TECHNICAL PARTICULAR AND GUARANTEE

CIRCUIT BREAKER FAILURE PROTECTION

No. Description
1 Name :
2 Manufacture/Type :
3 Ordering Code :
4 Technology :
5 Protection Function :
6 Models :
Nominal Current ( In ) :
7
AC Burden
8 In = 1 A :
In = 5 A :
9 Frequency :
Auxiliary DC Voltage ( Vx ) :
10

11 DC burden
Setting range CBF
12
- Over Current :
13 Setting range SZP/EFP
- Over Current :
14 Characteristic :
Time Setting Range CBF
15 Definite Time Stage 1(tBF 1) :
Definite Time Stage 2(tBF 2) :
Time Setting Range SZP/EFP
Definite Time :
Binary output rating
Rated Voltage :
16 Continous :
Make and Carry :
Number of binary output :
Binary input rating
17 Rated Voltage
Number of binary input
18 Drop off to pick up ratio :
Minimum Feature
Retrip / first stage trip :
Backtrip / adjacent trip / second stage trip :

19 Watch dog :
Block for Relay Failure :
Default logic and setting :
MMI (Man Machine Interface) :
20 Event records :
Internal disturbance recorder :
21

22 Measurement :
23 Display :
24 Communication Protocol :
Performance Test
Type Test :
25 Routine Test :
- Protocol Test (interoperability test)
:

High Voltage withstand :


Dielectric Withstand

26
Impulse Voltage Withstand

Electrical Environment Strength :


DC supply interruption

27

AC ripple on dc supply :

Electromagnetic compatibility (EMC) :


Fast Transient Disturbance :

Radio Interference Withstand :


Radiated Immunity :

28

Surge Withstand Capability :

Electromagnetic Compability
Atmospheric Environment :
Operation temperature

29
Operation temperature

29 Humidity

Enclosure protection

Mechanical Strength :
Vibration

30 Shock and bump :

Seismic
31 Licensed Software for setting & analysis :
32 Connection between relay to computer :
Default Setting & Programmable Logic Controller
33 :

34 Guarantee :
35 Training :
Manual book (original hard and soft copy) and
36 enclosed with original certificate of routine :
test/certificate of manufacture

Tanggal :
Nama Kontraktor :
Tanda Tangan Kontraktor :
TECHNICAL PARTICULAR AND GUARANTEE
CIRCUIT BREAKER FAILURE PROTECTION

Requirement
Circuit breaker failure
…………../…………………..
…………../…………………..
Numerical IED
Circuit breaker failure protection
3 phase - 4 wires
1 A and 5 A (Able to accommodate 1 A and 5 A in one
device)

≤ 0.2 VA
≤ 0.3 VA
50 Hz
110 Volt DC -15%;+10% tolerable AC ripple up to
12%
≤ 15 W

min 0.1 – 2.0 * In (in 0.05 steps)

min 0.1 – 2.0 * In (in 0.05 steps)


Definite Time

min 0 – 30 s in 0.1 steps


min 0 – 30 s in 0.1 steps

min 0 – 30 s in 0.1 steps

250 V dc
≥5 A
≥ 30 A for 0.5 sec
≥4

Min 100 Vdc, -15%


≥4
≥95 %

Enable
Enable

Enable
Enable
Enable
Switch or keypad and can communicate with PC or
laptop
≥5 event record
≥4 analog signal
≥4 digital signal
≥2 oscillograph each 2 second
Enable
Enable
IEC 61850

Submitted
Submitted
Has ability to communicate with other manufacturer (min. 3
brands)
Minimum complied with
IEC 60255-27:2005
• 2 kV common mode
• 1 kV differential mode
IEC 60255-5:2000
• 5 kV common mode
• 1 kV differential mode
Minimum complied with
IEC 60255-11: 1979
The unit will withstand a 20 ms interruption in the auxiliary supply,
in its quiescent state, without deenergising.
IEC 60255-11: 1979
The unit will withstand a 12% ac ripple on the dc supply.
Minimum complied with
IEC 60255-22-4 Class IV / ANSI C37.90.1
• 4kV, 2.5kHz applied directly to auxiliary supply
• 4kV, 2.5kHz applied to all inputs
IEC 60255-22-3/ANSI C37.90.2
ANSI C37.90.2:1995
• 25Mhz – 1000Mhz, zeroand 100% square wave modulated

• Field strength of 35V/m


IEC 255-22-1/ANSI C37.90.1
4kV fast transient and 2.5kV oscillatory applied directly across
each output contact, opto input and power supply circuit

: Compliance
Minimum complied with
10 – 500 C
(IEC 60255-6 : 1988
-25°C to +55°C)
: 90 % (IEC 60068-2-3 : 1969
56 days at 93% RH and +40°C)
: IEC 60529:1989
IP52 Protection (front panel) against dust and dripping water at
15° to the vertical
Minimum complied with
: IEC 60255-21-1
• Response class 2
• Endurance class 2
IEC 60255-21-2
• Shock response class 2
• Shock withstand class 1
• Bump class 1
: IEC 60255-21-3:1995 Class 2
Included
Included
Yes, can be edited and created by user via software

Min 5 (five) years after accepted (BAST)


Included

Submitted
ANTEE
CTION

PROPOSED REFERENCE DOC./ REMARK