ANNEXURE-2

PROJECT ENGINEERING BASIC DESIGN DATA


1.00 Meteorological Data
1.01 General Climate Hot and Humid, Corrosive
1.02 Height above Mean Sea Level 19.2 Meters
1.03 Finish Ground Level EL 100.00 Meters
1.04 Latitude N 21° 44’ 30.3”
1.05 Longitude E 73° 00’ 44.52”

2.00 Atmospheric Pressure (Barometric)


2.01 Maximum 1012.3 m bar
2.02 Minimum 995.2 m bar
2.03 Average 1006 m bar

3.00 Ambient temperature


3.01 Dry Bulb (Maximum / Minimum) 48 °C / 5 °C
3.02 Wet Bulb (Maximum) 27.8 °C
3.03 For electrical design Max. 50 °C

4.00 Rainfall
4.01 Highest recorded rainfall 65 mm / hour
4.02 Average annual rainfall 1000 mm
4.03 Average rainfall 920 mm (June to Sept.)

5.00 Wind Data


Max. wind velocity (as per IS-875,
5.01 158.4Kmph (44 Metre / Sec)
latest)
5.02 Frequency of winds from different Wind direction normally North-East.
direction For details, refer Wind Rose diagram
as per clause no. 12.00
5.03 Importance Factor, k4 1.15
5.04 Wind Zone Number 3
5.05 Risk Factor, k1 1.07
5.06 Terrain Category & Class 3, Class-A
5.07 Topography Factor, k3 1

6.00 Earthquake (Seismic) design


6.01 Seismic Zone Zone-3 as per IS-1893, latest edition
& Roorkee Earth Quake School

02_Project_Engg_Design_Data_Annexure-2 Page 1 of 4
ANNEXURE-2

report for Bharuch


6.02 Importance Factor 2 (as per IS 1893)
6.03 Soil Factor 1.2 (Type-II, Medium)

7.00 Relative Humidity 80% for design

8.00 Topography and Soil Data


8.01 Stratification state
a 0 – 1.5 m deep Black soil
Clay silt with sand dense and Kankar
b 1.5 – 23 m deep
compact
c 23 – 29 m deep Fine to medium dense sand
d 29 – 35 m deep Very stiff silty clay
e Water table at about 16 meters from ground level
f Depth of foundation Min. 2 m below ground level
g Back filling done with sand / yellow soil
Maximum pressure on foundation will be about 8 ton / m2 and will
h never exceed the net stratum bearing
pressure specified in 8.02 below
8.02 Net bearing pressure
a Stratum I 12 MT / m^2 (Max.)
b Stratum II 20 MT / m^2 (Max.)

8.03 Other Details of Soil


Specific Bulk
Stratu Co-efficient of
Gravity Density Void Poisson’s Ratio
m Permeability
Ton / m^3
I 2.45 1.9 1 x 10-8 to 1 x 10-9 0.5 --
0.45
II 2.55 ~ 2.60 1.95 ~ 2.0 1 x 10-7 0.35
~ 0.5
III 2.1 2.1 -- -- 0.30
IV 2.1 2.1 -- -- 0.40

9.00 Seismic Zone (As per IS : 1893, 2002), Design Seismic Co-efficient
Design Design
Type of Basic Importan
Sr. Co-efficient Co-efficient
Structure Co- ce
No. for support for support
efficient Factor
structure structure
I Equipment and
0.108 2.0 0.216 0.180
support stratum
II Ordinary Structure for
0.070 1.0 0.070 0.070
(Building -RCC)
02_Project_Engg_Design_Data_Annexure-2 Page 2 of 4
ANNEXURE-2

Steel 0.110 1.0 0.110 0.110


III Structure support for
Eccentric Service 0.070 1.5 0.105 0.105
(RCC)
Steel 0.110 1.5 0.165 0.165
IV Small Vessels,
Equipment viz. Pumps,
0.050 2.0 --- 0.100
Heat Exchangers,
Coolers, etc
Note:
1.Design of all equipment, piping, machines etc. will incorporate the above
conditions and effectively compensate for them.
2. The Co-efficient given above are for guidance. However successful bidder
to submit calculation as per IS 1893 part-II and relevant IS codes for
approval of GNFC/PDIL.

10.00 Other data


a Noise level 85 dB at 1 meter distance from
machine
b Dust emission in the discharged air Not more than 150 mg / Nm^3

11.00 Load Combinations


The following combinations of loads and forces shall be considered for the
design of vessels and their supports including anchor bolts.
Calculations shall contain stress analysis at various points for the
following three conditions:
11.01 Erection (all loads & forces are additive)
a Dead weight of the vessel, excluding internals, packings,
insulation, fireproofing, piping and platforms supported from the vessel
b Wind load or earth quakes load whichever is greater
c Testing or flushing in operation position(all loads & forces are additive)
d Dead weight of vessel, including all internals, insulation, fireproofing, piping
and platforms supported from the vessels
e Weight of water for testing or flushing the vessel
f Pressure applied for testing and static head

11.02 Normal operation (all loads & forces are additive)


a Dead weight of vessel, including all internals, insulation, fire-proofing and
platforms supported from the vessels
b Operating weight of fluid
c Design pressure and static head

02_Project_Engg_Design_Data_Annexure-2 Page 3 of 4
ANNEXURE-2

d Wind load or ea
arthquake loads whichever is greater

12.00 Frequency of winds from different directions at Bharuch

Note: figures in diagram show in days. The frequency of winds from different
compass points in four
fo seasons and in year.

02_Project_Engg_Design_Data_Annexure-2 Page 4 of 4