Name of the Project- Development of Alambagh Bus Terminal, Lucknow

Name & Address of the Owner- Shalimar Malls Pvt. Ltd, 11th floor Shalimar Titanium, Vibhuti Khand, Gomti Nagar, Lucknow- 226010
Name & Addres of the Contractor- M/s Priority Enginners & Techologies Pvt Ltd, T-311Hans Plaza Complex, New Delhi-110003
Scope of Work- Fire Alarm, Public Addresable System & CCTV System
Fire Logics in case of Fire Detections; controlled by Fire Alarm Panel
Fire Signals detects by ALARM AHU JET FAN EXHAUST FAN LIFTS AUTOMATIC DOOR

If Fire signal detects by only one Fire Floor, + & -


Logic-1 Not Change Not Change Not Change Not Change Not Change
detector One floor

All lifts will be on the


If Fire signal detects by any two Fire Floor, + & - All will off Fire Floor, + All will Start on Fire All will Start on Fire
Logic-2 ground floor and doors All will Open
or more detectors in same floor One floor & - One floor Floor, + & - One floor Floor, + & - One floor
will remain open

All lifts will be on the


Fire Floor, + & - All will off Fire Floor, + All will Start on Fire All will Start on Fire
Logic-3 If MCP Pulled ground floor and doors All will Open
One floor & - One floor Floor, + & - One floor Floor, + & - One floor
will remain open

All lifts will be on the


If Fire Signal receives from Flow Fire Floor, + & - All will off Fire Floor, + All will Start on Fire All will Start on Fire
Logic-4 ground floor and doors All will Open
Switch One floor & - One floor Floor, + & - One floor Floor, + & - One floor
will remain open

If Fire Signal receives from Bus


Logic-5
Terminal