Tie the cables as close as possible to the connections to avoid any mechanical
stresses on the device terminals. When not using cable glands, also attach the
cables near to the cubicle entry point.
Cables must never be in contact with or passed between live conductors.
Sharp edges of the framework must be protected where cables pass to avoid
damaging the conductors.
Comply with a minimum radius of curvature of 6 to 8 times the cable outside
diameter.
All power connections must be made with class 8.8 mounting hardware and
elastic contact washers, tightened to the torque indicated in the table below.
When connecting aluminium cables to copper terminals, use bimetal lugs or
interfaces.