Emergi-Fire Sensa with Alarmsense

The Emergi-Fire Sensa control panel operating


with Apollo Alarmsense devices is an advanced
and cost-effective 2-wire fire system for small to
medium-sized buildings. System flexibility
enables use in applications such as ‘dwellings
and in houses of multiple occupation’ (HMO)
and distributed buildings using a proven and
extensive networking capability.
In summary this is a flexible, reliable and cost
effective fire detection system that is easy to install
and extend.

Eurofire Sensa panels


Eurofire Sensa panels are designed to comply with the
European Standard EN54 Parts 2 and 4 and are
suitable for BS 5839-1:2002 and BS 5839-6:2004
installations.
Panels are available in 4, 8, 12 or 16 zones of fire
detection cover, with powerful and flexible setup,
control and display capabilities.

AlarmSense devices
AlarmSense devices (detectors, manual call points,
sounders, sounder beacons and alarm relays) are
designed to operate normally on the same pair of
zone wires from the panel. A key feature is that alarm
sounders can be programmed to operate as so-called
‘priority’ or ‘non-priority’ devices.

The principle of priority and


non-priority response
In a Sensa system, the nominal operating voltage is
12 volts, which enables AlarmSense detectors and (i.e. heat or fumes from cooking). After 2 minutes, if
manual call points (MCPs) to operate. Sounders and the detector is still activated, the Eurofire panel will
beacons operate at 24 volts, so remain dormant at this go into a full fire situation. At any time during the
stage. When a detector or MCP is activated, the panel alert period, if another device is activated, the system
will register a change and will take the zone voltage goes into a full fire situation.
up to 24 volts, which will switch the sounders on.
Eurofire can be programmed to react to ‘non-priority’
A ‘priority’ set device reacts as a normal sounder in signals in one of two ways:
standard use and sounds a full alarm. A ‘non-priority’
set device will give an initial local alert prior to going ● The panel sends out a ‘non-priority’ pattern to the
into full alarm. zone, which causes only the sounder on the
activated detector to sound, or
AlarmSense sounder and sounder beacon bases are
changeable between ‘priority’ and ‘non-priority’ modes. ● The panel sends out a ‘non-priority’ pattern to all
zones, which have been set to include ‘non-
‘Non-priority’ devices are intended for use in HMO priority’ devices. This will cause any local response
type applications where there are a number of (LR) devices set as ‘non-priority’ to also sound –
individual dwellings. The operating method is no other ‘non-priority’ devices will sound.
intended to help reduce the instances of unwanted
alarms and give a local warning before the full If another device of any type or a ‘priority/non-
alarm/evacuation. priority’ is activated during the alert period, the
system goes into a full fire alarm condition.
A sounder-beacon base (with a detector on the base
seat) when set to ‘non-priority’, will sound a local alert A ‘non-priority’ alert cannot be generated if the
for 2 minutes at that locality. People in the vicinity or system is already in a fire alarm condition.
36
occupants in the dwelling will be the first warned of a When a heat detector is attached on a sounder or
possible fire situation or false alarm. They will have sounder beacon base, we recommend that the
2 minutes to investigate and rectify a false alarm, sounder be set as a ‘priority’ device.

Conventional | Emergi-Fire Sensa with Alarmsense www.emergi-lite.co.uk


Programming non-priority detectors
for local alarm operation
The diagram below illustrates a 2-storey block containing After the alert period, with fumes dispersed, the panel
3 flats and an entrance lobby. A Eurofire panel controls will return to the quiescent state. If the detector
the fire alarm system for all 3 flats. Manual call points are remains activated after the alert period, the panel will
situated in the lobby and along the corridors. Sounder go into a full fire alarm condition.
detector bases are situated throughout with a separate
sounder adjacent to the fire panel. Scenario 2 – Non-priority detector in Flat 1 is
activated as a real fire condition
Scenario 1 – ‘Non-priority’ detector in Flat 1 The sequence is the same as in the first scenario, until
activates owing to fumes from cooking the 2-minute alert period is over. After the alert
The base sounder above the detector will sound for 2 period, with a real fire, the detector remains activated
minutes (alerting the occupants in flat 1). and the panel will go into a full fire alarm condition.
The sounder beacon (Zone 8) next to the panel Scenario 3 – Detector or MCP is activated as a fire
activates, if it is programmed for local response (LR).
The occupant has time to expel the smoke from the The panel goes into a full fire situation. If a ‘non-
detector vicinity. priority’ detector is activated afterwards – the panel
treats this as a normal detector being activated in a
During this period, the panel indicates ‘Zone 1 Local fire situation.
Alert’, and sounds the buzzer in the control panel. The
responsible person has time to investigate the alert
and act accordingly. If any detector or MCP activates Key:
during the alert, the system goes into a full fire
Sounder-beacon base
situation and sounds the alarm. Manual call point

Combined sounder-detector
base (priority set)
Standalone smoke alarm

Combined sounder-detector
base (non-priority set)

Zone 5
Floor 2
Zone 6
Up

# # Zone 2
Zone 3

Flat 3 Flat 2

Floor 1 Zone 7
Zone 4
Up

#
Zn8 Zone 1
Zn1
Zn7
Zn6

Zn5 Flat 1
CIE Zn2
Zn4 Zn3

37
# = Set as non-priority detector
Apartment building with a floor plan of 2 floors: Illustration of
detector programming for local alarm operation

www.emergi-lite.co.uk Emergi-Fire Sensa with Alarmsense | Conventional


Eurofire Sensa 2-wire panels

Eurofire Sensa 2-wire fire panels Benefits and features


Comprehensive zone coverage:
Available in 4, 8, 12 or 16 zone
models.
Zone capacity:
Nominally 30 devices per zone.
Soft select:
Non-latching or latching zones:
The non-latching zone feature
allows a better integrity
connection to existing systems
(other manufacture). This prevents
lockout and allows panels to be
reset more readily (the panel
being connected to must have a
spare zone and auxiliary contacts
with a volt-free pair). Short circuit
fire or fault for older systems.
Output wiring:
2-wire configuration to the zones,
giving reduced wiring cost.
Outputs:
4 alarm outputs and auxiliary volt-
free contacts, which are
programmable for continuous,
pulsing or delayed operation.
Fault volt-free relay contacts.
Sounder delay activation:
Eurofire includes a sounder ‘delay-
on’ facility. This allows the user to
programme chosen sounders or
beacons to activate at a later
moment. This is suited to
applications where it is beneficial
not to have undue panic, such as
in bars or Soft Play centres.
2-wire and 4-wire system
integration:
The Eurofire system has the ability
to recognise and operate a 4-wire
zone, which can potentially save on
Eurofire Sensa is a range of conventional (non-addressable) fire wiring when a refurbishment is
detection panels with extensive safety, technical and practical undertaken. For example in a small
hotel or guesthouse where no
features for the installer and user. Eurofire Sensa panels are
sounders or sounder-beacons are
designed to comply with the European Standard EN54 Parts 2 and 4 fitted in bedrooms, a bedroom zone
and are suitable for BS 5839-1:2002 and BS 5839-6:2004 can be the 2-wire format, with
installations. detectors and alarms wired on the
Panels are available in 4, 8, 12 or 16 zones of fire detection cover, with same pair. Other existing 4-wire
powerful and flexible setup, control and display capabilities and are zones in the building can remain if
configured to operate with Apollo AlarmSense devices. desired (it will be necessary to check
for sounder tone compatibility).
The 2-wire convention uses one pair of wires for the connection of Sensa-
compatible devices (detectors, manual call points and alarm sounders). This Networking capability:
gives the scheme designer a greater flexibility of choice, whilst retaining Coverage in larger building
compliance with the relevant standards. Benefits can be seen in having complexes can be achieved by
reduced field wiring costs and time saving with ease of installation. linking Eurofire EN54 panels and
repeaters together via a ‘CAN
Panels are supplied as a complete package, with all end of line devices,
38 Connect’ link. It is also possible to
batteries and a logbook included.
make more power available for
sounder circuits, or save on field
wiring.

Conventional | Eurofire Sensa 2-wire panels www.emergi-lite.co.uk


Eurofire Sensa 2-wire panels

Panel Display
The Eurofire Sensa panel includes an easy to reference display with LCD screen allowing for up to four lines of text,
with text programmable for each zone. 6 buttons are included on the front of the panel which can be used to access
the following functions:
● Lamp test, silence alarms, silence buzzer
● User zone, sounder and 2-wire sounder isolation
● Walk and alarm test facility with mute option
● 99-event history log that stores any events with
time and date stamp, for the user to scroll
● Configurable system message for the user with
normal time and date displayed
The panel also features indicator LEDs which advise
the current state of the fire detection system, and give
a clear signal of fire or fault in any particular zone.
Further functionality includes the facility to review
event logs, to override any pre-set alarm delays, and
to enable sounding the evacuation to all zones.

Indicator details
The panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminate
or flash to establish the zone affected.

Networking capability
Fire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaters
together via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possible
to make more power available for sounder circuits (additional 4), or save on field wiring:

Scenario: In a
building, one panel
might be sited in the
office area and one
in the warehouse
area. The zones for
each area are wired
to their respective
panels. Network the
panels and the
office unit has full Eurofire c-net Eurofire c-net

visibility of the
building. It may be
CAN NET CARD

CAN NET CARD

necessary to use a
higher rated cable Isolated Isolated
and the Emergi-Lite CAN CAN
CAN network network CAN network network
network card (please
contact Technical
sales for further
guidance).
To next
panel

Eurofire c-net

39
Illustration: Network of Eurofire panels, in star format
[wired to the CAN network facility]

www.emergi-lite.co.uk Eurofire Sensa 2-wire panels | Conventional


Eurofire Sensa 2-wire panels

Connection diagram
The diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points, with settings for
both ‘priority’ and non-priority’.

Z1: Priority zone


EOL diode on last detector
o o [cathode to zone +ve end]
No spurs

o
Z3: Non- No spurs
o priority zone

2- wire zones; 2 & 4 to 8,


wired as priority or non
- EOL
priority EOL diode to unused zones [cathode to zone, resistor in
o o +ve end] unused
alarm ccts
Auxiliary relay
contacts
Fault 1 Fault 2

NC C NO NC C NO NC C NO NC C NO +Z1- +Z2- +Z3- +Z4- +Z5- +Z6- +Z7- +Z8- +Z9- +Z10- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16- +AL1- +AL2- +AL3- +AL4-

Common fault
TTL fault

Bomb alert
GND

Class change
Aux 1 Aux 2

Prog i/p
Additonal alarm
circuits

Aux Aux CAN network Isolated CAN network


Batt outputs i/p
AC AC - + - 12v + - 24v + - 24v + HI LO SCR HI LO SCR HI LO SCR HI LO SCR

Priority 2w Standard
Key: Call point -2w
sounder sounder Eurofire Sensa 2 wire: Illustration of zonal wiring
Optical 2w 2w Sounder, set
o detector as non-priority

Fire exit Fire exit


Eurofire 2-wire Kitchen

zonal layout A1R

The illustration below o


o
o o
shows a potential scheme
layout for a Eurofire panel, o

over 5 active zones, with EOL

Zone circuits to o
1 additional alarm circuit. Eurofire 2w o
Sensa panel
EOL
Key: o
SEOL
o o
o
Call point o

Optical smoke detector Programmable


o
sounder circuits
from the panel ROOF
WINDOW
EOL

Heat detector CONTROL

A1R
A1 R

Sounder (priority)

Sounder-beacon (priority) EOL


o

Beam
detector set
Apex roof Motorised
window
EOL End of line device vents
-detector circuit

SEOL
End of line device -
alarm circuit
40 Auxiliary
circuits
o

Zone: detection circuit


wiring
EOL

A1R

Alarm circuit wiring Fire exit

Conventional | Eurofire Sensa 2-wire panels www.emergi-lite.co.uk


Eurofire Sensa 2-wire panels

Eurofire Sensa, 2-wire panel technical specification


PRODUCT ORDER CODE FEWN-4 FEWN-8 FEWN-12 FEWN-16
No. of zones 4 Zone 8 Zone 12 Zone 16 Zone
Detectors per zone 30 per zone, maximum
Sounders per zone [1] 30 per zone, maximum
Sounder-Beacons per zone [2] 15 per zone, maximum
Zone Sounder Current (panel total) 1.25A max (see notes 1 & 2)
Sounder current 5mA at either low (70dBA) or high (87dBA) output
Sounders per panel 250
Sounder-Beacon Current 9mA at either low (70dBA) or high (87dBA) output
Sounder-Beacons per panel 135
Inputs Class change, Bomb Alert, Programmable
Display 4 x 20 character LCD + zone fire & fault LEDs and system LEDs
Mains input voltage 230Vac +10% –6% 50Hz
Output auxiliary voltage, DC 24Vdc @ 250mA 12Vdc @ 250mA
Battery size 12V 7AH x 2 (connected in series)
Battery standby Minimum 24 hours (please contact technical sales for further information.)
Construction: Metal back box with moulded polycarbonate front panel in cool grey
Panel dimensions hwd (mm) 469 x 373 x 103
Detector & call point compatibility Sensa – Alarmsense detectors, call points and alarm devices.
Programmable features Extensive via buttons and LCD display
CAN Network Panel and repeater combinations via CAN 2.0b link
Outputs:
Alarm Lines 4
Alarm current total 1.25A- zone sounder current, see note 3
Auxiliary outputs 2 sets of volt free contacts, rated @ 2A 30Vdc
Fault outputs 2 sets of volt free contacts, rated @ 2A 30Vdc
Notes:
[1] – Version 2 sounders only
[2] – Using version 2 sounder-beacons only
[3] – Total Panel Alarm Current is 1.25A. The total zone sounder current must be taken into account when deciding how much load is available for alarm lines
AL1 – 4
For example: a maximum of 250 sounders (5mA each) or 135 sounder beacons (9mA each) can be loaded onto the system.

Warning: do not use FAP6 detectors on Alarmsense systems. Although they would appear to work initially, using them could cause severe system malfunction in the longer term. Also be
aware that if used with the Sounder/Sounder Beacon Bases the non-priority function will not operate correctly.

Eurofire Repeater panel


PRODUCT ORDER CODE FEUN-RP
Connections 2-core for data from the main panel and 2-core for 24 Vdc power
Display 4 x 20 character LCD with Zone, Fire and Fault LEDs
Inputs Data and DC supply inputs from the main panel (repeater loading must be included when calculating load at the main panel)
Outputs 4 programmable alarm outputs (load to be included in main panel alarm load)
Construction Metal back box with moulded polycarbonate front panel in cool grey
Dimensions hwd (mm) 469 x 373 x 103

To Order
STANDARD ORDER CODE DESCRIPTION ACCESSORIES

FEWN-4 Eurofire 4 Zone Panel F4ALMB 4 way Alarm Extender

FEWN-8 Eurofire 8 Zone Panel F4COB Relay Unit, 4 pole

FEWN-12 Eurofire 12 Zone Panel FEUN-EOL-KIT End of Line Component Kit

FEWN-16 Eurofire 16 Zone Panel FEUN-NETCAN CAN Isolator Assembly

OPTIONS FEUR-BG Semi-recessing bezel grey

Suffix LD Lockable door option for Eurofire Panel FEUN-SPARES Eurofire Spares Pack

FEUN-RP Eurofire Repeater Panel

41

www.emergi-lite.co.uk Eurofire Sensa 2-wire panels | Conventional


Firetec Sensa 2-wire panels

Firetec Sensa 2-wire fire panels Benefits and features


The panel is easy to install and
comes with a wide range of
features for the user and
maintenance engineer.
The panel enclosure is shaped
with gentle curves and clean lines
to fit in with surrounding décor.
Comprehensive zone coverage:
Available in 2, 4 or 8 zone models.
Zone capacity:
Nominally 25 devices per zone.
Output wiring:
2-wire, giving reduced wiring cost.
Standby duration:
48 hours
Walk test:
1 man operation
Security coded push button entry:
Status can be checked via level 1.
Subsequent levels are password
protected for the authorised user
and engineer respectively
Programmability:
Several features such as ‘priority –
non priority setting’, ‘delays to
alarms’, ‘day mode’ are available
to tailor the function of the panel
Firetec Sensa is a range of conventional (non-addressable) fire to local requirements.
detection panels offering a practical, cost effective fire safety Details are listed in the
solution for smaller to medium sized premises. Firetec Sensa panels specification table.
are designed to comply with the European Standard EN54 Parts 2 Outputs:
and 4 and are suitable for BS 5839-1:2002 and BS 5839-6:2004 Output facilities for Alarm,
installations. Volt-free alarm and TTL Fault.
Firetec Sensa is now more versatile than ever with the ability of handling
detection and alarm in up to 8 separate zones. Panels are available in STANDARD DESCRIPTION
2, 4 and 8 zones of fire cover, with flexible setup, control and display ORDER CODE
capabilities, and are configured to operate with ‘2-wire’ Sensa: Alarmsense FTEW2 Firetec 2 Zone Panel
detection and alarm devices. FTEW4 Firetec 4 Zone Panel
The 2-wire convention uses one pair of wires for the connection of Sensa- FTEW8 Firetec 8 Zone Panel
compatible devices (detectors, manual call points and alarm sounders). This
gives the scheme designer a greater flexibility of choice, whilst retaining
compliance with the relevant standards. Benefits can be seen in having Note: Firetec Sensa 2-wire panel
reduced field wiring costs and time saving with ease of installation. available soon. Please contact
Emergi-Lite Sales Team for further
Panels are supplied as a complete package, with all end of line devices,
details.
batteries and a logbook included.

Secure panel operation:


Key switch activation option
For installations where it is necessary to secure the panel from interference,
a key switch option is available, which enables or disables the control
buttons on the front fascia. To order this option a suffix KS should be
added to the standard product code.
42
OPTION

Suffix KS Optional security keyswitch for Firetec panels

Conventional | Firetec Sensa 2-wire panels www.emergi-lite.co.uk


Firetec Sensa 2-wire panels

Display & user interface


The Firetec Sensa panel includes a clear, easy to
reference push button and LED display capable of
providing the user with all the necessary information
to determine fire, fault or ‘fire and fault’ within a
particular zone. 5 buttons are included on the front of
the panel which can be used to access the following
functions:
● Silence alarms or enable/disable zones
● Silence buzzer
● User zone and 2-wire sounder isolation
● Lamp test
● Walk and alarm test facility
● Reset function

Indicator details
The panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminate
or flash to establish the zone affected.
The panel also features indicator LEDs which advise the current state of the fire detection system, to highlight
system, earth, or supply faults, system disabled or test status, and alarm silenced mode.

Connection diagram
The diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.

End of line resistor


10K, on last
sounder

o
EOL diode on last o
detector [cathode No spurs
to zone +ve end]

o
No spurs
Z3: Non-
priority zone
o

Zones 2,4,5 wired but


not shown

Enable alarm
delay switch
EOL diode to unused C - Class
zones [cathode to EOL change switch
o o
zone, +ve end] resistor in
Z1: Priority zone unused C
alarm cct

+Z1- +Z2- +Z3- +Z4- +Z5- +Z6- +Z7- +Z8- +AL2- +AL1- Aux 1 Aux 2 Lo Hi +Aux-
NC C NO NC C NO 24v
Class change

Mon input
Enable delay

TTL fault

Auxiliary relay
GND

Alarm circuits
contacts

Call point Non-prioity alarm device

Detector Standard alarm device


43
o

Priority alarm device

www.emergi-lite.co.uk Firetec Sensa 2-wire panels | Conventional


Firetec Sensa 2-wire panels

Firetec Sensa, 2-wire panel technical specification


PRODUCT ORDER CODE FTEW2 FTEW4 FTEW8
No. of Zones 2 Zone 4 Zone 8 Zone
Detection Circuits Compatible with Emergi-Lite Sensa sounders, manual call points, smoke and heat detectors, Emergi-Lite Sensa zone
sounders & zone sounder-beacon bases, Emergi-Lite Sensa priority/non priority devices
Detectors per Zone 25 Detectors per zone
Total Alarm Current (panel total) 1A, see note 1
Maximum Alarm Current Per Zone 0.15A
Sounders Per Zone 25
(Low{70dB(A)} 5mA
High{87dB(A)} 5mA)
Sounder-Beacons Per Zone 16
(Low{70dB(A)} 9mA
High{87dB(A)} 9mA)
Alarm Lines [AL1 & AL2] 2 Alarm circuits per panel each rated @ 24Vdc 0.5A max, panel total is 1A. Each sounder circuit protected by a resettable
fuse - resets when fault is removed. Expandable to 8 circuits in groups of 4 with 4 way alarm extender board
Auxiliary Relay Contacts 2 Sets of volt-free contacts rated 30Vdc @2A - activated during a fire condition when the alarm circuits are activated
Auxiliary Output 24Vdc rated 250mA protected by resettable fuse - resets when fault is removed.
Class Change Connect CC to Gnd terminal to activate sounders.
Fault Monitoring Zone: Short circuit & open circuit/detector removed monitoring using end of line device
Alarm: Short circuit & open circuit using end of line resistor
Mains Input Voltage 230Vac +10% -6%, 50Hz (mains fuse: 20mm, 240Vac 1A High rupture capacity)
Battery 1 x 12V 7AH VRLA (valve regulated lead acid) battery. Temperature compensated charger. Deep discharge protected with
cut off at approx. 10.5V. Protected by a resettable fuse - resets when fault is removed.
Battery Standby 48 hours. For more details refer to technical sales for standby calculations.
Supply Fault Monitoring Mains missing - battery missing - battery charger fault
Controls 5 push buttons with coded entry access
Construction Moulded polycarbonate plastic fascia and back box in cool grey
Dimensions hwd (mm) 263 x 337 x 90
Fault Output TTL fault output: Active (5Vdc) when no faults are present - fail safe to off

Programmability Zones individually programmed as latching or unlatching fire conditions


Zones individually programmed as Priority or Non Priority
Class change can be programmed to illuminate 'general fire' led when activated.
Delay of 1-10 mins to alarms activating in a fire condition - this works in conjunction with
Enable delay' input. 'Enable delay' can also be used as a 'day switch/input.'

Notes:
1 Total panel alarm current, is total zone alarm current + total sounder current on AL1 & AL2. Total should not exceed 1A.
2 Ensure that maximum number of sounders/sounder-beacon devices does not exceed total current allowed for zones.
30 sounders on a zone = 5mA * 30 = 0.15A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on zone.
16 sounder-beacons on a zone = 9mA * 16 = 0.144A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on the zone.
Sounders and sounder-beacon devices can be used together on a zone but should not exceed the maximum alarm current per zone.
3 Current available for alarm lines AL1 & AL2 = 1A - Total zone alarm current being used.

44

Conventional | Firetec Sensa 2-wire panels www.emergi-lite.co.uk


AlarmSense devices

AlarmSense devices (detectors, manual call points, sounders, sounder beacons and alarm relays) are
designed to operate normally on the same pair of zone wires from the panel. A key feature is that
alarm sounders can be programmed to operate as so-called ‘priority’ or ‘non-priority’ devices.
A ‘priority’ set device reacts as a normal sounder in
standard use and sounds a full alarm. A ‘non-priority’
set device will give an initial local alert prior to going
into full alarm.
‘Non-priority’ devices are intended for use in HMO type
applications where there are a number of individual
dwellings. The operating method is intended to help
reduce the instances of unwanted alarms and give a
local warning before the full alarm/evacuation.
When a heat detector is attached on a sounder or
sounder beacon base, we recommend that the sounder
be set as a ‘priority’ device.
For more information about priority/non-priority
devices, please refer to pages 36 – 37.

Device benefits and features


The table below highlights the key features of the sounder bases and sounder-beacon bases available as part of our
conventional 2-wire range.

Amber, Clear or Red lens

Apollo Alert / Evac tone


Red or White body

Integrated base

Conventional

Accessories
Features:

Sounder
Beacon

PRODUCT CODE DESCRIPTION


FAPW2-BS24W Sounder base ✔ W ✔ ✔ ✔

FAPW2-BSB24W Sounder base beacon ✔ ✔ C W ✔ ✔ ✔

FAPW2-CBSW Sounder base cap W ✔

FAPW2-CBSR Sounder base cap R ✔

Detector base FAPW2-ASB


The Sensa detector base is specific for the Sensa detector range. Electronic
circuitry is included, which monitors the presence of the detector and will
signal a fault if a device is removed.

SPECIFICATION
Quiescent current at 15V <30µA
Load shown to the zone with 47Ω for 10ms every 4 seconds
head removed
Wiring & polarity 2 wire supply, polarity insensitive
Termination Connectors accept up to 2.5mm2 cables
FAPW2-ASB
Construction White moulded polycarbonate
Dimensions ø d (mm) 100
Weight g 55

45

www.emergi-lite.co.uk AlarmSense devices | Conventional


AlarmSense devices

Sounder base unit FAPW2-BS24W


A compact low profile device fitted with a base seat for fitting compatible
smoke or heat detectors. For standalone use, optional caps in red or white
are available. The sounder has a volume control (DIL switch selection for
high or low output) and can operate within the ‘priority/non-priority’
signalling regime.

SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 12V <20µA
Sounder active current @ 24V 5mA
Sound output dBA, high volume 87
FAPW2-BS24W
Low volume dBA 70 nominal
Operating temperature –20 to +60ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Connectors accept up to 2.5mm2 cables
Construction Polycarbonate/ABS
Dimensions ø d (mm) 115 x 40
Weight g 150
Standards EN54-3
OPTIONS
FAPW2-CBSW White cap
FAPW2-CBSR Red cap

Sounder beacon base FAPW2-BSB24W


A compact low profile device with visual and sound warning indication.
The unit is fitted with an integral base seat for fitting compatible smoke or
heat detectors. For standalone use, optional caps in red or white are
available. The sounder has a volume control (DIL switch selection for high
or low output) and can operate within the ‘priority/non-priority’ signalling
regime.
Suited to premises where visual warning indication is needed for the hard
of hearing.
Enables the user to comply with the Disability Discrimination Act (DDA).

FAPW2-BSB24W SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 12V <20µA
Sounder active current @ 24V 9mA
Sound output dBA, high volume 87
Low volume dBA 70 nominal
Operating temperature –20 to +60ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Connectors accept up to 2.5mm2 cables
Construction Polycarbonate
Dimensions ø d (mm) 115 x 40
Weight g 150
Standards EN54-3
OPTIONS
FAPW2-CBSW White cap
FAPW2-CBSR Red cap

Application
Owing the level of sound these devices can produce; they are effective for
46 local use. For example, in situations where there is a corridor with a
number of adjoining rooms, closed doors can reduce the sound level
somewhat. Consequently, it is recommended that this type of sounder
should be placed in both the room and the corridor.

Conventional | AlarmSense devices www.emergi-lite.co.uk


AlarmSense devices

Optical smoke detector FAPW2-OP


The optical detector measures the level of smoke particles using light
scatter, then going to alarm at a pre-set threshold.

Integrating optical smoke detector FAPW2-OP-INT


This detector is available for spaces in buildings where smoke particles
(cigarette smoke for example) might be present normally, to help avoid
false alarms.

SPECIFICATION
FAPW2-OP
Voltage range 9 – 33Vdc
Quiescent current at 15V <50µA
Alarm current at 2 – 8.5V <1.5mA
10.5 – 15V 25 +/- 2mA
Wiring & polarity 2 wire supply, polarity insensitive
Construction Polycarbonate
Dimensions ø d (mm) 100 x 42
Weight g 100
Standards EN54-7: 2000

Rate of rise device, grade A1R FAPW2-R6


The detector monitors the rate of temperature rise in the vicinity and will
also trigger when a fixed upper threshold of 50°C is reached.

Fixed temperature detector, grade CS FAPW2-F84


The static heat detector will signify fire, when a preset temperature is
reached. The CS device will trigger at 80°C.

SPECIFICATION
Voltage range 9 – 33Vdc
FAPW2-R6
Quiescent current at 15V <50µA
Alarm current at 12V <1.5mA
24V 25 +/- 2mA
Grades A1R & CS
Wiring & polarity 2 wire supply, polarity insensitive
Construction Polycarbonate
Dimensions ø d (mm) 100 x 42
Weight g 100
Standards EN54-5: 2000

FAPW2-F84

47

www.emergi-lite.co.uk AlarmSense devices | Conventional


AlarmSense devices

Surface mount unit FMFW2-800


The Sensa call point is fitted with frangible element. A key test facility is
situated underside, which is fully reset when the key is removed. The device
is detected as an operated call point by the Sensa system.

SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 15V <50µA
Alarm current at 2 – 8.5V <1.5mA
10.5 – 15V 25 +/- 2mA
Wiring & polarity 2 wire supply, polarity insensitive
Reset time 1 second
LED indicator Red
FMFW2-800
Construction Polycarbonate/ABS
Dimensions ø d (mm) 87 x 87 x 52
Weight g 170
Standards EN54-11: 2000
ACCESSORY
RSL800 Fire call point notice sticker

RSL800

Protective covers for manual call points


A tough protective cover is available to help prevent accidental operation
of call points, or prevent unauthorised use by those with malicious intent.
The cover is suitable for use in educational buildings, hospitals, nursing
homes or places where the threat of false alarm is prevalent.

STANDARD ORDER CODE DESCRIPTION

FMC-ST30 Surface mount protective cover, with 30mm spacer

FMC-ST50WP Surface mount weatherproof cover, with 50mm spacer

For further options, please contact technical sales.

FMC-ST30

48 FMC-ST50WP

Conventional | AlarmSense devices www.emergi-lite.co.uk


AlarmSense devices

Standard remote indicator unit FAP6-P10


(standard base)
A remote indicator is used to help an investigator quickly identify the
location where a device has registered a fire, without having to gain entry
to every room or inaccessible space.

o o
Normal FAP6-P10
detection:
Closed room Indicator visible
space

Solid door Vision panel in door

Remote indicator
Corridor

Remote indicator unit FMFW2-PBD20

Remote LED board


(sounder base or sounder beacon base)

-ve
Zone

The PBD version is designed to show indication from a detector fitted to a

-R
+ve
Zone

sounder base or sounder beacon base in premises such as an HMO. Zone in


Zone out

R5
SPECIFICATION L1 zone +ve

L2 zone -ve

LED indicator Red


Construction Polycarbonate/ABS Connection of remote LED unit to Sensa
sounder or sounder-beacon bases
Termination Terminal block
Dimensions ø d (mm) 85 x 85 x 5
Weight g 38.2

Alarm relay FAPW2-ALR


This ancillary unit allows external items, including paging devices and
magnetic door closers to be connected to the 2-wire fire detection system.
The relay can be configured to provide two sets of volt-free contacts for
use by external devices.
Selectable DIL switch features:
● A relay-reset delay of 2 seconds is selectable by DIL switch.
● Non-priority signals from the fire panel can be recognised at the relay
according to a DIL switch setting, which could enable the relay to be
used as a stand-alone alarm indicator or activate an external function
like a staff alarm.

SPECIFICATION
Voltage range 9 – 33Vdc
Relay operating voltage >18V FAPW2-ALR
Quiescent current at 12V <20µA
Surge current at relay set voltage 15mA for 20ms
Relay contact ratings 1A at 30Vdc
Wiring & polarity 2 wire supply, polarity sensitive
Termination Connectors accept up to 2.5mm2 cables
Dimensions ø d (mm) 65 x 45 x 25
Weight g 35
Standards EN54
49
Commissioning note: At commissioning the relay should be reset prior to
use. During operation the relay will reset if there is a power loss on the fire
alarm circuit.

www.emergi-lite.co.uk AlarmSense devices | Conventional


Eurofire 4-wire panels

Eurofire 4-wire fire panels Benefits and features


The panel has an extensive array
of useful tools and features
designed to help both the installer
to set up the system easily and the
user to manage the system
effectively.
Standby duration:
48 hours
Zone capacity:
Up to 30 devices per zone.
Soft select:
Non-latching or latching on fire:
The non-latching zone feature
allows a better integrity
connection to existing systems
(other manufacture). This method
will monitor the interconnection
between panels and allow panels
to be reset more readily (the
panel being connected to, must
have a spare zone and alarm line
or auxiliary contacts with a
volt-free pair). Short circuit fire or
fault for older systems.
Security control:
Coded push button entry:
The status viewer has quick entry at
level 1. Levels 2 and 3 are password
protected for the authorised user
and Engineer respectively.
Outputs:
4 Programmable Alarm outputs.
Fire auxiliary volt-free relay
contacts, which are programmable
for continuous, pulsing and
delayed operation. Fault volt-free
relay contacts.
Output wiring:
Conventional 4-wire to the zones.
2-wire zone selection:
In instances, where it is desired to
run a zone of 2-wire devices, the
Traditionally, conventional fire systems have been wired as ‘4-wire’ panel can be programmed to
achieve this by a trained
installations, where the detection and alarm devices are wired
commissioning engineer.
separately from the panel. This does give some integral protection
where the alarm circuit would not be affected by a fault on the Sounder delay activation:
A sounder ‘delay-on’ facility
detection side. allows the user to programme
Eurofire EN54 is a conventional (non-addressable) fire detection system chosen sounders or beacons to
with enhanced safety, technical and practical features for the installer and activate at a later moment. Ideal
user. Eurofire EN54 panels are designed to comply with the European where it is beneficial not to have
Standard EN54 Parts 2 and 4 and are suitable for BS 5839-1:2002 and undue panic, such as in bars or
BS 5839-6:2004 installations. Soft Play centres.
Panels are configured to operate with ‘4-wire’ detection and alarm devices Networking capability:
and are available as a standalone panel for 4, 8, 12 or 16 zones of fire Coverage in larger building
cover, ideal for medium sized premises. Alternatively, for larger installations complexes can be achieved by
linking Eurofire EN54 panels and
Eurofire can be networked with sister Eurofire panels and repeaters for
repeaters together via a ‘CAN
complete cover over the site.
Connect’ link. It is also possible to
50 Panels are supplied as a complete package, with all end of line devices, make more power available for
batteries and a logbook included. sounder circuits or save on field
wiring.

Conventional | Eurofire 4-wire panels www.emergi-lite.co.uk


Eurofire 4-wire panels

Panel Display
The Eurofire panel includes an easy to reference display with LCD screen allowing for up to four lines of text, with
text programmable for each zone. 6 buttons are included on the front of the panel which can be used to access the
following functions:
● Lamp test, silence alarms, silence buzzer
● User zone and sounder isolation
● Walk and alarm test facility with mute option
● 99-event history log that stores any events with
time and date stamp, for the user to scroll
● Configurable system message for the user with
normal time and date displayed
The panel also features indicator LEDs which advise
the current state of the fire detection system, and give
a clear signal of fire or fault in any particular zone.
Further functionality includes the facility to review
event logs, to override any pre-set alarm delays, and
to enable sounding the evacuation to all zones.

Indicator details
The panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminate
or flash to establish the zone affected.

Networking capability
Fire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaters
together via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possible
to make more power available for sounder circuits (additional 4), or save on field wiring:

EOL
Scenario: In a
building, one panel
EOL

might be sited in the


o
office area and one SEOL
Zone 7
in the warehouse
o
area. The zones for
o
each area are wired
EOL

Zone 2
to their respective o
o

panels. Network the Zone 8


panels and the A1 R

office unit has full


EOL

c s

visibility of the SEOL


building. It may be o
necessary to use a o
higher rated cable
and the Emergi-Lite o

network card (please Zone 1


contact Technical
sales for further
guidance). 4 sounder circuits, 2
shown connected

Illustration: 8 zone Eurofire


Eurofire c-net with network panel connected

51

Network

www.emergi-lite.co.uk Eurofire 4-wire panels | Conventional


Eurofire 4-wire panels

Connection diagram
The diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points.

EOL diode on last


detector [cathode
to zone +ve end]
No spurs o

o
No spurs
o

EOL
Zones 2-8 wired as Z1 resistor in
unused
EOL diode to unused
alarm ccts
o zones [cathode to
zone, +ve end]
Auxiliary relay
contacts
Fault 1 Fault 2

NC C NO NC C NO NC C NO NC C NO +Z1- +Z2- +Z3- +Z4- +Z5- +Z6- +Z7- +Z8- +Z9- +Z10- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16- +AL1- +AL2- +AL3- +AL4-

Common fault
TTL fault

Bomb alert
GND

Class change
Aux 1 Aux 2

Prog i/p
Alarm circuits

Aux Aux CAN network Isolated CAN network


Batt outputs i/p
AC AC - + - 12v + - 24v + - 24v + HI LO SCR HI LO SCR HI LO SCR HI LO SCR

Eurofire 4-wire zonal layout


The illustration below shows a potential scheme layout for a Eurofire panel, over 5 active zones, with 4 alarm circuits.
Fire exit
Key:
Kitchen
Illustration: cs
Call point
Scheme layout using a SEOL

Eurofire panel [5 zones active, o Optical


EOL

o o
with four alarm circuits] smoke
o
detector

o Heat detector
c s
o
EOL End of line device -
detector circuit
o SEOL End of line device -
alarm circuit
EOL

o o
Sounder
o
Fire o EOL
exit o
o Sounder-beacon

SEOL
Beam detector set

Zone circuits to Zone: detection circuit


wiring
Eurofire 4w o
panel Alarm circuit wiring

EOL SEOL

o Apex roof
SEOL

Programmable o
52 sounder circuits from
the panel
o
EOL

Fire exit

Conventional | Eurofire 4-wire panels www.emergi-lite.co.uk


Eurofire 4-wire panels

Eurofire conventional, 4-wire panel technical specification


PRODUCT ORDER CODE FEUN-4 FEUN-8 FEUN-12 FEUN-16
No. of zones 4 Zone 8 Zone 12 Zone 16 Zone
Detectors per zone 30 per zone maximum
No. of alarm lines 4 (expandable to 16 programmed in groups of 4, with card extenders)
Maximum alarm load Total = 1.25A. Maximum per line or circuit = 1A
Inputs Class change. Bomb Alert and Programmable input
Display 4 x 20 character LCD, plus zone fire and fault LEDs
Mains input voltage 230Vac +10%, –6% 50Hz
Output auxiliary voltage, DC 24Vdc & 12Vdc @ 250mA
Battery size 12V 7AH x 2 (connected in series)
Battery standby 24 hours minimum (please contact technical sales for further information.)
Construction: Metal back box with moulded polycarbonate front panel in cool grey
Dimensions hwd (mm) 469 x 373 x 103
Detector & call point compatibility ‘Emergi-Lite Orbis’ and FAP6 smoke and heat with diode base. Manual call points with 220-680 ohm resistor
Outputs:
Auxiliary outputs Two sets of volt-free aux. programmable contacts (rated 2A @ 30Vdc)
Fault outputs Two sets of volt-free fault contacts (rated 2A @ 30Vdc)
Additional options:
FEUN-BG Semi-recessing trim bezel finished in grey
Networking Panels networked using ‘CAN’ Network terminals. An ‘isolated CAN network driver’ is available for isolated networks.
Please contact technical sales for particular need
Zone upgrade Where a user expects to expand coverage in the future a special upgradeable version can be supplied.
Please specify the requirement when requesting a quotation

Eurofire Repeater panel


PRODUCT ORDER CODE FEUN-RP
Connections 2-core for data from the main panel and 2-core for 24Vdc power
Display 4 x 20 character LCD with Zone, Fire and Fault LEDs
Inputs Data and DC supply inputs from the main panel (repeater loading must be included when calculating load at the main panel)
Outputs 4 programmable alarm outputs (load to be included in main panel alarm load)
Battery size 12V 7AH x 2 (connected in series)
Construction Metal back box with moulded polycarbonate front panel in cool qrey
Dimensions hwd (mm) 469 x 373 x 103

To Order
STANDARD ORDER CODE DESCRIPTION ACCESSORIES

FEUN-4 Eurofire 4 Zone Panel F4ALMB 4 way Alarm Extender

FEUN-8 Eurofire 8 Zone Panel F4COB Relay Unit, 4 pole

FEUN-12 Eurofire 12 Zone Panel FEUN-EOL-KIT End of Line Component Kit

FEUN-16 Eurofire 16 Zone Panel FEUN-NETCAN CAN Isolator Assembly

OPTIONS FEUR-BG Semi-recessing bezel grey

Suffix LD Lockable door option for Eurofire Panels FEUN-SPARES Eurofire Spares Pack

FEUN-RP Eurofire Repeater Panel

53

www.emergi-lite.co.uk Eurofire 4-wire panels | Conventional


Firetec 4-wire panels

Firetec 4-wire fire panels Benefits and features


The panel is easy to install and comes with a wide
range of features for the user and maintenance
engineer.
The panel enclosure is shaped with gentle curves and
clean lines to fit in with surrounding décor.
Comprehensive zone coverage:
Available in 1, 2, 4 or 8 zone models.
Zone capacity:
Nominally 25 devices per zone.
Standby duration:
48 hours
Walk test:
1 man operation
Display and user interface:
Indicators for information, fire, fault and ‘fire & fault’
Security coded push button entry:
Status can be checked via level 1. Subsequent levels
are password protected for the authorised user and
engineer respectively
Programmability:
Traditionally, conventional fire systems have A number of features are available including
been wired as ‘4-wire’ installations, where the ‘latching/unlatching zones’, ‘delays to alarm
detection and alarm devices are wired activation’, ‘monitored input’ (which can be on or off).
separately from the panel. This does give some Programmability is detailed in the specification table.
integral protection where the alarm circuit Outputs:
would not be affected by a fault on the A set of output facilities for Alarm, Volt-free alarm
detection side. and TTL fault
Firetec is a conventional (non-addressable) fire
detection panel that is suited for fire detection STANDARD ORDER CODE DESCRIPTION
coverage in smaller premises, such as offices and FTEP1 Firetec 1 Zone Panel
shops. The panel is configured to operate with ‘4-wire’
FTEP2 Firetec 2 Zone Panel
detection and alarm devices and is available as a
standalone panel for 1, 2, 4 or 8 zones of fire cover. FTEP4 Firetec 4 Zone Panel

Firetec panels are designed to comply with the FTEP8 Firetec 8 Zone Panel

European Standard EN54 Parts 2 and 4 and are ACCESSORIES


suitable for BS 5839-1:2002 and BS 5839-6:2004 FTE-EOL-KIT End of Line Component Kit
installations.
FTE-BG Semi-recessing bezel grey
Panels are supplied as a complete package, with all
FTE-SPARES Firetec Spares Pack
end of line devices, batteries and a logbook included.

Secure panel operation:


Key switch activation option
For installations where it is necessary to secure the panel from interference,
a key switch option is available, which enables or disables the control
buttons on the front fascia. To order this option a suffix KS should be
added to the standard product code.

OPTION

54 Suffix KS Optional security keyswitch for Firetec panels

Conventional | Firetec 4-wire panels www.emergi-lite.co.uk


Firetec 4-wire panels

Display & user interface


The Firetec 4-wire panel includes a clear, easy to
reference push button and LED display capable of
providing the user with all the necessary information
to determine fire, fault or ‘fire and fault’ within a
particular zone. 5 buttons are included on the front of
the panel which can be used to access the following
functions:
● Silence alarms or enable/disable zones
● Silence buzzer
● User zone and sounder isolation
● Lamp test
● Walk and alarm test facility
● Reset function

Indicator details
The panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminate
or flash to establish the zone affected.
The panel also features indicator LEDs which advise the current state of the fire detection system, to highlight
system, earth, or supply faults, system disabled or test status, and alarm silenced mode.

Connection diagram
The diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.

EOL diode on last


End of line resistor
detector [cathode
10K, on last
to zone +ve end]
o sounder

No spurs

No spurs o

Enable alarm
delay switch
o Zones 2-5 wired as Z1 EOL diode to unused C - Class
zones [cathode to EOL change switch
zone, +ve end] resistor –
unused C
alarm cct

+Z1- +Z2- +Z3- +Z4- +Z5- +Z6- +Z7- +Z8- +AL2- +AL1- Aux 1 Aux 2 Lo Hi +Aux-
NC C NO NC C NO 24v
Mon input
Class change
Enable delay

TTL fault

Auxiliary relay
GND

Alarm circuits
contacts

Call point

Detector 55
o Firetec 8 zone: wiring illustration -zones & alarms
Alarm device

www.emergi-lite.co.uk Firetec 4-wire panels | Conventional


Firetec 4-wire panels

Firetec conventional, 4-wire panel technical specification


PRODUCT ORDER CODE FTEP1 FTEP2 FTEP4 FTEP8
Zones of Fire Protection 1 2 4 8
Detectors per zone 25
Alarm Lines 2 Alarm circuits per panel each rated @ 24Vdc 0.5A max. 2 Alarm circuits per panel each rated @ 24Vdc 1A max.
Panel total is 0.5A Panel total is 1A
Each sounder circuit protected by a resettable fuse – resets when fault is removed
Expandable to 8 circuits in groups of 4 with 4 way alarm extender board
Power supply:
Supply Fault Monitoring 230Vac +10% -6%, 50Hz (mains fuse: 20mm, 240Vac 1A High rupture capacity)
Supply Fault Monitoring Mains missing – battery missing – battery charger fault
Battery 1 x 12V 7AH VRLA (valve regulated lead acid) battery
Battery charger Battery charger is temperature compensated
Battery deep discharge protection Battery is deep discharge protected (cut off at approx. 10.5V)
Battery fuse protection Battery protected by resettable fuse – resets when fault is removed
48 hours with 20 detectors
Battery Standby [up to 4z, then 8z] 72 hours with 20 detectors per zone and 30 mins of
per zone and 30 mins of
0.75A alarm load
1A alarm
For more details refer to technical sales for standby calculations
Auxiliary output 24Vdc rated 250mA protected by resettable fuse – resets when fault is removed
Auxiliary relay 2 Sets of volt-free contacts rated 30Vdc @2A – activated during a fire condition when the alarm circuits are activated
Panel controls & indicators:
Controls 5 push buttons (with coded entry access)
Indicators 27 LED indicators for fire, fault or fire and fault
Construction: Moulded polycarbonate plastic fascia and back box in cool grey
Dimensions hwd (mm) 263 x 337 x 90
Weight (Kg), without battery 2.55
Cable requirements To comply with the recommendations of BS 5839-1:2002, section 26 for cables, wiring and other interconnections
Detector & call point compatibility * Compatible with Emergi-Lite Orbis smoke and heat detectors with diode base.
* Compatible with FAP6 smoke and heat detectors with diode base.
* Compatible with 220 – 680 Ohm Manual Call Points (MCP).

Programmability Zones individually programmed as latching or unlatching fire conditions


Zones individually programmed as 470 Ohm or short circuit fire detection
Class change can be programmed to illuminate ‘general fire’ led when activated.
Delay of 1-10 mins to alarms activating in a fire condition – this works in congunction with
Enable delay’ input. ‘Enable delay’ can also be used as a ‘day switch/input.’
Class Change Connect CC to Gnd terminal to activate sounders
Fault Monitoring Zone: Short circuit & open circuit/detector removed monitoring using end of line device
Alarm: Short circuit & open circuit using end of line resistor
Fault Output TTL fault output: Active (5Vdc) when no faults are present – fail safe to off
Additional options:
FTEP-BG Recessing bezel kit

56

Conventional | Firetec 4-wire panels www.emergi-lite.co.uk


Emergi-Lite Orbis detectors

Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofire
systems. Non-addressable (conventional) smoke and heat sensors respond to fire situations within a
given zone, sending a signal to the fire panel, which will indicate a fire condition and sound the alarm.
Orbis provides valuable core features, with high reliability, a marked reduction in unwanted false alarms,
complemented by operational and maintenance enhancements.

Features:
● StartUp: Correct installation – a flashing red LED
● Continuity link: Zone wiring can be voltage
tested before commissioning
● Wide-angle optics: Responsive to fires with black
or white smoke
● Drift Compensation: Calibrated sensitivity levels
are maintained despite contamination
● DustDefy: Dust ingress prevented while airflow is
unimpeded
● Transient Rejection: Abnormal readings are
filtered out to reduce false alarms
● DirtAlert: A flashing yellow LED will indicate
when the drift compensation limit has been
reached
● SensAlert: A flashing yellow LED indicates
incorrect sensor operation
● Fast Test: A 4 second test confirms correct detector operation
● E-Z Fit slots: Remove and refit the base without dismounting the fixing screws

Detector base with diode FAPO-TDB


The standard detector base has a diode fitted beneath the connectors. A
link feature enables voltage testing of zone wiring before commissioning.
The base is a five terminal unit – positive IN, positive OUT, Negative IN &
OUT, remote LED negative and functional earth (screen) wire. Two fixing
centre positions are provided at 51 and 60mm.

SPECIFICATION
Construction White moulded polycarbonate
Termination Connectors accept up to 2.5mm2 cables
Dimensions ø d (mm) 100 x 15 FAPO-TDB
Weight g 60

Detector relay base FAPO-TRB


The relay base has a single pole voltage free changeover contact for use to
switch ancillary equipment. When the detector goes to alarm the relay is
energised and changes state.
Contacts rated at 30Vdc, 1A.

SPECIFICATION
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate 57
Dimensions ø d (mm) 100 x 15
FAPO-TRB
Weight g 60

www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional


Emergi-Lite Orbis detectors

Optical smoke detector FAPO-OPT


The optical detector measures the level of smoke particles using light
scatter, going to alarm at a pre-set threshold. New optics help reduce false
alarms while stability is strengthened by using internal software control.
Recommended for general purpose use to give early warning of fire.

SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V 20mA
FAPO-OPT 24V 40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 97 x 31 (100 x 46 inc base)
Weight g 75, 135 with base
Standards EN54-7: 2000

Optical smoke and thermally FAPO-MUS


enhanced detector
The detector uses optical and heat sensing technology in deciding when to
trigger an alarm condition. The unit is designed as a smoke detector and
cannot be switched from smoke to heat detection.
This detector is more sensitive to fast burning, flaming fires than the
optical model. Ideal for where heat is prevalent at an early stage in
the fire.

SPECIFICATION
FAPO-MUS
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V 20mA
24V 40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 97 x 42 (100 x 57 inc base)
Weight g 80, 140 with base
Standards EN54-7: 2000

58

Conventional | Emergi-Lite Orbis detectors www.emergi-lite.co.uk


Emergi-Lite Orbis detectors

Heat detectors – FAPO-HR1, FAPO-HR2, FAPO-HR3


Fixed temperature
The fixed (static) heat detector will trigger when a pre-set upper
temperature threshold is exceeded at the sensor.
Classification – maximum application temperature: HR1 = 50ºC, HR2 = 65ºC,
HR3 = 80ºC

SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
FAPO-HR1
Alarm current at 12V 20mA
24V 40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42
Weight g 100
Standards EN54-5: 2000

STANDARD ORDER CODE DESCRIPTION


FAPO-HR1 Heat detector – Fixed upper threshold 50ºC, A2S
FAPO-HR2 Heat detector – Fixed upper threshold 65ºC, BS
FAPO-HR3 Heat detector – Fixed upper threshold 80ºC, CS

Heat detectors – FAPO-RR1, FAPO-RR2 , FAPO-RR3


Rate of rise
The heat detector will monitor the rate of temperature increase in the
vicinity and will also be triggered when a fixed upper threshold
temperature level is exceeded.
Readings are taken every 2 seconds, the stored values are compared against
a preset value to decide if an alarm level has been reached.
Classification – maximum application temperature: RR1= 50ºC, RR2 = 65ºC,
RR3 = 80ºC
FAPO-RR1
SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V 20mA
24V 40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 97 x 36 (100 x 51 inc base)
Weight g 70, 130 with base
Standards EN54-7: 2000

STANDARD ORDER CODE DESCRIPTION


FAPO-RR1 Heat detector -Rate of rise with fixed upper threshold 50ºC, A1R
FAPO-RR2 Heat detector -Rate of rise with fixed upper threshold 65ºC, BR
FAPO-RR3 Heat detector -Rate of rise with fixed upper threshold 80ºC, CR

59

www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional


Conventional 4-wire detectors

Conventional 4-wire detection: The FAP6 range


Introducing the FAP6 range of detectors, for use with the Firetec and Eurofire 4-wire panels. FAP6
provides proven technology in a slim package, the concise range comprises optical and heat detectors
(fixed and rate of rise temperature). In conjunction with Firetec the range is suited to small to medium
sized buildings.

Detector base with diode FAP6-STB


The standard detector base has a diode fitted beneath the connectors.

SPECIFICATION
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 15
Weight g 60

FAP6-STB

Relay base FAP6-RLB


The relay base incorporates a set of volt-free changeover contacts, which
will latch when the detector registers an alarm.

SPECIFICATION
Voltage range 9 – 33Vdc
Relay base alarm current at 24V 17mA
Modes Latching
Operating temperature -20 to +70ºC
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
FAP6-RLB Dimensions ø d (mm) 100, 25
Weight g 100

60 FAP6 is based on series 65


technology from Apollo Fire
Detectors Ltd

Conventional | Conventional 4-wire detectors www.emergi-lite.co.uk


Conventional 4-wire detectors

Relay base, 12 volt FAP6-RLB12


The low voltage relay base incorporates a set of volt-free changeover
contacts that can be used for either latching or non-latching (security
system) purposes. To enable control of an automatic door closer,
for example.

SPECIFICATION
Voltage range 9 – 15Vdc
Average quiescent current at 12V <10µA
Relay base alarm current, at 12V 20mA
Modes Latching or non-latching
FAP6-RLB12
Operating temperature –20 to +70ºC
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
Dimensions ø d (mm) 100, 25
Weight g 100

Optical smoke detector FAP6-OPT


The optical detector measures the level of smoke particles using light
scatter, going to alarm at a pre-set threshold. New optics help reduce false
alarms while stability is strengthened by using internal software control.
Recommended for general purpose use to give early warning of fire.

SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V 20mA
24V 40mA FAP6-OPT
Alarm indication Clear LED, red on alarm
Operating temperature -20 to +60ºC
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)
Weight g 99, 150 with base
Standards EN54-7: 2000

61

www.emergi-lite.co.uk Conventional 4-wire detectors | Conventional


Conventional 4-wire detectors

Heat detector – FAP6-FT8


fixed temperature
The fixed (static) heat detector will trigger when a pre-set upper
temperature threshold is exceeded at the sensor.

SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 24V <50µA
Alarm current at 9V 17mA
24V 52mA
FAP6-FT8 Alarm indication Red LED
Operating temperature –20 to +90ºC
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)
Weight g 80, 131 with base
Standards EN54-5: 2000

Heat detector – FAP6-RR6, FAP6-RR75, FAP6-RR90


Rate of rise
The heat detector will monitor the rate of temperature increase in the
vicinity and will also be triggered when a fixed upper threshold
temperature level is exceeded.
Classification – maximum application temperature: RR6= 50ºC, RR75 = 65ºC,
RR90 = 80ºC

SPECIFICATION
Voltage range 9 – 33Vdc
FAP6-RR6
Quiescent current at 24V <50µA
Alarm current at 9V 17mA
24V 52mA
Alarm indication Red LED
Operating temperature –20 to +90ºC
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)
Weight g 80, 131 with base
Standards EN54-7: 2000

STANDARD ORDER CODE DESCRIPTION


FAP6-RR6 Heat detector – Rate of rise with fixed upper threshold 50ºC, A1R
FAP6-RR75 Heat detector – Rate of rise with fixed upper threshold 65ºC, BR
FAP6-RR90 Heat detector – Rate of rise with fixed upper threshold 80ºC, CR

62

Conventional | Conventional 4-wire detectors www.emergi-lite.co.uk


Conventional 4-wire call points

Call point FMC-200R


Surface mounted manually operated call point with LED indicator,
providing a switch closure to the panel when operated. Features:
● Secure clip-fix front cover
● A single key for test, reset and removal of cover

SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Alarm indication Red LED
Operating temperature -25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
FMC-200R
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP42
Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)
Weight g 190
Standards EN54-11
OPTIONS
FMC-200RS Call point with re-settable plastic element
FMC-10G Spare glass (pack of 10)
FMC-10GRS Spare re-settable element (pack of 10)

RSL800

Weatherproof call point FMC-200RWP


Surface mounted manually operated call point with LED indicator,
providing a switch closure to the panel when operated. Features:
● Secure clip-fix front cover
● One key for test, reset and removal of cover
● Weatherproof to IP67

SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Alarm indication Red LED
Operating temperature –25 to +55ºC FMC-200RWP
Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP67
Dimensions lwd (mm) 110 x 110 x 65
Weight g 290
Standards EN54-11
OPTION
FMC-200RSWP Weatherproof call point with re-settable plastic element

ACCESSORIES FOR FMC CALL POINTS


FMC-KEY Spare test key (pack of 10)
FMC-10G Spare glass (pack of 10)
FMC-10GRS Spare re-settable element (pack of 10)
FMC-PC Polycarbonate cover
FMC-PCS Polycarbonate cover with security tie
RSL800 Fire call point notice sticker
SPARES FOR FMC INDOOR CALL POINTS For standard and weatherproof 63
FMC-BBR Back box in red protective call point covers, see
FMC-BBW Back box in green page 88.

www.emergi-lite.co.uk Conventional 4-wire call points | Conventional


Conventional 4-wire call points

Call point FMC-800R


Surface mounted manually operated call point, providing a switch closure
to the panel when operated. Features:
● Secure clip-fix front cover
● A single key for test, reset and removal of cover

SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Operating temperature –25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
FMC-800R Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP42
Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)
Weight g 190
Standards EN54-11
OPTION
FMC-800RS Call point with re-settable plastic element

RSL800

Weather resistant call point FMC-800RWP


Surface mounted manually operated call point, providing a switch closure
to the panel when operated. Features:
● Secure clip-fix front cover
● One key for test, reset and removal of cover
● Weatherproof to IP67

SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Operating temperature –25 to +55ºC
FMC-800RWP Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP67
Dimensions lwd (mm) 110 x 110 x 65
Weight g 290
Standards EN54-11
OPTION
FMC-800RSWP Weatherproof call point with re-settable plastic element

ACCESSORIES FOR FMC CALL POINTS


FMC-KEY Spare test key (pack of 10)
FMC-10G Spare glass (pack of 10)
FMC-10GRS Spare re-settable element (pack of 10)
FMC-PC Polycarbonate cover
FMC-PCS Polycarbonate cover with security tie
RSL800 Fire call point notice sticker
For standard and weatherproof
64 protective call point covers, see SPARES FOR FMC INDOOR CALL POINTS
page 88. FMC-BBR Back box in red
FMC-BBW Back box in green

Conventional | Conventional 4-wire call points www.emergi-lite.co.uk


Conventional 4-wire
call points/ancillary

Key-switch operated call point FMC-2KSW


A key-switch operated call point for use in secure premises where restricted
access is needed.
● Suitable for use with 230Vac systems
SPECIFICATION
Voltage range 24Vdc
Operation 2 position keyswitch with 1 NO contact and 1 NC contact
Switch rating 10A, 24Vdc 2A, 230Vac
Operating temperature –25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Flying lead connections
Construction ABS plastic in red FMC-2KSW
Ingress rating IP42, when fitted to a standard back box
Dimensions lwd (mm) 87 x 87 x 20
Weight g 190
Standards EN54-11
Fitting The 2KSW can be used with either a standard or a weather
resistant back box.

Remote Indicator unit FAP6-P10


A remote indicator is used to help an investigator quickly identify the
location where a device has registered a fire, without having to gain entry
to every room or inaccessible space. Features:
● Fire detector operated text

SPECIFICATION
LED indicator Red
Termination Terminal block
IP rating IP42
Dimensions lwd (mm) 86.5 x 86.5 x 9
FAP6-P10

Weight g 38

Remote LED
indicator
Zone +ve
L1 in L1 in
Zone+
-R -R COM- COM-

o o
IN+
IN+

Normal End of line LED- OUT+


LED-
OUT+

device Zone
detection:
Closed room Indicator visible

EOL
space L1 out L1 out
Zone -ve

L2 L2
Earth
Solid door Vision panel in door Zone -
Note: A diode is normally
Remote indicator fitted between L1 in & L1 out Note: A diode is normally
Corridor fitted between IN+ & OUT-

Example: Connecting a remote indicator to an


FAP6 detector base (shown common across Connection of remote LED unit
two detectors) in a zone to FAPO Orbis detector

Illustration: Use of remote indicator


in conventional fire system

Ceiling tile mounting box FAP-MBCT


The fixture is used to fit a detector or sounder into a false ceiling matrix.
The devices can be pre-wired and tested before the ceiling is fitted. With
the ceiling tiles in place, the MBCT assemblies can be slotted into place.

STANDARD ORDER CODE DESCRIPTION


FAP-MBCT-FD Ceiling tile mounting box for detectors 65
FAP-MBCT-SO Ceiling tile mounting box for sounders

FAP-MBCT-FD

www.emergi-lite.co.uk Conventional 4-wire call points/ancillary | Conventional


Conventional 4-wire alarms

FACS Conventional 4-wire sounders,


beacons and alarm bells
Emergi-Lite Safety Systems offers a range of sounder
and alarm options, for use with Firetec and Eurofire
4-wire panels.
The table below highlights the key features of
individual alarms to assist with planning and selection,
when preparing a fire detection and evacuation
system.

Sounder: room / bedhead

Amber, Clear or Red lens

Red. White or Grey body


Sounder beacon

Integrated base

Page reference
32 Tone range
Bell 6in diam

Accessories
Visual LED

100 dB(A)
Features:

Sounder

IP rating
Beacon

PRODUCT CODE DESCRIPTION

FACS-5W Sounder base ✔ W ✔ 67

FACS-5TPR Sounder base cap R ✔ 67

FACS-5TPW Sounder base cap W ✔ 67

FACS-1R Sounder ✔ ✔ R 67

FACS-1RL Sounder ✔ ✔ R ✔ 67

FACS-1W Sounder ✔ ✔ W 67

FACS-1WL Sounder ✔ ✔ W ✔ 67

FACS-BBR Back box for FACS1R R ✔ 67

FACS-BBW Back box for FACS1W W ✔ 67

FACS-4R Sounder ✔ R ✔ 68

FACS-4RDB Sounder ✔ R 65 ✔ 68

FACS-4W Sounder ✔ W ✔ 68

FACS-4WDB Sounder ✔ W 65 ✔ 68

FACS-8R Sounder-beacon ✔ R R ✔ ✔ 68

FACS-8RDB Sounder-beacon ✔ R R 65 ✔ ✔ 68

FACS-8RDB-A Sounder-beacon ✔ A R 65 ✔ ✔ 68

FACS-8W Sounder-beacon ✔ R W ✔ ✔ 68

FACS-8WDB Sounder-beacon ✔ R W 65 ✔ ✔ 68

FACS-BEA-R Beacon ✔ R R 69

FACS-BEA-RDB Beacon ✔ R R 65 69

FACB-624 Bell ✔ R 69

FACB-624-G Bell ✔ G 69

FAAB-624-WP Bell ✔ R 55 70

66

Conventional | Conventional 4-wire alarms www.emergi-lite.co.uk


Conventional 4-wire alarms

Low profile sounder FACS-5W


A low height sounder that can be used standalone with an optional cover
or as a platform for a smoke/heat detector with a detector base. Features:
● Four selectable tones including warble, pips and sweep

SPECIFICATION
Voltage range 8 – 35Vdc
Current draw @ 24Vdc 11mA
Sound output, at 1m (dBA) 91 (94 with cover plate)
No. of tones 4
Operating frequency 800Hz to 1Khz FACS-5W
Operating temperature –20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear
Construction ABS plastic
Ingress rating IP43 (DB version - IP65)
Dimensions ø h (mm) 106 x 25 (35 with cover)
Weight g 121
OPTIONS
FACS-5TPW White cover
FACS-5TPW
FACS-5TPR Red cover

Room sounder FACS-1R


A room sounder, suitable for bedroom and passageway use. Features:
● Low profile with a small footprint
● Audio/visual version with flashing LEDs on alarm
● Four selectable tones including warble, pips and sweep

SPECIFICATION
Voltage range 8 – 35Vdc
Current draw @ 24Vdc 11mA
FACS-1R
Sound output, at 1m (dBA) 97
No. of tones 4
Volume control -50dBA
Operating frequency 800Hz to 1Khz
Operating temperature -20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear (or side entry with surface box)
Construction ABS plastic
Ingress rating IP43
Dimensions lwd (mm) 86.5 x 86.5 x 9 (+25.2 back box or recessed)
Weight g 103
OPTIONS
FACS-1RL Room sounder, red, with two flashing hi-intensity LEDs
FACS-1W Room sounder, white
FACS-1WL Room sounder, white, with two flashing hi-intensity LEDs
FACS-BBR Back box for FACS-1R
FACS-BBW Back fox for FACS-1W
67

www.emergi-lite.co.uk Conventional 4-wire alarms | Conventional


Conventional 4-wire alarms

Open area sounder FACS-4R


A multi-tone sounder for open area use, operating across a range of
frequencies. Features:
● Quick fit installation
● 32 tones, selectable by DIL switch
● High, medium and low outputs can be selected to fit in with a local
sound pattern requirement
● Side grub screw for security locking
SPECIFICATION
FACS-4R Voltage range 15 – 35Vdc
Sound level Low Med Hi
Current draw @ 24Vdc <9mA <18mA <36mA
Sound output, at 1m, 1st tone (dBA) 91 106 111
No. of tones 32
Operating frequency 440 to 2900Hz
Operating temperature –20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear (DB rear or side entry [with cover plate])
Construction ABS plastic
Ingress rating IP43 (DB version - IP65)
Dimensions ø h (mm) 93.6 (DB-93) x 84.3 (DB-101.6)
Weight g 220 (DB-250)
FACS-4RDB OPTIONS
FACS-4RDB Open area sounder, red, deep base
FACS-4W Open area sounder, white, shallow base
FACS-4WDB Open area sounder, white, deep base

Open area sounder beacon FACS-8R


A multi tone sounder-beacon, for open area use. Features:
● LED cluster beacon light
● 32 tones, selectable by DIL switch
● Enables compliance with the Disability Discrimination Act (DDA)
● Side grub screw for security locking
SPECIFICATION
Voltage range 15 – 35Vdc
Sound level Low Med Hi
FACS-8R
Current draw @ 24Vdc <14mA <20mA <41mA
Sound output, at 1m, 1st tone (dBA) 88 103 109
No. of tones 32
Operating frequency 440 to 2900Hz
Operating temperature –20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear (DB rear or side entry [with cover plate])
Construction ABS plastic, with red lens
Ingress rating IP43 (DB version – IP65)
Dimensions ø h (mm) 93.6 (DB-93) x 89.6 (DB-106.9)
Weight g 233 (DB-258)
OPTIONS
FACS-8RDB Open area sounder, red, deep base
FACS-8RDB
FACS-8W Open area sounder, white, shallow base
68 FACS-8WDB Open area sounder, white, deep base
FACS-8RDB-A Open area sounder, red, deep base with amber cover

Conventional | Conventional 4-wire alarms www.emergi-lite.co.uk


Conventional 4-wire alarms

Alarm beacon FACS-BEA-R


A bright output flashing beacon to augment sounders, particularly in areas
of higher ambient noise. LED light source with low power requirement.

SPECIFICATION
Voltage range 20 – 35Vdc
Set up Standard Low
Current draw @ 24Vdc 5mA 3mA
Light output (equiv) @24Vdc 0.7w 0.4w
Operating frequency 1Hz
Operating temperature –20 to +70ºC FACS-BEA-R
Wiring & polarity 2 wire supply, polarity sensitive
Termination 6 way angled terminal block
Cable entry Rear (DB - rear or side entry)
Construction ABS plastic in red
Ingress rating IP43 (DB version - IP65)
Dimensions ø h (mm) 93.6 (DB-93) x 60.2 (DB-77.1)
Weight g 145
OPTION
FACS-BEA-RDB Alarm beacon, deep base

FACS-BEA-RDB

Alarm fire bell FACB-624


A wall mountable motorised fire bell for fire alarm or class change.
The gong is secured by a tamper resistant bolt.

SPECIFICATION
Voltage range 18 – 28Vdc
Current draw @ 24Vdc 25mA
Sound output, at 1m (dBA) 96
Operating temperature –10 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
FACB-624
Termination 4 way terminal block
Cable entry Rear (or side entry with surface box)
Construction Metal gong in red
Ingress rating IP42
Dimensions ø h (mm) 150 x 54
Weight g 527
OPTION
FACB-624-G Alarm fire bell with grey gong

69

www.emergi-lite.co.uk Conventional 4-wire alarms | Conventional


Conventional 4-wire alarms

Alarm fire bell FAAB-624-WP


A wall mountable fire bell for fire alarm or class change applications.
Weather resistant rating achieved with a rubber gasket.

SPECIFICATION
Voltage range 18 – 30Vdc
Current draw @ 24Vdc 30mA
Sound output, at 1m (dBA) 93 – 95
Operating temperature –10 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
FAAB-624-WP Termination 4 way terminal block
Cable entry Rear (or side entry with surface box)
Construction Metal gong in red, base in polycarbonate
Ingress rating IP55
Dimensions ø h (mm) 150 x 85
Weight g 1,100

70

Conventional | Conventional 4-wire alarms www.emergi-lite.co.uk