EQUIPMENT DATASHEET PROJECT NUMBER

GPC transfer and proportioning SG1572FD


APP2 戈广金 DOCUMENT NUMBER
APP1 刘春昊 SG1572FD-3C02-31-107-0002
CHK 蒋小铭 Rev:0
DES 郗恺 Status:Issued for Bid
Section A - EQUIPMENT IDENTIFICATION
Remarks
A1 Equipment Type TRANSFROMER
A2 Equipment Name 11kV TRANSFROMER
A3 Equipment Number 3C02-EFI-0001 3C02-EFI-0002
A4 Quantity 2
Section B - REFERENCE DOCUMENTS TO BE READ WITH THIS DATASHEET
Remarks
B1 SLD
B2 General Arrangement SG1567FD-3C02-31-021-0001
Referenced Standard
IEC-60076
B3 Specification
Section C - Duty
Remarks
C1 Service Description Power Transformer
C2 Operating or Standby Operating
Section D - PERFORMANCE/PROCESS DATA/OTHERS
Item Title Unit Data Notes Remarks
D1 Rated Primary Voltage kV 11
D2 Voltage Variations ±% 5
D3 Rated Power KVA 800
Rated Nominal
D4 Hz 50
Frequency
D5 Method of Cooling text Natural Air
D6 Tapping Range kV 10.5~11.5
D7 All Tappings Full Power Yes/No No
Rated Secondary
D8 kV 0.4
Voltage
D9 Impedance % 5.5 4& 5
Type (Oil Immersed/Air
D10 text Oil Immersed
insulated/Resin)
Sealed Tank or
D11 text Sealed Tank 4& 5
Breathing Tank
Vector
D12 text Ydn11
Group/Connection
Primary Bushings
D13 Connect Type(Cable /Air text Cable
wire/Bus bar
Secondary Bushings
D14 Connect Type(Cable /Air text Cable
wire/Bus bar
D15 Number of Radiators qty. 1 4& 5
D16 Oil Temp. Indicator Yes/No Yes
D17 Winding Temp.Indicator Yes/No 4& 5
Gas Accomulater and
D18 Yes/No Yes
Sudden Pressure
Munsell
D19 External Colour text 4& 5
2.5 Y 8.5/0.8
D20 Enclosure IP Rating text IP55 4& 5 Outdoor
HAC(Hazardous Area
D21 text Non HAC
Classification)
Section E-DIMENSIONS AND WEIGHT
E1 Length mm 2000 4& 5
E2 Width mm 2000 4& 5

Focus on Energy-saving, Environment, Safety and Efficiency Page 1 of 2


EQUIPMENT DATASHEET PROJECT NUMBER
GPC transfer and proportioning SG1572FD
APP2 戈广金 DOCUMENT NUMBER
APP1 刘春昊 SG1572FD-3C02-31-107-0002
CHK 蒋小铭 Rev:0
DES 郗恺 Status:Issued for Bid
E3 Height mm 2600 4& 5
Mass of Transformer
E4 kg 4& 5
Filled with Oil
E5 Dry Mass of Transformer kg 4& 5
Section F-SITE CONDITION
F1 Ambient Pressure kpa
F2 Elevation of Plant Site m ~5
F3 Average Temperature ℃ 30
NOTES
1 The equipment data detailed in this datasheet may differ from the data of equipment delivered on site
2 The equipment data in this datasheet shall be revised accordingly during the detailed engingeering phase.
3 This datasheet shall not be used for purchasing equipment.
4 Supplier Data Required with Bid
5 Supplier Data Required after Award

Focus on Energy-saving, Environment, Safety and Efficiency Page 2 of 2