Dewatering and drainage system

3.6 Dewatering and drainage


system
Overview
Dewatering system is to discharge the water in flow passage when unit
maintenance, the drainage system is to drainage all the water in the
power house. The test in this manual is to ensure that completed
installations are in accordance with design information, and verify the
whole system operation in accordance with design requirements.

Scope of this document is applied the systems below in BUI


Hydroelectric Project:

➢ Dewatering system
➢ Drainage system

Equipment to be used for testing


➢ Megohmmeter
➢ Multimeter

Commissioning procedure

Note: All data of the test should be recorded at the end of this
section. And the owner representative and contractor tester, by their
signature on the sheets (records), confirms that the results have been
read by the person(s) responsible for implementation.

Dewatering System Commissioning


Status Date
Initials
OK Checked
1 Ensure the Dewatering System is installed

correctly.
2 Ensure all power cables connections are tight.

3 Verify that all piping and tubing supports are

installed properly.

Page 1 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
4 Verify that all valves are installed properly.

5 Verify that the system has been cleaned.

6 Pump routine test

1#Dewatering Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:

Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
2#Dewatering Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:

Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
3#Dewatering Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:

Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
4#Dewatering Pump
Type:
Serial Number: □
Rated Voltage:
Rated Current:

Page 2 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
7 Measure the voltage of the DC,and switch on

DC Voltage:
8 Measure the voltage of the AC,and switch on

AC Voltage:
9 Check the indicating lamp and the screen normal

10 the motors startup and shutdown check

Operate the 1#Deatering pump on control panel


check whether the motors startup and shutdown □
normally.
Operate the 2#Deatering pump on control panel
check whether the motors startup and shutdown □
normally.
Operate the 3#Deatering pump on control panel
check whether the motors startup and shutdown □
normally.
Operate the 4#Deatering pump on control panel
check whether the motors startup and shutdown □
normally.
11 The valves open and close

Operate the 1#Deatering pump valve on control


panel check whether the valve open and close □
normally.
Operate the 2#Deatering pump valve on control
panel check whether the valve open and close □
normally.
Operate the 3#Deatering pump valve on control
panel check whether the valve open and close □
normally.
Operate the 4#Deatering pump valve on control
panel check whether the valve open and close 
normally.
12 Check the rotate direction of every pumps

Page 3 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked

1#Deatering pump rotate direction 

2#Deatering pump rotate direction 

3#Deatering pump rotate direction 

4#Deatering pump rotate direction 


13 Check the flow and pressure of every pumps
when the pump is running

1#Deatering pump
Flow: 
Pressure:

2#Deatering pump
Flow: 
Pressure:

3#Deatering pump
Flow: 
Pressure:

4#Deatering pump
Flow: 
Pressure:
14 Check the current of every pumps form the soft
starter when the pump is running

1#Deatering pump
Phase A:

Phase B:
Phase C:

2#Deatering pump
Phase A:

Phase B:
Phase C:

3#Deatering pump
Phase A: 
Phase B:

Page 4 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
Phase C:

4#Deatering pump
Phase A:

Phase B:
Phase C:
15 Check the temperature of every pump

1# Dewatering Pump temperature


RTD resistance: 
Pump temperature:

2# Dewatering Pump temperature


RTD resistance: 
Pump temperature:

3# Dewatering Pump temperature


RTD resistance: 
Pump temperature:

4# Dewatering Pump temperature


RTD resistance: 
Pump temperature:
16 Auto start and stop dewatering pump by level
switch(If not have the conditions on site , can
simulate the test)
Level 918.5 start 1 pump 
Level 919.0 start 2 pump 
Level 919.5 start 3 pump 
Level 918.0 stop pump 

Page 5 of 18 Version 0
Dewatering and drainage system

I/0 check
DIM1 Digital input
No. Contents I/0 Conclusion sign
1 PS1 power monitoring XDI1-1 □
2 PS2 power monitoring XDI1-2 □
3 Reset XDI1-3 □
4 Local XDI1-4 □
5 Control power disappear XDI1-5 □
6 Auto XDI1-6 □
5#pump
7 Running XDI1-7 □
8 Fault XDI1-8 □
9 Control power disappear XDI1-9 □
10 Auto XDI1-10 □
1#pump
11 Running XDI1-11 □
12 Fault XDI1-12 □
13 Control power disappear XDI1-13 □
14 Auto XDI1-14 □
2#pump
15 Running XDI1-15 □
16 Fault XDI1-16 □
17 Control power disappear XDI1-17 □
18 Auto XDI1-18 □
3#pump
19 Running XDI1-19 □
20 Fault XDI1-20 □
21 Control power disappear XDI1-21 □
22 Auto XDI1-22 □
4#pump
23 Running XDI1-23 □
24 Fault XDI1-24 □
25 1#pump XDI1-25 □
26 2#pump XDI1-26 □
Outlet Flow normal
27 3#pump XDI1-27 □
28 4#pump XDI1-28 □
29 Start pump level XDI2-1 □
30 Stop pump level XDI2-2 □
31 Start spare pump level XDI2-3 □
32 High level XDI2-4 □
33 1#valve closed XDI2-9 □
34 2#valve closed XDI2-10 □
35 3#valve closed XDI2-11 □
36 4#valve closed XDI2-12 □

Page 6 of 18 Version 0
Dewatering and drainage system

Leakage and emergency Drainage System


Status Date
Initials
OK Checked
7 Ensure the Dewatering System is installed

correctly.
8 Ensure all power cables connections are tight.

9 Verify that all piping and tubing supports are

installed properly.
10 Verify that all valves are installed properly.

11 Verify that the system has been cleaned.

12 Pump routine test

1#Drainge submergible Pump


Type:
Serial Number:
Rated Voltage:
Rated Current:

Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:

No. Contents I/0 Relay Conclusion sign


1 5# pump start/stop XDO1-1 1K1 □
2 1# pump start/stop XDO1-2 1K2 □
3 1# valve open/close XDO1-3 1K3 □
4 2# pump start/stop XDO1-4 1K4 □
5 2# valve open/close XDO1-5 1K5 □
6 3# pump start/stop XDO1-6 1K6 □
7 3# valve open/close XDO1-7 1K7 □
8 4# pump start/stop XDO1-8 1K8 □
9 4# valve open/close XDO1-9 1K9 □

Page 7 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
2#Drainge submergible Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:

Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
3#Drainge submergible Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:

Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
4#Drainge submergible Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:

Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
1#Emergency Drainge Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:
Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:

Page 8 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
2#Emergency Drainge Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:
Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
3#Emergency Drainge Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:
Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
4#Emergency Drainge Pump
Type:
Serial Number:
Rated Voltage:
Rated Current:
Rated Power:
Insulation resistance:
DC resistance:AB:
AC:
BC:
7 Measure the voltage of the DC,and switch on

DC Voltage:
8 Measure the voltage of the AC,and switch on

AC Voltage:
9 Check the indicating lamp and the screen normal

10 the motors startup and shutdown check

Operate the 1#Drainge submergible Pump on


control panel check whether the motors startup □
and shutdown normally.

Page 9 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
Operate the 2#Drainge submergible Pump on
control panel check whether the motors startup □
and shutdown normally.
Operate the 3#Drainge submergible Pump on
control panel check whether the motors startup □
and shutdown normally.
Operate the 4#Drainge submergible Pump on
control panel check whether the motors startup □
and shutdown normally.
Operate the 1#Emergency Drainge Pump on
control panel check whether the motors startup □
and shutdown normally.
Operate the 2#Emergency Drainge Pump on
control panel check whether the motors startup □
and shutdown normally.
Operate the 3#Emergency Drainge Pump on
control panel check whether the motors startup □
and shutdown normally.
Operate the 4#Emergency Drainge Pump on
control panel check whether the motors startup □
and shutdown normally.
11 The valves open and close

Operate the 1#Drainge submergible Pump valve


on control panel check whether the valve open □
and close normally.
Operate the 2#Drainge submergible Pump valve
on control panel check whether the valve open □
and close normally.
Operate the 3#Drainge submergible Pump valve
on control panel check whether the valve open □
and close normally.
Operate the 4#Drainge submergible Pump valve
on control panel check whether the valve open 
and close normally.
Operate the 1#Emergency Drainge Pump valve
on control panel check whether the valve open 
and close normally.
Operate the 2#Emergency Drainge Pump valve

on control panel check whether the valve open

Page 10 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
and close normally.

Operate the 3#Emergency Drainge Pump valve


on control panel check whether the valve open 
and close normally.
Operate the 4#Emergency Drainge Pump valve
on control panel check whether the valve open 
and close normally.
12 Check the rotate direction of every pumps

1#Drainge submergible Pump rotate direction 

2#Drainge submergible Pump rotate direction 

3#Drainge submergible Pump rotate direction 

4#Drainge submergible Pump rotate direction 

1#Emergency Drainge Pump rotate direction

2#Emergency Drainge Pump rotate direction 

3#Emergency Drainge Pump rotate direction 

4#Emergency Drainge Pump rotate direction 


13 Check the flow and pressure of every pumps
when the pump is running

1#Drainge submergible Pump


Flow: 
Pressure:

2#Drainge submergible Pump


Flow: 
Pressure:

3#Drainge submergible Pump


Flow: 
Pressure:

4#Drainge submergible Pump


Flow: 
Pressure:

Page 11 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
1#Emergency Drainge Pump
Flow:
Pressure:

2#Emergency Drainge Pump


Flow:
Pressure:

3#Emergency Drainge Pump


Flow:
Pressure:

4#Emergency Drainge Pump


Flow:
Pressure:
14 Check the current of every pumps form the soft
starter when the pump is running

1#Drainge submergible Pump


Phase A:

Phase B:
Phase C:

2#Drainge submergible Pump


Phase A:

Phase B:
Phase C:

3#Drainge submergible Pump


Phase A:

Phase B:
Phase C:

4#Drainge submergible Pump


Phase A:

Phase B:
Phase C:

1#Emergency Drainge Pump


Phase A:

Page 12 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
Phase B:
Phase C:

2#Emergency Drainge Pump


Phase A:
Phase B:
Phase C:

3#Emergency Drainge Pump


Phase A:
Phase B:
Phase C:

4#Emergency Drainge Pump


Phase A:
Phase B:
Phase C:
15 Check the temperature of every pump

1# Drainge submergible Pump temperature


RTD resistance: 
Pump temperature:

2# Drainge submergible Pump temperature


RTD resistance: 
Pump temperature:

3# Drainge submergible Pump temperature


RTD resistance: 
Pump temperature:

4# Drainge submergible Pump temperature


RTD resistance: 
Pump temperature:
16 Auto start and stop Drainge submergible Pump by
level switch(If not have the conditions on site ,
can simulate the test)
Level 918.0 start 1 pump 

Page 13 of 18 Version 0
Dewatering and drainage system

Status Date
Initials
OK Checked
Level 918.5 start 2 pump 
Level 915.0 stop pump 
Level 919.0 Alarm level 
Level 919.5 Emergency pump start 

Page 14 of 18 Version 0
Dewatering and drainage system

I/0 check
No. Contents I/0 Conclusion sign
1 PS1 power monitoring XDI1-1 □
2 PS2 power monitoring XDI1-2 □
3 Reset XDI1-3 □
4 Local XDI1-4 □
5 Control power disappear XDI1-5 □
6 Auto XDI1-6 □
9#pump
7 Running XDI1-7 □
8 Fault XDI1-8 □
9 Control power disappear XDI1-9 □
1#
10 Auto XDI1-10 □
leakage
11 Running XDI1-11 □
pump
12 Fault XDI1-12 □
13 Control power disappear XDI1-13 □
2#
14 Auto XDI1-14 □
leakage
15 Running XDI1-15 □
pump
16 Fault XDI1-16 □
17 Control power disappear XDI1-17 □
18 3# leakage Auto XDI1-18 □
19 pump Running XDI1-19 □
20 Fault XDI1-20 □
21 Control power disappear XDI1-21 □
22 4# leakage Auto XDI1-22 □
23 pump Running XDI1-23 □
24 Fault XDI1-24 □
25 1# Control power disappear XDI1-25 □
26 emergency Auto XDI1-26 □
27 drainage Running XDI1-27 □
28 pump Fault XDI1-28 □
29 1# Control power disappear XDI1-29 □
30 emergency Auto XDI1-30 □
31 drainage Running XDI1-31 □
32 pump Fault XDI1-32 □

Page 15 of 18 Version 0
Dewatering and drainage system

No. Contents I/0 Relay Conclusion sign


1 9# pump start/stop XDO1-1 1K1 □
2 1#leakage pump start/stop XDO1-2 1K2 □
3 1#leakage valve open/close XDO1-3 1K3 □
4 2#leakage pump start/stop XDO1-4 1K4 □
5 2#leakage valve open/close XDO1-5 1K5 □
6 3#leakage pump start/stop XDO1-6 1K6 □
7 3#leakage valve open/close XDO1-7 1K7 □
8 4#leakage pump start/stop XDO1-8 1K8 □
9 4#leakage valve open/close XDO1-8 1K9 □
1#emergency drainage pump
10 XDO1-9 1K10 □
start/stop
1#emergency drainage valve
11 XDO1-10 1K11 □
start/stop
2#emergency drainage
12 XDO1-11 1K12 □
pump start/stop
2#emergency drainage valve
13 XDO1-12 1K13 □
open/close
3#emergency drainage
14 XDO1-13 1K14 □
pump start/stop
3#emergency drainage valve
15 XDO1-14 1K15 □
open/close
4#emergency drainage
16 XDO1-15 1K16 □
pump start/stop
4#emergency drainage valve
17 XDO1-16 2K1 □
open/close
1#emergency drainage
18 XDO1-17 2K2 □
pump protector reset
2#emergency drainage
19 XDO1-18 2K3 □
pump protector reset
3#emergency drainage
20 XDO1-19 2K4 □
pump protector reset
4#emergency drainage
21 XDO1-20 2K5 □
pump protector reset

Page 16 of 18 Version 0
Dewatering and drainage system

No. Contents I/0 Relay Conclusion sign


1#emergency drainage pump
1 XDI1-1 □
Outlet flow normal
2#emergency drainage pump
2 XDI1-2 □
Outlet flow normal
3#emergency drainage pump
3 XDI1-3 □
Outlet flow normal
4#emergency drainage pump
4 XDI1-4 □
Outlet flow normal
1#leakage drainage pump
5 XDI1-5 □
Outlet flow normal
2#leakage drainage pump
6 XDI1-6 □
Outlet flow normal
3#leakage drainage pump
7 XDI1-7 □
Outlet flow normal
4#leakage drainage pump
8 XDI1-8 □
Outlet flow normal

Page 17 of 18 Version 0
Dewatering and drainage system

No. Contents I/0 Conclusion Sign


1 3# Control power disappear XDI2-1 □
2 emergency Auto XDI2-2 □
3 drainage Running XDI2-3 □
4 pump Fault XDI2-4 □
5 4# Control power disappear XDI2-5 □
6 emergency Auto XDI2-6 □
7 drainage Running XDI2-7 □
8 pump Fault XDI2-8 □
9 Start pump level XDI2-9 □
10 Stop pump level XDI2-10 □
11 Start spare pump level XDI2-11 □
12 High level XDI2-12 □
13 Start emergency pump level XDI2-13 □
1# emergency drainage pump
14 XDI2-17 □
high temp.
1# emergency drainage pump
15 XDI2-18 □
high leakage
2# emergency drainage pump
16 XDI2-19 □
high temp.
2# emergency drainage pump
17 XDI2-20 □
high leakage
3# emergency drainage pump
18 XDI2-21 □
high temp.
3# emergency drainage pump
19 XDI2-22 □
high leakage
4# emergency drainage pump
20 XDI2-23 □
high temp.
4# emergency drainage pump
21 XDI2-24 □
high leakage
22 1#leakage valve closed XDI2-25 □
23 2#leakage valve closed XDI2-26 □
24 3#leakage valve closed XDI2-27 □
25 4#leakage valve closed XDI2-28 □
26 1# emergency drainage valve closed XDI2-29 □
27 2# emergency drainage valve closed XDI2-30 □
28 3# emergency drainage valve closed XDI2-31 □
29 4# emergency drainage valve closed XDI2-32 □

Page 18 of 18 Version 0