You are on page 1of 290

Chapter 2

Approximate Methods of Analysis

Lecture 6
‘K’ Factors and Their
Applications

1
Review of Chapter 1
Introduction to a Electrical Distribution System
Lecture 1: Structure of distribution system, primary distribution system,
secondary distribution system, why distribution system analysis?, course
content
Lecture 2: Substation components, various substation layouts
Lecture 3: Components and configurations of Distribution Feeders
Lecture 4: Nature of loads, load curves, demand factor, load factor, diversity
factor, utilization factor
Lecture 5: Load allocation to distribution transformers and feeder sections

2
Approximate Methods of Analysis
Actual distribution system is
Lines: un-transposed (three-phase, two-phase, single-phase)
Loads: unbalanced (three-phase, two-phase, single-phase)
It need detailed or exact model of distribution system

However, many times, we need approximate


but quick answer.
In approximate methods, we assume
Lines: transposed
Loads: balanced
Thus, single phase equivalent can be used.
3
Voltage Drop

VS  = VL 0 + ( I  −  )( R + jX )
VS cos  + jVS sin  = VL 0 + ( I cos  − jI sin  )( R + jX )
VS cos  + jVS sin  = VL 0 + ( IR cos  + IX sin  ) + j ( IX cos  − IR sin  )

When δ is small VS cos   VS and VS sin   0

VS = VL + IR cos  + IX sin  VS − VL = IR cos  + IX sin  = Re( ZI )

4
Example-01
1 2 Z12 = 0.2841 + j 0.5682 
I12 = 43.00 − 25.84 A
V1 = VS = 24000 V

V2 = VL = 24000 − ( 0.2841 + j 0.5682 )( 43.00 − 25.84 )


= 2378.41 − 0.40

Exact Vdrop = 2400 − 2378.41 = 21.59 V

Approximate Vdrop = Re ( ZI ) = Re ( 0.2841 + j 0.5682 )( 43.00 − 25.84 ) = 21.65 V


21.59 − 21.65
Error = = −0.0028 OR − 0.28%
21.59
5
“K” Factors: The Kdrop Factor
The Kdrop factor is determined by computing the percent voltage drop down
a line that is one km long and serving a balanced three-phase load of 1 kVA.

Percent voltage drop


K drop =
kVA×km

If the unit of length of line is mile, then

Percent voltage drop


K drop =
kVA×mile

6
“K” Factors: The Kdrop Factor
Percent voltage drop
K drop =
kVA×km

GMD
Li = 2  10−7 ln
GMR

zi = ri + j Li

I=
1(kVA)
3 VLL (kV)
(
 − cos −1 pf ) K drop = % Vdrop =
Re ( ZI )
100
Vbase

7
Example-02
Line impedance per km Z = 0.19 + j 0.32 Ω/km
Load power factor of 0.9 lagging and a nominal voltage of 11 kV (line-to-
line) or 6.35 kV (Line-to-Neutral).
The current taken by 1 kVA at 0.9 lagging power factor

I=
S (kVA)
3 VLL (kV)
( )
 − cos −1 pf =
1
3 11
( )
 − cos −1 0.9 = 0.0525 − 25.84

The voltage drop Vdrop = Re ( ZI ) = Re ( 0.19 + j 0.32 )( 0.0525 − 25.84 ) = 0.0161 V

0.0161
Thus, K drop = 100 = 0.000254 % drop/kVA-km
6350

8
Example-03
Let the Kdrop factor is 0.000254 %drop/kVA-km.
For example, assume a load of 7500 kVA is to be served at a point 2.4 kms
from the substation.

Vdrop = K drop ×kVA×km = 0.000254  7500  2.4 = 4.6%

Suppose now that the utility has a maximum allowable voltage drop of
3.0%. How much load can be served 2.4 kms from the substation?
Vdrop 3.0
kVA load = = = 4921.26 kVA
K drop ×km 0.000254×2.4

9
Example-04

K drop = 0.0002014 %drop/kVA-km

Segment kVA Length km %Drop


N0 to N1 300 + 750 + 500 = 1550 2.4 0.75
N1 to N2 750 + 500 = 1250 1.2 0.30
N2 to N3 500 0.8 0.08
Total Drop from N0 to N3 = 0.75 + 0.3 + 0.08 = 1.13 %

10
The Krise Factor
cap

Capacitor
Bank

Vrise = Re( ZI cap ) = X I cap

The Krise factor is defined

Percent voltage rise Percent voltage rise


K rise = or K rise =
kVAr×km kVAr×mile

11
Example-05
Line impedance per km Z = 0.19 + j0.32 Ω/km
The nominal voltage of 11 kV (line-to-line) or 6.35 kV (Line-to-Neutral).
The current taken by 1 kVAr
Q(kVAr) 1
I cap = 90 = 90 = 0.0525 90
3 VL (kV) 3 11.0

The voltage rise Vrise = X I cap = 0.0168

Thus, 0.0168
K rise =  100 = 0.000265% rise/kVA-km
6350

12
Example-06
In Example-03, the percent voltage drop in for 7500 kVA for 2.4 km was
computed to be 4.6%.
To limit the total voltage drop to 3%, the required voltage rise due to a
shunt capacitor bank is
Vrise = 4.6 − 3.0 = 1.6 %

The required rating of the shunt capacitor is


Percent voltage rise
K rise =
kVAr×km
Percent voltage rise 1.6
or kVAr = = = 2516 kVAr
K rise ×km 0.000265  2.4

13
Summary of the Lecture
Approximate methods of Analysis of Distribution System

Assumptions: Balanced 3-phase, transposed

K-FACTORS
Percent voltage drop
K drop =
▪ The Kdrop Factor kVA×km
Percent voltage rise
▪ The Krise Factor K rise =
kVAr×km

Applications of K-factors
14
Lecture 7
Analysis of Uniformly
Distributed Loads

1
Review of the Last Lecture
Approximate methods of Analysis of Distribution System
Assumptions: Balanced 3-phase, transposed
K-FACTORS
▪ The Kdrop Factor
▪ The Krise Factor
Applications of K-factors

2
Uniformly Distributed Load

To simplify the computation,


many times the loads are
assumed to be distributed
uniformly over a feeder.
It is an ideal case.
Examples: The load connected
to every pole like street lights,
houses in colony, etc.

3
Uniformly Distributed Load

IT
IT
di =
n
l = length of the feeder
z = r + jx = impedance of the feeder in  /km
dx = length of each line section
di = load current at each node
n = number of nodes and number of line sections
IT = total current entering into the feeder

4
Voltage Drop in Uniformly Distributed Load

IT
IT
di =
n
Section Impedance Current Voltage drop

0 to 1 z dx n di V01 = Re ( z dx  n di )

1 to 2 z dx (n-1) di V12 = Re ( z dx  ( n − 1) di )
2 to 3 z dx (n-2) di V23 = Re ( z dx  ( n − 2 ) di )

n-1 to n z dx (n-(n-1)) di = di V( n −1) n = Re ( z dx  di )

5
Voltage Drop in Uniformly Distributed Load
IT
IT di =
n

Vdrop = V01 + V12 + V23 + V34 + + V( n −1) n


= Re ( z dx  di ( n + (n − 1) + (n − 2) + (n − 3) + + 1 ))
  n ( n + 1)   dx =
l
= Re  z dx  di   
 n
  2 
I
 l IT  n ( n + 1)   di = T
= Re  z   
 n n  n
  2 

6
Voltage Drop in Uniformly Distributed Load
l
dx =
IT n
I
di = T
n
  ( n + 1)  
Vdrop = Re  Z  IT   

  2 n 
1  1
= Re  Z  IT 1 +  
2  n 
In the limiting case, where n goes infinity (i.e. large number of sections)
1 
Vdrop = Re  Z  IT 
2 
7
Voltage Drop in Uniformly Distributed Load

1   I 
Vdrop = Re  Z  IT  = Re  Z  T 
2   2 

R 3 2
Ploss = 3 IT2 = IT R
2 2

2
I  3
Ploss = 3  T  R = IT2 R
 2 4

8
Power Loss in Uniformly Distributed Load

IT
IT
di =
n
Section Resistance Current Power Loss

0 to 1 r dx n di (
PL01 = 3  r dx  n 2 di 2 )
1 to 2 r dx (n-1) di (
PL12 = 3  r dx  ( n − 1) di 2
2
)
= 3  ( r dx  ( n − 2 ) di )
2
2 to 3 r dx (n-2) di PL23 2

n-1 to n r dx (n-(n-1)) di = di (
PLn −1 n = 3  r dx  di 2 )
9
Power Loss in Uniformly Distributed Load
l
dx =
IT n
I
di = T
n
Ploss = PL01 + PL12 + PL23 + + PLn −1 n

( (
= 3 r dx  di 2  n 2 + ( n − 1) + ( n − 2 ) +
2 2
+ 12 ))
  n ( n + 1)( 2n + 1)    l  I  2  n ( n + 1)( 2n + 1)  
= 3  r dx  di 2    = 3  r     
T
  
  6    n  n   6  
 
  ( n + 1)( 2n + 1)    2  2n + 3n + 1 
2

= 3  R  IT  
2
  = 3  R  IT    
 2

2

  6 n    6 n 
10
Power Loss in Uniformly Distributed Load
l
dx =
IT n
I
di = T
n

 2  2n + 3n + 1 
2
  2 1 1 1  
Ploss = 3  R  IT     = 3  R  IT   + + 2 
 3 2n 6n  
2
  6 n   

In the limiting case, where n goes infinity (i.e. large number of sections)
1 
Ploss = 3  R  IT2 
3 

11
Power Loss in Uniformly Distributed Load

IT    
2

1 2 I
Ploss = 3  R  IT  = 3  R   T
 
  
  3 
3

12
Exact Lumped Load Model

1 
Vdrop = Re ( k Z  IT + (1 − k ) Z  cIT ) also Vdrop = Re  Z  IT 
2 

1
Therefore Z  IT = k Z  IT + (1 − k ) Z  cIT
2
0.5 − c
0.5 = k + c − ck = c + (1 − c)k k=
(1 − c)

13
Lumped Load Model

1 
(
Ploss = 3 k R  IT2 + ( k − 1) R  c 2 IT2 ) also Ploss = 3  R  IT2 
3 

1 
Therefore
3 
(
3  R  IT2  = 3 k R  IT2 + (1 − k ) R  c 2 IT2)
1
3
( )
= k + (1 − k ) c 2 = 1 − c 2 k + c 2

14
Exact Lumped Load Model
0.5 − c
k=
(1 − c)
and 1
3
( )
= 1 − c2 k + c2

0.5 − c
1
3
(
= 1 − c2 )
(1 − c)
+ c 2 = (1 + c)(0.5 − c) + c 2

1 1
Therefore c = and k=
3 4

15
Summary of the Lecture
• Uniformly distributed load
• Voltage drop
• Power loss
• Exact Lumped model

16
Lecture 8
Lumping Loads in Geometric
Configurations: Rectangular

1
Review of the Last Lecture
• Uniformly distributed load

• Voltage drop Vdrop = Re  Z  IT  = Re  Z 


1 IT 

2   2 

1    I 2 
• Power loss Ploss = 3  R  IT2  = 3  R   T  
3    3 
 

• Exact Lumped model

2
Lumping Loads in Geometric Configurations

3
Lumping Loads in Geometric Configurations
• Lumping the loads with feeders supplying various areas (geometric
configurations): Rectangles, triangles, etc.
• Approximate calculations of voltage drop and total power losses by
assuming constant load density.
• The approximate calculations of the maximum load at a given
voltage level and conductor size.
• Approximate locations capacitor or DG and their sizes

4
Lumping Loads in Geometric Configurations

kVA
D = load density in
km 2
z = line impedance in Ω/km

5
Rectangular Area Configuration
dx
kVA
D = load density in
km 2
PF = average power factor
z = line impedance in Ω/km
l = length of the area
w = width of the area
kVLL = nominal line-to-line voltage in kV
IT
di = A/km 2
wl

6
Rectangular Area Configuration
IT
di = A/km 2
wl
IT =
S (kVA)
3 VLL (kV)
(
 − cos −1 PF )
D l  w
=
3 VLL
(
 − cos −1 PF )

The current at any distance x from the node n


I  x
i = IT − ( w  x)  di = IT − ( w  x )  T = IT 1 − 
wl  l

7
The Rectangle : Voltage Drop
The voltage drop in the incremental
segment is
dV = Re ( zdx  i )
  x 
= Re  zdx  IT  1 − 
  l 

The total voltage drop down the primary main feeder is


l l   x   l  x 
Vdrop = 0 dV = 0  z dx  IT
Re 

1 −
l


= Re  z  IT

0  l  
1 −  dx

  x 2   
l
  l2   1  1 
= Re  z  IT    x −   = Re  z  IT   l −   = Re  z  IT  l  = Re  Z  I T 
  2l  0     2l    2  2 
  
8
The Rectangle: Voltage Drop

1 
Vdrop = Re  Z  IT 
2 

9
The Rectangle: Power Loss
IT
di = A/km 2
wl

 x
i = IT 1 − 
 l

Power loss in the incremental length is

2 x x2 
2
 x
dp = 3  r dx  i = 3  r dx IT 1 −  = 3  r dx I T 1 − 2 + 2 
2 2

 l  l l 

10
The Rectangle: Power Loss

 x x2 
dp = 3  r dx IT 1 − 2 + 2 
2

 l l 

Total three-phase power loss down the primary main is


l  l x x2    x 2
x 3

l

=  dp = 3  r IT  1 − 2 + 2  dx = 3  r  IT  x − 2 + 2 
2 2
Ploss
0 0
 l l   2l 3l  0 
 
2 l l 1 2 
= 3  r  IT  l − l +  = 3  r  IT = 3   R  IT 
2

 3 3 3 
11
The Rectangle: Power Loss

1 2 
Ploss = 3   R  IT 
3 

12
Example
• l= 3.05 km
• w=1.83 km.
• A = l × w = 5.58 km2.
• D = 965.55 kVA/km2, pf 0.9 lag.
• Total kVA = D × A = 5387.8 kVA
• z = 0.19 + j 0.32 Ω/km
• Allowed voltage drop is ±3%.
• The choices of nominal voltages are 4.16 kV and 11 kV

13
Solution
The total impedance (Z) =z  l = (0.19 + j 0.32)  3.05 = 0.58 + j 0.98
For a nominal voltage of 4.16 kV, the total current is,
kVA 5387.8
IT = =  − cos −1 0.9 = 747.7 − 25.84 A
( 3  kVLL ) 3  4.16

1 
The total voltage drop = Vdrop = Re   Z  IT  = 354.86 V
2 

Vdrop 354.86
The percentage voltage drop = %Vdrop = 100 = 100 = 14.78 %
VLN 4160 / 3

14
Solution
For a nominal voltage of 11 kV,
kVA 5387.8
IT = =  − cos −1 0.9 = 282.78 − 25.84 A
( 3  kVLL ) 3 11.0

The total voltage drop down the primary main is


1 
Vdrop = Re   Z  IT  = 134.20 V
2 
The percentage voltage drop is
Vdrop 134.20
Vdrop % = 100 = 100=2.11 %
VLN 11000 / 3

15
Summary
• Lumping Loads in Geometric Configurations
– Rectangular
1 
Vdrop = Re  Z  IT 
2 

1 2
Ploss = 3   R  IT 
3 

– Application

16
Lecture 9
Lumping Loads in Geometric
Configurations: Triangular

1
Review of the Last Lecture
• Lumping Loads in Geometric Configurations
– Rectangular
1 
Vdrop = Re  Z  IT 
2 

1 2 
Ploss = 3   R  IT 
3 

– Application

2
The Triangle: Voltage Drop

kVA
D = load density in
km 2
z = line impedance in Ω/km

3
The Triangle: Voltage Drop
The total current entering the area:
S kVA
IT =  − cos −1 ( PF ) A
3  kVLL
D  Area
=  − cos −1 ( PF ) A
3  kVLL

IT IT 2  IT
di = = = A/km 2
Area 1  l  w l  w
2

4
The Triangle: Voltage Drop
The current entering the line segment
i = IT − A1  di

where A1 = area of triangle up to the


incremental line segment.

2  IT 1 1 w
di = A/km 2 A1 = w1 x =  x    x
lw 2 2 l 
Also,
x w1 xw
=  w1 =
l w l
5
The Triangle: Voltage Drop
i = IT − A1  di

1 w   2  IT 
= IT −    x 2    
2 l   lw 
 x2 
= IT  1 − 2 
 l 
IT IT 2  IT
di = = = A/km 2
Area 1  l  w l  w Therefore,
2
1 w   x2 
and A1 =  x    x dv = Re  zdx  i  = Re  z dx  IT 1 − 2  
2 l    l 

6
The Triangle: Voltage Drop
  x2 
dv = Re  z dx  IT 1 − 2  
  l 

The total voltage drop from node n to node m is


l l
  x2   l
 x2  
Vdrop =  dv =  Re  z dx  IT 1 − 2   = Re  z  IT   1 − 2   dx 
0 0   l   0
l  
  x3
l
   l3  2 
= Re  z  IT  x − 2   = Re  z  IT l − 2   = Re  Z  I T 
  3l    3l  3 
  0 

7
The Triangle: Voltage Drop
2 
Vdrop = Re   ZT  IT 
3 

8
The Triangle: Power Loss
 x2 
i = IT 1 − 2 
 l 

Power loss in area dx


dp = 3 ( rdx | i |2 )

 2 2
 x2 x4  
2  x  2 
Substituting dp = 3  r dx  | IT | 1 − 2   = 3  r | IT | 1 − 2  2 + 4  dx 
  l     l l  

9
The Triangle: Power Loss
 2  x2 x4  
dp = 3  r | IT | 1 − 2  2 + 4  dx 
  l l  

The total three-phase power loss from node n to node m becomes


l l
 2  x2 x4  
l
 x2 x4 
Ploss =  dp =  3  r | IT | 1 − 2  2 + 4  dx  = 3  r | IT |  1 − 2  2 + 4   dx
2

0 0   l l   0
l l 

  x 3
x 5

l
 2 2 l  8 
= 3r IT   x − 2 2 + 4   = 3r IT  l − l +  = 3  R | IT |2 
2

 3l 5l  0   3 5  15 
 

10
The Triangle: Power Loss
 8 
Ploss = 3  R | IT |2 
 15 

11
Example
• l = 4.5 km
• w = 1.8 km
• A = 1/2 × l × w = area=4.14 km2
• D = 1351.8 kVA/km2, pf 0.9 lag.
• Total kVA = D × A = 5596.45 kVA
• Kdrop = 0.0002191 % drop/kVA-km,
• Krise = 0.0002504 % rise/kvar-km
• Nominal voltage = 11 kV
• Find the location of 1800 kVAr capacitor bank to keep the voltage drop
within ±3% at the end.

12
Solution
The total load of the triangular area is
kVA = 5596.45 − 25.84 kVA

Using the K drop factor and lumping the total load


2 
Vdrop = K drop  kVA    dist 
3 
2 
= 0.0002191 5596.45    4.6 
3 
= 3.76 %

13
Solution
The required voltage rise due to the capacitor is
Vrise = Vdrop − 3.0 = 3.76 − 3.0 = 0.76

The distance from node n is determined by:


Vrise
dist =
K rise = 0.0002504 % rise/kvar-km K rise  kvar
0.76
=
Vrise Vrise 0.0002504 1800
K rise =  dist =
dist  kvar K rise  kvar = 1.69 km

14
Summary
• Lumping Loads in Geometric Configurations
– Triangular
2 
Vdrop = Re  ZT IT 
3 

 8 
Ploss = 3  R | IT |2 
 15 
– Application

15
Chapter 3
Modelling of Distribution System Components

Lecture 10
Impedance of Distribution Lines
and Feeders - Part I

1
Review of the Chapter 2
• K-FACTORS: Kdrop and Krise
• Uniformly distributed load:
– Voltage drop
– Power loss
– Exact lumped load model
• Lumping Loads in Geometric
Configurations
– Rectangular
– Triangular

2
Types of Conductor
• Copper
• Aluminum: Cheaper, lighter, but less conductive and less tensile strength
than copper
– ACSR (Aluminum Conductor Steel Reinforced)
– AAC (All Aluminum Conductor)
– AAAC (All Aluminum Alloy Conductor)
– ACAR (Aluminum Conductor Alloy Reinforced)
ACSR Conductor

• Internal steel strands increase the


tensile strength
• Outer aluminum strands carry the
current
• Stranded conductor with twisted wires
for strength and flexibility of
mechanical handling
Resistance
The DC resistance of conductor at specified temperature is:
T l
R= 
A
ρT is the resistivity of the conductor at temperature T
l is the length of the conductor in m
A is the cross-sectional area of conductor in m2

Rt 2 (1  0 + T2 )
=
Rt1 (1  0 + T1 )
Resistance of the Stranded Conductor

a l  a (1.05  103 )
a l a
R= = = = 1337 Ω/km
A ns As   d s2  ns d s2
ns 
 

 4 
Conductor Data Sheet

Source: http://www.stabiloy.com/NR/rdonlyres/5FFCCF8A-8706-4FE5-9C9D- 7
CFD2DEEAEDB2/0/SEC4_Overhead_Conductors.pdf
Transposed Three-Phase Lines
GMD Deq
Li = 2  10−7 ln or Li = 2  10−7 ln H m
GMR GMR

GMD or Deq = 3 Dab Dbc Dca

• Line impedance for in Ω/km for 50 Hz


zi = ri + j Li
GMD
= ri + j 2 50  2  10−7 ln 1000  km
GMR
GMD
= ri + j 0.0628 ln  km
GMR
Transposed Three-Phase Lines
GMD Deq
Li = 2 10−7 ln or Li = 2 10−7 ln H m
GMR GMR

GMD or Deq = 3 Dab Dbc Dca

• Line impedance for in Ω/mile for 60 Hz


zi = ri + j Li
GMD
= ri + j 2 60  2 10−7 ln 1609.34  mile
GMR
GMD
= ri + j 0.1213 ln  mile
GMR
Un-Transposed Distribution Lines
1
ii = 2 10−7 ln I i Wb
GMRi
ii 1
Lii = = 2  10−7 ln H m
Ii GMRi

zii = ri + j Lii
1
= ri + j 2 50  2  10−7 ln  1000  km
GMRi
1
= ri + j 0.0628ln  km
GMRi
Un-Transposed Distribution Lines
1
ij = 2  10−7 ln I j Wb
Dij
ij 1
Lij = = 2  10 −7 ln H m
Ij Dij

zij = j Lij
1
= j 2 50  2  10 −7 ln  1000  km
Dij
1
= j 0.0628 ln  km
Dij
Impedance of Distribution Line
– Transposed line
GMD
zi = ri + j  2  10−7 ln  m
GMR
GMD
= ri + j 0.0628 ln  km
GMR

– Un-transposed line
1
zii = ri + j 0.0628 ln  km
GMRi  Z aa Z ab Z ac 
 Z bc 
1 Z abc  =  Z ba Z bb
zij = j 0.0628 ln  km
Dij  Z ca Z cb Z cc 
Zero-sequence current paths

Source: T. A. Short, Electric Power Distribution Handbook, CRC Press, Boca Raton,
2003. 13
Un-Transposed and Unbalanced System

Vig = zii I i + zij I j + zid I d − zdd I d − zid I i − z jd I j


= zii I i + zij I j + zid ( − I i − I j ) − zdd ( − I i − I j ) − zid I i − z jd I j
= ( zii − zid + zdd − zid ) I i + ( zij − zid + zdd − z jd ) I j = zˆii I i + zˆij I j
Source: W. H. Kresting, Distribution System Modeling and Analysis, CRC
Press, New York, 2002.
Un-transposed and Unbalanced System

Vig = zˆii .I i + zˆij .I j

zˆii = zii + zdd − zdi − zid zˆij = zij + zdd − zdj − zid

= ri + jxii + rd + jxdd − j ( xid + xdi ) = jxij + rd + jxdd − j ( xdj + xid )


Un-transposed and Unbalanced System

zˆii = zii + zdd − zdi − zid

= ri + jxii + rd + jxdd − j ( xid + xdi )

 1 1 1 1 
= ri + rd + j  2  10−7  ln + ln − ln − ln 
 GMRi GMRd Did Ddi 

 1 D .D 
= ri + rd + j  2  10−7  ln + ln id di 
 GMRi GMRd 
Un-transposed and Unbalanced System

zˆij = zij + zdd − zdj − zid

= jxij + rd + jxdd − j ( xdj + xid )

 1 1 1 1 
= rd + j  2  10  ln
−7
+ ln − ln − ln 
 Dij GMRd Ddj Did 

 1 Ddj .Did 
= rd + j  2  10 −7
 ln + ln 
 Dij GMRd 
Earth Layers of Sub-conductors
The Summary of The Lecture
Chapter 3: Modelling of Distribution System Components

Series impedance of distribution lines and feeders


Resistance of the distribution line conductors
Inductance transposed distribution lines
Inductance and impedance of un-transposed line
Impedance of distribution line with earth return

19
Lecture 11
Series Impedance of Distribution
Lines and Feeders - Part II

1
Review of the Last Lecture

 1 D .D 
zˆii = ri + rd + j  2  10−7  ln + ln id di   / m
 GMRi GMRd 

 1 Ddj .Did 
zˆij = rd + j  2  10  ln
−7
+ ln   / m
 Dij GMRd
 
Source: W. H. Kresting, Distribution System Modeling and Analysis, CRC
Press, New York, 2002.
Earth Layers of Sub-conductors
Carson’s Equations
Since a distribution feeder is inherently unbalanced.
The earth is a conductor of enormous dimension and non-uniform conductivity.
Thus earth current distribution is not uniform.
To calculate the impedance of conductor with earth return, it is necessary to
know the distribution of current returning in the earth.
Many engineers attacked this problem using different methods and
assumptions.
In 1926, Carson developed a technique to get the self and mutual impedances
for an arbitrary number of overhead conductors.
Carson assumed that the earth is an infinite, uniform solid with a flat uniform
upper surface and a constant resistivity.
Carson’s Equations

p
De = 2160 ft
f
p
= 0.305  2160 meter
f

Equivalent Depth of Earth


Return (De)
Modified Carson’s Equations
 1 D .D 
zˆii = ri + rd + j  2 10−7  ln + ln id di   / m
 GMRi GMRd 

 1 Ddj .Did 
zˆij = rd + j  2 10  ln −7
+ ln   / m
 Dij GMRd
 

 1 
ˆzii = ri + 9.86  10−7 f + j  2  10−7  ln + ln De  Ω m De = 2160
p
ft
 GMRi  f

−7 −7
 1  = 0.305  2160
p
zˆij = 9.86  10 f + j  2  10  ln + ln De  Ω m meter
 Dij  f
 
Modified Carson’s Equations (50 Hz and km)
 1  Conductor
zˆii = ri + 9.86  10−7 f + j  2  10−7  ln + ln De  Ω m
 GMRi  distances in meter
  1 
=  ri + 9.86  10−7  50 + j 2  50  2  10−7  ln + ln De   1000 Ω km
  Soil P
  GMRi 
Damp earth 100
 1 
= ri + 0.0493 + j 0.0628  ln + 6.843  Ω km Dry earth 1000
 GMRi 
Sea water 1

 1 
zˆij = 9.86  10−7 f + j  2  10−7  ln + ln De  Ω m
 Dij  De = 2160
p
  ft
f
 1 
= 0.0493 + j 0.0628  ln + 6.843  Ω km p
 Dij  = 0.305  2160 meter
  f
Modified Carson’s Equations (60 Hz and mile)
Conductor
 1 
zˆii = ri + 9.86  10−7 f + j  2  10−7  ln + ln De  Ω m distances in ft
 GMRi 
  1  De = 2160
p
=  ri + 9.86  10−7  60 + j 2 60  2  10 −7  ln + ln De   1609.34 Ω mile ft
  f
  GMRi 
 1 
= ri + 0.0953 + j 0.12134  ln + 7.93402  Ω mile
 GMRi  Soil P

−7 −7
 1  Damp earth 100
zˆij = 9.86  10 f + j  2  10  ln + ln De  Ω m
 Dij  Dry earth 1000
 
Sea water 1
 1 
= 0.0953 + j 0.12134  ln + 7.93402  Ω mile
 Dij 
 
Summary Impedances of Distribution Line
• Impedance at 50 Hz per km
GMD
– Transposed line zi = ri + j 0.0628 ln Ω km
GMR
– Self and mutual impedances of un-transposed line without ground return
1
zii = ri + j 0.0628 ln Ω km
GMRi
1
zij = j 0.0628ln Ω km
Dij
– Self and mutual impedances of un-transposed line with ground return
 1 
zˆii = ri + 0.0493 + j 0.0628  ln + 6.843  Ω km
 GMRi 
 1 
zˆij = 0.0493 + j 0.0628  ln + 6.843  Ω km
 Dij 
 
Primitive Impedance Matrix
 1 
zˆii = ri + 0.0493 + j 0.0628  ln + 6.843  Ω km
 GMRi 
 1 
ˆzij = 0.0493 + j 0.0628  ln + 6.843  Ω km
 Dij 
 

 zˆaa zˆab zˆac zˆan 


 zˆ zˆbn 
  zˆij   zˆin  
zˆ pri =  ba
zˆbb zˆbc
  
 zˆca

zˆcb zˆcc zˆcn 

  zˆnj 
   zˆnn 
 zˆna zˆnb zˆnc zˆnn 

10
Primitive Impedance Matrix

 zˆaa zˆab zˆac | zˆal zˆam zˆan 


 zˆ zˆbb zˆbc | zˆbl zˆbm zˆbn 
 ba
 zˆca zˆcb zˆcc zˆcl zˆcm zˆcn 

|
   zˆij 
   zˆin  
 zˆ pri  =  − − −− −− −− −− −− − −  ˆ
z  =  
 pri  
 zˆla zˆlb zˆlc | zˆll zˆlm zˆl n 
ˆ 
  znj   zˆnn 
 
 zˆma zˆmb zˆmc | zˆml zˆmm zˆmn 
 zˆ zˆnb zˆnc zˆnl zˆnm zˆnn 
 na |
Kron Reduction

Vag  V 'ag   zˆaa zˆab zˆac zˆan   I a 


     zˆ
 bg   bg 
V V '
 ba zˆbb zˆbc zˆbn   I b  Vabc  V 'abc    zˆij   zˆin    I abc 
V  = V '  +  zˆca zˆcb zˆcc zˆcn   I c  V  = V '  +   
 cg   cg      ng   ng    zˆnj   zˆnn   I n 
Vng  V 'ng   zˆna zˆnb zˆnc zˆnn   I n 
   

12
Kron Reduction
Vabc  V 'abc    zˆij   zˆin    I abc 
V  = V '  +   
 ng   ng    zˆnj   zˆnn   I n 
Two separate equations
Vabc  = V 'abc  +  zˆij   I abc  +  zˆin   I n  and Vng  = V 'ng  +  zˆnj   I abc  +  zˆnn   I n 

Neutral and ground wires are grounded at several locations.


0 = 0 +  zˆnj   I abc  +  zˆnn   I n   I n  = −  zˆnn   zˆnj   I abc 
−1

Vabc  = V 'abc  +  zˆij   I abc  −  zˆin   zˆnn −1  zˆnj   I abc 


(
= V 'abc  +  zˆij  −  zˆin   zˆnn   znj 
−1
)  I abc   zabc  =  zˆij  −  zˆin   zˆnn −1  zˆnj 
= V 'abc  +  zabc  I abc 

13
Kron Reduction

zbc

Vag  V 'ag   zˆaa zˆab zˆac zˆan   I a  Vag  V 'ag   zaa zab zac   I a 
        
 bg   bg 
V V '  zˆ
 ba zˆbb zˆbc zˆbn   I b  V
   = V '  +  zba zbb zbc   I b 
V  = V '  +
bg bg
 zˆca zˆcb zˆcc zˆcn   I c  Vcg  V 'cg   zca zcb zcc   I c 
 cg   cg        
Vng  V 'ng   zˆna zˆnb zˆnc zˆnn   I n 
   
  zˆij   zˆin  
    zabc  =  zˆij  −  zˆin  zˆnn 
−1
 zˆnj 
  zˆnj 
   zˆnn 
Impedance of Distribution Line
 1 
zˆii = ri + 0.0493 + j 0.0628  ln + 6.843  Ω km
 GMRi 
 1 
ˆzij = 0.0493 + j 0.0628  ln + 6.843  Ω km
 Dij 
 

 zˆaa zˆab zˆac zˆan 


 zˆ zˆbb zˆbc zˆbn 
zˆ pri =  ba
 zˆca zˆcb zˆcc zˆcn 
 
 zˆna zˆnb zˆnc zˆnn 

 Z aa Z ab Z ac 
 Z bc 
Z abc  =  Z ba
 zabc  =  zˆij  −  zˆin   zˆnn 
−1 Z bb
 zˆnj 
 Z ca Z cb Z cc 
Example
Determine the phase impedance matrix. The
phase conductors are 336,400 26/7 ACSR, and
the neutral conductor is 4/0 6/1 ACSR.

Dab = 0.76 m, Dbc = 1.37 m, Dca = 2.13 m


Dan = 1.72 m, Dbn = 1.30 m, Dcn = 1.52 m

Conductor Types Diameter GMR Resistance Capacity


(cm) (m) (Ω/km) (Amp)
336,400 26/7 ACSR 1.83134 0.0074 0.1901 530
4/0 6/1 ACSR 1.43 0.0025 0.3679 340

16
Solutions
Conductor Types GMR Resistance
(m) (Ω/km)
336,400 26/7 ACSR 0.0074 0.1901
4/0 6/1 ACSR 0.0025 0.3679

 1 
Z aa = ri + 0.0493 + j 0.0628  ln + 6.843   /km
 GMRa 
 1 
=0.1901+0.0493+j 0.0628  ln + 6.843   /km
 0.0074 
=0.2394+j 0.7378  /km

17
Solutions
Conductor Types GMR Resistance
(m) (Ω/km)
336,400 26/7 ACSR 0.0074 0.1901
4/0 6/1 ACSR 0.0025 0.3679

 1 
Z ab = 0.0493 + j 0.0628  ln + 6.843   /km
 Dab 
 1 
=0.0493+j 0.0628  ln + 6.843   /km
 0.762 
=0.0493+j 0.4467  /km

18
Solution
 1 
zˆii = ri + 0.0493 + j 0.0628  ln + 6.843  Ω km
 GMRi 
 1 
ˆzij = 0.0493 + j 0.0628  ln + 6.843  Ω km
 Dij 
 

• Primitive Impedance Matrix


 0.2394+j 0.7378 0.0493+j 0.4467 0.0493+j 0.3819 0.0493+j 0.3953
0.0493+j 0.4467 0.2394+j 0.7378 0.0493+j 0.4097 0.0493+j 0.4129 
 zˆ pri  =   /km
 0.0493+j 0.3819 0.0493+j 0.4097 0.2394+j 0.7378 0.0493+j 0.4031
 
 0.0493+j 0.3953 0.0493+j 0.4129 0.0493+j 0.4031 0.4172+j 0.8060 
Solution
 0.2394+j 0.7378 0.0493+j 0.4467 0.0493+j 0.3819 0.0493+j 0.3953
0.0493+j 0.4467 0.2394+j 0.7378 0.0493+j 0.4097 0.0493+j 0.4129 
 zˆ pri  =   /km
 0.0493+j 0.3819 0.0493+j 0.4097 0.2394+j 0.7378 0.0493+j 0.4031
 
 0.0493+j 0.3953 0.0493+j 0.4129 0.0493+j 0.4031 0.4172+j 0.8060 

 0.2394+j 0.7378 0.0493+j 0.4467 0.0493+j 0.3819 


 zˆij  = 0.0493+j 0.4467 0.2394+j 0.7378 0.0493+j 0.4097 
 
 0.0493+j 0.3819 0.0493+j 0.4097 0.2394+j 0.7378 
0.0493 + j 0.3953 
 zin  = 0.0493 + j 0.4129
0.0493 + j 0.4031 
 znn  = 0.4172+j 0.8060
 znj  =  0.0493 + j 0.3953 0.0493 + j 0.4129 0.0493 + j 0.4031
Solution
 0.2394+j 0.7378 0.0493+j 0.4467 0.0493+j 0.3819 
 zˆij  = 0.0493+j 0.4467 0.2394+j 0.7378 0.0493+j 0.4097 
 
 0.0493+j 0.3819 0.0493+j 0.4097 0.2394+j 0.7378
0.0493 + j 0.3953 
 zin  = 0.0493 + j 0.4129
0.0493 + j 0.4031 
 znn  = 0.4172+j 0.8060
 znj  =  0.0493 + j 0.3953 0.0493 + j 0.4129 0.0493 + j 0.4031

 zabc  =  zij  −  zin    znn 


−1
  znj 
0.2792 + j 0.5675 0.0918 + j 0.2691 0.0902 + j 0.2085 
=  0.0918 + j 0.2691 0.2847 + j 0.5527 0.0930 + j 0.2289   /km
0.0902 + j 0.2085 0.0930 + j 0.2289 0.2816 + j 0.5611
The Summary of The Lecture

Series impedance of distribution lines and feeders


Impedance of distribution line with earth return
Kron Reduction
Example of calculations of impedance of distribution lines and feeders

22
Lecture 12
Models of Distribution Lines
and Cables

1
Review of the Last Lecture
• Impedance at 50 Hz per km GMD
– Transposed line zi = ri + j 0.0628 ln Ω km
GMR
– Self and mutual of Un-transposed without ground return
1
zˆii = ri + j 0.0628 ln Ω km
GMRi
1
zˆij = j 0.0628ln Ω km
Dij
– Self and mutual impedances with ground return
 1 
zˆii = ri + 0.0493 + j 0.0628  ln + 6.843  Ω km
 GMRi 
 1 
zˆij = 0.0493 + j 0.0628  ln + 6.843  Ω km
 Dij 
 
Review of the Last Lecture
 1 
zˆii = ri + 0.0493 + j 0.0628  ln + 6.843  Ω km
 GMRi 
 1 
ˆzij = 0.0493 + j 0.0628  ln + 6.843  Ω km
 Dij 
 

 zˆaa zˆab zˆac zˆan 


 zˆ zˆbn 
  zˆij   zˆin  
zˆ pri =  ba
zˆbb zˆbc
  
 zˆca

zˆcb zˆcc zˆcn 

  zˆnj 
   zˆnn 
 zˆna zˆnb zˆnc zˆnn 

3
Review of the Last Lecture

zbc

Vag  V 'ag   zˆaa zˆab zˆac zˆan   I a  Vag  V 'ag   zaa zab zac   I a 
        
 bg   bg 
V V '  zˆ
 ba zˆbb zˆbc zˆbn   I b  V
   = V '  +  zba zbb zbc   I b 
V  = V '  +
bg bg
 zˆca zˆcb zˆcc zˆcn   I c  Vcg  V 'cg   zca zcb zcc   I c 
 cg   cg        
Vng  V 'ng   zˆna zˆnb zˆnc zˆnn   I n 
   
  zˆij   zˆin  
    zabc  =  zˆij  −  zˆin . zˆnn 
−1
.  zˆnj 
  zˆnj 
   zˆnn 
Shunt Admittance of Overhead Line
Qi Vi =
Qi
ln
1
+
( −Qi ) ln 1 + Q j ln 1 + ( −Q j ) ln 1
Qj 2 0 GMRi 2 0 Sii 2 0 Dij 2 0 Sij
Dij
Qi S Qj Sij
Vi = ln ii + ln
Sij 2 0 GMRi 2 0 Dij
Sii
Vj =
Qi
ln
1
+
( −Qi ) ln 1 + Q j ln 1 + ( −Q j ) ln 1
2 0 Dij 2 0 Sij 2 0 GMR j 2 0 S jj
Qi Sij Qj S jj
Vj = ln + ln
2 0 Dij 2 0 GMR j
-Qj
-Qi  1 S 1 Sij 
 ln ii ln 
Vi   2 0 GMRi 2 0 Dij   Qi  =  Pii Pij   Qi 
V  =   Q j   Pij Pjj  Q j 
 j  1
ln
Sij 1
ln
S jj
  
 2 0 Dij 2 0 GMR j 
Shunt Admittance of Overhead Line
Qi Qj Vi   Pii Pij   Qi 
Dij V  =  P Pjj  Q j 
 j   ij
Sij Therefore
Sii −1
 Qi   Pii Pij  Vi 
Q  =  P Pjj  V j 
 j   ij
−1
Cii Cij  Vi   Pii Pij  Vi 
C =
-Qj  ij Cij  V j   Pij Pjj  V j 
−1
-Qi Cii Cij   Pii Pij 
C =
 ij Cij   Pij Pjj 

C  =  P 
−1
Shunt Admittance of Overhead Line
Q1 Qn
Qi Qj ˆ ˆ ˆ ˆ  Q
Dij V1   Paa P P .. P  
V   P  1
ab ac an

ˆ ˆ ˆ ˆ  Q
Sij
Q2  2   ba Pbb Pbc .. P bn  2
Sii V3  =  Pˆ ˆ ˆ ˆ   Q3 
   ca Pcb Pcc .. P cn 
 
 :   : : : .. :  : 
   
 n 
V ˆ ˆ ˆ ˆ
Pnn   Qn 

 Pna Pnb Pnc .. 
-Q2
-Qj
-Qi -Qn 1 Sii 1 Sij
-Q1 Pii = ln m/F Pij = ln F/m
2 0 GMRi 2 0 Dij
Sii Sij
=17.98 ln km /  F = 17.98 ln km /  F
GMRi Dij
Shunt Admittance of Overhead Line
ˆ ˆ ˆ ˆ  Q
V1   Paa P P .. P  
V   P  1
ab ac an

ˆ ˆ ˆ ˆ  Q  ˆ   Pˆin   Q
 2   ba Pbb P bc .. P bn  2 Vabc    Pij      abc 
V3  =  Pˆ ˆ ˆ ˆ   Q3  V =  
   ca Pcb Pcc .. P cn 
   n   Pˆ   Pˆnn    Qn 
  nj   
 :   : : : .. :  : 
  
Vn 
  ˆ
 Pna
ˆ
Pnb
ˆ
P nc .. ˆ
Pnn  Q 
 n
−1
Therefore  Pabc  =  Pˆij  −  Pˆin  .  Pˆnn  .  Pˆnj 
Cabc  =  Pabc 
−1
And  F/km
Neglecting the shunt conductance, the phase shunt admittance
matrix is given by  y  = 0 + j C   S km
abc abc
Admittance of Distribution Line
1 Sii 1 Sij
Pii = ln m/F Pij = ln F/m
2 0 GMRi 2 0 Dij
Sii Sij
=17.98 ln km /  F = 17.98 ln km /  F
GMRi Dij

Pˆ Pab Pac Pan 


 
aa

P Pbb Pbc Pbn 


Ppri =  ba 
 Pca Pcb Pcc Pcn 
P Pnn 
 na Pnb Pnc 
 Paa Pab Pac 
 Pbc 
−1   =  Pba
 Pabc  Pbb
 Pabc  =  Pˆij  −  Pˆin  .  Pˆnn  .  Pˆnj  

Pcc 
 Pca Pcb 
Admittance of Distribution Line
Sii Sij
Pii =17.98 ln km /  F Pij = 17.98 ln km /  F
GMRi Dij

136.12 56.64 38.13 40.55


56.64 136.12 46.02 45.70 km /  F
38.13 46.02 136.12 42.80
40.55 45.70 42.80 137.89

−1
 Pabc  =  Pˆij  −  Pˆin  .  Pˆnn  .  Pˆnj 
Conductor Types GMR(m)
124.20 43.20 25.55
Phase 0.0074
43.20 120.98 31.83 km /  F
Neutral 0.0025 25.55 31.83 122.84
Admittance of Distribution Line
Caa Cab Cac 
−1  Cbb Cbc   F/km
Cabc  = Pabc  = Cba
 Cca Ccb Ccc 

0.0093 -0.0030 -0.0012


Cabc  = -0.0030 0.0099 -0.0019  F/km
-0.0012 -0.0019 0.0089

Caa Cab Cac  3.52 -1.14 -0.44


 Cbb Cbc  = j
Yabc  = j  Cba -1.14 3.72 -0.73 μS/km
 Cca Ccb Ccc  -0.44 -0.73 3.35
Impedance and Admittance of
Underground Cables
Underground Cable

dc= diameter of phase conductor


ds= outside diameter of the tape shield
dod =outside diameter over jacket
T= thickness of copper tap shield
Source: W. H. Kresting, Distribution System Modeling and Analysis, CRC
Press, New York, 2002.
Cable Layouts

RC and GMRC
DS
GMRS =
2

• The Carson’s equations can be applied to underground cables in much


the same manner as for overhead lines.
• The circuit will result in a 6 by 6 primitive impedance matrix.
• For underground circuits those have the additional neutral conductor,
the primitive impedance matrix will be 7 by 7.
Impedance of Tape-Shielded Cables
 zˆaa zˆab zˆac | zˆal zˆam zˆan 
 zˆ ˆ ˆ zˆbl zˆbm zˆbn 
 ba zbb zbc |
 zˆca zˆcb zˆcc | zˆcl zˆcm zˆcn 
 
 zˆ pri  =  − − − − − − − − − − −− − −
 zˆla zˆlb zˆlc | zˆll zˆlm zˆl n 
 
 zˆma zˆmb zˆmc | zˆml zˆmm zˆmn 
 zˆ zˆnn 
 na zˆnb zˆnc | zˆnl zˆnm
 
 Z abc  =  zˆij  −  zˆin  zˆnn 
1 −1
zˆii = ri + 0.0493 + j 0.0628  ln + 6.843  Ω km  zˆnj 
 GMRi 
 1   Z aa Z ab Z ac 
zˆij = 0.0493 + j 0.0628  ln + 6.843  Ω km 
 Dij  Z abc  =  Z ba Z bb Z bc 
 
 Z ca Z cb Z cc 
Capacitance of Tape-Shielded Cables
2 0 r
Cag =
R
ln s
Rc
Can 0 0 
 0  F/m
Cabc  =  0 Cbn
 0 0 Ccn 

Can 0 0 
 0  μS/km
Yabc  = j  1000  106   0 Cbn
 0 0 Ccn 
PI model of Distribution Lines or Cables

VLGabc n   a  b  . VLGabc m 


 =   
  I abc n   c      abc m 
d I
PI model of Distribution Lines or Cables

1
a = d = 1+ ZY
2
b=Z
 1 
c = Y  1 + YZ 
 4 

1
 a  =  d  = u  +  Z abc Yabc 
VLGabc n   a  b  . VLGabc m  2
 =    b  =  Z abc 
  abc n 
 I   c      abc m 
d I
 c  = Yabc  u  + Yabc  Z abc 
1
 4 
PI model of Distribution Lines or Cables
1
 a  =  d  = u  +  Z abc Yabc 
2
b =  Z abc 
c  = Yabc  u  + Yabc  Z abc 
1
 4 

VLGabc n =  a VLGabc m + b  I abc m


  a VLGabc m = VLGabc n − b  I abc m
VLGabc m =  a  VLGabc n −  a  b  I abc m
−1 −1

[ A] =  a 
−1

Therefore VLGabc m =  A .VLGabc n −  B  . I abc m  B  =  a  b 


−1
The Short Line Model of Distribution Lines or Cables

a = d =1
b=Z
c=0

1
 a  =  d  = u  +  Z abc Yabc   a  =  d  = u 
2
b =  Z abc  Ignoring shunt b =  Z abc 
c  = Yabc  1 + Yabc  Z abc 
1 susceptance
 4   c  =  0
Summary of The Lecture
Shunt admittance of overhead distribution lines
Impedance and Admittance of Underground Cables
Distribution system line models
PI Model
Short-line model

21
Lecture 13
Modeling of Single-Phase and
Three-Phase Transformers

1
Review of The Last Lecture: PI Model

1
 a  =  d  = u  +  Z abc Yabc 
VLGabc n   a  b   . VLGabc m  2
 =    b  =  Z abc 
  abc n 
 I   c      abc m 
d I
 c  = Yabc  1 + Yabc  Z abc 
1
 4 
Review of The Last Lecture: Short Line Model

1
 a  =  d  = u  +  Z abc Yabc   a  =  d  = u 
2
b =  Z abc  Ignoring shunt b =  Z abc 
c  = Yabc  1 + Yabc  Z abc 
1 susceptance
 4   c  =  0
Single-Phase Two-Winding Transformer
E1 N
nt = = 1
E2 N2

Vs   a b  VL 
I  =   
 s  c d   I 2 

VL = AVs − BI 2

VS = nt (VL + Z t I 2 ) = ntVL + nt Z t I 2
I2  1
I S = YmVS + I1 = ntYmVL + ntYm Z t I 2 + = ntYmVL +  ntYm Z t +  I 2
nt  nt 
Single-Phase Two-Winding Transformer

VS = ntVL + nt Z t I 2
 1
I S = ntYmVL +  ntYm Z t +  I 2
 nt 

1
at = nt bt = nt Z t VL = VS − Z t I 2
nt
 1
ct = ntYm d t =  ntYm Z t +  1
 nt  At = Bt = Z t
nt
The Two-Winding Autotransformer

N1
nt = N1
N2 N1 N2 n
nt _ new = = = t
N 2 + N1 1 + N1
1 + nt
N 2

at = nt bt = nt Z t at _ new = nt _ new bt _ new = nt _ new Z t


 1 1
ct = ntYm dt =  ntYm Z t +  ct _ new = nt _ newYm dt _ new =nt _ new Ym  Z t +
 nt  nt _ new
Representation of Voltages and Currents
Gr. Wye-Gr. Wye

T VLN ABC  VLN abc 


VAN VBN VCN IA IB I C  =   Van Vbn Vcn Ia Ib I c  T =  
 I ABC   I abc 

Delta-Delta

VLLABC  VLLabc 
VAB VBC VCA IA IB I C  T =   Vab Vbc Vca Ia Ib
T
I c  =  
 I ABC   I abc 
T
Winding Currents = IDAB IDBC IDCA  = [ IDABC ] Winding Currents = IDab IDbc
T
IDca  = [ IDabc ]
The Delta–Grounded Wye Connection

VAN VBN VCN IA IB I C  T Van Vbn Vcn Ia Ib I c  T

VLN ABC   at  bt   VLN abc 


= c
 I
 ABC   t   dt   I abc 
We would like to
derive VLN abc  =  At   VLN ABC  −  Bt    I abc 
Common Variable and Matrices
• Transformer turns ratio VLLRated HV
Delta-Star nt =
VHV VLN Rated LV
nt =
VLV VLN Rated HV
Star-Star nt =
VLN Rated LV

 Zta 0 0 
 Ztabc  = 0 Ztb 0 

 0 0 Ztc 

Common Variable and Matrices
VAG   nt 0 0  Vta 
V  =  0 n 0   Vt 
 BG   t   b
VCG   0 0 nt  Vtc 
VLGABC  =  AV Vtabc 

 I A  1 nt 0 0   I a   Ia 
 I  =  0 1 n 0   I  = AI  I 
 B  t   b    b 
 I C   0 0 1 nt   I c   I c 

 I ABC  =  AI  I abc 
Voltage Conversion: Line to Neutral -> Line to Line
VAB = VAN − VBN VAB   1 −1 0  VAN 
V  =  0 1 −1 V 
VBC = VBN − VCN  BC     BN 
VCA = VCN − VAN VCA   −1 0 1  VCN 

VLLABC  =  D   VLN ABC 


1 -1 0 
Where  D  = 
 0 1 -1


 -1 0 1

Voltage Conversion: Line to Line -> Line to Neutral
VAN  VAB 
V  = W V 
 BN     BC 
VLN ABC  = W VLLABC 
VCN  VCA 
−1
VLL _ 0  1 1 1 VAB 
VLL012  =  AS  VLLABC 
−1
  
 LL _1  = 1 as
V 2
as  V 
 BC 
VLL _ 2  1 as as2  VCA  Where as = 11200 and as2 = 12400
 
−1
VLN _ 0  1 1 1 VAN 
  
 VLN _1 =
  1 a 2
s as  V 
 BN  VLN 012  = [ AS ]−1 VLN ABC  VLN ABC  = [ AS ]VLN 012 
VLN _ 2  1 as as2  VCN 
 

12
Voltage Conversion: Line to Line -> Line to Neutral
Also
VLN _ 0  1 0 0  VLL _ 0  1 1
    V  Where ts = 300 and ts* =  − 300
V
 LN _1  = 0 t *
s 0   LL _1  3 3
VLN _ 2  0 0 ts  VLL _ 2 
   
VLN 012  = [T ]VLL012 

Positive Sequence Negative Sequence

13
Voltage Conversion: Line to Line -> Line to Neutral
VLL012  =  AS  VLLABC 
−1

VLN ABC  = [ AS ]VLN 012 


VLN ABC  =  AS [T ]VLL012 
VLN 012  = [T ]VLL012  VLN ABC  =  AS [T ][ AS ]−1 VLLABC 
VLN ABC  = W VLLABC 
−1
1 1 1  1 0 0  1 1 1 2 1 0 
W  = 1 as2 a  0 ts* 0  1 as2 a  = 0 2 1 
1
3 
1 a as2  0 0 ts  1 a as 
2
1 0 2 

1 1
Where as = 11200 , as2 = 12400 , ts = 300 and ts* =  − 300
3 3
14
Summary of the Lecture
Modeling of single-phase distribution transformer
Representation of voltages and currents in three-phase
distribution transformers
Voltage Conversion
1 -1 0 
Line to Neutral -> Line to Line [VLLABC ] = [ D ][VLN ABC ] where  D  = 0 1 -1
 -1 0 1

2 1 0
where W  = 0 2 1 
1
Line to Line -> Line to Neutral [VLN ABC ] = [W ][VLLABC ]
3
1 0 2 

15
Lecture 14
Modeling of Three-Phase
Transformers-Part I

1
Single-Phase Two-Winding Transformer

VS = ntVL + nt Z t I 2
 1
I S = ntYmVL +  ntYm Z t +  I 2
 nt 

1
at = nt bt = nt Z t VL = VS − Z t I 2
nt
 1
ct = ntYm d t =  ntYm Z t +  1
 nt  A= B = Zt
nt
Representation of Voltages and Currents
Gr. Wye-Gr. Wye

VAN VBN VCN IA IB I C  Van Vbn Vcn Ia Ib I c 

Delta-Delta

VAB VBC VCA I A I B I C 


Vab Vbc Vca I a I b I c 
IDABC  = I AB I BC I CA 
IDabc  = I ab I bc I ca 
Common Variable and Matrices
• Transformer turns ratio VLLRated HV
Delta-Star nt =
VHV VLN Rated LV
nt =
VLV VLN Rated HV
Star-Star nt =
VLN Rated LV

 Zta 0 0 
 Ztabc  = 0 Ztb 0 

 0 0 Ztc 

VLGABC  =  AV Vtabc 

 I ABC  =  AI  I abc 
Voltage Conversion
Line to Neutral -> Line to Line
1 -1 0 
VLLABC  =  D VLN ABC  Where  D  = 0 1 -1
 -1 0 1

Line to Line -> Line to Neutral


2 1 0
W  = 0 2 1 
1
VLN ABC  = W VLLABC  Where
3
1 0 2 
Current Conversion: Delta Phase Currents -> Line Currents
 I A  1 0 -1  I AB 
 I  =  -1 1 0   I 
 B    BC 
 I C   0 -1 1  I CA 

 I ABC  =  K  IDABC 
1 0 -1
where  K  = -1 1 0 
0 -1 1 
Current Conversion: Line Currents -> Delta Phase Currents
−1
• Case-1  I a   1 0 −1  I ba   I ba   1 0 −1  I a 
 I  =  −1 1 0   I    I cb  =  −1 1 0   I b 
 b    cb 
0   1 1 1   I ac   I ac   1 1 1   0 

Therefore
 I ba  1 -1 1   Ia 
I  =  1 1
2 1    I b 
 cb  3 
 I ac   -2 -1 1   0 

It can also be written as


 I ba  1 -1 0   Ia 
I  = 1  1 2 0   I b 
 cb  3 
 I ac   −2 -1 0   I c   IDabc  =  L   I abc 
Current Conversion: Line Currents -> Delta Phase Currents
• Case-2
Current Conversion: Line Currents -> Delta Phase Currents
I a = I ba − I ac
• Case-2 I b = I cb − I ba
Applying KVL to secondary side delta

Vtab − Ztab  I ba + Vtbc − Ztbc  I cb + Vtca − Ztca  I ac = 0

Vtab + Vtbc + Vtca = Ztab  I ba + Ztbc  I cb + Ztca  I ac

VAB VBC VCA


+ + = Ztab  I ba + Ztbc  I cb + Ztca  I ac
nt nt nt

0 = Ztab  I ba + Ztbc  I cb + Ztca  I ac


Current Conversion: Line Currents -> Delta Phase Currents
I a = I ba − I ac
• Case-2
I b = I cb − I ba
0 = Ztab  Iba + Ztbc  I cb + Ztca  I ac
In matrix form
 I a  1 0 -1   I ba 
 I  =  -1 1 0   I cb 
 b 
 0   Ztab Ztbc Ztca   I ac 

Therefore
−1
 I ba  1 0 -1   Ia 
 I  = -1 1 0  I 
 cb    b
 I ac   Ztab Ztbc Ztca   0 
Current Conversion: Line Currents -> Delta Phase Currents
−1
• Case-2  I ba  1 0 -1   I a 
 I  = -1 1 0   I 
  cb   b
 I ac   Ztab Ztbc Ztca   0 
Therefore
 I ba   Ztca -Ztbc 1  I a 
I  = 1  Zt Ztab + Ztca 1  I b 
  Zt + Zt + Zt
cb  ca

 I ac  ab bc ca
 − Ztab − Ztbc -Ztbc 1  0 

Setting the last column of the matrix to zeros


 I ba   Ztca -Ztbc 0  Ia 
I  = 1  Zt Ztab + Ztca 0   I b 
  Zt + Zt + Zt
cb  ca

 I ac  ab bc ca
 − Ztab − Ztbc -Ztbc 0   I c 
Current Conversion: Line Currents -> Delta Phase Currents
• Case-2  I ba   Ztca -Ztbc 0   Ia 
I  = 1  Zt Ztab + Ztca 0   I b 
  Zt + Zt + Zt
cb  ca

 I ac  ab bc ca
 − Ztab − Ztbc -Ztbc 0   I c 

In matrix form
 IDabc  =  M  I abc 

Where
 Ztca -Ztbc 0
1  Zt 0 
M  = Ztab + Ztca
Ztab + Ztbc + Ztca 
ca

 − Ztab − Ztbc -Ztbc 0 


Current Conversion: Line Currents -> Delta Phase Currents
• Case-2  IDabc  =  M  I abc 

 Ztca -Ztbc 0
1  Zt 0 
M  = Ztab + Ztca
Ztab + Ztbc + Ztca 
ca

 − Ztab − Ztbc -Ztbc 0 

If the three transformers have equal impedances

 I ba  1 -1 0  I a 
 I  = 1 1 2 0   I b 
 cb  3 
 I ac   -2 -1 0   I c 

 IDabc  =  L    I abc 
Summary: Voltage Conversion
Line to Neutral -> Line to Line
1 -1 0 
VLLABC  =  DVLN ABC  Where  D  = 0 1 -1
-1 0 1

Line to Line -> Line to Neutral


2 1 0
W  = 0 2 1 
1
VLN ABC  = W VLLABC  Where
3
1 0 2 
Summary: Current Conversion
Delta Phase Currents -> Line Currents 1 0 -1
 I abc  =  K  IDabc  Where  K  = -1 1 0 
 0 -1 1 
Line Currents -> Delta Phase Currents
• Path for zero sequence is not available in transformer
1 -1 0
1
 IDabc  =  L  I abc  Where  L =  1 2 0 
3
 −2 -1 0 
• Path for zero sequence current is available in transformer
 Ztca -Ztbc 0
 IDabc  =  M  I abc  1  Zt 0 
Where M  = Ztab + Ztca
Ztab + Ztbc + Ztca 
ca

 − Ztab − Ztbc -Ztbc 0 


Lecture 15
Modeling of Three-Phase
Transformers – Part II

1
Representation of Voltages and Currents
Gr. Wye-Gr. Wye

VAN VBN VCN IA IB I C  Van Vbn Vcn Ia Ib I c 

Delta-Delta

VAB VBC VCA I A I B I C 


Vab Vbc Vca I a I b I c 
IDABC  = I AB I BC I CA 
IDabc  = I ab I bc I ca 
The Delta–Grounded Wye Connection

VAN VBN VCN IA IB I C  T Van Vbn Vcn Ia Ib I c  T

VLN ABC   at  bt   VLN abc 


= c
 I
 ABC   t   dt   I abc 
We would like to
derive VLN abc  =  At   VLN ABC  −  Bt    I abc 
Common Variable and Matrices
• Transformer turns ratio VLLRated HV
Delta-Star nt =
VHV VLN Rated LV
nt =
VLV VLN Rated HV
Star-Star nt =
VLN Rated LV

 Zta 0 0 
 Ztabc  = 0 Ztb 0 

 0 0 Ztc 

VLGABC  =  AV Vtabc 

 I ABC  =  AI  I abc 
Summary: Voltage Conversion
Line to Neutral -> Line to Line
1 -1 0 
VLLABC  =  D VLN ABC  Where  D  = 0 1 -1
 -1 0 1

Line to Line -> Line to Neutral


2 1 0
W  = 0 2 1 
1
VLN ABC  = W VLLABC  Where
3
1 0 2 
Summary: Current Conversion
Delta Phase Currents -> Line Currents 1 0 -1
 I abc  =  K  IDabc  Where  K  = -1 1 0 
 0 -1 1 
Line Currents -> Delta Phase Currents
• Path for zero sequence is not available in transformer
1 -1 0
1
 IDabc  =  L   I abc  Where  L =  1 2 0 
3
 −2 -1 0 
• Path for zero sequence current is available in transformer
 Ztca -Ztbc 0
 IDabc  =  M  I abc  1  Zt 0 
Where M  = Ztab + Ztca
Ztab + Ztbc + Ztca 
ca

 − Ztab − Ztbc -Ztbc 0 


The Grounded Wye–Grounded Wye Connection
The Grounded Wye–Grounded Wye Connection
Vtabc  = VLGabc  +  Ztabc    I abc 
Also,
VAG   nt 0 0  Vta 
V  =  0 n 0   Vt 
 BG   t   b
VCG   0 0 nt  Vtc 

VLGABC  =  AV   Vtabc 
Thus,
VLGABC  =  AV   VLGabc  +  Ztabc    I abc 

VLGABC  =  AV   VLGabc  +  AV    Ztabc    I abc 


The Grounded Wye–Grounded Wye Connection

VLGABC  =  AV   VLGabc  +  AV    Ztabc    I abc 

Where
 nt 0 0
 at  =  AV  = 0 nt 0 
0 0 nt 

 nt  Zt a 0 0 
 nt  Zt b 0 
bt  =  AV    Ztabc  = 0
0 0 nt  Ztc 
The Grounded Wye–Grounded Wye Connection
 I ABC  =  AI  I abc 
Comparing with
 I ABC  = Ct   VLGabc  +  dt    I abc 
0 0 0
 ct  = 0 0 0
 and

0 0 0

1 
 0 0 
 nt 
 1 
 dt  = [ AI ] = 0 0 
 nt 
 1
0 0 
 nt 
The Grounded Wye–Grounded Wye Connection

VLGABC  =  AV   VLGabc  +  AV    Ztabc    I abc 


Can be written as
VLGabc  =  AV   VLGABC  −  Ztabc    I abc 
−1

1 
 0 0
 nt   Zta 0 0
   0 
1
 At  =  AV   Bt  = 0 Ztb
−1
= 0 0 
 nt   0 0 Ztc 
 1
0 0 
 nt 
The Delta–Grounded Wye Connection
The Delta–Grounded Wye Connection
Vtabc  = VLGabc  +  Ztabc    I abc 

VLLABC  =  AV   Vtabc 

W   VLLABC  = W  AV   VLGabc  +  Ztabc    I abc 


VLN ABC  = W  AV VLGabc  + W  AV  Ztabc    I abc 
Comparing with
VLN ABC  =  at VLGabc  + bt    I abc 
VLLRated High Side
nt =
VLN Rated Low Side
The Delta–Grounded Wye Connection

2 1 0   nt 0 0 2 1 0
1   0 0  = t  0
1
1 
n
at  = W  AV  =  0 2 nt 2
3 3
 1 0 2   0 0 nt   1 0 2 

and

 2 1 0   Zta 0 0   2 Zta Ztb 0 


0 2 1   0 0  = t  0 Ztc 
nt  n
bt  = W  AV  Ztabc  =  Ztb 2 Ztb
3 3
 1 0 2   0 0 Ztc   Zta 0 2 Ztc 
The Delta–Grounded Wye Connection
 IDABC  =  AI  I abc 

and I ABC = [ K ][ IDABC ]


I ABC = [ K ][ AI ][ I abc ]

Comparing with
 I ABC  =  ct VLN abc  +  dt  I abc 

0 0 0  1 0 −1 1 nt 0 0  1 0 −1
ct  = 0 0 0   d t  = [ K ][ AI ] =  −1 1 0   0 0  =  −1 1 0
1
1 nt
nt  
0 0 0   0 −1 1   0 0 1 nt   0 −1 1 
The Delta–Grounded Wye Connection

1 
 nt 0 0
VLN ABC  = W  AV VLN abc  + W  AV  Ztabc    I abc    1 -1 0 
0 1 -1
 At  =  AV   D  =  0 0
−1 1
nt   
   -1 0 1
Therefore 0 1
0
W  AV VLN abc  = VLN ABC  − W  AV  Ztabc    I abc   nt 
1 -1 0 
VLN abc  =  AV  W  VLN ABC  −  Ztabc    I abc 
−1 −1
=  0 1 -1
1 
nt
VLN abc  =  AV   D VLN ABC  −  Ztabc    I abc 
−1  -1 0 1

Comparing with  Zta 0 0


 0 
VLN abc  =  At VLN ABC  −  Bt    I abc   Bt  = 0 Ztb
 0 0 Ztc 
Summary of the Lecture

• Three-phase transformer models


• Transformation Matrices
• Grounded Wye/Grounded Wye
• Delta /Grounded Wye
Lecture 16
Modeling of Three-Phase
Transformers – Part III

1
Review of the Transformer Modeling
1 -1 0 
[VLLABC ] = [ D ][VLN ABC ] where  D  = 0 1 -1
 -1 0 1
2 1 0
1
[VLN ABC ] = [W ][VLLABC ] where W  = 0 2 1 
3
1 0 2 
1 0 -1
[ I ABC ] = [ K ][ IDABC ] where  K  = -1 1 0 
 0 -1 1 

[ IDABC ] = [ L][ I ABC ]


Or [ IDABC ] = [ M ][ I ABC ]
1 -1 0  Ztca -Ztbc 0
1
 L =  1 0  and  M  =  Zt 0 
Where 1
2
 Ztab + Ztca
Ztab + Ztbc + Ztca
ca
3
 −2 -1 0   − Ztab − Ztbc -Ztbc 0 

2
Summary of the Last Lecture
• Three-phase transformer models
VLN ABC  =  at VLN abc  + bt  I abc 
 I ABC  = ct VLN abc  +  dt  I abc 
• Grounded Wye/Grounded Wye (Yg yg0)
VLGABC  =  AV VLGabc  +  AV  Ztabc  I abc  VLGABC  = nt u VLGabc  + nt Zt u  I abc 
 I ABC  =  AI  I abc  1
 I ABC  = u  I abc 
nt
Summary of the Last Lecture
• Three-phase transformer models 2 1 0 1 0 -1
VLN ABC  =  at VLN abc  + bt  I abc  1
W  = 0 2 1  and  K  = -1 1 0 
3
 I ABC  = ct VLN abc  +  dt  I abc  1 0 2   0 -1 1 

• Delta /Grounded Wye (D yg11)


VLN ABC  = W  AV VLGabc  + W  AV  Ztabc    I abc  VLN ABC  = nt W VLGabc  + nt Zt W  I abc 
 I ABC  = [ K ][ AI ][ I abc ] 1
 I ABC  = [ K ][ I abc ]
nt
The Ungrounded Wye–Delta Connection (Yd1)
The Ungrounded Wye–Delta Connection (Yd1)
Vtabc  = VLLabc  +  Ztabc  IDabc  1
VLN ABC  =  AV Vtabc  2


VLN ABC  =  AV  VLLabc  + Ztabc  IDabc 
=  AV  VLLabc  +  AV  Ztabc  IDabc 

VLN ABC  =  AV  D  VLN abc  +  AV  Ztabc   L  I abc 

VLN ABC  =  at VLN abc  + bt  I abc 


The Ungrounded Wye–Delta Connection (Yd1)
VLN ABC  =  AV  D VLN abc  +  AV Ztabc   L I abc 

 nt 0 0   1 −1 0   1 −1 0 
   
0   0 1 −1 = nt  0 1 −1
at  =  AV  D  =  0 nt
 0 0 nt   −1 0 1   −1 0 1 

 nt 0 0   Ztab 0 0   1 −1 0 
 0   0 0    1 2 0 
1
bt  =  AV Ztabc  L  =  0 nt Ztbc
3
 0 0 nt   0 0 Ztca   −2 −1 0 
The Ungrounded Wye–Delta Connection (Yd1)
The Ungrounded Wye–Delta Connection (Yd1)
 I ABC  =  AI   IDabc 
=  AI [ L]I abc 

0 0 0 
 ct  = 0 0 0  and
 0 0 0 

1 nt 0 0  1 −1 0
 0    1
1
0 
dt  =  0 1 nt 2
3
 0 0 1 nt   −2 −1 0 

 I ABC  =  ct VLN abc  +  dt  I abc 


The Ungrounded Wye–Delta Connection (Yd1)
VLN ABC  =  AV  D VLN abc  +  AV Ztabc   L I abc 

VLN abc  =  At 
VLN ABC  −  Bt 
 I abc 
The Ungrounded Wye–Delta Connection (Yd1)
−1
 2 1 0   nt 0 0
=  0 2 1   0 0 
1
 At  = W  AV 
−1
nt 
3
 1 0 2   0 0 nt 

 2 1 0   Ztab 0 0  1 −1 0 
1  0    1
1
2 0 
 Bt  = W  Ztabc  L  =  0 2 1   0 Ztbc
3 3
 1 0 2   0 0 Ztca   −2 −1 0 
The Delta-Delta Connection (Dd0)
The Delta-Delta Connection (Dd0)
VLLABC  =  AV   Vtabc  1
Vtabc  = VLLabc  +  Ztabc    IDabc  2


VLLABC  =  AV  VLLabc  + Ztabc   IDabc  
VLLABC  =  AV  VLLabc  +  AV  Ztabc  IDabc 

W VLLABC  = W  AV VLLabc  + W  AV Ztabc  IDabc 

VLN ABC  = W  AV  VLLabc  + W  AV  Ztabc   IDabc 


VLLRated High Side
nt = VLN ABC  = W  AV  D  VLN abc  + W  AV Ztabc  M I abc 
VLLRated Low Side
The Delta-Delta Connection (Dd0)

 2 1 0   nt 0 0  1 -1 0 
at = W  AV  D  = 0 2 1   0 0  0 1 -1
1
nt
3
1 0 2   0 0 nt  -1 0 1

 2 1 0   nt 0 0   Ztab 0 0   Ztca -Ztbc 0


 
bt = W  AV   Ztabc   M  = 0 2 1   0 0   0 0  
1 1
nt Ztab  Ztca Ztab + Ztca 0
3 Ztab + Ztbc + Ztca
1 0 2   0 0 nt   0 0 Ztab   − Ztab − Ztbc -Ztbc 0 

If Ztab = Ztbc = Ztca = Zt


  2 1 0    1 -1 0 
1   1  
bt = W  AV   Ztabc   M  = nt Zt  0 2 1    -1 2 0  
 3 1 0 2    3  −2 − 1 0  
     

14
The Delta-Delta Connection (Dd0)

15
The Delta-Delta Connection (Dd0)
 IDABC  =  AI  IDabc 
 K  IDABC  =  AI  K  IDabc 
 I ABC  =  AI  I abc 

0 0 0  1/ nt 0 0 
ct = 0 0 0  and  dt  =  0 1/ nt 0 
0 0 0   0 0 1/ nt 
 I ABC  = ct   VLN abc  +  dt    I abc 
The Delta-Delta Connection (Dd0)

VLN ABC  = W  AV  D  VLN abc  + W  AV Ztabc  M I abc 

W  AV  D VLN abc  = VLN ABC  − W  AV Ztabc  M I abc 


VLN abc  =  D   AV  W  VLN ABC  −  D  Ztabc  M  I abc 
−1 −1 −1 −1

VLN abc  = W   AV   D  VLN ABC  − W  Ztabc   M  I abc 


−1

At Bt
The Delta-Delta Connection (Dd0)
VLN abc  = W   AV   D  VLN ABC  − W  Ztabc   M  I abc 
−1

At Bt
 2 -1 -1 Bt = Zt W  L 
1  
At = -1 2 -1
3nt  
-1 -1 2 

1 -1 0  2 1 0 1 -1 0  Ztca -Ztbc 0
 Zt 0 
W  = 0 2 1 
1 1
0 
1
 D  = 0 1 -1  L =  1 2 M  = Ztab + Ztca
Ztab + Ztbc + Ztca 
ca
3 3  − Ztab − Ztbc
 -1 0 1 1 0 2   −2 -1 0  -Ztbc 0 
Summary of the Lecture

• Three-phase transformer models


• Un-Grounded Wye-Delta (Yd1)
• Delta-Delta (Dd0)
Lecture 17
Modeling of Three-Phase
Transformers – Part IV

1
Review of the Last Lecture
• Three-phase transformer models 2 1 0 1 0 -1
VLN ABC  =  at VLN abc  + bt  I abc  1
W  = 0 2 1  and  K  = -1 1 0 
3
 I ABC  = ct VLN abc  +  dt  I abc  1 0 2   0 -1 1 

• Grounded Wye/Grounded Wye (Yg yg0)


VLGABC  =  AV VLGabc  +  AV  Ztabc  I abc  VLGABC  = nt u VLGabc  + nt Zt u  I abc 
 I ABC  =  AI  I abc  1
 I ABC  = u  I abc 
nt

• Delta /Grounded Wye (D yg11)


VLN ABC  = W  AV VLGabc  + W  AV  Ztabc    I abc  VLN ABC  = nt W VLGabc  + nt Zt W  I abc 
1
 I ABC  = [ K ][ AI ][ I abc ]  I ABC  = [ K ][ I abc ]
nt
Review of the Last Lecture
• Un-Grounded Wye/Delta (Y d1)
VLN ABC  = nt  D VLN abc  + nt Z t  L I abc 
VLN ABC  =  AV  D VLN abc  +  AV Ztabc   L I abc 
1
 I ABC  =  AI [ L] I abc   I ABC  = [ L] I abc 
nt
• Delta /Delta (Dd0)
VLN ABC  = W  AV  D  VLN abc  VLN ABC  = nt W  D  VLN abc 
+ W  AV  Ztabc  M  I abc  + nt Z t W  L  I abc 

 I ABC  =  AI  I abc 
1
 I ABC  = u  I abc 
nt

1 -1 0  2 1 0 1 -1 0  Ztca -Ztbc 0
1  Zt 0 
W  = 0 2 1  0 
1 1
 D  = 0 1 -1  L =  1 2 M  = Ztab + Ztca
Ztab + Ztbc + Ztca 
ca
3 3  − Ztab − Ztbc
 -1 0 1 1 0 2   −2 -1 0  -Ztbc 0 
Review of the Last Lecture

at bt ct dt

nt u   0 1
Yg yg0 nt Zt u  u 
nt

1
D yg11 nt W  nt Zt W   0 nt
[K ]

1
Y d1 nt  D  nt Z t  L   0 nt
[ L]

1
Dd0 nt W  D  + nt Z t W  L   0 u 
nt

4
Example
3-phase, 200kVA, 11 kV / 433 V, 50 Hz kVLLHV = 11 kV
Connection HV->Delta kVLN LV = 0.433 3 kV
Connection LV-> Star (Neutral brought out) kVA = 200 kVA
Vector group-> Dyn-11
kVLLHV
The percentage impedance 4 87 0 % (at 750 C) nt = = 44.0
kVLN LV

Z PU = 0.0021 + 0.0399i
kVLL2
Z base = = 0.9374
MVA
Z t = Z PU  Z base
= 0.0020 + 0.0374i

5
Example
0.0020 + 0.0374i 0 0
2 1 0
W  = 0 2 1 
Ztabc = 0 0.0020 + 0.0374i 0 1
0 0 0.0020 + 0.0374i 3
1 0 2 
29.3342 14.6671 0
at = nt W  = 0 29.3342 14.6671
1 0 -1
14.6671 0 29.3342
 K  = -1 1 0 
0.0576 + 1.0985i 0.0288 + 0.5492i 0 0 -1 1 
bt = nt Zt W  = 0 0.0576 + 1.0985i 0.0288 + 0.5492i
0.0288 + 0.5492i 0 0.0576 + 1.0985i
0.0227 0 -0.0227
0 0 0 1
ct = dt = [ K ] = -0.0227 0.0227 0
0 0 0 nt 0 -0.0227 0.0227
0 0 0
Open Wye–Open Delta Connection
Vtab = Vab + Ztab I a
Vtbc = Vbc − Ztbc I c
Also
VAG   nt 0 0  Vtab 
V  =  0 nt 0  Vtbc 
 BG  
VCG   0 0 0  Vtca 

VLGABC  =  AV Vtabc 

VAG = nt Vtab = nt Vab + nt Ztab I a


VBG = nt Vtbc = nt Vbc − nt Ztbc I c
Open Wye–Open Delta Connection
VAG = nt Vab + nt Ztab I a
VBG = nt Vbc − nt Ztbc I c
Writing them in matrix form
VAG   nt 0 0  Vab   nt Ztab 0 0  Ia 
V  =  0 nt 0  Vbc  +  0 0 -nt Ztbc   I b 
 BG  
VCG   0 0 0  Vca   0 0 0   I c 

VLGABC  =  AV   VLLabc  + bt    I abc 


VLGABC  =  AV    D   VLN abc  + bt    I abc 

at bt
Open Wye–Open Delta Connection
1 
n 0 0
I A   t  Ia 
 I  = 0 0
1  
-   Ib 
 B  nt
 I C     Ic 
 
0 0 0
 
 

 I ABC  =  dt    I abc 

 I ABC  =  ct   VLN abc  +  dt    I abc 


Open Wye–Open Delta Connection
1
Vab =  VAG − Ztab  I a
VAG = nt Vab + nt Ztab I a nt
VBG = nt Vbc − nt Ztbc I c Vbc =
1
 VBG + Ztbc  I c
nt

1 
 0 0
Vab   nt  VAG   Ztab 0 0  Ia 
V   
0   VBG  −  0 -Ztab    I b 
1
 bc  = 0 0
 nt  V   − Zt 0
Vca  Ztab   I c 
 1 1   CG   ab

- - 0
 nt nt 

VLLabc  =  BV   VLGABC  −  Ztabc    I abc 


Open Wye–Open Delta Connection

VLLabc  =  BV   VLGABC  −  Ztabc    I abc 

W VLLabc  = W  BV   VLGABC  − W    Ztabc    I abc 

VLN abc  =  At   VLGABC  −  Bt    I abc 


The Thevenin’s Equivalent Circuit
The Thevenin’s Equivalent Circuit

VLN ABC  =  ELN ABC  −  Zsys ABC  I ABC 

Where  I ABC  =  dt  I abc 

VLN ABC  =  ELN ABC  −  Zsys ABC  dt  I abc 


Also VLN abc  =  At VLN ABC  −  Bt  I abc 
VLN abc  =  At  ELN ABC  −  Zsys ABC  dt  I abc  −  Bt  I abc 
The Thevenin’s Equivalent Circuit

VLN abc  =  At  ELN ABC  −  Zsys ABC  dt  I abc  −  Bt  I abc 


VLN abc  =  At   ELN ABC  −  At  Zsys ABC  d t   I abc  −  Bt   I abc 

   
VLN abc  =  At   ELN ABC  −  At  Zsys ABC  d t  +  Bt   I abc 

 =
VLN abc  − 
 Ethabc  Zthabc 
 I abc 

Summary of the Lecture
• Summary of three-phase transformer model
• Example of 11 / 0.433 kV
• Three-phase transformer models
• Open Wye/Open Delta
• The Thevenin’s equivalent circuit

15
Lecture 18
Modeling of Step Voltage
Regulators - Part I

1
Review of the Transformer Modeling
Modeling of Transformers
• Single-phase transformer models
• Transformation Matrices
• Three-phase transformer models
• Grounded Wye/Grounded Wye
• Delta /Grounded Wye
• Un-Grounded Wye/Delta
• Delta/Delta
• Open Wye/Open Delta

2
Voltage Regulation

3
Causes of under-voltage and over-voltage
Improper or less-efficient equipment operation

Tripping of sensitive loads

Equipment damage or failure

High no-load losses in transformer

Overheating or burning of induction motor

4
Voltage Regulation Techniques

On-Load Tap Changing (OLTC) Transformer


Bus Step-voltage Regulator
Voltage Booster
Feeder Voltage Regulators (Induction Regulator)
Fixed and Switched Capacitor

5
Step-Voltage Regulator
• Voltage level: The desired voltage to be maintained at the load center.
• Bandwidth: The allowed variance of voltage at load center from set
voltage level.
• Time delay: Time between tap change operation ‘called for’ and actual
execution of command.

6
Types of Step-voltage Regulator
A step-voltage regulator consists of an auto-transformer and a load tap-changing
mechanism.
A-Type Regulator

7
Types of Step-voltage Regulator
B-Type Regulator

8
Types of Step-voltage Regulator
B-Type Regulator

9
Summary of The Lecture
Voltage regulation
Effects of under and over-voltage in distribution system
Various techniques of the voltage control
Single phase regulators
Type-A
Type-B

10
Lecture 19
Modeling of Step Voltage
Regulators – Part II

1
Review of The Last Lecture
Voltage regulation
Effects of under and over-voltage in distribution system
Various techniques of the voltage control
Single phase regulators
Type-A
Type-B

2
Step-voltage Regulator

Type –A Type – B
Source: W. H. Kresting, Distribution System Modeling and Analysis, CRC
3
Press, New York, 2002.
B-Type Regulator (Raise)

Source: W. H. Kresting, Distribution System Modeling and Analysis, CRC


4
Press, New York, 2002.
B-Type Regulator (Lower)

Source: W. H. Kresting, Distribution System Modeling and Analysis, CRC


5
Press, New York, 2002.
Transformation of Current and Voltages

6
The Line Drop Compensator

7
The Line Drop Compensator

8
Three-Phase Regulator: Wye Connected

9
Summary of the Lecture
• Line drop compensator
• Modeling of three-phase voltage regulators
– Wye connected
– Closed delta connected

10
Lecture 20
Modeling of Step Voltage
Regulators – Part III

1
Summary of the Lecture
• Line drop compensator
• Modeling of three-phase voltage regulators
– Wye connected

2
Three-Phase Regulator: Closed Delta Connected

3
Three-Phase Regulator: Closed Delta Connected

4
Three-Phase Regulator: Closed Delta Connected

5
Three-Phase Regulator: Closed Delta Connected

6
Open Delta Connected Regulator

7
Open Delta Connected Regulator

8
Open Delta Connected Regulator

9
Open Delta Connected Regulator

10
Summary of the Lecture
• Modeling of three-phase voltage regulators

– Closed Delta Connected

– Open delta connected

11
Lecture 21
Modeling of Step Voltage
Regulators – Part IV

1
Review of the Last Lecture
• Modeling of three-phase voltage regulators
– Closed Delta connected
– Open delta connected

2
Example-01
6300
N PT = = 52.5
120
CTP = 200 A
CTS = 5 A
I = 150 − 25 A
120 − 115.37
VLC = VL − Z I T ap = = 6.17  Tap = 6
0.75
= 6057.2 -20 V aR = 1 − 0.00625  6
= 0.9625
6057.2  − 2
VLC _120V = = 115.37 − 20 VS
52.5 VL _ new = = 6545.5 V
ar

3
Example-01
6300
N PT = = 52.5
120
CTP = 200 A
CTS = 5 A
I = 150 − 25 A

VLC _ new = VL _ new − Z I CTP 200


Rc + jX c = Z  = ( 0.867 + j1.98 ) 
= 6302.5 -1.910 V N PT CTS 52.5  5
= 0.6606 + 1.5086i

4
Example-02
Ia = 308.200  - 58.00
Ib = 264.200  -176.10
Ic = 297.000  70.30

VS ab = 11000  0.00 N PT = 11000/120 = 91.67


VSbc = 11000  -120.00 CTP = 500
VSca = 11000  120.00 CTS = 5

VLCab = 10506.693  -1.40 VLCab _120 = 114.621  -1.40


VLCbc = 10688.406  -122.30 VLCbc _120 = 116.603  -122.30
VLCca = 10460.824  117.30 VLCca _120 = 114.120  117.30

5
Example-02
Ia = 308.200  - 58.00
Ib = 264.200  -176.10
Ic = 297.000  70.30

VS ab = 11000  0.00
VSbc = 11000  -120.00
VSca = 11000  120.00 Zeqab = 0.1469 + j1.8068
Zeqcb = 1.3183 + j1.2283
VLCab = 10506.693  -1.40
VLCbc = 10688.406  -122.30 ZCab = 0.1602 + j1.9711
VLCca = 10460.824  117.30 ZCcb = 1.4382 + j1.3400

6
Example-02
N PT = 11000/120 = 91.67
CTP = 500
CTS = 5
ZCab = 0.1602 + j1.9711
ZCcb = 1.4382 + j1.3400
VS ab = 11000.000  0.00
VSbc = 11000.000  -120.00
VSca = 11000.000  120.00
VLCab = 10506.693  -1.40
VLCbc = 10688.406  -122.30 Vrelay ab = 114.621  -1.40
VLCca = 10460.824  117.30 Vrelay cb = 116.603  57.70
Ia = 308.200  - 58.00
Tap_ab =7.1724  Tap_ab = 7
Ib = 264.200  -176.10
Ic = 297.000  70.30 Tap_cb =4.5293  Tap_cb = 5

7
Summary of the Lecture
• Example

– Single-phase regulator modeling

– Three-phase regulator modeling (Open Delta)

8
Lecture 22
Load Models in Distribution
System - Part I

1
Summary of the Step Voltage Regulator Modeling
Voltage regulation and effects of under- and over-voltage on distribution
system components
Various techniques of the voltage control in distribution system
Single phase regulators: Type-A and Type-B
Line drop compensator
Three-phase regulator: Wye connected, closed-delta connected, open-delta
connected
Few examples

2
Load Models
Constant real and reactive power (constant PQ)
Induction motors, air conditioners, etc.
Constant Impedance (Z)
Incandescent lighting, resistive water heating, cooking
loads (stove and oven with resistive heating coils) , etc.
Constant current (I)
Welding, smelting, electroplating operation, etc.
Combination or mix type
Polynomial (ZIP)
Exponential (EXP)

3
Constant Real and Reactive (PQ) Loads

4
Constant Real and Reactive (PQ) Loads

5
Constant Impedance (Z) Loads

6
Constant Current (I) Loads

7
Polynomial Load (ZIP) Models

8
Exponential Load (EXP) Models

9
Effect of Load Models

Source: J.C. Das, Power System Analysis: Short-Circuit, Load Flow and Harmonics, 10
Second Edition, CRC Press, Boca Raton, 2012
Summary of the Lecture
Constant real and reactive power (constant PQ)
Induction motors, air conditioners, etc.
Constant Impedance (Z)
Incandescent lighting, resistive water heating, cooking loads (stove and oven
with resistive heating coils) , etc.
Constant current (I)
Welding, smelting, electroplating operation, etc.
Combination or mix type
Polynomial (ZIP)
Exponential (EXP)

11
Lecture 23
Load Models in Distribution
System - Part-II

1
Review of the Last Lecture
Constant real and reactive power (constant PQ)
Induction motors, air conditioners, etc.
Constant Impedance (Z)
Incandescent lighting, resistive water heating, cooking loads (stove and
oven with resistive heating coils) , etc.
Constant current (I)
Welding, smelting, electroplating operation, etc.
Combination or mix type
Polynomial (ZIP)
Exponential (EXP)

2
Three-Phase Induction Motor Model

3
Three-Phase Induction Motor Model

4
Three-Phase Induction Motor Model

5
Example: Constant Power
Nominal Voltages
Van 0 = 6350.85  0.00
Vbn 0 = 6350.85  -120.00
Vcn 0 = 6350.85  120.00
Load =1MW with 0.9 pf lagging

Voltage Set:01
Van = 6350.85  0.00 ILa = 157.46  - 25.84
Vbn = 6350.85  -120.00 ILb = 157.46  -145.84
Vcn = 6350.85  120.00 ILc = 157.46  94.16

6
Example: Constant Power
Nominal Voltages
Van 0 = 6350.85  0.00
Vbn 0 = 6350.85  -120.00
Vcn 0 = 6350.85  120.00
Load =1 MW with 0.9 pf lagging

Van = 6350.85  0.00 ILa = 157.46  - 25.84


Vbn = 6639.53  -120.00 ILb = 150.61  -145.84
Vcn = 6062.18  120.00 ILc = 164.96  94.16

7
Example: Constant Impedance
Nominal Voltages Actual Voltage
Van 0 = 6350.85  0.00 Van = 6350.85  0.00
Vbn 0 = 6350.85  -120.00 Vbn = 6639.53  -120.00
Vcn 0 = 6350.85  120.00 Vcn = 6062.18  120.00
Load =1MW with 0.9 pf lagging

2
Van 0 Van
Za = *
= 36.30 + j17.58 ILa = = 157.46  - 25.84
S a Za
2
Vbn 0 Vbn
Zb = = 36.30 + j17.58 ILb = = 164.62  -145.84
Sb* Zb
2
Vcn 0 Vcn
Zc = *
= 36.30 + j17.58 ILc = = 150.30  94.16
S c Zc

8
Example: Constant Current
Actual Voltage
Nominal Voltages
Van = 6350.85  0.00
Van 0 = 6350.85  0.00
Vbn = 6639.53  -130.00
Vbn 0 = 6350.85  -120.00
Vcn = 6062.18  110.00
Vcn 0 = 6350.85  120.00
Load =1MW with 0.9 pf lagging

Sa
ILa = = 157.46 ILa = 157.46  - 25.84
Van 0
Sb
ILb = = 157.46 ILb = 157.46  -155.84
Vbn 0
Sc
ILc = = 157.46 ILc = 157.46  84.21
Vcn 0

9
Example: Mix Load
Nominal Voltages
Actual Voltage
Van 0 = 6350.85  0.00
Van = 6350.85  0.00
Vbn 0 = 6350.85  -120.00
Vbn = 6639.53  -120.00
Vcn 0 = 6350.85  120.00
Vcn = 6062.18  120.00
Load =1MW with 0.9 pf lagging
60% constant Power, %25 Constant Current and
15% constant impedance

S a = 1.0  25.84 MW ILa = 157.46  - 25.84


Sb = 1.025  25.84 MW ILb = 154.43  -145.84
Sc = 0.97  25.84 MW ILc = 160.88  94.16

10
Summary of the Lecture
• Three-phase induction motor model
• Example: Load modeling

11
Lecture 24
Modeling of Distributed
Generation

1
Review of the Load Modeling
Constant real and reactive power (constant PQ)
Constant Impedance (Z)
Constant current (I)
Combination or mix type
Polynomial (ZIP)
Exponential (EXP)
Induction Motor Model
Examples of various load models and effect of voltage variation on load
currents

2
Distributed Generation
• Small-scale generation connected to the distribution grid is commonly referred as
Distributed Generation (DG).
• It is also referred as ‘Embedded Generation’ or ‘Dispersed Generation’.
• DG units are based on conventional as well as renewable energy resources.
• Technologies such as IC engines, reciprocating engines, gas turbines, micro-
turbines, etc. are associated with conventional energy sources.
• Renewable energy technologies are solar PV, wind, fuel-cell, small hydro, biomass,
solar-thermal, and geothermal systems, etc.

3
Benefits of DG Integration
• Reduced line losses,
• Improved voltage profile and improved power quality
• Enhanced system efficiency, reliability and security,
• Transmission and distribution capacity release and reduced T&D congestion,
• Deferred investments for up-gradation of facilities
• Reduced harmful emissions and greenhouse gas (GHG), thereby earning carbon
credits,
• Reduced operational costs of some DG technologies, e.g. solar and wind,
• Reduced reserve requirements,
• Lower operating costs due to peak shaving,

4
Type of Generators used
Internal
Wind Micro- Combustion
Fuel Cell Solar PV
Turbine turbine Engine

Static Power Synchronous Induction


Converter Generator Generator

Power System Interface

Ref: J. H. Teng, “Modelling distributed generations in threephase distribution load flow,”IET Gener. Transm. Distrib., vol. 2, no. 3, pp. 330– 340, 2008

Ref: ‘Engineering guide for integration of distributed generation and storage into power
5
distribution systems’, EPRI Technical Report TR-100419 Report, December 2000
PQ node and PV node
PQ Node (Constant Power Factor Model)
Small DGs (Induction or Synchronous) approximately modeled as PQ node.
Contant Power Load Negative Constant Power Load
* *
 P + jQLi   P + jQGi 
I Li =  Li  I Gi =  Gi 
 Vi   Vi 

PV Node (Constant Terminal Voltage Model)


Large DGs with AVR are modeled as PV nodes

6
Synchronous Generator Model

Power Factor control mode (PQ Node)


Power factor can be controlled by controlling the excitation
*

QGi = PGi tan ( cos −1


( pfGi ) )  P + jQGi 
I Gi =  Gi 
 Vi 

7
Synchronous Generator Model
2. Voltage Control Mode (PV Node)
Reactive power is controlled to control the voltage at
bus i
Vi = Vspec − Vi
If not within the limit
 E −V 
QGi = Vi  Gi i 
 Xi 
Xi is the sensitivity reactance.
If the calculated reactive power violates the upper or lower limits, the DG
switch from PV to PQ mode and the reactive power is kept at its limits.

8
Synchronous Generator Model
3. Constant Excitation Mode (PQ Node)
Excitation is constant
EGi Vi
PGi = sin( −  ) (1)
Xi
EGi Vi Vi 2
QGi = cos( −  ) − (2)
Xi Xi

From (1) and (2)


*
E V 
2
V 2  P + jQGi 
QGi =  Gi i  − PGi2 − i I Gi =  Gi 
 Xi  Xi  Vi 

9
Induction Generator Model
• Based on ratings and generator parameters (PQ node)
Xc Xm
X S = ( X1 + X 2 ) and XP =
Xc − Xm
Therefore

− PGi ( s 2 X S2 + R22 )
Vi = (1)
R2 s
 Vi 2 PGi X S 
QGi = −  + s (2)
 P
X R2 
From (1) and (2) *
 P + jQGi 
Vi 2 −Vi + Vi − 4 P X I Gi =  Gi
2 4 2 2

QGi = − + Gi S 
XP 2XS  Vi 

10
Induction Generator Model
• Based on experimental data (PQ node)

QGi = −Q0 − Q1 PGi − Q2 PGi2

Where Q0 , Q1 , and Q2 are experimentally obtained.

 P + j (QGi + QCi ) 
*

I Gi =  Gi 
 Vi 

11
Power Electronic Converter Interface

Active and reactive power can


be controlled by regulating ψ
and m respectively

• Voltage control with limited reactive power (PQ or PV node)


P
Smax = Gi QGi _ max = Smax
2
− PGi2
pf min
If the calculated reactive power violates the upper limits, the DG switch from PV to
PQ mode and the reactive power is kept at its limits.
12
Power Electronic Converter Interface

• Current control mode:


In current control mode where active power output and injection
current are specified.

Smax = Vi I Spec

QGi = Smax
2
− PGi2

13
Summary of the Lecture
• DG Definition
• Benefits of DG integration
• Various DG technologies
• PQ and PV nodes
• Models of various generators
– Synchronous generator
– Induction generator
– DG with power electronic convertor interface

14
Lecture 25
Applications and Modeling of
Capacitor Banks

1
Review of the Last Lecture
• DG Definition
• Benefits of DG integration
• Various DG technologies
• PQ and PV nodes
• Models of various generators
– Synchronous generator
– Induction generator
– DG with power electronic convertor interface

2
Applications of Capacitors in Distribution System
Capacitors provide many benefits to distribution system performance.
Capacitors decrease the line current
Reduce losses in distribution system
Free up system capacity
Reduce voltage drop
Improves power factor
Switched capacitors can regulate voltage on a circuit

Capacitors can be placed at consumer ends, on feeder, and at substation.

3
Capacity Release

4
Ref: T. A. Short, Electric Power Distribution Handbook, CRC Press, Boca Raton, 2003.
Voltage Support: Loaded

5
Voltage Support: No Load

6
Capacitor Local Controls

• Time clock
• Temperature
• Voltage
• Current
• Vars
• Power factor

7
Modeling of Capacitor

8
Wye Connected Capacitor Bank

9
Delta Connected Capacitor Bank

10
Shunt Line Elements of Distribution Line

11

You might also like