DATA SHEET
FOR
CATHODIC PROTECTION
TRANSFORMER RECTIFIER (TR) UNIT

SPECIFICATION NO.- MEC/DS/05/E9/082A

(OIL & GAS SBU)


MECON LIMITED
MECON LIMITED STANDARD DATA SHEET
REGD. OFF: RANCHI
834002 ELECTRICAL SECTION, DELHI

DOCUMENT NO. Page 1 of 5


CATHODIC PROTECTION
TITLE TRANSFORMER RECTIFIER MEC/DS/05/E9/082A REVISION : 1
UNIT
EDITION : 1

ANNEXURE - I
PURCHASER'S DATA FOR CPTR UNIT
1 Type Floor mounted , Indoor – IP 42 AC Operated
Transformer Rectifier Unit for Impressed Current CP
System
2 Cooling Natural Air cooling (AN)
3 Quantity As per Scope of work
4 Transformer Insulation Vacuum pressure Impregnated Insulation,
Class-F, FOS-125%
5 Input Power Supply As per Scope of work/Design basis

6 Input Fault Level 10 KA (for 1 Second)


7 Number of output circuits One/Two As required
8 Modes of Operation (a) Auto Ref
(b) Manual mode
9 Rated output Voltage (+ve As per Scope of work/As per design calculations
earthed)
10 DC Voltage Regulation Better than ± 0.25V
11 Rated Output Current As per Scope of work /As per design calculations
12 DC Current Regulation ±0.5 Amp
13 PSP Voltage Regulation Better than ±15 mV
14 Pipe to Soil Potential Setting (-)0.700mV to (-) 2500 mV – (For Cu/CuSO4
range (Vps) Electrode)
15 Minimum set potential (-)0.4 V to (-)1 V
range (Vrs)
16 Maximum pipeline potential (-)1.2 V to (-)2.5 V
range (Vpm)
17 Minimum pipeline potential (-)0.7 V to (-)1.0 V
range (Vpn)

18 Number of reference cells Required (3 Nos.) & 01 on unprotected side of IJ.


for control

19 SCADA Interface and Required


Current Interruption facility

20 Inbuilt Current Interruption Required


Facility
MECON LIMITED STANDARD DATA SHEET
REGD. OFF: RANCHI
834002 ELECTRICAL SECTION, DELHI

DOCUMENT NO. Page 2 of 5


CATHODIC PROTECTION
TITLE TRANSFORMER RECTIFIER MEC/DS/05/E9/082A REVISION : 1
UNIT
EDITION : 1

21 Site conditions: As defined in scope of work/design basis, minimum


conditions are follows-
(i) Ambient Temperature
0°-50°C (max.)
(ii) Relative Humidity

94% (max.)
(iii) Altitude above mean
sea level.
Less than 1000m above MSL
(iv) Specific Environment

To withstand site condition


(Dry & Dust Storms during summer & low temp during
winter)
22 Shade for final paint RAL 7032

23 Commissioning at site By Vendor


24 Meters 1) Digital Meters (Three & Half Digits) for
a) Input Voltage
b) Input Current
c) DC output voltage
d) DC output current
e) Reference voltage (P.S.P.)
f) PSP on unprotected side of IJ

25 Alarm & Indication a) T/R UNIT ON/OFF (AC Supply ON) – Visible.
(Indication Lamp shall be b) Reference 1 lowest –Visual
Cluster LED type) Reference 2 lowest – Visual
Reference 3 lowest – Visual

c) Reference 1 Fail – Visual


Reference 2 Fail – Visual
Reference 3 Fail – Visual
d) Pipeline over protected – Visual & Remote
e) Pipeline under protected – Visual & Remote
f) Unit in Auto – Visual & Remote
Unit in Manual – Visual & Remote
g) DC output over current (Current Limit-Visual)
h) All Reference Fail – Visual & Remote
i) Current Interrupter
Power ON, ON time & OFF time
26 SCADA Monitoring Facility Signals / Contacts shall be provided for remote
monitoring & control as per cl. No. 6.6 of specification
MEC/TS/05/E9/082A.
MECON LIMITED STANDARD DATA SHEET
REGD. OFF: RANCHI
834002 ELECTRICAL SECTION, DELHI

DOCUMENT NO. Page 3 of 5


CATHODIC PROTECTION
TITLE TRANSFORMER RECTIFIER MEC/DS/05/E9/082A REVISION : 1
UNIT
EDITION : 1

27 Current interruption Facility Current interruption facility will be provided by


means of a built-in Electronic Interrupter logic &
microprocessor based digital timer with real time
clock & ON/OFF time display. The timer will have
facility for adjusting the ON time & OFF time from 0 to
999 Sec. by means of digital setting facility. The timer
will also have Start/stop facility thru a single external
potential free contact. The Timer will have GPS
Synchronisation facility.
28 Protection a) Lightning Arrestor on AC & DC Sides
b) HRC fuses in input AC supply lines and in each
DC leads
c) Surge suppressors on input, output and across
each diode and SCR (Power Transistors).
d) Adjustable current limit, overcurrent and short-
circuit protection.
e) HRC fuses outgoing DC +ve lead and the DC –
ve lead.
f) MCB/MCCB in AC I/P (2-Pole).
g) MCB/MCCM in DC O/P (2-Pole).
h) Fast acting electronic over current limit circuit.
i) Glass cartridge fuses in live line of all lamps,
auxiliary power line to control circuit.
Note-Electronic earthing for PLC/Modules shall be
provided separately (Other then equipment earthing)
MECON LIMITED STANDARD DATA SHEET
REGD. OFF: RANCHI
834002 ELECTRICAL SECTION, DELHI

DOCUMENT NO. Page 4 of 5


CATHODIC PROTECTION
TITLE TRANSFORMER RECTIFIER MEC/DS/05/E9/082A REVISION : 1
UNIT
EDITION : 1

ANNEXURE – I A

1 Guaranteed Technical Particulars


Efficiency:
At 10% Load
1.1
At 25% Load
At 50% Load
At 75% Load
At 100% Load

Voltage regulation (from zero


to 100% load variation and
1.2
throughout the output voltage
range) Better than ±0.25V
Manual mode
Auto mode
Output ripple at full load
current (less than 5% RMS)
1.3
At 10% output voltage
At 100% output voltage
16 hour heat run test & routine test shall be witnessed
by MECON/Owner at manufacturers work.
2 Inspection
Final integrated field testing shall be done at site.
3 Combined Combined load test at site.

Note- Various Settings of CP unit for Zn ref electrode will be differ from conventional Cu-
Cuso4 ref electrode, Bidder shall submit the data sheet of the CP unit for approval before
manufacturing of CP unit considering the Constant conversion factor of -1.1v to CuSO4.
MECON LIMITED STANDARD DATA SHEET
REGD. OFF: RANCHI
834002 ELECTRICAL SECTION, DELHI

DOCUMENT NO. Page 5 of 5


CATHODIC PROTECTION
TITLE TRANSFORMER RECTIFIER MEC/DS/05/E9/082A REVISION : 1
UNIT
EDITION : 1

ANNEXURE-II
ACCEPTABLE MAKES FOR COMPONENTS
S.No. Material Make

1 Contactors Siemens/ L&T/ BCH/ Telemechnique


2 Moulded Case Circuit Breaker GE/ Cromption/ L&T / Hager
3 Miniature circuit breaker MDS/ Indoasian/ Havell / Hager
4 Transformer Indcoil/ Kappa Electrical/ AE
5 Switches, Fuses, Fuse base Siemens/ L&T/ GE / Kaycee/Salzer
6 PB Elements/ Indication Lamps Siemens / L&T / Teknic / Concord/ BCH

7 Selector Switch EE/ Siemens/ Kaycee/ L&T

8 Terminals Elmex/ Connect Well/ Phoenix


9 Meters AEP/ Simco/ IMP/ GEC/ Rishab/Meco
10 Cable Glands Commet/ Baliga / Flexpro/ Sudhir

(List of suppliers for solid-state devices shall be furnished by the vendor for Owner’s approval).

(1) HRC Fuses (13) Lightning Arrestor


(2) Auxikary Fuses (14) Blade Resistance
(3) Interrupter Contractor (15) Potentio Meter
(4) DC – DC Converter Power Transistors (16) LED’s
(5) Volt Meter (Digital) 3 1/2 (17) Convertors (4 to 20 ma)
(6) Ammeter (Digital) 3 1/2 (18) Timer (Interrupter)
(7) Shunt (19) All electronic (AC DC)
(8) Filter Choke in DC Output (20) Display Board
(9) Filter Capacitor bank in DC Output (21) Filters
(10) Power Diode (22) Links
(11) Diode
(12) Search Suppressor Network