AlarmSense devices
AlarmSense devices (detectors, manual call points,
sounders, sounder beacons and alarm relays) are
designed to operate normally on the same pair of
zone wires from the panel. A key feature is that alarm
sounders can be programmed to operate as so-called
‘priority’ or ‘non-priority’ devices.
Combined sounder-detector
base (priority set)
Standalone smoke alarm
Combined sounder-detector
base (non-priority set)
Zone 5
Floor 2
Zone 6
Up
# # Zone 2
Zone 3
Flat 3 Flat 2
Floor 1 Zone 7
Zone 4
Up
#
Zn8 Zone 1
Zn1
Zn7
Zn6
Zn5 Flat 1
CIE Zn2
Zn4 Zn3
37
# = Set as non-priority detector
Apartment building with a floor plan of 2 floors: Illustration of
detector programming for local alarm operation
Panel Display
The Eurofire Sensa panel includes an easy to reference display with LCD screen allowing for up to four lines of text,
with text programmable for each zone. 6 buttons are included on the front of the panel which can be used to access
the following functions:
● Lamp test, silence alarms, silence buzzer
● User zone, sounder and 2-wire sounder isolation
● Walk and alarm test facility with mute option
● 99-event history log that stores any events with
time and date stamp, for the user to scroll
● Configurable system message for the user with
normal time and date displayed
The panel also features indicator LEDs which advise
the current state of the fire detection system, and give
a clear signal of fire or fault in any particular zone.
Further functionality includes the facility to review
event logs, to override any pre-set alarm delays, and
to enable sounding the evacuation to all zones.
Indicator details
The panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminate
or flash to establish the zone affected.
Networking capability
Fire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaters
together via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possible
to make more power available for sounder circuits (additional 4), or save on field wiring:
Scenario: In a
building, one panel
might be sited in the
office area and one
in the warehouse
area. The zones for
each area are wired
to their respective
panels. Network the
panels and the
office unit has full Eurofire c-net Eurofire c-net
visibility of the
building. It may be
CAN NET CARD
necessary to use a
higher rated cable Isolated Isolated
and the Emergi-Lite CAN CAN
CAN network network CAN network network
network card (please
contact Technical
sales for further
guidance).
To next
panel
Eurofire c-net
39
Illustration: Network of Eurofire panels, in star format
[wired to the CAN network facility]
Connection diagram
The diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points, with settings for
both ‘priority’ and non-priority’.
o
Z3: Non- No spurs
o priority zone
NC C NO NC C NO NC C NO NC C NO +Z1- +Z2- +Z3- +Z4- +Z5- +Z6- +Z7- +Z8- +Z9- +Z10- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16- +AL1- +AL2- +AL3- +AL4-
Common fault
TTL fault
Bomb alert
GND
Class change
Aux 1 Aux 2
Prog i/p
Additonal alarm
circuits
Priority 2w Standard
Key: Call point -2w
sounder sounder Eurofire Sensa 2 wire: Illustration of zonal wiring
Optical 2w 2w Sounder, set
o detector as non-priority
Zone circuits to o
1 additional alarm circuit. Eurofire 2w o
Sensa panel
EOL
Key: o
SEOL
o o
o
Call point o
A1R
A1 R
Sounder (priority)
Beam
detector set
Apex roof Motorised
window
EOL End of line device vents
-detector circuit
SEOL
End of line device -
alarm circuit
40 Auxiliary
circuits
o
A1R
Warning: do not use FAP6 detectors on Alarmsense systems. Although they would appear to work initially, using them could cause severe system malfunction in the longer term. Also be
aware that if used with the Sounder/Sounder Beacon Bases the non-priority function will not operate correctly.
To Order
STANDARD ORDER CODE DESCRIPTION ACCESSORIES
Suffix LD Lockable door option for Eurofire Panel FEUN-SPARES Eurofire Spares Pack
41
Indicator details
The panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminate
or flash to establish the zone affected.
The panel also features indicator LEDs which advise the current state of the fire detection system, to highlight
system, earth, or supply faults, system disabled or test status, and alarm silenced mode.
Connection diagram
The diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.
o
EOL diode on last o
detector [cathode No spurs
to zone +ve end]
o
No spurs
Z3: Non-
priority zone
o
Enable alarm
delay switch
EOL diode to unused C - Class
zones [cathode to EOL change switch
o o
zone, +ve end] resistor in
Z1: Priority zone unused C
alarm cct
+Z1- +Z2- +Z3- +Z4- +Z5- +Z6- +Z7- +Z8- +AL2- +AL1- Aux 1 Aux 2 Lo Hi +Aux-
NC C NO NC C NO 24v
Class change
Mon input
Enable delay
TTL fault
Auxiliary relay
GND
Alarm circuits
contacts
Notes:
1 Total panel alarm current, is total zone alarm current + total sounder current on AL1 & AL2. Total should not exceed 1A.
2 Ensure that maximum number of sounders/sounder-beacon devices does not exceed total current allowed for zones.
30 sounders on a zone = 5mA * 30 = 0.15A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on zone.
16 sounder-beacons on a zone = 9mA * 16 = 0.144A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on the zone.
Sounders and sounder-beacon devices can be used together on a zone but should not exceed the maximum alarm current per zone.
3 Current available for alarm lines AL1 & AL2 = 1A - Total zone alarm current being used.
44
AlarmSense devices (detectors, manual call points, sounders, sounder beacons and alarm relays) are
designed to operate normally on the same pair of zone wires from the panel. A key feature is that
alarm sounders can be programmed to operate as so-called ‘priority’ or ‘non-priority’ devices.
A ‘priority’ set device reacts as a normal sounder in
standard use and sounds a full alarm. A ‘non-priority’
set device will give an initial local alert prior to going
into full alarm.
‘Non-priority’ devices are intended for use in HMO type
applications where there are a number of individual
dwellings. The operating method is intended to help
reduce the instances of unwanted alarms and give a
local warning before the full alarm/evacuation.
When a heat detector is attached on a sounder or
sounder beacon base, we recommend that the sounder
be set as a ‘priority’ device.
For more information about priority/non-priority
devices, please refer to pages 36 – 37.
Integrated base
Conventional
Accessories
Features:
Sounder
Beacon
SPECIFICATION
Quiescent current at 15V <30µA
Load shown to the zone with 47Ω for 10ms every 4 seconds
head removed
Wiring & polarity 2 wire supply, polarity insensitive
Termination Connectors accept up to 2.5mm2 cables
FAPW2-ASB
Construction White moulded polycarbonate
Dimensions ø d (mm) 100
Weight g 55
45
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 12V <20µA
Sounder active current @ 24V 5mA
Sound output dBA, high volume 87
FAPW2-BS24W
Low volume dBA 70 nominal
Operating temperature –20 to +60ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Connectors accept up to 2.5mm2 cables
Construction Polycarbonate/ABS
Dimensions ø d (mm) 115 x 40
Weight g 150
Standards EN54-3
OPTIONS
FAPW2-CBSW White cap
FAPW2-CBSR Red cap
FAPW2-BSB24W SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 12V <20µA
Sounder active current @ 24V 9mA
Sound output dBA, high volume 87
Low volume dBA 70 nominal
Operating temperature –20 to +60ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Connectors accept up to 2.5mm2 cables
Construction Polycarbonate
Dimensions ø d (mm) 115 x 40
Weight g 150
Standards EN54-3
OPTIONS
FAPW2-CBSW White cap
FAPW2-CBSR Red cap
Application
Owing the level of sound these devices can produce; they are effective for
46 local use. For example, in situations where there is a corridor with a
number of adjoining rooms, closed doors can reduce the sound level
somewhat. Consequently, it is recommended that this type of sounder
should be placed in both the room and the corridor.
SPECIFICATION
FAPW2-OP
Voltage range 9 – 33Vdc
Quiescent current at 15V <50µA
Alarm current at 2 – 8.5V <1.5mA
10.5 – 15V 25 +/- 2mA
Wiring & polarity 2 wire supply, polarity insensitive
Construction Polycarbonate
Dimensions ø d (mm) 100 x 42
Weight g 100
Standards EN54-7: 2000
SPECIFICATION
Voltage range 9 – 33Vdc
FAPW2-R6
Quiescent current at 15V <50µA
Alarm current at 12V <1.5mA
24V 25 +/- 2mA
Grades A1R & CS
Wiring & polarity 2 wire supply, polarity insensitive
Construction Polycarbonate
Dimensions ø d (mm) 100 x 42
Weight g 100
Standards EN54-5: 2000
FAPW2-F84
47
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 15V <50µA
Alarm current at 2 – 8.5V <1.5mA
10.5 – 15V 25 +/- 2mA
Wiring & polarity 2 wire supply, polarity insensitive
Reset time 1 second
LED indicator Red
FMFW2-800
Construction Polycarbonate/ABS
Dimensions ø d (mm) 87 x 87 x 52
Weight g 170
Standards EN54-11: 2000
ACCESSORY
RSL800 Fire call point notice sticker
RSL800
FMC-ST30
48 FMC-ST50WP
o o
Normal FAP6-P10
detection:
Closed room Indicator visible
space
Remote indicator
Corridor
-ve
Zone
-R
+ve
Zone
R5
SPECIFICATION L1 zone +ve
L2 zone -ve
SPECIFICATION
Voltage range 9 – 33Vdc
Relay operating voltage >18V FAPW2-ALR
Quiescent current at 12V <20µA
Surge current at relay set voltage 15mA for 20ms
Relay contact ratings 1A at 30Vdc
Wiring & polarity 2 wire supply, polarity sensitive
Termination Connectors accept up to 2.5mm2 cables
Dimensions ø d (mm) 65 x 45 x 25
Weight g 35
Standards EN54
49
Commissioning note: At commissioning the relay should be reset prior to
use. During operation the relay will reset if there is a power loss on the fire
alarm circuit.
Panel Display
The Eurofire panel includes an easy to reference display with LCD screen allowing for up to four lines of text, with
text programmable for each zone. 6 buttons are included on the front of the panel which can be used to access the
following functions:
● Lamp test, silence alarms, silence buzzer
● User zone and sounder isolation
● Walk and alarm test facility with mute option
● 99-event history log that stores any events with
time and date stamp, for the user to scroll
● Configurable system message for the user with
normal time and date displayed
The panel also features indicator LEDs which advise
the current state of the fire detection system, and give
a clear signal of fire or fault in any particular zone.
Further functionality includes the facility to review
event logs, to override any pre-set alarm delays, and
to enable sounding the evacuation to all zones.
Indicator details
The panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminate
or flash to establish the zone affected.
Networking capability
Fire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaters
together via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possible
to make more power available for sounder circuits (additional 4), or save on field wiring:
EOL
Scenario: In a
building, one panel
EOL
Zone 2
to their respective o
o
c s
51
Network
Connection diagram
The diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points.
o
No spurs
o
EOL
Zones 2-8 wired as Z1 resistor in
unused
EOL diode to unused
alarm ccts
o zones [cathode to
zone, +ve end]
Auxiliary relay
contacts
Fault 1 Fault 2
NC C NO NC C NO NC C NO NC C NO +Z1- +Z2- +Z3- +Z4- +Z5- +Z6- +Z7- +Z8- +Z9- +Z10- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16- +AL1- +AL2- +AL3- +AL4-
Common fault
TTL fault
Bomb alert
GND
Class change
Aux 1 Aux 2
Prog i/p
Alarm circuits
o o
with four alarm circuits] smoke
o
detector
o Heat detector
c s
o
EOL End of line device -
detector circuit
o SEOL End of line device -
alarm circuit
EOL
o o
Sounder
o
Fire o EOL
exit o
o Sounder-beacon
SEOL
Beam detector set
EOL SEOL
o Apex roof
SEOL
Programmable o
52 sounder circuits from
the panel
o
EOL
Fire exit
To Order
STANDARD ORDER CODE DESCRIPTION ACCESSORIES
Suffix LD Lockable door option for Eurofire Panels FEUN-SPARES Eurofire Spares Pack
53
Firetec panels are designed to comply with the FTEP8 Firetec 8 Zone Panel
OPTION
Indicator details
The panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminate
or flash to establish the zone affected.
The panel also features indicator LEDs which advise the current state of the fire detection system, to highlight
system, earth, or supply faults, system disabled or test status, and alarm silenced mode.
Connection diagram
The diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.
No spurs
No spurs o
Enable alarm
delay switch
o Zones 2-5 wired as Z1 EOL diode to unused C - Class
zones [cathode to EOL change switch
zone, +ve end] resistor –
unused C
alarm cct
+Z1- +Z2- +Z3- +Z4- +Z5- +Z6- +Z7- +Z8- +AL2- +AL1- Aux 1 Aux 2 Lo Hi +Aux-
NC C NO NC C NO 24v
Mon input
Class change
Enable delay
TTL fault
Auxiliary relay
GND
Alarm circuits
contacts
Call point
Detector 55
o Firetec 8 zone: wiring illustration -zones & alarms
Alarm device
56
Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofire
systems. Non-addressable (conventional) smoke and heat sensors respond to fire situations within a
given zone, sending a signal to the fire panel, which will indicate a fire condition and sound the alarm.
Orbis provides valuable core features, with high reliability, a marked reduction in unwanted false alarms,
complemented by operational and maintenance enhancements.
Features:
● StartUp: Correct installation – a flashing red LED
● Continuity link: Zone wiring can be voltage
tested before commissioning
● Wide-angle optics: Responsive to fires with black
or white smoke
● Drift Compensation: Calibrated sensitivity levels
are maintained despite contamination
● DustDefy: Dust ingress prevented while airflow is
unimpeded
● Transient Rejection: Abnormal readings are
filtered out to reduce false alarms
● DirtAlert: A flashing yellow LED will indicate
when the drift compensation limit has been
reached
● SensAlert: A flashing yellow LED indicates
incorrect sensor operation
● Fast Test: A 4 second test confirms correct detector operation
● E-Z Fit slots: Remove and refit the base without dismounting the fixing screws
SPECIFICATION
Construction White moulded polycarbonate
Termination Connectors accept up to 2.5mm2 cables
Dimensions ø d (mm) 100 x 15 FAPO-TDB
Weight g 60
SPECIFICATION
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate 57
Dimensions ø d (mm) 100 x 15
FAPO-TRB
Weight g 60
SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V 20mA
FAPO-OPT 24V 40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 97 x 31 (100 x 46 inc base)
Weight g 75, 135 with base
Standards EN54-7: 2000
SPECIFICATION
FAPO-MUS
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V 20mA
24V 40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 97 x 42 (100 x 57 inc base)
Weight g 80, 140 with base
Standards EN54-7: 2000
58
SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
FAPO-HR1
Alarm current at 12V 20mA
24V 40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42
Weight g 100
Standards EN54-5: 2000
59
SPECIFICATION
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 15
Weight g 60
FAP6-STB
SPECIFICATION
Voltage range 9 – 33Vdc
Relay base alarm current at 24V 17mA
Modes Latching
Operating temperature -20 to +70ºC
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
FAP6-RLB Dimensions ø d (mm) 100, 25
Weight g 100
SPECIFICATION
Voltage range 9 – 15Vdc
Average quiescent current at 12V <10µA
Relay base alarm current, at 12V 20mA
Modes Latching or non-latching
FAP6-RLB12
Operating temperature –20 to +70ºC
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
Dimensions ø d (mm) 100, 25
Weight g 100
SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V 20mA
24V 40mA FAP6-OPT
Alarm indication Clear LED, red on alarm
Operating temperature -20 to +60ºC
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)
Weight g 99, 150 with base
Standards EN54-7: 2000
61
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 24V <50µA
Alarm current at 9V 17mA
24V 52mA
FAP6-FT8 Alarm indication Red LED
Operating temperature –20 to +90ºC
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)
Weight g 80, 131 with base
Standards EN54-5: 2000
SPECIFICATION
Voltage range 9 – 33Vdc
FAP6-RR6
Quiescent current at 24V <50µA
Alarm current at 9V 17mA
24V 52mA
Alarm indication Red LED
Operating temperature –20 to +90ºC
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)
Weight g 80, 131 with base
Standards EN54-7: 2000
62
SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Alarm indication Red LED
Operating temperature -25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
FMC-200R
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP42
Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)
Weight g 190
Standards EN54-11
OPTIONS
FMC-200RS Call point with re-settable plastic element
FMC-10G Spare glass (pack of 10)
FMC-10GRS Spare re-settable element (pack of 10)
RSL800
SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Alarm indication Red LED
Operating temperature –25 to +55ºC FMC-200RWP
Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP67
Dimensions lwd (mm) 110 x 110 x 65
Weight g 290
Standards EN54-11
OPTION
FMC-200RSWP Weatherproof call point with re-settable plastic element
SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Operating temperature –25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
FMC-800R Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP42
Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)
Weight g 190
Standards EN54-11
OPTION
FMC-800RS Call point with re-settable plastic element
RSL800
SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Operating temperature –25 to +55ºC
FMC-800RWP Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP67
Dimensions lwd (mm) 110 x 110 x 65
Weight g 290
Standards EN54-11
OPTION
FMC-800RSWP Weatherproof call point with re-settable plastic element
SPECIFICATION
LED indicator Red
Termination Terminal block
IP rating IP42
Dimensions lwd (mm) 86.5 x 86.5 x 9
FAP6-P10
Weight g 38
Remote LED
indicator
Zone +ve
L1 in L1 in
Zone+
-R -R COM- COM-
o o
IN+
IN+
device Zone
detection:
Closed room Indicator visible
EOL
space L1 out L1 out
Zone -ve
L2 L2
Earth
Solid door Vision panel in door Zone -
Note: A diode is normally
Remote indicator fitted between L1 in & L1 out Note: A diode is normally
Corridor fitted between IN+ & OUT-
FAP-MBCT-FD
Integrated base
Page reference
32 Tone range
Bell 6in diam
Accessories
Visual LED
100 dB(A)
Features:
Sounder
IP rating
Beacon
FACS-1R Sounder ✔ ✔ R 67
FACS-1RL Sounder ✔ ✔ R ✔ 67
FACS-1W Sounder ✔ ✔ W 67
FACS-1WL Sounder ✔ ✔ W ✔ 67
FACS-4R Sounder ✔ R ✔ 68
FACS-4RDB Sounder ✔ R 65 ✔ 68
FACS-4W Sounder ✔ W ✔ 68
FACS-4WDB Sounder ✔ W 65 ✔ 68
FACS-8R Sounder-beacon ✔ R R ✔ ✔ 68
FACS-8RDB Sounder-beacon ✔ R R 65 ✔ ✔ 68
FACS-8RDB-A Sounder-beacon ✔ A R 65 ✔ ✔ 68
FACS-8W Sounder-beacon ✔ R W ✔ ✔ 68
FACS-8WDB Sounder-beacon ✔ R W 65 ✔ ✔ 68
FACS-BEA-R Beacon ✔ R R 69
FACS-BEA-RDB Beacon ✔ R R 65 69
FACB-624 Bell ✔ R 69
FACB-624-G Bell ✔ G 69
FAAB-624-WP Bell ✔ R 55 70
66
SPECIFICATION
Voltage range 8 – 35Vdc
Current draw @ 24Vdc 11mA
Sound output, at 1m (dBA) 91 (94 with cover plate)
No. of tones 4
Operating frequency 800Hz to 1Khz FACS-5W
Operating temperature –20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear
Construction ABS plastic
Ingress rating IP43 (DB version - IP65)
Dimensions ø h (mm) 106 x 25 (35 with cover)
Weight g 121
OPTIONS
FACS-5TPW White cover
FACS-5TPW
FACS-5TPR Red cover
SPECIFICATION
Voltage range 8 – 35Vdc
Current draw @ 24Vdc 11mA
FACS-1R
Sound output, at 1m (dBA) 97
No. of tones 4
Volume control -50dBA
Operating frequency 800Hz to 1Khz
Operating temperature -20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear (or side entry with surface box)
Construction ABS plastic
Ingress rating IP43
Dimensions lwd (mm) 86.5 x 86.5 x 9 (+25.2 back box or recessed)
Weight g 103
OPTIONS
FACS-1RL Room sounder, red, with two flashing hi-intensity LEDs
FACS-1W Room sounder, white
FACS-1WL Room sounder, white, with two flashing hi-intensity LEDs
FACS-BBR Back box for FACS-1R
FACS-BBW Back fox for FACS-1W
67
SPECIFICATION
Voltage range 20 – 35Vdc
Set up Standard Low
Current draw @ 24Vdc 5mA 3mA
Light output (equiv) @24Vdc 0.7w 0.4w
Operating frequency 1Hz
Operating temperature –20 to +70ºC FACS-BEA-R
Wiring & polarity 2 wire supply, polarity sensitive
Termination 6 way angled terminal block
Cable entry Rear (DB - rear or side entry)
Construction ABS plastic in red
Ingress rating IP43 (DB version - IP65)
Dimensions ø h (mm) 93.6 (DB-93) x 60.2 (DB-77.1)
Weight g 145
OPTION
FACS-BEA-RDB Alarm beacon, deep base
FACS-BEA-RDB
SPECIFICATION
Voltage range 18 – 28Vdc
Current draw @ 24Vdc 25mA
Sound output, at 1m (dBA) 96
Operating temperature –10 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
FACB-624
Termination 4 way terminal block
Cable entry Rear (or side entry with surface box)
Construction Metal gong in red
Ingress rating IP42
Dimensions ø h (mm) 150 x 54
Weight g 527
OPTION
FACB-624-G Alarm fire bell with grey gong
69
SPECIFICATION
Voltage range 18 – 30Vdc
Current draw @ 24Vdc 30mA
Sound output, at 1m (dBA) 93 – 95
Operating temperature –10 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
FAAB-624-WP Termination 4 way terminal block
Cable entry Rear (or side entry with surface box)
Construction Metal gong in red, base in polycarbonate
Ingress rating IP55
Dimensions ø h (mm) 150 x 85
Weight g 1,100
70