutral shift will occur
The extreme voltage rise shown in Figure 2 (during the during a fault to ground.
fault) doesn’t actually occur until the substation breaker
opens and an island forms. Until that time the line-to- Certain types of transformers don’t provide any zero
ground voltage on the power system will be held “in check” sequence path (Xo and Ro are essentially infinity). For
to a certain extent by the “grounding bank” effect of the example, an interface transformer using a delta winding on
substation transformer. It is not until the feeder circuit the high-side would appear as an ungrounded DR source
breaker opens that the DR begins to impose the serious
with respect to the utility system – even if the DR is
overvoltage on the feeder. However, a partial overvoltage
grounded on the low voltage side. To be effectively
could occur prior to opening of the breaker depending on
how strong the DR source is relative to the utility system at grounded, only a grounded-wye winding on the high side
the point of connection. will generally work. Figure 3 shows four common
transformer interfaces.
Low Voltage
Low Voltage Side
Side
In practice, transformer saturation can reduce the severity High Voltage
High Voltage Side
Side
Distribution System
(Utility Distribution System Primary)
Primary) (to DG
(to DG facility)
facility)

of the ground fault overvoltage slightly and loading on the Neutral wye
delta
delta DG
Configuration 1
generator (if the generator is small relatively to the island)
can significantly limit the severity of the overvoltage too.
However, despite these limiting effects, the overvoltage can wye wye
Configuration 2
Neutral
Neutral wye wye
DG
DG
be high enough to cause damage – especially for a larger
generator. Interconnection designs should implement Neutral
Neutral

means to prevent or at least limit the overvoltage. There are


several approaches to limit the impact of ground fault
Configuration 3 delta
delta wye
wye DG
overvoltages:
Neutral
Neutral

1. Use “effective grounding” of the generator


Configuration 4
interface. delta
delta delta
delta DG
2. Locally detect the ground fault as quickly as
possible to trip the DG unit prior to islanding
Figure 3 – Four common transformer interfaces for DR.
3. Use a transfer trip to trip prior to islanding
Only the first two can provide effective grounding
Configuration 1 – Grounded-wye to delta
A. Effective Grounding Approaches
This type of arrangement provides the best way to
The first approach, effective grounding, is usually required effectively ground a generator. It also provides good

110

Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on May 18,2023 at 11:01:11 UTC from IEEE Xplore. Restrictions apply.
isolation of the generator from ground faults on the utility primary a large zero sequence voltage-component suddenly
side and isolation of triplen harmonics to/from the appears across the broke delta terminals of the PT bank –
generator. The generator does not need to have a grounded causing the relay to trip.
neutral for this type of arrangement to serve as an
effectively grounded source. A
B
Phase C is Faulted -
C
Substation Raising neutral to
A key drawback of this approach is that it is actually too Neutral potential of Phase C
Breaker
good of a grounding arrangement in that it has a very low
Opens After Zero Sequence
zero sequence impedance that can interfere with the normal 5 cycles Components in phase

flow of fault current on the distribution system. This can


upset protection coordination by causing desensitization of
ground relays, nuisance fuse operations and false operations Gen.
of upstream protective devices (like reclosers and
sectionalizers). There can also be unwanted circulating
59G
current in the delta winding due to the steady state zero Trip Signal Grounded Wye /
sequence component of the utility system voltage. Use of a Broken delta PT Bank
grounding-impedance in the neutral grounding connection
of the transformer, when appropriate, can reduce these Figure 4 – Ground fault overvoltage detection scheme
problems to acceptable levels in many cases. The using 59G relay and grounded-wye/broken delta PT
impedance must be selected to still not exceed the effective bank.
grounding ratios of C62.92. The major problem with this approach is that if it is used in
lieu of effective grounding, then the overvoltage still occurs
Configuration 2 – Grounded-wye to grounded-wye and the DR may not be tripped before damage occurs to
This type of connection creates an effectively grounded utility equipment and customer loads. This approach works
generator with respect to the utility system only if the best if the 59G relay and breaker clearing time are fast
generator itself has a grounded neutral and can meet the
enough to trip the generator off-line before the upstream
grounding ratios (Xo/X1 ≤ 3 and Ro/X1 ≤ 1). If the generator
utility protection opens. This cannot always be achieved
does not meet these ratios or is not grounded at all, then
due to the need to time delay the relay to avoid nuisance
this type of transformer will not provide effective grounding
trips. Since loads may be damaged in just a few cycles of
(even if the neutral connections to the transformer on both
sides are grounded). extreme overvoltage, this can be risky.

A key drawback of this arrangement is that some generators C. Use of Transfer trip
(certain inverters and rotating machines) don’t work well
A transfer tripping signal from the upstream feeder circuit
or are not designed for a grounded neutral connection.
breaker at the substation to the DR can help prevent
Triplen harmonics will also be directly passed to/from the
utility system and generator. Some rotating machine overvoltages much in the same way the 59G relay can.
designs need an impedance in the neutral connection to However, it can be employed with greater speed and
limit the fault levels to magnitudes that won’t damage the without fear of nuisance trips and should be more reliable
winding. than the 59G relay method. The drawback is that the
generator still can create an overvoltage until it is tripped
Configurations 3 and 4 – Delta on the high side and there may be scenarios where the feeder breaker does
Either of these two configurations don’t provide effective not trip (send a transfer trip signal) but yet there is a fault
grounding for the utility system regardless of how the on the line and an open feeder between the DR and
generator is grounded. They do have some advantages from substation.
the perspective of having less interference to utility ground
fault protection, isolation of harmonics, etc. These types of III. RESONANT OVERVOLTAGES DURING ISLANDING
transformers are ideal feeding into an ungrounded
distribution system (3 wire delta), but are not recommended
Another form of overvoltages that can occur are resonant
for a four-wire multigrounded neutral type of system. If
overvoltages. If islanding of the DR occurs, it is possible for
they are used on four wire multigrounded neutral systems,
a series resonant condition to develop between the
then some form of ground fault overvoltage
generator and power factor correction capacitor banks
detection/tripping is usually employed (see next section)
connected on the feeder (see Figure 5). This resonance can
occur during faulted or unfaulted conditions with any type
B. Ground Fault Overvoltage Detection and Tripping of transformer interface. The simplest form of series
Another way to limit the overvoltage during line to ground resonance occurs between the generator subtransient
faults is to limit its duration. This can be done by detecting reactance and the system capacitors [2]. The severity of the
the overvoltage and shutting down the generator as quickly overvoltage that occurs will depend on the Q of the
as possible. The scheme consists a grounded-wye to delta resonant circuit this is formed and the characteristics of the
PT bank that feeds an overvoltage relay (59G) (see Figure generator. Loads on the island act as damping resistors,
4). In this arrangement when a ground-fault occurs on the lowering the Q of the resonance, and so the worst scenarios

111

Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on May 18,2023 at 11:01:11 UTC from IEEE Xplore. Restrictions apply.
occur under light load conditions on the island. This type
of resonance is also referred to as self-excitation and is the 1. The generator must be operating in an islanded
phenomenon that occurs with induction motors with state
capacitors and, of course, induction generators. 2. The generator must supply more power than there
is load on the island
Open
Resonance creates
high voltage on line 3. Sufficient capacitance must be available on the
island to resonate (typically 30-400% of the
Impedance generator rating)
Capacitor 4. A transformer must be present on the island to
Bank Voltage
Source serve as the non-linear reactance.

The best way to prevent ferroresonance conditions with DR


Figure 5 – Series resonance condition between DR and is to insure that the generator has reliable, fast acting anti-
feeder capacitor bank islanding protection and cannot be isolated with large
capacitor banks. Good anti-sland protection is also helpful
Another form of resonance is ferroresonance. This is an in reducing other potential system impacts too – such as
interaction between the non-linear magnetizing reactance ground fault overvoltages. Anti-island protection is
of transformers and other magnetic devices and system accomplished by use of tight voltage and frequency
capacitance. When DR serves as the driving source for operating windows where voltage and frequency relays are
ferroresonance, overvoltages can occur that can reach as employed to quickly detect when the voltage and/or
high as three per unit [3][4]. Both induction and frequency at the terminals of the machine are outside of
synchronous generators can excite this resonance and it can “normal” limits. Typical windows are fairly tight such as
occur with all three phases connected (single phasing is not +/-10% for voltage and within +/-1% or tighter for
a requirements as with conventional ferroresonance) during frequency. IEEE 929-2000 is a currently active standard
islanding. The worst forms of this condition tend to occur for PV inverters that prescribes the settings for PV inverters
on ungrounded DR interfaces (e.g. delta or ungrounded- [6]. UL1741 is another standard that specifies the settings
wye) but the phenomenon can occur to some degree with (they are the same as 929 settings) for all types of inverter
any type of interface transformer. There are many or converter packages [7] and IEEE P1547, once it becomes
opportunities for interactions between DR and feeder an active standard, will prescribe settings for all types of
devices that can lead to such ferroresonances (see Figure 6). DR devices including both rotating machines and inverter
type devices) [8].
R Open recloser

IV. VOLTAGE REGULATION RELATED OVERVOLTAGES

Regulation related overvoltages are not as severe as those


due to ground-fault related neutral shift or system
resonance. However, they can still pose a threat to loads.
Under the right conditions, it is possible for the voltage to
G
be pushed above the normal limits when DR feeds a large
DG capacitors amount power into the system (see Figure 7). The normal
maximum limit is 106% per ANSI C84.1-1989 Range B
(see reference 9). One might think that the voltage-window
utility
capacitors
protection used on most DR would protect against this.
However, such window protection is intended for anti-
island protection and the settings currently used (such as
those in IEEE 929-2000) do not protect against voltage
Figure 6 – There are many possible interactions between regulation problems that are just slightly outside the normal
capacitors, DR and transformer devices that may lead to ANSI operating windows. These settings allow sustained
either series resonance or ferroresonance conditions overvoltages up to 110% of nominal to exist. Perhaps an
improvement in future versions of these standards would be
DR ferroresonance can cause surge arrester failures in cases to use settings that coordinate better with the ANSI Range
where tightly rated arresters have been applied [5]. A B upper voltage limit.
tightly rated arrester is one where the primary arrester
rating is applied such that its MCOV (maximum
continuous operating voltage) has little margin above the
nominal system rating. For example, an arrester with an
8.4-kV MCOV applied on a 13.8-kV feeder with a line-to-
ground voltage of 7.97-kV.

There are four conditions necessary for ferroresonance with


DR to occur. These are:

112

Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on May 18,2023 at 11:01:11 UTC from IEEE Xplore. Restrictions apply.
SUBSTATION
FEEDER End of Feeder could be hit by direct lightning strikes. Even nearby
Injected Power lightning strikes can induce surges of many thousands of
G volts into the wiring systems.
After DG
ANSI Range A
Upper Limit
Inverters are exposed to these surges coming from many
Voltage directions; the DC input port, AC interconnection port and
via the communication and control ports (see Figure 8).
ANSI Range A All ports must be protected with surge arresters connected
Before DG to a common ground reference. Even a nearby lightning
Lower Limit
strike to earth can cause enough difference in ground
Substation End of Feeder potential between different ground reference points to fail
Distance sensitive solid-state components if proper ground reference
equalization is not provided.
Figure 7 – Regulation related overvoltage

In applying DR, voltage regulation problems can be easily


screened by looking at the pre-DR voltage levels at the
connection point, the line impedances and regulator Utility System

settings employed, and the expected output current of the


Primary
Service Panel

DR. The voltage change on the line (not including voltage PV Array
AC Power Port
regulator and switched capacitor bank interactions) can be
predicted from the following equation:
Neutral/GRND Inverter
DC Power Port

Voltage Rise = IDR (R cos[θ] + X sin[θ]) PWR Ground


reference
Connection

Communication 50 m Remote Array


Where: Port Ground

IDR is the injected current from the distributed resource Data/Control Line

R and X are the line resistance and reactance looking back to the nearest
upstream regulator, and
θ is the angle of the injected current relative to the utility system reference Figure 8 - Inverters may be exposed to surges from
voltage.
many different ports. All ports must be protectedwith
lightning arresters referenced to a single ground point.
V. OVERVOLTAGE ENVIRONMENT FOR DR The type of lightning arrester used to protect sensitive solid
So far the discussion has centered on the overvoltage state devices such as inverters is critical to the success of
impacts of DR on the power system. However, a variety of the protection. Most simple gapped surge arrester devices
anomalous voltage events that include transient have a sparkover voltage that does not coordinate with the
overvoltages as well as significant power frequency voltage surge withstand of transistors. An unpgapped metal oxide
swells can originate on the power system. These result in surge arrester (MOV) is a much more suitable device that is
peak voltage levels that, while of short duration, may recommended for protecting the power (AC and DC) ports
damage DR if it has not been adequately specified to of inverters. Communication ports may need other devices
withstand these events. This section discusses protecting due to the high capacitance of the MOV that can block
the DR from the power system! some communication circuits.

Lightning Surges on Low Voltage Power Systems Lightning Surges on Medium and High Voltage DR
Lightning surges are a threat to DR in locations that have Larger DR will employ medium and high voltage rated
moderate to high lightning incidence. These are short equipment such as transformers, switchgear, and
duration impulsive events a few hundred microseconds or generators. In any area with at least modest lightning
less in duration. Lightning surge magnitudes may be as activity or greater, these devices must be protected with
high as 6 kV on secondary power systems depending on the suitable lightning arresters coordinated per accepted
nature of the system design and exposure. IEEE C62.41 industry practices (such as per IEEE C62.22 – see reference
characterizes the lightning and switching surge 11). In addition, underground cables should be protected
environment that can be expected within buildings of with riser-pole arresters and open point arresters. Lightning
various types [10]. DR equipment should be designed to arresters need to be selected so they can withstand the
withstand these surge voltages without damage. Properly maximum continuous steady state voltage on the line and
coordinated lightning arresters are key to insure that the temporary over voltages. The arrester maximum continuous
surge related equipment failures can be minimized. Good operating voltage (MCOV) rating and temporary
protection practices for lightning surges should also protect overvoltage (TOV) capability must meet these
against most typical switching surges. requirements. Sloping capacitors may be used on rotating
machines in conjunction with lightning arresters to reduce
Some types of DR are more vulnerable than others. For winding stress imposed by steep rising surges.
example, wind turbines towers can be struck by lightning
and PV arrays are often exposed on fields or rooftops and

113

Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on May 18,2023 at 11:01:11 UTC from IEEE Xplore. Restrictions apply.
Voltage Swells arresters on all ports and protection against all
Another type of overvoltage event common on distribution modes of surge entry. Ground potential differences
systems is the voltage swell. This is the same phenomenon between surge protection devices may be
discussed earlier with regards to ground faults. However, particularly threatening to some equipment (such
the focus here is how power system voltage swells impact as PV inverters) and should be avoided.
the DR (not how the DR causes swells). Since the four-wire 5. Power system neutral shift during faults can
power distribution system is normally intended to be subject DR to voltage swells up to about 125% of
effectively-grounded, this means that faults on the system nominal. DR should be designed survive these
will lead to voltage swells up to about 125% of nominal. swells without damage. Surge arresters do not
These may occur many times per year due to the various offer protection for voltage swells. Protection is
faults that can be expected. Any DR connected phase to afforded only through connecting the generator
neutral on a four-wire multigrounded neutral system will be equipment in a line-to-line mode or by using
exposed to these swells. To insure survival without damage, equipment designed to survive the line-to-neutral
the DR should be designed to survive up to the expected voltage swells.
maximum swell level plus some margin (135% for 5
seconds is a good rule of thumb). DR installers should also VII. REFERENCES
recognize that lightning arresters are meant for short [1] ANSI/IEEE C62.92-1989, Guide for the Application of Neutral
duration impulsive surges and are not suitable for voltage Grounding in Electrical Utility Systems, Part 1-Introduction
[2] R.C. Dugan, D.T. Ritzy, “Electric Distribution System Protection
swell protection. The only means of protection is to connect Problems Associated with the Interconnection of Small, Dispersed
the generator in a fashion (phase-to-phase) where it won’t Generation Devices, IEEE Transaction on Power Apparatus and
see the voltage swell or to design the equipment to Systems, vol. PAS-103, No. 6, pp. 1121-1127., June 1984
withstand the condition without damage. [3] W.E. Feero, W.B. Gish, “Overvoltages Caused by DSG Operation:
Synchronous and Induction Generators,” IEEE Transactions on Power
Delivery, Vol. PWRD-1, pp. 258-264, Jan. 1986
VI. RECOMMENDATIONS [4] W. B. Gish, W.E. Feero, and S Greuel, “Ferroresonance and Loading
Relashionships for DSG Installations,” IEEE Transactions on Power
This paper has covered a range of overvoltage issues Delivery, vol. PWRD-2, no. 3, pp. 953-959, July 1987.
associated with DR. It is clear that improperly interfaced [5] T.A. Short, J.J. Burke, R.T. Mancao, “ Application of MOV’s in the
DR can cause overvoltages that can damage utility Distribution Environment,” IEEE Transactions on Power Delivery, vol.
9, no. 1, pp. 293-305, Jan. 1994.
equipment and customer loads. Conversely, DR may be [6] IEEE Std. 929-2000, “Recommended Practice for Utility Inteface of
susceptible to damage due to incoming overvoltages Photovoltaic Systems
originating from the power system or lightning. Proper [7] UL Std. 1741, “Inverters, Converters and Controllers for Use in
Independent Power Systems,” January 17, 2001
design, operation and specification of connected DR [8] IEEE Std. P1547 Draft Version 8.0, “Standard for Distributed
equipment can mitigate most of the problems associated Resources Interconnected with Electric Power Systems,” August 28,
with these issues. Key factors to consider in the design of 2001.
[9] ANSI Std. C84.1-1989, “Electric Power Systems and Equipment –
DR equipment and installations are: Voltage Ratings (60Hz)
[10] IEEE C62.41-1991, “IEEE Recommended Practice on Surge Voltages
1. Always use a proper grounding and transformer in Low-Voltage AC Power Circuits
[11] IEEE C62.22-1995, “Application of Metal Oxide Surge Arresters on
interface that is acceptable to the utility company AC Power Systems
and limits potential for dangerous ground fault
overvoltages. In most cases, utilities will want an VIII. BIOGRAPHY
effectively grounded generator interface for four-
wire multigrounded neutral type power systems.
Philip Barker (M’1986, SM’1999) was born in
2. Ferroresonance and self-excitation are potential Schenectady, NY, USA on March 8, 1963. He
sources of overvoltage from DR. Reliable, fast received his BSEE and MSEE from Clarkson
acting anti-island protection is crucial not only to University, Potsdam, NY in 1985 and 1986
respectively.
avoid these problems but also to coordinate with His employment experience includes Power
upstream utility protection devices and limit the Technologies Incorporated (from 1987-2000) where
duration of ground fault overvoltages. he worked as a Consulting Engineer in distribution
systems, lightning protection, distributed generation
3. Regulation related overvoltages up to 110% may and power quality monitoring/analysis.
occur if DR feeds high power into the system Since June 2000 Mr. Barker has worked as the Engineering Manager for
relative to the capacity of the connection point. the Schenectady, NY branch office of EPRI PEAC Corporation. This office is
focused on T&D studies and distributed resource applications and
Applications can be screened to identify the technologies.
likelihood of a problem. Standard anti-island Mr. Barker has published over 25 papers and is active in various IEEE
protection “voltage windows” afford no protection working groups related to distributed generation and power distribution
systems.
for this type of overvoltage – unless the industry
changes the windows to coincide with ANSI C84.1
upper limits.
4. DR equipment connected on the power system
secondary can be exposed to lightning and
switching surges. Surge protection is critical to the
reliability of both rotating and inverter based DR.
Proper surge protection includes the use of surge

114

Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on May 18,2023 at 11:01:11 UTC from IEEE Xplore. Restrictions apply.

You might also like