Anti-freeze security valve kit
SL
EL
DA
RO
HU
EN Mechanical protection device for the water circuit. The anti-freeze device will drain water out of the unit in case
of power shortage under freezing temperatures. No electrical power is needed.
SL
EL
DA
RO
HU
ASB_antifreeze valve_208674_230601_V01_EN
Important
User & equipment safety
The activation of the anti-freeze valve kit will drain the water out of the heat pump. A
correct installation of the heat pump includes a drainage point on the ground to prevent
the formation of ice or black ice (slippery floor).
Always depressurize the water circuit before removing any part of this kit.
The lowest end of the valve kit shall be positioned at minimum 15 cm of the ground.
The pipes of the outdoor circuit should be slightly inclined towards the antifreeze kit.
Avoid any corrosive product when cleaning the anti-freeze valve kit. Please refer to the
EN maintenance guidelines at the end of this document.
Do not use glycol when the anti-freeze valve kit is fitted as the anti-freeze valves may be
activated in the operating range of the glycol. In case of adding glycol despite our
recommendations, make sure that the drained glycol water in case of activation of the
anti-freeze valve kit is conducted to a collecting tank to avoid spillage of glycol water in
the environment.
Important: Do not add any insulation to the kit. Keep it away from any heating source.
SL
EL
ASB_antifreeze valve_208674_230601_V01_EN
DA
RO
HU
ASB_antifreeze valve_208674_230601_V01_EN
EN Kit content DA
SL RO
EL HU
a ×2
b ×1
a ×2
b ×1
c ×2
d ×1
ASB_antifreeze valve_208674_230601_V01_EN
EN Mounting instructions DA
SL RO
EL HU
EN Screw the kit directly on the lowest of the two water connections.
SL
EL
DA
RO
HU
ASB_antifreeze valve_208674_230601_V01_EN
7841698 Ø 1”1/2
7841699 Ø 2”
Use PTFE band or any appropriate sealing material to ensure sealing (To be supplied by the
EN installer). Recommended tightening torque: 50 Nm.
SL
EL
DA
RO
HU
SL
EL
ASB_antifreeze valve_208674_230601_V01_EN
DA
RO
HU
1 2 3
ASB_antifreeze valve_208674_230601_V01_EN
SL
EL
DA
RO
HU
EN Technical data DA
SL RO
EL HU
ASB_antifreeze valve_208674_230601_V01_EN
EN Model/reference 7841697 7841698 7841699
Cross connection diameter inch 1” ¼ 1” ½ 2”
Anti-freeze valve connection inch ½” ½” ½”
Admissible fluid water water water
Maximum operating pressure bar; mwc; kPa 8; 80; 800 8; 80; 800 8; 80; 800
Maximum operating temperature °C +80 +80 +80
Opening temperature °C +1 +1 +1
Closing temperature °C +4 +4 +4
Accuracy °C ±1 ±1 ±1
ASB_antifreeze valve_208674_230601_V01_EN
HU 7841697 7841698 7841699
1” ¼ 1” ½ 2”
½” ½” ½”
ASB_antifreeze valve_208674_230601_V01_EN