Professional Documents
Culture Documents
Lecture 6
‘K’ Factors and Their
Applications
1
Review of Chapter 1
Introduction to a Electrical Distribution System
Lecture 1: Structure of distribution system, primary distribution system,
secondary distribution system, why distribution system analysis?, course
content
Lecture 2: Substation components, various substation layouts
Lecture 3: Components and configurations of Distribution Feeders
Lecture 4: Nature of loads, load curves, demand factor, load factor, diversity
factor, utilization factor
Lecture 5: Load allocation to distribution transformers and feeder sections
2
Approximate Methods of Analysis
Actual distribution system is
Lines: un-transposed (three-phase, two-phase, single-phase)
Loads: unbalanced (three-phase, two-phase, single-phase)
It need detailed or exact model of distribution system
VS = VL 0 + ( I − )( R + jX )
VS cos + jVS sin = VL 0 + ( I cos − jI sin )( R + jX )
VS cos + jVS sin = VL 0 + ( IR cos + IX sin ) + j ( IX cos − IR sin )
4
Example-01
1 2 Z12 = 0.2841 + j 0.5682
I12 = 43.00 − 25.84 A
V1 = VS = 24000 V
6
“K” Factors: The Kdrop Factor
Percent voltage drop
K drop =
kVA×km
GMD
Li = 2 10−7 ln
GMR
zi = ri + j Li
I=
1(kVA)
3 VLL (kV)
(
− cos −1 pf ) K drop = % Vdrop =
Re ( ZI )
100
Vbase
7
Example-02
Line impedance per km Z = 0.19 + j 0.32 Ω/km
Load power factor of 0.9 lagging and a nominal voltage of 11 kV (line-to-
line) or 6.35 kV (Line-to-Neutral).
The current taken by 1 kVA at 0.9 lagging power factor
I=
S (kVA)
3 VLL (kV)
( )
− cos −1 pf =
1
3 11
( )
− cos −1 0.9 = 0.0525 − 25.84
0.0161
Thus, K drop = 100 = 0.000254 % drop/kVA-km
6350
8
Example-03
Let the Kdrop factor is 0.000254 %drop/kVA-km.
For example, assume a load of 7500 kVA is to be served at a point 2.4 kms
from the substation.
Suppose now that the utility has a maximum allowable voltage drop of
3.0%. How much load can be served 2.4 kms from the substation?
Vdrop 3.0
kVA load = = = 4921.26 kVA
K drop ×km 0.000254×2.4
9
Example-04
10
The Krise Factor
cap
Capacitor
Bank
11
Example-05
Line impedance per km Z = 0.19 + j0.32 Ω/km
The nominal voltage of 11 kV (line-to-line) or 6.35 kV (Line-to-Neutral).
The current taken by 1 kVAr
Q(kVAr) 1
I cap = 90 = 90 = 0.0525 90
3 VL (kV) 3 11.0
Thus, 0.0168
K rise = 100 = 0.000265% rise/kVA-km
6350
12
Example-06
In Example-03, the percent voltage drop in for 7500 kVA for 2.4 km was
computed to be 4.6%.
To limit the total voltage drop to 3%, the required voltage rise due to a
shunt capacitor bank is
Vrise = 4.6 − 3.0 = 1.6 %
13
Summary of the Lecture
Approximate methods of Analysis of Distribution System
K-FACTORS
Percent voltage drop
K drop =
▪ The Kdrop Factor kVA×km
Percent voltage rise
▪ The Krise Factor K rise =
kVAr×km
Applications of K-factors
14
Lecture 7
Analysis of Uniformly
Distributed Loads
1
Review of the Last Lecture
Approximate methods of Analysis of Distribution System
Assumptions: Balanced 3-phase, transposed
K-FACTORS
▪ The Kdrop Factor
▪ The Krise Factor
Applications of K-factors
2
Uniformly Distributed Load
3
Uniformly Distributed Load
IT
IT
di =
n
l = length of the feeder
z = r + jx = impedance of the feeder in /km
dx = length of each line section
di = load current at each node
n = number of nodes and number of line sections
IT = total current entering into the feeder
4
Voltage Drop in Uniformly Distributed Load
IT
IT
di =
n
Section Impedance Current Voltage drop
0 to 1 z dx n di V01 = Re ( z dx n di )
1 to 2 z dx (n-1) di V12 = Re ( z dx ( n − 1) di )
2 to 3 z dx (n-2) di V23 = Re ( z dx ( n − 2 ) di )
5
Voltage Drop in Uniformly Distributed Load
IT
IT di =
n
6
Voltage Drop in Uniformly Distributed Load
l
dx =
IT n
I
di = T
n
( n + 1)
Vdrop = Re Z IT
2 n
1 1
= Re Z IT 1 +
2 n
In the limiting case, where n goes infinity (i.e. large number of sections)
1
Vdrop = Re Z IT
2
7
Voltage Drop in Uniformly Distributed Load
1 I
Vdrop = Re Z IT = Re Z T
2 2
R 3 2
Ploss = 3 IT2 = IT R
2 2
2
I 3
Ploss = 3 T R = IT2 R
2 4
8
Power Loss in Uniformly Distributed Load
IT
IT
di =
n
Section Resistance Current Power Loss
0 to 1 r dx n di (
PL01 = 3 r dx n 2 di 2 )
1 to 2 r dx (n-1) di (
PL12 = 3 r dx ( n − 1) di 2
2
)
= 3 ( r dx ( n − 2 ) di )
2
2 to 3 r dx (n-2) di PL23 2
n-1 to n r dx (n-(n-1)) di = di (
PLn −1 n = 3 r dx di 2 )
9
Power Loss in Uniformly Distributed Load
l
dx =
IT n
I
di = T
n
Ploss = PL01 + PL12 + PL23 + + PLn −1 n
( (
= 3 r dx di 2 n 2 + ( n − 1) + ( n − 2 ) +
2 2
+ 12 ))
n ( n + 1)( 2n + 1) l I 2 n ( n + 1)( 2n + 1)
= 3 r dx di 2 = 3 r
T
6 n n 6
( n + 1)( 2n + 1) 2 2n + 3n + 1
2
= 3 R IT
2
= 3 R IT
2
2
6 n 6 n
10
Power Loss in Uniformly Distributed Load
l
dx =
IT n
I
di = T
n
2 2n + 3n + 1
2
2 1 1 1
Ploss = 3 R IT = 3 R IT + + 2
3 2n 6n
2
6 n
In the limiting case, where n goes infinity (i.e. large number of sections)
1
Ploss = 3 R IT2
3
11
Power Loss in Uniformly Distributed Load
IT
2
1 2 I
Ploss = 3 R IT = 3 R T
3
3
12
Exact Lumped Load Model
1
Vdrop = Re ( k Z IT + (1 − k ) Z cIT ) also Vdrop = Re Z IT
2
1
Therefore Z IT = k Z IT + (1 − k ) Z cIT
2
0.5 − c
0.5 = k + c − ck = c + (1 − c)k k=
(1 − c)
13
Lumped Load Model
1
(
Ploss = 3 k R IT2 + ( k − 1) R c 2 IT2 ) also Ploss = 3 R IT2
3
1
Therefore
3
(
3 R IT2 = 3 k R IT2 + (1 − k ) R c 2 IT2)
1
3
( )
= k + (1 − k ) c 2 = 1 − c 2 k + c 2
14
Exact Lumped Load Model
0.5 − c
k=
(1 − c)
and 1
3
( )
= 1 − c2 k + c2
0.5 − c
1
3
(
= 1 − c2 )
(1 − c)
+ c 2 = (1 + c)(0.5 − c) + c 2
1 1
Therefore c = and k=
3 4
15
Summary of the Lecture
• Uniformly distributed load
• Voltage drop
• Power loss
• Exact Lumped model
16
Lecture 8
Lumping Loads in Geometric
Configurations: Rectangular
1
Review of the Last Lecture
• Uniformly distributed load
1 I 2
• Power loss Ploss = 3 R IT2 = 3 R T
3 3
2
Lumping Loads in Geometric Configurations
3
Lumping Loads in Geometric Configurations
• Lumping the loads with feeders supplying various areas (geometric
configurations): Rectangles, triangles, etc.
• Approximate calculations of voltage drop and total power losses by
assuming constant load density.
• The approximate calculations of the maximum load at a given
voltage level and conductor size.
• Approximate locations capacitor or DG and their sizes
4
Lumping Loads in Geometric Configurations
kVA
D = load density in
km 2
z = line impedance in Ω/km
5
Rectangular Area Configuration
dx
kVA
D = load density in
km 2
PF = average power factor
z = line impedance in Ω/km
l = length of the area
w = width of the area
kVLL = nominal line-to-line voltage in kV
IT
di = A/km 2
wl
6
Rectangular Area Configuration
IT
di = A/km 2
wl
IT =
S (kVA)
3 VLL (kV)
(
− cos −1 PF )
D l w
=
3 VLL
(
− cos −1 PF )
7
The Rectangle : Voltage Drop
The voltage drop in the incremental
segment is
dV = Re ( zdx i )
x
= Re zdx IT 1 −
l
x 2
l
l2 1 1
= Re z IT x − = Re z IT l − = Re z IT l = Re Z I T
2l 0 2l 2 2
8
The Rectangle: Voltage Drop
1
Vdrop = Re Z IT
2
9
The Rectangle: Power Loss
IT
di = A/km 2
wl
x
i = IT 1 −
l
2 x x2
2
x
dp = 3 r dx i = 3 r dx IT 1 − = 3 r dx I T 1 − 2 + 2
2 2
l l l
10
The Rectangle: Power Loss
x x2
dp = 3 r dx IT 1 − 2 + 2
2
l l
3 3 3
11
The Rectangle: Power Loss
1 2
Ploss = 3 R IT
3
12
Example
• l= 3.05 km
• w=1.83 km.
• A = l × w = 5.58 km2.
• D = 965.55 kVA/km2, pf 0.9 lag.
• Total kVA = D × A = 5387.8 kVA
• z = 0.19 + j 0.32 Ω/km
• Allowed voltage drop is ±3%.
• The choices of nominal voltages are 4.16 kV and 11 kV
13
Solution
The total impedance (Z) =z l = (0.19 + j 0.32) 3.05 = 0.58 + j 0.98
For a nominal voltage of 4.16 kV, the total current is,
kVA 5387.8
IT = = − cos −1 0.9 = 747.7 − 25.84 A
( 3 kVLL ) 3 4.16
1
The total voltage drop = Vdrop = Re Z IT = 354.86 V
2
Vdrop 354.86
The percentage voltage drop = %Vdrop = 100 = 100 = 14.78 %
VLN 4160 / 3
14
Solution
For a nominal voltage of 11 kV,
kVA 5387.8
IT = = − cos −1 0.9 = 282.78 − 25.84 A
( 3 kVLL ) 3 11.0
15
Summary
• Lumping Loads in Geometric Configurations
– Rectangular
1
Vdrop = Re Z IT
2
1 2
Ploss = 3 R IT
3
– Application
16
Lecture 9
Lumping Loads in Geometric
Configurations: Triangular
1
Review of the Last Lecture
• Lumping Loads in Geometric Configurations
– Rectangular
1
Vdrop = Re Z IT
2
1 2
Ploss = 3 R IT
3
– Application
2
The Triangle: Voltage Drop
kVA
D = load density in
km 2
z = line impedance in Ω/km
3
The Triangle: Voltage Drop
The total current entering the area:
S kVA
IT = − cos −1 ( PF ) A
3 kVLL
D Area
= − cos −1 ( PF ) A
3 kVLL
IT IT 2 IT
di = = = A/km 2
Area 1 l w l w
2
4
The Triangle: Voltage Drop
The current entering the line segment
i = IT − A1 di
2 IT 1 1 w
di = A/km 2 A1 = w1 x = x x
lw 2 2 l
Also,
x w1 xw
= w1 =
l w l
5
The Triangle: Voltage Drop
i = IT − A1 di
1 w 2 IT
= IT − x 2
2 l lw
x2
= IT 1 − 2
l
IT IT 2 IT
di = = = A/km 2
Area 1 l w l w Therefore,
2
1 w x2
and A1 = x x dv = Re zdx i = Re z dx IT 1 − 2
2 l l
6
The Triangle: Voltage Drop
x2
dv = Re z dx IT 1 − 2
l
7
The Triangle: Voltage Drop
2
Vdrop = Re ZT IT
3
8
The Triangle: Power Loss
x2
i = IT 1 − 2
l
2 2
x2 x4
2 x 2
Substituting dp = 3 r dx | IT | 1 − 2 = 3 r | IT | 1 − 2 2 + 4 dx
l l l
9
The Triangle: Power Loss
2 x2 x4
dp = 3 r | IT | 1 − 2 2 + 4 dx
l l
0 0 l l 0
l l
x 3
x 5
l
2 2 l 8
= 3r IT x − 2 2 + 4 = 3r IT l − l + = 3 R | IT |2
2
3l 5l 0 3 5 15
10
The Triangle: Power Loss
8
Ploss = 3 R | IT |2
15
11
Example
• l = 4.5 km
• w = 1.8 km
• A = 1/2 × l × w = area=4.14 km2
• D = 1351.8 kVA/km2, pf 0.9 lag.
• Total kVA = D × A = 5596.45 kVA
• Kdrop = 0.0002191 % drop/kVA-km,
• Krise = 0.0002504 % rise/kvar-km
• Nominal voltage = 11 kV
• Find the location of 1800 kVAr capacitor bank to keep the voltage drop
within ±3% at the end.
12
Solution
The total load of the triangular area is
kVA = 5596.45 − 25.84 kVA
13
Solution
The required voltage rise due to the capacitor is
Vrise = Vdrop − 3.0 = 3.76 − 3.0 = 0.76
14
Summary
• Lumping Loads in Geometric Configurations
– Triangular
2
Vdrop = Re ZT IT
3
8
Ploss = 3 R | IT |2
15
– Application
15
Chapter 3
Modelling of Distribution System Components
Lecture 10
Impedance of Distribution Lines
and Feeders - Part I
1
Review of the Chapter 2
• K-FACTORS: Kdrop and Krise
• Uniformly distributed load:
– Voltage drop
– Power loss
– Exact lumped load model
• Lumping Loads in Geometric
Configurations
– Rectangular
– Triangular
2
Types of Conductor
• Copper
• Aluminum: Cheaper, lighter, but less conductive and less tensile strength
than copper
– ACSR (Aluminum Conductor Steel Reinforced)
– AAC (All Aluminum Conductor)
– AAAC (All Aluminum Alloy Conductor)
– ACAR (Aluminum Conductor Alloy Reinforced)
ACSR Conductor
Rt 2 (1 0 + T2 )
=
Rt1 (1 0 + T1 )
Resistance of the Stranded Conductor
a l a (1.05 103 )
a l a
R= = = = 1337 Ω/km
A ns As d s2 ns d s2
ns
4
Conductor Data Sheet
Source: http://www.stabiloy.com/NR/rdonlyres/5FFCCF8A-8706-4FE5-9C9D- 7
CFD2DEEAEDB2/0/SEC4_Overhead_Conductors.pdf
Transposed Three-Phase Lines
GMD Deq
Li = 2 10−7 ln or Li = 2 10−7 ln H m
GMR GMR
zii = ri + j Lii
1
= ri + j 2 50 2 10−7 ln 1000 km
GMRi
1
= ri + j 0.0628ln km
GMRi
Un-Transposed Distribution Lines
1
ij = 2 10−7 ln I j Wb
Dij
ij 1
Lij = = 2 10 −7 ln H m
Ij Dij
zij = j Lij
1
= j 2 50 2 10 −7 ln 1000 km
Dij
1
= j 0.0628 ln km
Dij
Impedance of Distribution Line
– Transposed line
GMD
zi = ri + j 2 10−7 ln m
GMR
GMD
= ri + j 0.0628 ln km
GMR
– Un-transposed line
1
zii = ri + j 0.0628 ln km
GMRi Z aa Z ab Z ac
Z bc
1 Z abc = Z ba Z bb
zij = j 0.0628 ln km
Dij Z ca Z cb Z cc
Zero-sequence current paths
Source: T. A. Short, Electric Power Distribution Handbook, CRC Press, Boca Raton,
2003. 13
Un-Transposed and Unbalanced System
zˆii = zii + zdd − zdi − zid zˆij = zij + zdd − zdj − zid
1 1 1 1
= ri + rd + j 2 10−7 ln + ln − ln − ln
GMRi GMRd Did Ddi
1 D .D
= ri + rd + j 2 10−7 ln + ln id di
GMRi GMRd
Un-transposed and Unbalanced System
1 1 1 1
= rd + j 2 10 ln
−7
+ ln − ln − ln
Dij GMRd Ddj Did
1 Ddj .Did
= rd + j 2 10 −7
ln + ln
Dij GMRd
Earth Layers of Sub-conductors
The Summary of The Lecture
Chapter 3: Modelling of Distribution System Components
19
Lecture 11
Series Impedance of Distribution
Lines and Feeders - Part II
1
Review of the Last Lecture
1 D .D
zˆii = ri + rd + j 2 10−7 ln + ln id di / m
GMRi GMRd
1 Ddj .Did
zˆij = rd + j 2 10 ln
−7
+ ln / m
Dij GMRd
Source: W. H. Kresting, Distribution System Modeling and Analysis, CRC
Press, New York, 2002.
Earth Layers of Sub-conductors
Carson’s Equations
Since a distribution feeder is inherently unbalanced.
The earth is a conductor of enormous dimension and non-uniform conductivity.
Thus earth current distribution is not uniform.
To calculate the impedance of conductor with earth return, it is necessary to
know the distribution of current returning in the earth.
Many engineers attacked this problem using different methods and
assumptions.
In 1926, Carson developed a technique to get the self and mutual impedances
for an arbitrary number of overhead conductors.
Carson assumed that the earth is an infinite, uniform solid with a flat uniform
upper surface and a constant resistivity.
Carson’s Equations
p
De = 2160 ft
f
p
= 0.305 2160 meter
f
1 Ddj .Did
zˆij = rd + j 2 10 ln −7
+ ln / m
Dij GMRd
1
ˆzii = ri + 9.86 10−7 f + j 2 10−7 ln + ln De Ω m De = 2160
p
ft
GMRi f
−7 −7
1 = 0.305 2160
p
zˆij = 9.86 10 f + j 2 10 ln + ln De Ω m meter
Dij f
Modified Carson’s Equations (50 Hz and km)
1 Conductor
zˆii = ri + 9.86 10−7 f + j 2 10−7 ln + ln De Ω m
GMRi distances in meter
1
= ri + 9.86 10−7 50 + j 2 50 2 10−7 ln + ln De 1000 Ω km
Soil P
GMRi
Damp earth 100
1
= ri + 0.0493 + j 0.0628 ln + 6.843 Ω km Dry earth 1000
GMRi
Sea water 1
1
zˆij = 9.86 10−7 f + j 2 10−7 ln + ln De Ω m
Dij De = 2160
p
ft
f
1
= 0.0493 + j 0.0628 ln + 6.843 Ω km p
Dij = 0.305 2160 meter
f
Modified Carson’s Equations (60 Hz and mile)
Conductor
1
zˆii = ri + 9.86 10−7 f + j 2 10−7 ln + ln De Ω m distances in ft
GMRi
1 De = 2160
p
= ri + 9.86 10−7 60 + j 2 60 2 10 −7 ln + ln De 1609.34 Ω mile ft
f
GMRi
1
= ri + 0.0953 + j 0.12134 ln + 7.93402 Ω mile
GMRi Soil P
−7 −7
1 Damp earth 100
zˆij = 9.86 10 f + j 2 10 ln + ln De Ω m
Dij Dry earth 1000
Sea water 1
1
= 0.0953 + j 0.12134 ln + 7.93402 Ω mile
Dij
Summary Impedances of Distribution Line
• Impedance at 50 Hz per km
GMD
– Transposed line zi = ri + j 0.0628 ln Ω km
GMR
– Self and mutual impedances of un-transposed line without ground return
1
zii = ri + j 0.0628 ln Ω km
GMRi
1
zij = j 0.0628ln Ω km
Dij
– Self and mutual impedances of un-transposed line with ground return
1
zˆii = ri + 0.0493 + j 0.0628 ln + 6.843 Ω km
GMRi
1
zˆij = 0.0493 + j 0.0628 ln + 6.843 Ω km
Dij
Primitive Impedance Matrix
1
zˆii = ri + 0.0493 + j 0.0628 ln + 6.843 Ω km
GMRi
1
ˆzij = 0.0493 + j 0.0628 ln + 6.843 Ω km
Dij
10
Primitive Impedance Matrix
12
Kron Reduction
Vabc V 'abc zˆij zˆin I abc
V = V ' +
ng ng zˆnj zˆnn I n
Two separate equations
Vabc = V 'abc + zˆij I abc + zˆin I n and Vng = V 'ng + zˆnj I abc + zˆnn I n
13
Kron Reduction
zbc
Vag V 'ag zˆaa zˆab zˆac zˆan I a Vag V 'ag zaa zab zac I a
bg bg
V V ' zˆ
ba zˆbb zˆbc zˆbn I b V
= V ' + zba zbb zbc I b
V = V ' +
bg bg
zˆca zˆcb zˆcc zˆcn I c Vcg V 'cg zca zcb zcc I c
cg cg
Vng V 'ng zˆna zˆnb zˆnc zˆnn I n
zˆij zˆin
zabc = zˆij − zˆin zˆnn
−1
zˆnj
zˆnj
zˆnn
Impedance of Distribution Line
1
zˆii = ri + 0.0493 + j 0.0628 ln + 6.843 Ω km
GMRi
1
ˆzij = 0.0493 + j 0.0628 ln + 6.843 Ω km
Dij
Z aa Z ab Z ac
Z bc
Z abc = Z ba
zabc = zˆij − zˆin zˆnn
−1 Z bb
zˆnj
Z ca Z cb Z cc
Example
Determine the phase impedance matrix. The
phase conductors are 336,400 26/7 ACSR, and
the neutral conductor is 4/0 6/1 ACSR.
16
Solutions
Conductor Types GMR Resistance
(m) (Ω/km)
336,400 26/7 ACSR 0.0074 0.1901
4/0 6/1 ACSR 0.0025 0.3679
1
Z aa = ri + 0.0493 + j 0.0628 ln + 6.843 /km
GMRa
1
=0.1901+0.0493+j 0.0628 ln + 6.843 /km
0.0074
=0.2394+j 0.7378 /km
17
Solutions
Conductor Types GMR Resistance
(m) (Ω/km)
336,400 26/7 ACSR 0.0074 0.1901
4/0 6/1 ACSR 0.0025 0.3679
1
Z ab = 0.0493 + j 0.0628 ln + 6.843 /km
Dab
1
=0.0493+j 0.0628 ln + 6.843 /km
0.762
=0.0493+j 0.4467 /km
18
Solution
1
zˆii = ri + 0.0493 + j 0.0628 ln + 6.843 Ω km
GMRi
1
ˆzij = 0.0493 + j 0.0628 ln + 6.843 Ω km
Dij
22
Lecture 12
Models of Distribution Lines
and Cables
1
Review of the Last Lecture
• Impedance at 50 Hz per km GMD
– Transposed line zi = ri + j 0.0628 ln Ω km
GMR
– Self and mutual of Un-transposed without ground return
1
zˆii = ri + j 0.0628 ln Ω km
GMRi
1
zˆij = j 0.0628ln Ω km
Dij
– Self and mutual impedances with ground return
1
zˆii = ri + 0.0493 + j 0.0628 ln + 6.843 Ω km
GMRi
1
zˆij = 0.0493 + j 0.0628 ln + 6.843 Ω km
Dij
Review of the Last Lecture
1
zˆii = ri + 0.0493 + j 0.0628 ln + 6.843 Ω km
GMRi
1
ˆzij = 0.0493 + j 0.0628 ln + 6.843 Ω km
Dij
3
Review of the Last Lecture
zbc
Vag V 'ag zˆaa zˆab zˆac zˆan I a Vag V 'ag zaa zab zac I a
bg bg
V V ' zˆ
ba zˆbb zˆbc zˆbn I b V
= V ' + zba zbb zbc I b
V = V ' +
bg bg
zˆca zˆcb zˆcc zˆcn I c Vcg V 'cg zca zcb zcc I c
cg cg
Vng V 'ng zˆna zˆnb zˆnc zˆnn I n
zˆij zˆin
zabc = zˆij − zˆin . zˆnn
−1
. zˆnj
zˆnj
zˆnn
Shunt Admittance of Overhead Line
Qi Vi =
Qi
ln
1
+
( −Qi ) ln 1 + Q j ln 1 + ( −Q j ) ln 1
Qj 2 0 GMRi 2 0 Sii 2 0 Dij 2 0 Sij
Dij
Qi S Qj Sij
Vi = ln ii + ln
Sij 2 0 GMRi 2 0 Dij
Sii
Vj =
Qi
ln
1
+
( −Qi ) ln 1 + Q j ln 1 + ( −Q j ) ln 1
2 0 Dij 2 0 Sij 2 0 GMR j 2 0 S jj
Qi Sij Qj S jj
Vj = ln + ln
2 0 Dij 2 0 GMR j
-Qj
-Qi 1 S 1 Sij
ln ii ln
Vi 2 0 GMRi 2 0 Dij Qi = Pii Pij Qi
V = Q j Pij Pjj Q j
j 1
ln
Sij 1
ln
S jj
2 0 Dij 2 0 GMR j
Shunt Admittance of Overhead Line
Qi Qj Vi Pii Pij Qi
Dij V = P Pjj Q j
j ij
Sij Therefore
Sii −1
Qi Pii Pij Vi
Q = P Pjj V j
j ij
−1
Cii Cij Vi Pii Pij Vi
C =
-Qj ij Cij V j Pij Pjj V j
−1
-Qi Cii Cij Pii Pij
C =
ij Cij Pij Pjj
C = P
−1
Shunt Admittance of Overhead Line
Q1 Qn
Qi Qj ˆ ˆ ˆ ˆ Q
Dij V1 Paa P P .. P
V P 1
ab ac an
ˆ ˆ ˆ ˆ Q
Sij
Q2 2 ba Pbb Pbc .. P bn 2
Sii V3 = Pˆ ˆ ˆ ˆ Q3
ca Pcb Pcc .. P cn
: : : : .. : :
n
V ˆ ˆ ˆ ˆ
Pnn Qn
Pna Pnb Pnc ..
-Q2
-Qj
-Qi -Qn 1 Sii 1 Sij
-Q1 Pii = ln m/F Pij = ln F/m
2 0 GMRi 2 0 Dij
Sii Sij
=17.98 ln km / F = 17.98 ln km / F
GMRi Dij
Shunt Admittance of Overhead Line
ˆ ˆ ˆ ˆ Q
V1 Paa P P .. P
V P 1
ab ac an
ˆ ˆ ˆ ˆ Q ˆ Pˆin Q
2 ba Pbb P bc .. P bn 2 Vabc Pij abc
V3 = Pˆ ˆ ˆ ˆ Q3 V =
ca Pcb Pcc .. P cn
n Pˆ Pˆnn Qn
nj
: : : : .. : :
Vn
ˆ
Pna
ˆ
Pnb
ˆ
P nc .. ˆ
Pnn Q
n
−1
Therefore Pabc = Pˆij − Pˆin . Pˆnn . Pˆnj
Cabc = Pabc
−1
And F/km
Neglecting the shunt conductance, the phase shunt admittance
matrix is given by y = 0 + j C S km
abc abc
Admittance of Distribution Line
1 Sii 1 Sij
Pii = ln m/F Pij = ln F/m
2 0 GMRi 2 0 Dij
Sii Sij
=17.98 ln km / F = 17.98 ln km / F
GMRi Dij
−1
Pabc = Pˆij − Pˆin . Pˆnn . Pˆnj
Conductor Types GMR(m)
124.20 43.20 25.55
Phase 0.0074
43.20 120.98 31.83 km / F
Neutral 0.0025 25.55 31.83 122.84
Admittance of Distribution Line
Caa Cab Cac
−1 Cbb Cbc F/km
Cabc = Pabc = Cba
Cca Ccb Ccc
RC and GMRC
DS
GMRS =
2
Can 0 0
0 μS/km
Yabc = j 1000 106 0 Cbn
0 0 Ccn
PI model of Distribution Lines or Cables
1
a = d = 1+ ZY
2
b=Z
1
c = Y 1 + YZ
4
1
a = d = u + Z abc Yabc
VLGabc n a b . VLGabc m 2
= b = Z abc
abc n
I c abc m
d I
c = Yabc u + Yabc Z abc
1
4
PI model of Distribution Lines or Cables
1
a = d = u + Z abc Yabc
2
b = Z abc
c = Yabc u + Yabc Z abc
1
4
[ A] = a
−1
a = d =1
b=Z
c=0
1
a = d = u + Z abc Yabc a = d = u
2
b = Z abc Ignoring shunt b = Z abc
c = Yabc 1 + Yabc Z abc
1 susceptance
4 c = 0
Summary of The Lecture
Shunt admittance of overhead distribution lines
Impedance and Admittance of Underground Cables
Distribution system line models
PI Model
Short-line model
21
Lecture 13
Modeling of Single-Phase and
Three-Phase Transformers
1
Review of The Last Lecture: PI Model
1
a = d = u + Z abc Yabc
VLGabc n a b . VLGabc m 2
= b = Z abc
abc n
I c abc m
d I
c = Yabc 1 + Yabc Z abc
1
4
Review of The Last Lecture: Short Line Model
1
a = d = u + Z abc Yabc a = d = u
2
b = Z abc Ignoring shunt b = Z abc
c = Yabc 1 + Yabc Z abc
1 susceptance
4 c = 0
Single-Phase Two-Winding Transformer
E1 N
nt = = 1
E2 N2
Vs a b VL
I =
s c d I 2
VL = AVs − BI 2
VS = nt (VL + Z t I 2 ) = ntVL + nt Z t I 2
I2 1
I S = YmVS + I1 = ntYmVL + ntYm Z t I 2 + = ntYmVL + ntYm Z t + I 2
nt nt
Single-Phase Two-Winding Transformer
VS = ntVL + nt Z t I 2
1
I S = ntYmVL + ntYm Z t + I 2
nt
1
at = nt bt = nt Z t VL = VS − Z t I 2
nt
1
ct = ntYm d t = ntYm Z t + 1
nt At = Bt = Z t
nt
The Two-Winding Autotransformer
N1
nt = N1
N2 N1 N2 n
nt _ new = = = t
N 2 + N1 1 + N1
1 + nt
N 2
Delta-Delta
VLLABC VLLabc
VAB VBC VCA IA IB I C T = Vab Vbc Vca Ia Ib
T
I c =
I ABC I abc
T
Winding Currents = IDAB IDBC IDCA = [ IDABC ] Winding Currents = IDab IDbc
T
IDca = [ IDabc ]
The Delta–Grounded Wye Connection
Zta 0 0
Ztabc = 0 Ztb 0
0 0 Ztc
Common Variable and Matrices
VAG nt 0 0 Vta
V = 0 n 0 Vt
BG t b
VCG 0 0 nt Vtc
VLGABC = AV Vtabc
I A 1 nt 0 0 I a Ia
I = 0 1 n 0 I = AI I
B t b b
I C 0 0 1 nt I c I c
I ABC = AI I abc
Voltage Conversion: Line to Neutral -> Line to Line
VAB = VAN − VBN VAB 1 −1 0 VAN
V = 0 1 −1 V
VBC = VBN − VCN BC BN
VCA = VCN − VAN VCA −1 0 1 VCN
12
Voltage Conversion: Line to Line -> Line to Neutral
Also
VLN _ 0 1 0 0 VLL _ 0 1 1
V Where ts = 300 and ts* = − 300
V
LN _1 = 0 t *
s 0 LL _1 3 3
VLN _ 2 0 0 ts VLL _ 2
VLN 012 = [T ]VLL012
13
Voltage Conversion: Line to Line -> Line to Neutral
VLL012 = AS VLLABC
−1
1 1
Where as = 11200 , as2 = 12400 , ts = 300 and ts* = − 300
3 3
14
Summary of the Lecture
Modeling of single-phase distribution transformer
Representation of voltages and currents in three-phase
distribution transformers
Voltage Conversion
1 -1 0
Line to Neutral -> Line to Line [VLLABC ] = [ D ][VLN ABC ] where D = 0 1 -1
-1 0 1
2 1 0
where W = 0 2 1
1
Line to Line -> Line to Neutral [VLN ABC ] = [W ][VLLABC ]
3
1 0 2
15
Lecture 14
Modeling of Three-Phase
Transformers-Part I
1
Single-Phase Two-Winding Transformer
VS = ntVL + nt Z t I 2
1
I S = ntYmVL + ntYm Z t + I 2
nt
1
at = nt bt = nt Z t VL = VS − Z t I 2
nt
1
ct = ntYm d t = ntYm Z t + 1
nt A= B = Zt
nt
Representation of Voltages and Currents
Gr. Wye-Gr. Wye
Delta-Delta
Zta 0 0
Ztabc = 0 Ztb 0
0 0 Ztc
VLGABC = AV Vtabc
I ABC = AI I abc
Voltage Conversion
Line to Neutral -> Line to Line
1 -1 0
VLLABC = D VLN ABC Where D = 0 1 -1
-1 0 1
I ABC = K IDABC
1 0 -1
where K = -1 1 0
0 -1 1
Current Conversion: Line Currents -> Delta Phase Currents
−1
• Case-1 I a 1 0 −1 I ba I ba 1 0 −1 I a
I = −1 1 0 I I cb = −1 1 0 I b
b cb
0 1 1 1 I ac I ac 1 1 1 0
Therefore
I ba 1 -1 1 Ia
I = 1 1
2 1 I b
cb 3
I ac -2 -1 1 0
Therefore
−1
I ba 1 0 -1 Ia
I = -1 1 0 I
cb b
I ac Ztab Ztbc Ztca 0
Current Conversion: Line Currents -> Delta Phase Currents
−1
• Case-2 I ba 1 0 -1 I a
I = -1 1 0 I
cb b
I ac Ztab Ztbc Ztca 0
Therefore
I ba Ztca -Ztbc 1 I a
I = 1 Zt Ztab + Ztca 1 I b
Zt + Zt + Zt
cb ca
I ac ab bc ca
− Ztab − Ztbc -Ztbc 1 0
I ac ab bc ca
− Ztab − Ztbc -Ztbc 0 I c
Current Conversion: Line Currents -> Delta Phase Currents
• Case-2 I ba Ztca -Ztbc 0 Ia
I = 1 Zt Ztab + Ztca 0 I b
Zt + Zt + Zt
cb ca
I ac ab bc ca
− Ztab − Ztbc -Ztbc 0 I c
In matrix form
IDabc = M I abc
Where
Ztca -Ztbc 0
1 Zt 0
M = Ztab + Ztca
Ztab + Ztbc + Ztca
ca
Ztca -Ztbc 0
1 Zt 0
M = Ztab + Ztca
Ztab + Ztbc + Ztca
ca
I ba 1 -1 0 I a
I = 1 1 2 0 I b
cb 3
I ac -2 -1 0 I c
IDabc = L I abc
Summary: Voltage Conversion
Line to Neutral -> Line to Line
1 -1 0
VLLABC = DVLN ABC Where D = 0 1 -1
-1 0 1
1
Representation of Voltages and Currents
Gr. Wye-Gr. Wye
Delta-Delta
Zta 0 0
Ztabc = 0 Ztb 0
0 0 Ztc
VLGABC = AV Vtabc
I ABC = AI I abc
Summary: Voltage Conversion
Line to Neutral -> Line to Line
1 -1 0
VLLABC = D VLN ABC Where D = 0 1 -1
-1 0 1
VLGABC = AV Vtabc
Thus,
VLGABC = AV VLGabc + Ztabc I abc
Where
nt 0 0
at = AV = 0 nt 0
0 0 nt
nt Zt a 0 0
nt Zt b 0
bt = AV Ztabc = 0
0 0 nt Ztc
The Grounded Wye–Grounded Wye Connection
I ABC = AI I abc
Comparing with
I ABC = Ct VLGabc + dt I abc
0 0 0
ct = 0 0 0
and
0 0 0
1
0 0
nt
1
dt = [ AI ] = 0 0
nt
1
0 0
nt
The Grounded Wye–Grounded Wye Connection
1
0 0
nt Zta 0 0
0
1
At = AV Bt = 0 Ztb
−1
= 0 0
nt 0 0 Ztc
1
0 0
nt
The Delta–Grounded Wye Connection
The Delta–Grounded Wye Connection
Vtabc = VLGabc + Ztabc I abc
VLLABC = AV Vtabc
2 1 0 nt 0 0 2 1 0
1 0 0 = t 0
1
1
n
at = W AV = 0 2 nt 2
3 3
1 0 2 0 0 nt 1 0 2
and
Comparing with
I ABC = ct VLN abc + dt I abc
0 0 0 1 0 −1 1 nt 0 0 1 0 −1
ct = 0 0 0 d t = [ K ][ AI ] = −1 1 0 0 0 = −1 1 0
1
1 nt
nt
0 0 0 0 −1 1 0 0 1 nt 0 −1 1
The Delta–Grounded Wye Connection
1
nt 0 0
VLN ABC = W AV VLN abc + W AV Ztabc I abc 1 -1 0
0 1 -1
At = AV D = 0 0
−1 1
nt
-1 0 1
Therefore 0 1
0
W AV VLN abc = VLN ABC − W AV Ztabc I abc nt
1 -1 0
VLN abc = AV W VLN ABC − Ztabc I abc
−1 −1
= 0 1 -1
1
nt
VLN abc = AV D VLN ABC − Ztabc I abc
−1 -1 0 1
1
Review of the Transformer Modeling
1 -1 0
[VLLABC ] = [ D ][VLN ABC ] where D = 0 1 -1
-1 0 1
2 1 0
1
[VLN ABC ] = [W ][VLLABC ] where W = 0 2 1
3
1 0 2
1 0 -1
[ I ABC ] = [ K ][ IDABC ] where K = -1 1 0
0 -1 1
2
Summary of the Last Lecture
• Three-phase transformer models
VLN ABC = at VLN abc + bt I abc
I ABC = ct VLN abc + dt I abc
• Grounded Wye/Grounded Wye (Yg yg0)
VLGABC = AV VLGabc + AV Ztabc I abc VLGABC = nt u VLGabc + nt Zt u I abc
I ABC = AI I abc 1
I ABC = u I abc
nt
Summary of the Last Lecture
• Three-phase transformer models 2 1 0 1 0 -1
VLN ABC = at VLN abc + bt I abc 1
W = 0 2 1 and K = -1 1 0
3
I ABC = ct VLN abc + dt I abc 1 0 2 0 -1 1
VLN ABC = AV VLLabc + Ztabc IDabc
= AV VLLabc + AV Ztabc IDabc
nt 0 0 1 −1 0 1 −1 0
0 0 1 −1 = nt 0 1 −1
at = AV D = 0 nt
0 0 nt −1 0 1 −1 0 1
nt 0 0 Ztab 0 0 1 −1 0
0 0 0 1 2 0
1
bt = AV Ztabc L = 0 nt Ztbc
3
0 0 nt 0 0 Ztca −2 −1 0
The Ungrounded Wye–Delta Connection (Yd1)
The Ungrounded Wye–Delta Connection (Yd1)
I ABC = AI IDabc
= AI [ L]I abc
0 0 0
ct = 0 0 0 and
0 0 0
1 nt 0 0 1 −1 0
0 1
1
0
dt = 0 1 nt 2
3
0 0 1 nt −2 −1 0
VLN abc = At
VLN ABC − Bt
I abc
The Ungrounded Wye–Delta Connection (Yd1)
−1
2 1 0 nt 0 0
= 0 2 1 0 0
1
At = W AV
−1
nt
3
1 0 2 0 0 nt
2 1 0 Ztab 0 0 1 −1 0
1 0 1
1
2 0
Bt = W Ztabc L = 0 2 1 0 Ztbc
3 3
1 0 2 0 0 Ztca −2 −1 0
The Delta-Delta Connection (Dd0)
The Delta-Delta Connection (Dd0)
VLLABC = AV Vtabc 1
Vtabc = VLLabc + Ztabc IDabc 2
VLLABC = AV VLLabc + Ztabc IDabc
VLLABC = AV VLLabc + AV Ztabc IDabc
2 1 0 nt 0 0 1 -1 0
at = W AV D = 0 2 1 0 0 0 1 -1
1
nt
3
1 0 2 0 0 nt -1 0 1
14
The Delta-Delta Connection (Dd0)
15
The Delta-Delta Connection (Dd0)
IDABC = AI IDabc
K IDABC = AI K IDabc
I ABC = AI I abc
0 0 0 1/ nt 0 0
ct = 0 0 0 and dt = 0 1/ nt 0
0 0 0 0 0 1/ nt
I ABC = ct VLN abc + dt I abc
The Delta-Delta Connection (Dd0)
At Bt
The Delta-Delta Connection (Dd0)
VLN abc = W AV D VLN ABC − W Ztabc M I abc
−1
At Bt
2 -1 -1 Bt = Zt W L
1
At = -1 2 -1
3nt
-1 -1 2
1 -1 0 2 1 0 1 -1 0 Ztca -Ztbc 0
Zt 0
W = 0 2 1
1 1
0
1
D = 0 1 -1 L = 1 2 M = Ztab + Ztca
Ztab + Ztbc + Ztca
ca
3 3 − Ztab − Ztbc
-1 0 1 1 0 2 −2 -1 0 -Ztbc 0
Summary of the Lecture
1
Review of the Last Lecture
• Three-phase transformer models 2 1 0 1 0 -1
VLN ABC = at VLN abc + bt I abc 1
W = 0 2 1 and K = -1 1 0
3
I ABC = ct VLN abc + dt I abc 1 0 2 0 -1 1
I ABC = AI I abc
1
I ABC = u I abc
nt
1 -1 0 2 1 0 1 -1 0 Ztca -Ztbc 0
1 Zt 0
W = 0 2 1 0
1 1
D = 0 1 -1 L = 1 2 M = Ztab + Ztca
Ztab + Ztbc + Ztca
ca
3 3 − Ztab − Ztbc
-1 0 1 1 0 2 −2 -1 0 -Ztbc 0
Review of the Last Lecture
at bt ct dt
nt u 0 1
Yg yg0 nt Zt u u
nt
1
D yg11 nt W nt Zt W 0 nt
[K ]
1
Y d1 nt D nt Z t L 0 nt
[ L]
1
Dd0 nt W D + nt Z t W L 0 u
nt
4
Example
3-phase, 200kVA, 11 kV / 433 V, 50 Hz kVLLHV = 11 kV
Connection HV->Delta kVLN LV = 0.433 3 kV
Connection LV-> Star (Neutral brought out) kVA = 200 kVA
Vector group-> Dyn-11
kVLLHV
The percentage impedance 4 87 0 % (at 750 C) nt = = 44.0
kVLN LV
Z PU = 0.0021 + 0.0399i
kVLL2
Z base = = 0.9374
MVA
Z t = Z PU Z base
= 0.0020 + 0.0374i
5
Example
0.0020 + 0.0374i 0 0
2 1 0
W = 0 2 1
Ztabc = 0 0.0020 + 0.0374i 0 1
0 0 0.0020 + 0.0374i 3
1 0 2
29.3342 14.6671 0
at = nt W = 0 29.3342 14.6671
1 0 -1
14.6671 0 29.3342
K = -1 1 0
0.0576 + 1.0985i 0.0288 + 0.5492i 0 0 -1 1
bt = nt Zt W = 0 0.0576 + 1.0985i 0.0288 + 0.5492i
0.0288 + 0.5492i 0 0.0576 + 1.0985i
0.0227 0 -0.0227
0 0 0 1
ct = dt = [ K ] = -0.0227 0.0227 0
0 0 0 nt 0 -0.0227 0.0227
0 0 0
Open Wye–Open Delta Connection
Vtab = Vab + Ztab I a
Vtbc = Vbc − Ztbc I c
Also
VAG nt 0 0 Vtab
V = 0 nt 0 Vtbc
BG
VCG 0 0 0 Vtca
VLGABC = AV Vtabc
at bt
Open Wye–Open Delta Connection
1
n 0 0
I A t Ia
I = 0 0
1
- Ib
B nt
I C Ic
0 0 0
I ABC = dt I abc
1
0 0
Vab nt VAG Ztab 0 0 Ia
V
0 VBG − 0 -Ztab I b
1
bc = 0 0
nt V − Zt 0
Vca Ztab I c
1 1 CG ab
- - 0
nt nt
VLN abc = At ELN ABC − At Zsys ABC d t + Bt I abc
=
VLN abc −
Ethabc Zthabc
I abc
Summary of the Lecture
• Summary of three-phase transformer model
• Example of 11 / 0.433 kV
• Three-phase transformer models
• Open Wye/Open Delta
• The Thevenin’s equivalent circuit
15
Lecture 18
Modeling of Step Voltage
Regulators - Part I
1
Review of the Transformer Modeling
Modeling of Transformers
• Single-phase transformer models
• Transformation Matrices
• Three-phase transformer models
• Grounded Wye/Grounded Wye
• Delta /Grounded Wye
• Un-Grounded Wye/Delta
• Delta/Delta
• Open Wye/Open Delta
2
Voltage Regulation
3
Causes of under-voltage and over-voltage
Improper or less-efficient equipment operation
4
Voltage Regulation Techniques
5
Step-Voltage Regulator
• Voltage level: The desired voltage to be maintained at the load center.
• Bandwidth: The allowed variance of voltage at load center from set
voltage level.
• Time delay: Time between tap change operation ‘called for’ and actual
execution of command.
6
Types of Step-voltage Regulator
A step-voltage regulator consists of an auto-transformer and a load tap-changing
mechanism.
A-Type Regulator
7
Types of Step-voltage Regulator
B-Type Regulator
8
Types of Step-voltage Regulator
B-Type Regulator
9
Summary of The Lecture
Voltage regulation
Effects of under and over-voltage in distribution system
Various techniques of the voltage control
Single phase regulators
Type-A
Type-B
10
Lecture 19
Modeling of Step Voltage
Regulators – Part II
1
Review of The Last Lecture
Voltage regulation
Effects of under and over-voltage in distribution system
Various techniques of the voltage control
Single phase regulators
Type-A
Type-B
2
Step-voltage Regulator
Type –A Type – B
Source: W. H. Kresting, Distribution System Modeling and Analysis, CRC
3
Press, New York, 2002.
B-Type Regulator (Raise)
6
The Line Drop Compensator
7
The Line Drop Compensator
8
Three-Phase Regulator: Wye Connected
9
Summary of the Lecture
• Line drop compensator
• Modeling of three-phase voltage regulators
– Wye connected
– Closed delta connected
10
Lecture 20
Modeling of Step Voltage
Regulators – Part III
1
Summary of the Lecture
• Line drop compensator
• Modeling of three-phase voltage regulators
– Wye connected
2
Three-Phase Regulator: Closed Delta Connected
3
Three-Phase Regulator: Closed Delta Connected
4
Three-Phase Regulator: Closed Delta Connected
5
Three-Phase Regulator: Closed Delta Connected
6
Open Delta Connected Regulator
7
Open Delta Connected Regulator
8
Open Delta Connected Regulator
9
Open Delta Connected Regulator
10
Summary of the Lecture
• Modeling of three-phase voltage regulators
11
Lecture 21
Modeling of Step Voltage
Regulators – Part IV
1
Review of the Last Lecture
• Modeling of three-phase voltage regulators
– Closed Delta connected
– Open delta connected
2
Example-01
6300
N PT = = 52.5
120
CTP = 200 A
CTS = 5 A
I = 150 − 25 A
120 − 115.37
VLC = VL − Z I T ap = = 6.17 Tap = 6
0.75
= 6057.2 -20 V aR = 1 − 0.00625 6
= 0.9625
6057.2 − 2
VLC _120V = = 115.37 − 20 VS
52.5 VL _ new = = 6545.5 V
ar
3
Example-01
6300
N PT = = 52.5
120
CTP = 200 A
CTS = 5 A
I = 150 − 25 A
4
Example-02
Ia = 308.200 - 58.00
Ib = 264.200 -176.10
Ic = 297.000 70.30
5
Example-02
Ia = 308.200 - 58.00
Ib = 264.200 -176.10
Ic = 297.000 70.30
VS ab = 11000 0.00
VSbc = 11000 -120.00
VSca = 11000 120.00 Zeqab = 0.1469 + j1.8068
Zeqcb = 1.3183 + j1.2283
VLCab = 10506.693 -1.40
VLCbc = 10688.406 -122.30 ZCab = 0.1602 + j1.9711
VLCca = 10460.824 117.30 ZCcb = 1.4382 + j1.3400
6
Example-02
N PT = 11000/120 = 91.67
CTP = 500
CTS = 5
ZCab = 0.1602 + j1.9711
ZCcb = 1.4382 + j1.3400
VS ab = 11000.000 0.00
VSbc = 11000.000 -120.00
VSca = 11000.000 120.00
VLCab = 10506.693 -1.40
VLCbc = 10688.406 -122.30 Vrelay ab = 114.621 -1.40
VLCca = 10460.824 117.30 Vrelay cb = 116.603 57.70
Ia = 308.200 - 58.00
Tap_ab =7.1724 Tap_ab = 7
Ib = 264.200 -176.10
Ic = 297.000 70.30 Tap_cb =4.5293 Tap_cb = 5
7
Summary of the Lecture
• Example
8
Lecture 22
Load Models in Distribution
System - Part I
1
Summary of the Step Voltage Regulator Modeling
Voltage regulation and effects of under- and over-voltage on distribution
system components
Various techniques of the voltage control in distribution system
Single phase regulators: Type-A and Type-B
Line drop compensator
Three-phase regulator: Wye connected, closed-delta connected, open-delta
connected
Few examples
2
Load Models
Constant real and reactive power (constant PQ)
Induction motors, air conditioners, etc.
Constant Impedance (Z)
Incandescent lighting, resistive water heating, cooking
loads (stove and oven with resistive heating coils) , etc.
Constant current (I)
Welding, smelting, electroplating operation, etc.
Combination or mix type
Polynomial (ZIP)
Exponential (EXP)
3
Constant Real and Reactive (PQ) Loads
4
Constant Real and Reactive (PQ) Loads
5
Constant Impedance (Z) Loads
6
Constant Current (I) Loads
7
Polynomial Load (ZIP) Models
8
Exponential Load (EXP) Models
9
Effect of Load Models
Source: J.C. Das, Power System Analysis: Short-Circuit, Load Flow and Harmonics, 10
Second Edition, CRC Press, Boca Raton, 2012
Summary of the Lecture
Constant real and reactive power (constant PQ)
Induction motors, air conditioners, etc.
Constant Impedance (Z)
Incandescent lighting, resistive water heating, cooking loads (stove and oven
with resistive heating coils) , etc.
Constant current (I)
Welding, smelting, electroplating operation, etc.
Combination or mix type
Polynomial (ZIP)
Exponential (EXP)
11
Lecture 23
Load Models in Distribution
System - Part-II
1
Review of the Last Lecture
Constant real and reactive power (constant PQ)
Induction motors, air conditioners, etc.
Constant Impedance (Z)
Incandescent lighting, resistive water heating, cooking loads (stove and
oven with resistive heating coils) , etc.
Constant current (I)
Welding, smelting, electroplating operation, etc.
Combination or mix type
Polynomial (ZIP)
Exponential (EXP)
2
Three-Phase Induction Motor Model
3
Three-Phase Induction Motor Model
4
Three-Phase Induction Motor Model
5
Example: Constant Power
Nominal Voltages
Van 0 = 6350.85 0.00
Vbn 0 = 6350.85 -120.00
Vcn 0 = 6350.85 120.00
Load =1MW with 0.9 pf lagging
Voltage Set:01
Van = 6350.85 0.00 ILa = 157.46 - 25.84
Vbn = 6350.85 -120.00 ILb = 157.46 -145.84
Vcn = 6350.85 120.00 ILc = 157.46 94.16
6
Example: Constant Power
Nominal Voltages
Van 0 = 6350.85 0.00
Vbn 0 = 6350.85 -120.00
Vcn 0 = 6350.85 120.00
Load =1 MW with 0.9 pf lagging
7
Example: Constant Impedance
Nominal Voltages Actual Voltage
Van 0 = 6350.85 0.00 Van = 6350.85 0.00
Vbn 0 = 6350.85 -120.00 Vbn = 6639.53 -120.00
Vcn 0 = 6350.85 120.00 Vcn = 6062.18 120.00
Load =1MW with 0.9 pf lagging
2
Van 0 Van
Za = *
= 36.30 + j17.58 ILa = = 157.46 - 25.84
S a Za
2
Vbn 0 Vbn
Zb = = 36.30 + j17.58 ILb = = 164.62 -145.84
Sb* Zb
2
Vcn 0 Vcn
Zc = *
= 36.30 + j17.58 ILc = = 150.30 94.16
S c Zc
8
Example: Constant Current
Actual Voltage
Nominal Voltages
Van = 6350.85 0.00
Van 0 = 6350.85 0.00
Vbn = 6639.53 -130.00
Vbn 0 = 6350.85 -120.00
Vcn = 6062.18 110.00
Vcn 0 = 6350.85 120.00
Load =1MW with 0.9 pf lagging
Sa
ILa = = 157.46 ILa = 157.46 - 25.84
Van 0
Sb
ILb = = 157.46 ILb = 157.46 -155.84
Vbn 0
Sc
ILc = = 157.46 ILc = 157.46 84.21
Vcn 0
9
Example: Mix Load
Nominal Voltages
Actual Voltage
Van 0 = 6350.85 0.00
Van = 6350.85 0.00
Vbn 0 = 6350.85 -120.00
Vbn = 6639.53 -120.00
Vcn 0 = 6350.85 120.00
Vcn = 6062.18 120.00
Load =1MW with 0.9 pf lagging
60% constant Power, %25 Constant Current and
15% constant impedance
10
Summary of the Lecture
• Three-phase induction motor model
• Example: Load modeling
11
Lecture 24
Modeling of Distributed
Generation
1
Review of the Load Modeling
Constant real and reactive power (constant PQ)
Constant Impedance (Z)
Constant current (I)
Combination or mix type
Polynomial (ZIP)
Exponential (EXP)
Induction Motor Model
Examples of various load models and effect of voltage variation on load
currents
2
Distributed Generation
• Small-scale generation connected to the distribution grid is commonly referred as
Distributed Generation (DG).
• It is also referred as ‘Embedded Generation’ or ‘Dispersed Generation’.
• DG units are based on conventional as well as renewable energy resources.
• Technologies such as IC engines, reciprocating engines, gas turbines, micro-
turbines, etc. are associated with conventional energy sources.
• Renewable energy technologies are solar PV, wind, fuel-cell, small hydro, biomass,
solar-thermal, and geothermal systems, etc.
3
Benefits of DG Integration
• Reduced line losses,
• Improved voltage profile and improved power quality
• Enhanced system efficiency, reliability and security,
• Transmission and distribution capacity release and reduced T&D congestion,
• Deferred investments for up-gradation of facilities
• Reduced harmful emissions and greenhouse gas (GHG), thereby earning carbon
credits,
• Reduced operational costs of some DG technologies, e.g. solar and wind,
• Reduced reserve requirements,
• Lower operating costs due to peak shaving,
4
Type of Generators used
Internal
Wind Micro- Combustion
Fuel Cell Solar PV
Turbine turbine Engine
Ref: J. H. Teng, “Modelling distributed generations in threephase distribution load flow,”IET Gener. Transm. Distrib., vol. 2, no. 3, pp. 330– 340, 2008
Ref: ‘Engineering guide for integration of distributed generation and storage into power
5
distribution systems’, EPRI Technical Report TR-100419 Report, December 2000
PQ node and PV node
PQ Node (Constant Power Factor Model)
Small DGs (Induction or Synchronous) approximately modeled as PQ node.
Contant Power Load Negative Constant Power Load
* *
P + jQLi P + jQGi
I Li = Li I Gi = Gi
Vi Vi
6
Synchronous Generator Model
7
Synchronous Generator Model
2. Voltage Control Mode (PV Node)
Reactive power is controlled to control the voltage at
bus i
Vi = Vspec − Vi
If not within the limit
E −V
QGi = Vi Gi i
Xi
Xi is the sensitivity reactance.
If the calculated reactive power violates the upper or lower limits, the DG
switch from PV to PQ mode and the reactive power is kept at its limits.
8
Synchronous Generator Model
3. Constant Excitation Mode (PQ Node)
Excitation is constant
EGi Vi
PGi = sin( − ) (1)
Xi
EGi Vi Vi 2
QGi = cos( − ) − (2)
Xi Xi
9
Induction Generator Model
• Based on ratings and generator parameters (PQ node)
Xc Xm
X S = ( X1 + X 2 ) and XP =
Xc − Xm
Therefore
− PGi ( s 2 X S2 + R22 )
Vi = (1)
R2 s
Vi 2 PGi X S
QGi = − + s (2)
P
X R2
From (1) and (2) *
P + jQGi
Vi 2 −Vi + Vi − 4 P X I Gi = Gi
2 4 2 2
QGi = − + Gi S
XP 2XS Vi
10
Induction Generator Model
• Based on experimental data (PQ node)
P + j (QGi + QCi )
*
I Gi = Gi
Vi
11
Power Electronic Converter Interface
Smax = Vi I Spec
QGi = Smax
2
− PGi2
13
Summary of the Lecture
• DG Definition
• Benefits of DG integration
• Various DG technologies
• PQ and PV nodes
• Models of various generators
– Synchronous generator
– Induction generator
– DG with power electronic convertor interface
14
Lecture 25
Applications and Modeling of
Capacitor Banks
1
Review of the Last Lecture
• DG Definition
• Benefits of DG integration
• Various DG technologies
• PQ and PV nodes
• Models of various generators
– Synchronous generator
– Induction generator
– DG with power electronic convertor interface
2
Applications of Capacitors in Distribution System
Capacitors provide many benefits to distribution system performance.
Capacitors decrease the line current
Reduce losses in distribution system
Free up system capacity
Reduce voltage drop
Improves power factor
Switched capacitors can regulate voltage on a circuit
3
Capacity Release
4
Ref: T. A. Short, Electric Power Distribution Handbook, CRC Press, Boca Raton, 2003.
Voltage Support: Loaded
5
Voltage Support: No Load
6
Capacitor Local Controls
• Time clock
• Temperature
• Voltage
• Current
• Vars
• Power factor
7
Modeling of Capacitor
8
Wye Connected Capacitor Bank
9
Delta Connected Capacitor Bank
10
Shunt Line Elements of Distribution Line
11