Professional Documents
Culture Documents
Medical Gas System Management
Medical Gas System Management
Document Originating
21/10/2020
Date:
Document Effective Date: 3/6/2023
Revision Number: V.1
Originating Entity: Facility Management Department
Approved by: Facility Management Director, Chief Operation Officer
Document Ref: POLFM0005
Scope: Medical Gases Technicians at Abdali hospital
Next Revision Due Date: 6/2026
I. Purpose:
1.1 The purpose of this policy is to describe how can handle and store the medical gas cylinders.
II. Policy:
2.1 This policy applies to the supply, delivery, installation and maintenance of the medical gas
service from the point of supply, up to and including the terminal outlets.
2.2 This policy lays down the mandatory requirements for the activities associated within
medical gas pipeline systems for the supply of:
2.2.1 Medical Oxygen.
2.2.2 Nitrous Oxide.
2.2.3 Medical Compressed Air (4 Bar).
2.2.4 Surgical Compressed Air (7 Bar).
2.2.5 Medical Vacuum.
2.2.6 Anesthetic Gas Scavenging Systems.
2.3 This policy will cover handling and storage medical gas cylinders:
2.3.1 Carbon Dioxide Cylinders.
2.3.2 Compressed Air Cylinders.
2.3.3 Oxygen Cylinders.
2.3.4 Oxygen Crash Cart Cylinders.
2.3.5 Oxygen for Respirator/OR Cylinders.
III. Definition:
3.1 Medical gas systems: include the pipes, fixtures and other apparatus for medical gas, and
vacuum systems. These systems also include anesthetic gas scavenging system along with
medical air, nitrous oxide, oxygen, nitrogen, carbon dioxide, and other gas mixtures.
IV. Responsibilities:
4.1 It’s the responsibility of medical gas technician to follow the procedure inside this policy.
V. Procedure:
5.1 Liquid Oxygen System:
5.1.1 System Description: Oxygen is supplied from a tank located to operating rooms,
birthing center, recovery rooms, treatment rooms, emergency room, ICU, CCU and
other patient care areas via a central gas system. Complete medical gas distribution
drawings are found are located in the Engineering Department.
5.1.2 Normal Operation: In normal operation, the bulk storage tank supplies oxygen to
the hospital through a main valve located at the tank.
5.1.3 Backup Operation: cylinders back up on an automatic transfer manifold located on
the tank.
5.1.4 Alarms: A low-pressure set point of 3.8 bar has been established. A high-pressure set
point of 4.8 bar has been established. Upon an alarm condition, a visual and audible
alarm occurs at the local alarm panel. The departments involved shall notify
engineering department who will proceed to ascertain and correct the problem.
5.1.5 Test/Inspection/Maintenance: shall be checked daily for operation during daily
equipment rounds. The system is also inspected and maintained on a periodic basis
through the hospital’s preventive maintenance program. Records of repair shall be
kept in Engineering Department.
5.1.6 System Alarms Testing: The system alarms shall be tested dynamically by decreasing
the system pressure below the set point and check the all alarms parameters.
5.1.7 Results of Tests/Inspections: The results of the inspections, testing, or corrective
actions shall be recorded on the checklist PM sheets. The sheets shall be
documented in the engineering department.
VI. References:
6.1 External References: N/A
6.2 Quality References:
6.2.1 JCI (2020). Joint commission international accreditation standards for hospitals. 7th
edition. Joint Commission International
6.2.2 HCAC (2021). Healthcare Accreditation Hospital Manual.4th edition. Healthcare
Accreditation Council.
6.3 Cross Reference: N/A